Holes in exterior walls enclosed with windows, doors, and other related components must be integrated with surrounding building envelope components to effectively separate the outdoor environment from interior conditioned space. At the most basic level, windows allow natural light into buildings and resist the passage of water and excessive air. Windows also limit sound and heat transfer into and out of buildings and, in some instances, are designed to protect building occupants from forced entry, hurricane-force winds, and/or explosions. Properly functioning windows must allow desirable elements to be transmitted through them (i.e., light) and limit the transmission of undesirable elements (i.e., air and water).
The in-situ performance of windows remains inferior to specified performance criteria in many instances due to inadequate detailing during the design phase, variation of window installation methods, and imperfect jobsite conditions. Air infiltration and water penetration through and around windows are two items commonly impacted by project-specific variables and window installation practices.
The American Architectural Manufacturers Association/Window and Door Manufacturers Association/Canadian Standards Association’s (AAMA/WDMA/CSA’s) 101/I.S.2/A440, North American Fenestration Standard/Specification for Windows, Doors, and Skylights (NAFS) is mandated by several modern building codes. Although a revised version of NAFS is anticipated to be published in 2017, the 2011 version is currently referenced in the 2015 versions of the International Building Code (IBC 2015) and International Residential Code (IRC 2015).
As defined within NAFS, window Performance Class roughly describes the likely target application for installed window products, ranging from single-family residential to high-rise commercial buildings. Current NAFS 2011 Performance Classes include R, LC, CW, and AW (Figure 1).
Performance Grade is a numeric designator that defines a set of performance requirements for a specific design pressure range. A window product achieves a Performance Grade designation upon successfully completing all applicable tests, primarily those for structural performance and resistance to air infiltration and water penetration. These required tests are performed on prototype window specimens in a controlled laboratory environment.
NAFS 2011 requires air infiltration testing to be performed in accordance with ASTM E283, Standard Test Method for Determining Rate of Air Leakage through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen; and water penetration testing to be performed in accordance with ASTM E547, Standard Test Method for Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by Cyclic Static Air Pressure Difference; and/or ASTM E331, Standard Test Method for Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by Uniform Static Air Pressure Difference. Prototype test specimens are installed plumb, level, and square in a precise test buck opening in strict accordance with manufacturers’ instructions. The required laboratory tests are used primarily to evaluate the performance of the fenestration product and are not intended perimeter seals.
Clearly, laboratory tests used to validate product performance ratings cannot account for excessive air infiltration and/ or water penetration through or around inservice windows as a result of project specific conditions or substandard installation practices. Even if installed in general accordance with manufacturer instructions and industry standards, in-service products are unlikely to find such ideal conditions as during laboratory testing. Handling prior to and during installation, acts of subsequent trades, and environmental conditions may all adversely affect installed product performance compared to published laboratory test results.
Window performance requirements are typically included in Part 2 – Products of the applicable project specification section. In addition to items related to thermal performance and sound transmission, window Performance Class and Performance Grade are typically specified (Figure 2).
Taken together, specifying the Performance Class and Performance Grade for windows provides a baseline for air infiltration and water penetration resistance requirements. However, since those requirements are not explicitly specified, some ambiguity regarding performance requirements remains. The following questions, among others, would remain unanswered:
ASTM E2112-07 (2016), Standard Practice for Installation of Exterior Windows, Doors, and Skylights, is a consensus document maintained by ASTM International (ASTM). It acknowledges that window installation can significantly influence in-service performance of the units. Although ASTM E2112-07 (2016) defers to window manufacturers for product-specific installation instructions, it remains the default voluntary standard in cases where specific manufacturer recommendations are insufficient or otherwise not available. The document includes much useful information regarding the use of pan flashings, integration of weather-resistive barriers with flanged windows, and window installation best practices in wood-frame buildings (Figure 3), but it is not intended to be used as a project-specific resource. Stated within, the document is “intended to provide technical guidance to organizations that are developing training programs for installers of fenestration units in low-rise residential and light commercial structures.”
Window installation requirements are typically included in Part 3 – Execution of the applicable specification section (Figure 4). Although well-intended, typical specification language often does not provide adequate window installation guidance. Drawings (and subsequent shop drawings) and specifications must clearly and definitively provide installation instructions to answer the following questions:
The project team must clearly address these potentially unanswered questions prior to window fabrication, as relying on industry guidance and manufacturers’ written instructions alone will typically not be sufficient. Preparing sequencing diagrams is a useful tool to resolve how many building components interface (Figure 5).
