Skip to main content Skip to footer

The Use of Closed-Cell Spray Polyurethane Foam (CCSPF) To Enhance The Structural Properties Of Wall And Roof Assemblies

May 15, 2010

This article discusses field
observations and research that
document the ability of closedcell
spray polyurethane foam
(ccSPF)1 to add structural
strength to roof and wall
assem blies.
It has been known for many years that
an SPF roofing system can enhance the
wind uplift resistance of a roof covering.
Field observations of SPF performance after
Hurricanes Hugo and Andrew led to the
Spray Polyurethane Foam Alliance (SPFA)
sponsoring wind uplift testing of SPF roofing
systems by Underwriters Laboratories
(UL) and Factory Mutual Global (FM
Global). According to UL, SPF’s resistance
exceeded the capacity of the equipment to
measure wind uplift pressures. UL observed
that SPF roofs applied over BUR and metal
increased the wind resistance of those
existing roof coverings. FM Global measured
ccSPF’s adhesion to concrete at over
990 psf of uplift pressure; and over metal
deck assemblies, at over 220 psf of resistance.
(Note: The mode of failure was fastener
back-out, not the foam.) But little
mention has been made of ccSPF’s ability to
prevent structural damage to roof and wall
assemblies.
ROOF DECK STRUCTURAL ENHANCEMENT
First, let’s look at some recently conducted
laboratory research. In 2008,
Honeywell Corporation, Huntsman Cor po –
ra tion, and NCFI Polyurethanes sponsored
research on the wind uplift enhancement
capability of ccSPF installed to the underside
of wood deck assemblies. This was
prompted by field research conducted by
groups such as the Roofing Industry
Committee on Weather Issues’ (RICOWI)
hurricane team investigators and veteran
SPF industry professionals. The investiga-
Figure 1 – Wind uplift resistance testing
conducted at the Hurricane Research
Center, University of Florida, in 2008 and
presented by Richard Duncan, PhD, PE, at
Sprayfoam 2008.
4 • IN T E R FA C E S E P T E M B E R 2010
tors observed examples of ccSPF installed to
the interior structure of a building that
appeared to minimize or eliminate structural
damage caused by high wind events,
while other sections of the building without
ccSPF were destroyed by pressurization.
The sponsors contracted with the
Hurricane Research Center located at the
University of Florida to conduct ASTM
E330-02 (Standard Test Method for Struc –
tur al Performance of Exterior Windows,
Doors, Skylights, and Curtain Walls by
Uniform Static Air Pressure Difference) testing
of wood roof deck assemblies (Figure 1).
According to ASTM, “This test method is a
standard procedure for determining structural
performance under uniform static air
pressure difference.” This typically is
intended to represent wind loads on exterior
building elements and is accepted by the
state of Florida and Miami Dade County for
testing structural elements (including roof
deck assemblies) for high wind resistance.
Two types of SPF applications were tested
on OSB panels with wood studs installed
in accordance with Florida Building Code
requirements for high-wind-velocity
regions.
The results
were eye opening.
Even with a roof
deck assembly
that was constructed
to comply
with Florida’s
high wind re –
quire ments, the
ccSPF increased
wind uplift resistance
on the 3-in
fill from 3 to 3.2
times its original
resistance. The
fillet-style application
increased
wind uplift resistance
from 1.9 to
2.2 times its original resistance. (See Table
1.)
CASE STUDY 1
White’s Lumber, Port Isabel, TX
Hurricane Dolly Investigation;
Mason Knowles Consulting, LLC
Before Hurricane Allen blew into South
Padre Island, TX, in 1980, the author
installed a portion of an SPF application to
the office section of a lumberyard’s postframe-
construction building. The crew completed
one corrugated wall and roof section
before the storm hit. After the storm, the
only metal remaining were the sections
insulated with ccSPF.
Figure 2 shows White’s Lumber’s openend,
post-frame-construction building. New
metal was installed to half of the building
(right side of the photo) in 2008, and the old
metal originally installed in 1980 is on the
left. For close to 30 years, there were no significant
wind events in the area.
In 2009, Hurricane Dolly—a category 2
storm, packing winds of more than 110
mph—made a direct hit on the towns of Port
Isabel and South Padre Island, TX. White
The Promise.
As the leader in roofing
durability and
we’re owners, consultants, contractors
and architects
and long into the
future.
The Proof.
For almost 50 years,
Sika Sarnafil
has been producing products safely
that are safe to use—and good for the
environment. We live that commitment
the same way we serve
our customers:
not just by doing the
right thing,
but by doing things right.
