Skip to main content Skip to footer

Performance Attributes Of Fiberglass Shingles

May 15, 2007

Introduction
Fiberglass shingles have dominated the
market for steep-sloped roofs in the United
States for many years. The predominant
use of fiberglass shingles occurs on residential
structures, multifamily housing
units, and many commercial buildings.
Satisfactory performance of fiberglass shingles
during wind events is an extremely
important factor in the
protection of property.
Successful performance of
shingles is a combined
function of proper manufacture
and installation.
The past 30 years have
presented many opportunities
to examine numerous
shingle losses due to
wind events. For the most
part, fiberglass shingles
have performed well. In
many cases, however, it is
clear that improperly
manufactured or installed
shingles have prematurely
failed (Photo 1). Some
shingles, even when properly
manufactured or installed,
have failed at relatively
low wind speeds.
Purpose
The purpose of this
research is to examine
fiberglass shingle physical
properties and workmanship
factors that may contribute
to shingle failure during wind
events. Failure of shingles below the
required minimum wind speeds of the governing
building code is of particular importance.
Background
In the early 1990s, the performance of
fiberglass shingles came into question.
Numerous cases of fiberglass shingles splitting,
independent of external factors, were
reported (Photo 2). The shingles would split
on the exposed face of the roof in both horizontal
and vertical directions. Splitting occurred
predominantly on western and
southern exposures.
The causes of the splitting were widely
debated and resulted in the publication of
Photo 1 – Shingle failure. Note high placement of nails.
J U LY 2007 I N T E R FA C E • 2 3
numerous technical articles on the subject.
The causes of the splitting were attributed
to poor ventilation, workmanship, and in
some cases, poor quality of manufacture.
Eventually, through research, splitting was
found to be related to thermal cycling and
the physical properties of the shingles. The
earliest article on this subject was published
in Western Roofing, May/June 1990.1
Standards
One physical property that was identified
as a factor in the shingle splitting was
the “tear strength” of the shingles. Tear
strength is a physical property of fiberglass
shingles listed under American Society for
Testing and Materials (ASTM) Standard D
3462,2 “Asphalt Shingles Made from Glass
Felt and Surfaced with Mineral Granules.”
The minimum tear resistance listed under
this standard is 1,700.0 g.
The test method for tear strength is contained
within ASTM D 1922,3 “Propagation
Tear Resistance of Plastic Film and Thin
Sheeting by Pendulum Method.” The tear
strength test utilizes a pendulum device
that is based upon quality control procedures
initially developed by the textile
industry. Within the roofing industry, the
test procedure is commonly referred to as
the Elmendorf Tear Test. One conclusion
with regard to a factor contributing to splitting
is that shingles with a higher tear resistance
are less likely to split. In this regard,
there has been some improvement within
the industry. Some manufacturers tout the
tear resistance of their products, and in various
marketing literature state, “Bring on
your Elmendorf.” Regardless of the debate
over splitting, tear resistance is an important
physical property that helps to
describe the performance of shingles.
In addition to tear strength, fiberglass
shingles complying with ASTM Standard D
3462 must pass a fastener pull-through
test. Sufficient fastener pull-through resistance
values provide some assurance
that shingles will stay in place during
expected wind events. This test provides a
simple measurement of complex mechanical
effects that relate to the shingles’ resistance
to wind. It requires a minimum pullthrough
amount of a fastener for both one
and two layers of shingle material. One
layer is required to have a pull-through
resistance of 20.0 lbf, and two layers are
required to have a pull-through resistance
of 30.0 lbf.
Under ASTM D 3462, fiberglass shingles
must also meet other physical property
requirements, including a minimum net
mass of the reinforcement material. Under
Table 2 of ASTM D 3462, a
net mass of 1.35 lbs/100
ft2 is required.
Compliance with an
ASTM standard does not
necessarily imply a quality
product. ASTM standards
are developed through a
consensus agreement
among manufacturers,
contractors’ associations,
consultants, and other
interested parties. Often,
minimum product physical
properties are set as
standards.