AAMA 502-12, Voluntary Specification for Field Testing of Newly Installed Fenestrations, is a consensus document maintained by AAMA. The AAMA 502-12 voluntary specification is used to verify air infiltration resistance performance and water penetration performance of newly installed window products.
Performing field quality control testing early during the project can prove beneficial in identifying window-related issues before they become overwhelming (Figures 6 and 7). Remedial work, if required, will be easier to implement early during a project than if the building has been substantially completed and is occupied.
Field quality control requirements for windows are typically included in Part 3 – Execution of the applicable specification section (Figure 8). Project specifications requiring windows to be tested for air infiltration and water penetration resistance according to AAMA 502-12, without inclusion of any additional project specific requirements, stipulate the following:
The following questions, among others, would remain unanswered:
The project team must clearly address these potentially unanswered questions before field testing commences.
Current building codes and industry standards include several significant informational holes and gaps regarding window performance, installation, and field quality control requirements. Careful detailing during the design phase and quality installation practices will improve the likelihood of acceptable in-service window performance. Inclusion of appropriately robust field quality control requirements within the project documents will likely also prove beneficial. Designers can take several steps during the design phase to increase the likelihood of satisfactory performance of window units during their service life:
AAMA/WDMA/CSA 101/I.S.2/A440-11, North American Fenestration Standard/ Specification for Windows, Doors, and Skylights (NAFS). 2011.’
AAMA, Schaumburg, IL. AAMA 502-12, Voluntary Specification for Field Testing of Newly Installed Fenestration Products. 2012, AAMA, Schaumburg, IL. AAMA 450-10, Voluntary Performance Rating Method for Mulled Fenestration Assemblies. 2010, AAMA, Schaumburg, IL.
AAMA WSG-11, Window and Door Selection Guide. 2011, AAMA, Schaumburg, IL.
ASTM E283-04 (2012), Standard Test Method for Determining Rate of Air Leakage through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen. 2012, ASTM International, Conshohocken, PA.
ASTM E331-00(2009), Standard Test Method for Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by Uniform Static Air Pressure Difference. 2009, ASTM International, Conshohocken, PA.
ASTM E547-00(2009), Standard Test Method for Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by Cyclic Static Air Pressure Difference. 2009, ASTM International, Conshohocken, PA.
ASTM E783-02(2010), Standard Test Method for Field Measurement of Air Leakage Through Installed Exterior Windows and Doors. 2010, ASTM International, Conshohocken, PA.
ASTM E1105-00(2008), Standard Test Method for Field Determination of Water Penetration of Installed Exterior Windows, Skylights, Doors, and Curtain Walls, by Uniform or Cyclic Static Air Pressure Difference. 2012, ASTM International, Conshohocken, PA.
ASTM E2112-07 (2016), Standard Practice for Installation of Exterior Windows, Doors, and Skylights. 2016, ASTM International, Conshohocken, PA.
Robert Bateman. “A Flash in the Pan – A Field Guide for Windows and Doors,” RCI Interface, April 2010.
CSI SectionFormat™/PageFormat™, 2009. The Construction Specifications Institute, Alexandria, VA.
International Building Code, 2015. International Code Council, Country Club Hills, IL.
International Residential Code, 2015. International Code Council, Country Club Hills, IL.
Patrick Reicher is a senior engineer with Raths, Raths & Johnson, Inc. A licensed structural engineer in the state of Illinois, he has over 11 years of experience in the evaluation and repair design of exterior walls. Reicher is a Registered Exterior Wall Consultant (REWC), Registered Exterior Wall Observer (REWO), Certified Construction Specifier (CCS), and Certified Construction Contract Administrator (CCCA). He also serves on several committees as a professional member of the American Architectural Manufacturers Association (AAMA).
Rebecca Booth is an architectural intern with Raths, Raths & Johnson, Inc. (RRJ). She joined RRJ in 2013 after completing her Master of Architecture degree at the University of Illinois at Urbana- Champaign. Her experience includes façade investigations, condition survey documentation, repair design, construction administration, and litigation support for a range of materials and systems. She is a Certified Document Technologist (CDT) and is the secretary for the Building Enclosure Council – Chicago (BEC-C) Board of Directors.
Why should you advertise with IIBEC?