Unsurpassed in
Durability
Recycling
Energy Performance
Roofing 􀀖
􀀖
􀀖
􀀖
Learn what makes our long-lasting
roofing and waterproofing solutions
the smart choice by visiting:
www.sustainabilitythatpays.com
www.sustainabilitythatpays.com
SUSTA TAINAB
PR M
Prom
membrane recycling, w
to helping building ow
BILITY
MISE
mise.
g e’re committed
wners roofing
meet their sustainability
Proo
pr
a
th
wners, s y goals today—
e of.
roducts at customers
thin
First in Recyclin
Smartest in Ene
􀀖􀀖
􀀖􀀖
􀀖􀀖
􀀖􀀖
e ngs ng
ergy Savings
Best in Fire Perf
Longest Record
Sustainable Roo
􀀖
􀀖􀀖
formance
in
ofing Systems
ou
waterproo
b
sustainabilityt
r ofing hatpays.Table 1
Figure 2 – The author installed the old metal roof on this building in
1980. A new metal roof was installed in 2008 on the right side of the
building.
S E P T E M B E R 2010 I N T E R FA C E • 5
Maximum Wind Uplift Load PSF
(pounds per square foot)
SPF Avg. Max. Min. 1 2 3 4 5 Std. Dev.
None 75 105 47 75 105 71 76 47 21
Fillet 175 195 146 195 178 178 146 178 17
3-in Fill 250 283 200 283 246 200 254 269 31
Lumber and Supply lost half of its roof, as shown in Figures 3 and 4. But
something looks strange, doesn’t it? The left side of the building has a new
metal skin installed in 2008, while the right side has metal panels that are
over 29 years old. As can be seen, the new metal blew off in the storm, while
the old metal remained in place. Both are 29-gauge metal2 with similar fasteners
and fastening patterns (in fact, the new metal portion had a closer
fastening pattern than the old section, and both
are fastened to the same wood framing).
There is a simple explanation. When the
metal was replaced in 1980, the owner contracted
with the author to install a 2-lb, closed-cell
spray foam in a “picture frame” pattern to help
secure the metal panels to the wood trusses.
Twenty-nine years later, this safety net proved
invaluable (Photo 5). Unfortunately, when the
owner replaced the metal on half of the building