Building Codes
Building codes in use
across the United States
have listed limited information
concerning placement
and numbers of fasteners
for shingles. The
1997 Uniform Building
Code4 (UBC) requires four
fasteners per shingle. The
UBC refers to “special conditions
and in special wind
regions” where additional attachment shall
be per manufacturer’s instructions. The
2003 International Building Code5 (IBC) and
the 2001 Florida Building Code6 refer to
ASTM D 3462 as a minimum requirement
for fiberglass shingles. These two codes also
refer to ASTM D 3161,7 “Wind-Resistance of
Asphalt Shingles,” for attachment procedures
in winds up to 110 mph. The Florida
Building Code, under Roofing Application
Standard (RAS) No. 115, calls for six fasteners
per shingle in “High Velocity Hurricane
Zones.”
ASTM D 3161 is a test procedure and
does not provide specific requirements for
the number of fasteners to be installed in
shingles. ASTM D 3161 defers to recommendations
from shingle manufacturers.
Manufacturers typically refer back to the
local building code with regard to recommendations
for additional attachment. For
the consumer or applicator, this circuitous
route of recommendations does not provide
useful information that may be necessary for
proper shingle installation and performance.
Fastener Location and Number
Shingles manufactured with the highest
degree of quality control can be improperly
installed and used in inappropriate situations.
The proper number and location of
Photo 2 – Shingle splitting.
24 • I N T E R FA C E J U LY 2007
fasteners used to attach shingles is critical
to successful performance. With respect to
fastener location, many shingle manufacturers
refer to the “nail zone.” The nail zone,
for 12″ x 36″ shingles, is typically along the
midsection of the shingle, approximately
5.5″ to 6.5″ above the butt edge (Photo 3A).
Some manufacturers have a line marked on
the shingle that indicates the proper fastener
location. Typical manufacturer recommendations
call for placing the fasteners so
the upper top edge or “head lap” of the preceding
shingle is penetrated as shown in
Diagram A.
Proper placement of
shingles is also critical. It
is important that the shingles be installed
with the proper exposure and the proper
head lap. Improper placement is shown in
Diagram B. In order to ensure proper placement
of shingles, contractors should put
chalk lines both horizontally and vertically
on the underlayment prior to the placement
of shingles (Photo 3B).
All shingle manufacturers who were
reviewed require a minimum of four fasteners
per shingle. Specific recommendations
in “high wind zones” are somewhat vague.
Several manufacturers show up to six fasteners
per
shingle in
“high wind
areas.” The
decision of
what is considered
a
high wind area is left up to the designer,
roofer, or consumer.
Laboratory Analysis
A total of 13 fiberglass shingles from
various manufacturers were acquired for a
series of tests, including six three-tab shingles
and seven laminate shingles. Several
different laboratory tests were performed in
order to determine the physical properties
of each shingle:
• Desaturated mat weight
• Tensile strength
• Tear strength
• Fastener pull-through: single layer,
double layer
• Fastener pull-through, laminate
layer: single layer, double layer
Small samples from the 13 shingles
were placed in a bath of hot, circulating solvent.
The asphalt and granules were
Photo 3B – Chalk lines.
Diagram A
Diagram B
J U LY 2007 I N T E R FA C E • 2 5
Photo 3A – Nail zone.
extracted from each sample until a clean fiberglass mat was
obtained (Photo 4). The fiberglass mat samples were dried and
weighed. The desaturated, dry, fiberglass mat weights ranged
from a low of 1.67 lbs/100 ft2 to a high of 2.17 lbs/100 ft2. All
of the samples tested contained fiberglass mats that exceeded
the ASTM D 3462 minimum requirement of 1.35 lbs/100 ft2.
The shingles were also tested for tensile strength (Photo 5).
Tensile strength is not listed as a requirement under ASTM D
3462, but was performed for informational
and comparison purposes. The tensile
strength ranged from a low of 82.0 lbf to a
high of 119.0 lbf.
The Elmendorf Tear Test, ASTM D 1922
(Photo 6), was performed on each of the
thirteen new shingle samples. The tear
strength ranged from a low of 830.0 g to a
high of 2,190.0 g.