in 2008, he could not find an SPF applicator to
replace the foam (Photo 6). Consequently, high
winds blew off major portions of the new metal
panels.
Figures 3 (left) and 4 (below) – Half of the roof
blew off of White’s Lumber during Hurricane
Dolly.
Figure 6 – The ccSPF was removed to install new metal.
Figure 5 – Old metal secured with ccSPF.
6 • IN T E R FA C E S E P T E M B E R 2010
As shown in Figures 7 and 8, the main cause of failure of the
new metal skin was pulling of the fasteners through the metal.
INCREASING RACKING STRENGTH OF ASSEMBLIES
Research demonstrates that ccSPF can help increase the racking
strength of wall assemblies. Three research studies have been
conducted by the Spray Polyurethane Foam Alliance (SPFA) and
its predecessor, the Polyurethane Contractor’s Division (PFCD) of
the Society of the Plastics Industry, on the racking strength of
ccSPF. In 1992 and again in 1996, PFCD contracted with the
􀀤􀁐􀁈􀁕􀁌􀁆􀁄􀁑􀀃􀀫􀁜􀁇􀁕􀁒􀁗􀁈􀁆􀁋􀂷􀁖􀀃􀀪􀁄􀁕􀁇􀁈􀁑􀀃􀀵􀁒􀁒􀁉􀂊􀀃􀀤􀁖􀁖􀁈􀁐􀁅􀁏􀁜􀀃􀁋􀁄􀁖􀀃􀁖􀁈􀁗􀀃􀁗􀁋􀁈􀀃􀁖􀁗􀁄􀁑􀁇􀁄􀁕􀁇􀀃􀁅􀁜􀀃􀁚􀁋􀁌􀁆􀁋􀀃􀁄􀁏􀁏􀀃􀁒􀁗􀁋􀁈􀁕􀀃
􀁊􀁕􀁈􀁈􀁑􀀃􀁕􀁒􀁒􀁉􀁖􀀃􀁄􀁕􀁈􀀃􀁐􀁈􀁄􀁖􀁘􀁕􀁈􀁇􀀑􀀃􀀲􀁘􀁕􀀃􀀷􀁒􀁗􀁄􀁏􀀃􀀤􀁖􀁖􀁈􀁐􀁅􀁏􀁜􀀃􀀺􀁄􀁕􀁕􀁄􀁑􀁗􀁜􀀃􀁓􀁕􀁒􀁙􀁌􀁇􀁈􀁖􀀃􀁒􀁚􀁑􀁈􀁕􀁖􀀃􀁚􀁌􀁗􀁋􀀃􀁖􀁌􀁑􀁊􀁏􀁈􀀃􀁖􀁒􀁘􀁕􀁆􀁈􀀃
􀁕􀁈􀁖􀁓􀁒􀁑􀁖􀁌􀁅􀁌􀁏􀁌􀁗􀁜􀀃􀁉􀁕􀁒􀁐􀀃􀁗􀁋􀁈􀀃􀁇􀁈􀁆􀁎􀀃􀁘􀁓􀀑􀀃􀀷􀁋􀁌􀁖􀀃􀁌􀁖􀀃􀁓􀁈􀁄􀁆􀁈􀀃􀁒􀁉􀀃􀁐􀁌􀁑􀁇􀀃􀁗􀁋􀁄􀁗􀀃􀁒􀁑􀁏􀁜􀀃􀀤􀁐􀁈􀁕􀁌􀁆􀁄􀁑􀀃􀀫􀁜􀁇􀁕􀁒􀁗􀁈􀁆􀁋􀀃􀁆􀁄􀁑􀀃􀁒􀁉􀁉􀁈􀁕􀀑
􀀷􀁒􀀃􀁏􀁈􀁄􀁕􀁑􀀃􀁐􀁒􀁕􀁈􀀃􀁄􀁅􀁒􀁘􀁗􀀃􀁗􀁋􀁈􀀃􀀤􀁐􀁈􀁕􀁌􀁆􀁄􀁑􀀃􀀫􀁜􀁇􀁕􀁒􀁗􀁈􀁆􀁋􀀃􀀪􀁄􀁕􀁇􀁈􀁑􀀃􀀵􀁒􀁒􀁉􀀃􀀤􀁖􀁖􀁈􀁐􀁅􀁏􀁜􀀏􀀃􀁓􀁏􀁈􀁄􀁖􀁈􀀃􀁆􀁄􀁏􀁏􀀃􀀛􀀓􀀓􀀑􀀛􀀚􀀚􀀑􀀙􀀔􀀕􀀘􀀃
􀁒􀁕􀀃􀁙􀁌􀁖􀁌􀁗􀀃􀁘􀁖􀀃􀁒􀁑􀁏􀁌􀁑􀁈􀀃􀁄􀁗􀀃􀁚􀁚􀁚􀀑􀁋􀁜􀁇􀁕􀁒􀁗􀁈􀁆􀁋􀁘􀁖􀁄􀀑􀁆􀁒􀁐􀀑
The key to our
Garden Roof® is our
Monolithic Membrane
6125®, a seamless
rubberized asphalt
membrane with a 45+
year track record for
critical waterproofing
and roofing applications
world-wide.
From concept to completion
American Hydrotech, Inc. | 303 East Ohio | Chicago, IL 60611 | 800.877.6125 | www.hydrotechusa.com
􀂋􀀃􀀕􀀓􀀔􀀓􀀃􀀪􀁄􀁕􀁇􀁈􀁑􀀃􀀵􀁒􀁒􀁉􀀃􀁌􀁖􀀃􀁄􀀃􀁕􀁈􀁊􀁌􀁖􀁗􀁈􀁕􀁈􀁇􀀃􀁗􀁕􀁄􀁇􀁈􀁐􀁄􀁕􀁎􀀃􀁒􀁉􀀃􀀤􀁐􀁈􀁕􀁌􀁆􀁄􀁑􀀃􀀫􀁜􀁇􀁕􀁒􀁗􀁈􀁆􀁋􀀏􀀃􀀬􀁑􀁆􀀑
􀀹􀁄􀁑􀁆􀁒􀁘􀁙􀁈􀁕􀀃􀀳􀁘􀁅􀁏􀁌􀁆􀀃􀀯􀁌􀁅􀁕􀁄􀁕􀁜􀀃􀀐􀀃􀀹􀁄􀁑􀁆􀁒􀁘􀁙􀁈􀁕􀀏􀀃􀀥􀀦
S E P T E M B E R 2010 I N T E R FA C E • 7
Figures 7 (right) and 8 (below) – Fasteners pulled
through the new metal skin where there was no
ccSPF to help secure the panels to the wood trusses.
NAHB Research Cen –
ter to conduct racking
load tests on ccSPFinsulated
wall panels.
The NAHB Research
Center concluded,
“Dur ing a design
racking event such as
a hurricane, there
would be less permanent
deformation of
wall elements and
possibly less damage
to a structure that
was braced with SPFfilled
walls.“
The 1992 re –
search tested ccSPF
installed at 3 inches
to wall panels constructed
of plywood
and vinyl cladding,
respectively. The panels
used 2- x 4-in
wood studs with
spacing at 16, 24, 32,
and 48 inches off center
(OC). As indicated
in Table 2, ccSPF increased the maximum
average racking load of a vinyl-clad wall
assembly from 913 lbs to over 2,800 lbs at
16-in spacing and more than 2,300 lbs,
even at the 48-in stud spacing. It doubled
the maximum average racking load of a plywood-
clad wall assembly at 16-in spacing
and was 2.2 times the racking load at 24-in
spacing
The 1996 study measured the racking
strength of OSB- and drywall-clad walls,
respectively, with metal studs at 16 in OC.
As indicated in Table 3, the ccSPF-insulated
walls at 3 in thick increased the drywallclad
wall from 2,400 lbs of racking load to
5,380 lbs, and the OSB-clad walls from
4,800 lbs of racking load to 6,000 lbs.
In 2007, SPFA tested ccSPF-insulated
walls constructed with 2-in x 4-in wood
studs, 16 in OC to both polyiso- and OSBsheathed
wall assemblies at Architectural
Testing, Inc. (ATI). As indicated in Table 4,
the ccSPF doubled the racking load of the
polyiso-sheathed wall assemblies.
CASE STUDY 2
Pascagoula Shrimp and Ice Company
Hurricane Katrina Investigation;
RICOWI
As shown in Photo 9, internal pressurization
destroyed the tongue-and-groove
roof deck of this ice plant during Hurricane
Katrina. However, the metal building section
(depicted in Photo 10) that was insulated
with ccSPF and connected to the same
structure, survived with no damage.
Table 2 – 1992 NAHB Research Center racking study (average maximum racking load in
pounds).
Table 3 – 1996 NAHB Research Center racking study (average
maximum racking load in pounds).
Table 4 – ATI racking study (average maximum racking load in
pounds).
8 • IN T E R FA C E S E P T E M B E R 2010
1992 NAHB Research Center Racking Study
NonSPF Panels SPF Panels
Stud Vinyl Plywood Vinyl Plywood
Spacing Sheathed Sheathed w/ccSPF w/ccSPF
16 in 913 2,890 2,800 5,300
24 in Not tested 2,420 Not tested 6,387
32 in Not tested Not tested 2,588
48 in Not tested Not tested 2,298
1996 NAHB Research Center
Racking Study
Assembly Maximum Racking Load
OSB w/R19 fiberglass 4,800
OSB w/ccSPF 6,000
Drywall w/R19 fiberglass 2,400
Drywall w/ ccSPF 5,380
ATI Racking Study
Assembly Maximum Racking Load
1½-in, 2-lb density SPF 2,259
w/polyiso sheathing
3½-in, 2-lb density SPF 2,152
w/polyiso sheathing
Polyiso sheathing 1,109
OSB sheathing 2,908
None of the areas insulated with ccSPF
sustained any damage. An interesting
observation is that many of the ccSPF-insulated
portions of the building were areas
that would be considered less structurally
sound than other areas (if they were not
structurally reinforced with ccSPF). Figure
11 shows the foam sprayed against metal
roof decking and corrugated metal wall
panels.
EXTERIOR CCSPF APPLICATIONS TO MINIMIZE WIND
AND WATER DAMAGE
Another use of ccSPF is on the
exterior of buildings to prevent
their damage from high winds and
flying debris. There are many
cases of ccSPF installed to the
exterior of metal buildings, houses,
and small commercial buildings
where such application has
minimized structural damage and
water intrusion. The foam acts as
a shock absorber for wind-driven
debris;3 a barrier to wind-driven
rain; an air barrier to reduce the
potential for high wind pressurization
of the building; and a glue
that holds it together and distributes
the load so that if pressurization
occurs, the weakest individual
components and fastenings are
not exposed to the full brunt of the
pressure.
Figure 11 – Foam
sprayed against
metal roof
decking and
corrugated metal
wall panels.