Under ASTM D 3462, the minimum tear
strength requirement is 1,700.0 g. Overall,
eight of the 13 samples did not meet the
minimum ASTM requirement, including
three of the three-tab shingles and five of
the laminate shingles. It is interesting to
note that the product that fell below the
1,700.0 g tear resistance requirement was
contained within packaging that stated the
shingles were manufactured to ASTM D
3462 standards (Photo 7).
A fastener pull-through resistance test
was performed with single and double layers
of shingles. The purpose of the two
methods of testing was to simulate proper
and improper fastener placement. If a shin- Photo 6 – Elmendorf tear test.
26 • I N T E R FA C E J U LY 2007
Photo 4 – Desaturated mat weight.
Photo 5 – Tensile strength.
gle were to be nailed well above the nail zone, only one layer
of shingle would be penetrated. Within the three-tab shingles,
the single layer pull-through resistance ranged from a low of
19.50 lbf to a high of 32.25 lbf. The double-layer pull-through
resistance ranged from 38.55 lbf to 58.23 lbf. The ASTM D
3462 requirement for a single layer is a minimum pullthrough
resistance of 20.0 lbf.
To simulate nailing too high (out of the nail zone), a fastener pull-through test in the single layer of laminate shingles was performed
(Photos 8 and 9). The results ranged from a low of 16.46 lbf to a high of 29.91 lbf. When laminates are tested at the proper location (with-
Photo 8 – Fastener pull-through.
Photo 9 – Fastener pull-through.
Table A
J U LY 2007 I N T E R FA C E • 2 7
in the nail zone), the pull-through resistance
ranged from 24.55 lbf to 50.89 lbf.
Fastening with a headlap condition, the fastener
pull-through resistance ranged from a
low of 54.63 lbf to a high of 104.60 lbf.
Based on data listed in Table A, it is clear
that when a fastener is placed at the proper
location, fastener pull-through resistance
approximately doubles that seen when a
fastener is improperly placed.
A summary of overall physical property
data is included in Table A.
Comparison of Data
The correlation of the physical property
data was compared four different ways:
• Tear strength – tensile strength,
Graph A.
• Tear strength – desaturated mat
weight, Graph B.
• Fastener pull-through – desaturated
mat weight, Graph C.
• Fastener pull-through – tear
strength, Graph D.
Within Graphs A, B, and D, a vertical
line at 1,700.0 g has been inserted to indicate
samples that fell below the ASTM D
3462 minimum requirement for tear
strength. Data points to the left of the line
represent samples that did not meet the
minimum requirement.
A vertical line within Graph C and a horizontal
line within Graph D have been
inserted at 20.0 lbf to indicate those samples
that fell below the ASTM D 3462 minimum
requirement for fastener pull-
Graphs A-D
www.rci-mercury.com
28 • I N T E R FA C E J U LY 2007
through. Data points to the left of the vertical
line and below the horizontal line represent
samples that did not meet the minimum
requirement.
In reviewing Graphs A – D, clear correlations
exist between tear strength and tensile
strength, tear strength and desaturated
mat weight, fastener pull-through and
desaturated mat weight, and tear strength
and fastener pull-through.
Conclusions
Successful performance of fiberglass
shingles is clearly dependent upon quality
control and workmanship during the manufacturing
process. From a workmanship
standpoint, the proper number and location
of fasteners in the “nail zone” is critical. It is
also critical that the contractor aligns or
places the shingles properly. Other factors
certainly come into play, such as properly
driven fasteners and adequate performance
of the self-adhesive strip.
Test your knowledge with the following questions
developed by Donald E. Bush Sr., RRC,
FRCI, PE, chairman of RCI’s RRC Examination
Development Subcommittee.
1. What information should
be sought during an
interior inspection of a
roof soffit through
removal of a ceiling
panel or other access
mode? These
inspections should be
part of all roof condition
assessment inspections.
2. What information should
be noted when
inspecting the underside
of all roof decks?
3. Why is it important to
know if there are
changes in deck types
and/or span direction?
4. What conditions found
during a roof condition
assessment would
indicate the need for
tear-off and
replacement?
Answers on page 30
J U LY 2007 I N T E R FA C E • 2 9
Photo 7 – Shingle label on batch that fell below the 1,700.0 g tear resistance requirement.