S E P T E M B E R 2010 I N T E R FA C E • 1 1
Figure 9 – Internal pressurization
during Hurricane Katrina
destroyed a tongue-and-groove
wood deck at this ice plant.
Figure 10 – The metal building
below was connected to the
structure shown in Figure 9
and was insulated with ccSPF.
It received no damage during
Hurricane Katrina.
CASE STUDY 3
Port Isabel RV Park
Hurricane Dolly
Investigation;
Mason Knowles
Consulting, LLC
A recent example
of this design is
the recreation building
at the Port Isabel
RV Park. Around
1978, a tropical
storm caused damage
to the exterior
wood cladding, al –
low ing water intrusion
into the building.
After unsuccessful
attempts to
correct the problem, the author was contracted
to install 1.5 in of ccSPF to the outside
of the entire structure. The application
of ccSPF stopped the leaks into the building.
In 1980, the building was directly in the
path of Hurricane Allen, a category 5 storm
when it hit Port Isabel. Wind speeds were
recorded in Port Mansfield (50 miles north
of Port Isabel) at 130 knots.4 The Port Isabel
Press reported two weeks after the storm
that the Coast Guard station at Isla Blanca
Park on South Padre Island
(one mile from the buildings in
Port Isabel) recorded wind
speeds in excess of 125 mph.
The wood structure survived
with no damage and no leaks.
Many other buildings in the immediate
vicinity were seriously damaged from high
winds and water intrusion.
In 2009, the building was in the direct
path of Hurricane Dolly, with up to 110
mph winds. Again, the building survived
with no damage except for a small crack
(see Photo 15) and no water intrusion.
CASE STUDY 4
Military Tent and Plywood Buildings
Reinforcement;
Department of Defense
Presentation at Sprayfoam 2010
The Department of Defense (DOD) has
an ongoing program to insulate tents and
other nonair-conditioned structures in
selected bases in Iraq and Afghanistan with
2-lb density ccSPF (Photos 16
and 17). The main goal is to protect
against high temperatures
in the areas. According to John
Siller of the Power Surety Task
Force of the DOD, “The foam is
providing outstanding performance
in this goal.” [Editor’s
Note: See “How Insulation Saves
Lives and $$ in Iraq and
Afghanistan” on page 42 for
more about this project and the
activities of an RCI member
Figure 13 – Same
building, 2006.
Figure 15 –
Only
damage
after two
hurricanes
and 30
years of
service.
Figure 14 – Same building after
Hurricane Dolly in 2009.
Photo 16 – Example before
application of ccSPF.
Photo 17 – Example after ccSPF.
12 • I N T E R FA C E S E P T E M B E R 2010
Figure 12 – Port Isabel RV Park, 1979
(before Hurricane Allen).
working in the Middle East.] But a recent incident may be prompting
the military to look seriously at using ccSPF
to protect structures against damage from
mortars or improvised explosive devices
(IEDs). On October 17, 2008, Mearl “Skip”
Kline was working with a crew from West
Roofing that was insulating tents with
ccSPF at a military base just outside the
city of Baqubah, Iraq. According to Kline,
“The base was attacked by what Army personnel
assumed to be 107mm rockets. We
hit the ground when we heard the shells
coming into the camp. The shells impacted
approximately 40
yards from us and
80 to 100 yards
away from the
ccSPF tents. We
were told this type
of ordnance has a
kill radius of ap –
proximately 30
yards. The tents
[that were insulated
with ccSPF] absorbed shrapnel
from the shells
without [the
shrap nel] penetrating
the structures.
After the
attack, Army personnel
were im –
pressed by the
foam’s ability to absorb the shock of the
shrapnel hits. Many expressed a desire to
use the foam to increase the impact resistance
from enemy shells.” (See Photos 18
and 19.)
THE FUTURE OF CCSPF AS A STRUCTURAL
MATERIAL
It is clear from the research and case
studies cited that ccSPF can be an important
tool for designers to enhance the highwind
resistance of buildings. However, some
important steps are required to use the
materials as a structural enhancement.
Roofing contractors &
specifiers choose Durapax
coal tar roofing systems.
Coal Tar:
First Choice for Flat Roofs
Durapax:
First Choice in Coal Tar
610.579.9075 Durapax.com
• Coal tar roofing provides low cost and
long life (25+ years)
• Many coal tar roofs last more than
50 years
• Coal tar’s cold flow properties provide
self-healing
• Superior technical & customer support
• Delivery you can depend on
• Comprehensive warranties
• UL & FM approved systems
Specify your next flat roof with a
Durapax coal tar roofing system.