Based upon data generated to date,
shingles manufactured with a higher mat
weight have increased tear strength and a
higher fastener pull-through resistance. It
is also clear that shingles manufactured
with higher tear resistance will have
increased fastener pull-through resistance.
The higher the fastener pull-through
strength, the more resistant a shingle is to
failure at a nail head as a result of uplift
during wind events. Fiberglass shingles
should be manufactured in compliance with
ASTM D 3462 requirements.
Building codes and shingle manufacturer
recommendations for additional fasteners
in “high wind zones” are ambiguous and
confusing. The public would be better
served if building codes and shingle manufacturers
were more specific with regard to
the need for additional fasteners within
“high wind zones.”
Author’s Note: Special thanks to Gerald B.
Curtis, CPRC, for technical assistance in the
preparation of this article.
References
1. Koontz, Jim D., “Fiberglass Shingles:
Shingle Splitting Problem Observed
in a Number of Western
Applications,” Western Roofing,
May/June 1990.
2. “Standard Specification for Asphalt
Shingles Made from Glass Felt and
Surfaced with Mineral Granules,”
ASTM D 3462 – 03a.
3. “Standard Test Method for Propagation
Tear Resistance of Plastic
Film and Thin Sheeting by Pendulum
Method,” ASTM D 1922 – 00a.
4. Uniform Building Code (1997),
Seventy-Fifth Edition, International
Conference of Building Officials,
Chapters 15-16.
5. International Building Code (2003),
International Code Council, Chapter
15.
6. “Standard Test Method for Wind
Resistance of Asphalt Shingles (Faninduced
Method),” ASTM D 3161 –
03b.
7. Florida Building Code (2001), Second
Edition, International Code Council,
Chapter 15.
Jim D. Koontz, RRC, PE, has been involved in the roofing
industry since 1960, encompassing experience as a roofer,
estimator, manager of a roofing company, consultant, lecturer,
and researcher. As a consultant, Koontz has worked in
over 40 states, Canada, Mexico, and the Caribbean. Past
clients include numerous agencies of the federal and state
governments, large insurance companies, developers, material
manufacturers, contractors, and architects. Services provided
by Jim D. Koontz & Associates, Inc., of which Jim is
president, include investigation of roof problems, design of roofing projects, financial
analysis of proposed roofing and reroofing projects, inspection during construction, laboratory
analysis of roofing materials, and roofing research on all types of roofing, insulation,
and waterproofing systems.
Jim D. Koontz, RRC, PE
Answers to questions from page 29:
1. A. Steel decks
• Corrosion/rust.
• Differential deflection at side or
end laps.
• Condition of welds.
• Do rooftop components –
HVAC, other equipment, access
hatches, etc., have their own
structural angle supports?
B. Wood decks
• Warping.
• Shrinkage.
• Rotting.
• Excessive joint gaps.
• Anchorage.
C. Structural concrete
• Cracks over one-eighth inch.
• Excessive deflection in evidence.
• Spalling.
• Rust staining.
D. Poured gypsum
• Excessive deflection of bulb tees.
• Staining of form board.
• Cracking.
• Evidence of excess moisture.
2. Changes in deck type or span direction
• Drain locations and drain leader
accessibility.
• Evidence of foundation settlement
(cracks in bearing walls).
• Location of rooftop HVAC units and
supply ducts or chiller pipes.
• Evidence of leakage and/or
condensation.
3. Expansion and contraction must be
considered in the replacement roof
design.
4. Extensive ponding.
• Deteriorated deck.
• Wet and/or deteriorated insulation.
• Poor anchorage of deck and
insulation with no practical way to
mechanically anchor the
components.
• An essentially irreparable
membrane.
Reference: Manual of Low-slope Roof
Systems – Fourth Edition
NRCA
30 • I N T E R FA C E J U LY 2007
Recent statistics from the roofing industry have
shown that roofing accounts for 0.1 percent of the
U.S. Gross Domestic Product, but roofing materials
contribute 6 percent of the volume in landfills.
— RRCI
RO O F I N G W A S T E