Figure 19 – Shell fragments still capable of severely wounding
personnel were embedded in the foam of the structures, 80 to 100
yards away from impact.
Figure 18 – This metal building was approximately 50 yards from the mortar shell’s impact.
S E P T E M B E R 2010 I N T E R FA C E • 1 3
ADDITIONAL RESEARCH AND TESTING
• Engineering studies to quantify the
specific strength added when ccSPF
is installed to walls and ceilings
• Whole-building tests of ccSPF applications
for structural strength
• Effects of aging on the foam’s adhesive
and physical properties
• Fire testing
• Testing of a wider variety of roof and
wall assemblies
• Testing of assemblies for seismic
structural enhancement and impact
absorption
SPECIFICATIONS AND GUIDELINES
• Industry peer-reviewed guidelines
• Flashing details
• Substrate preparation
• Thickness and density required for
each application to achieve desired
result
• Building code approvals
QUALITY ASSURANCE
• Inspection procedures (sampling,
visual inspection, etc.)
• Training and certification of applicators
and inspectors
• Warranties and exclusions
CONCLUSIONS AND COMMENTS
Based on research and field observations,
it appears that the installation of
ccSPF to either the exterior or interior of a
building can result in significant structural
benefits and reduced building damage from
impact and high winds. Additional information
needs to be developed by the SPF
industry, building research, and design
community to provide the tools necessary to
offer this product as a primary structural
enhancement material.
FOOTNOTES
1. While not a new product, the term
“ccSPF” is the most current designation
that refers to a typical closedcell
spray polyurethane foam ranging
in density from 1.5 to 3.5 lbs per
cu ft used for insulation and roof
coverings. The newer designation
differentiates the product from a
low-density, nonstructural, opencell
spray polyurethane foam that
has become popular in interior
applications as an insulation and air
barrier material.
2. Since 29 gauge is a low-strength
metal sheathing material, it is much
more likely that fasteners will pull
out of such metal, causing damage
in a high-wind event. A thicker
sheathing might have survived the
storm without damage.
3. Wind-driven debris will typically
cause dents, cracks, and gouges to
exterior applications of ccSPF. A
sealant compatible with the coating
can repair small (less than 4 in)
mechanical damage. Larger areas of
damage can be repaired by removing
the damaged foam and replacing it
with new foam using high-density
foam kits or standard SPF proportioning
equipment. Recoating may
be required if the damage covers
large areas of the structure.
4. Joseph E. Minor, PE, William L.
Beason, and Timothy P. Marshall,
“Effects of Hurricane Allen on
Buildings and Construction,”
Proceedings of the Fourth National
Conference on Wind Engineering
Research, Seattle, WA, 1981.
REFERENCES
1. Architectural Testing, Inc., ccSPF
wall panel performance testing,
sponsored by Spray Polyurethane
Foam Alliance (SPFA), 2007.
2. Richard Duncan, PhD, PE, “Wind
Uplift Resistance Testing E330-02,”
conducted at the Hurricane
Research Center, University of
Florida, presented at Sprayfoam
2008.
3. FM Class 1 Roof Coverings Test
Program of SPF Roofing Systems
(sponsored by SPFA), 2005.
4. Mearle “Skip” Kline, in June 15,
2010, interview with author on his
observations of rocket damage mitigation
Oct. 17, 2008, to buildings
insulated with ccSPF at an army
base in Baqubah, Iraq.
5. Mason Knowles, Mason Knowles
Consulting, “Observations of Hur –
ricane Dolly,” presented at RICOWI
Fall Symposium, 2009.
6. Joseph E. Minor, PE, William L.
Beason, and Timothy P. Marshall,
“Effects of Hurricane Allen on
Buildings and Construction,” Fourth
National Conference on Wind
Engineering Research, Seattle, WA,
1981.
7. NAHB Research Center, ccSPF wall
panel performance testing, sponsored
by the Polyurethane Foam
Contractors Division of the Society
of Plastics Industry (PFCD), 1992
and 1996.
8. Roofing Industries Committee on
Weather Issues (RICOWI), Hurricane
Katrina Wind Damage Investigation,
2005.
9. John Spiller, “Spray Foam in the
Department of Defense,” OSD Power
Surety Task Force, presented at
Sprayfoam 2010 conference.
10. Underwriters Laboratories, Inc.,
Special Services Investigation of
Uplift Resistance Testing for UL
Classified BUR and Spray-Applied
SPUF Roofing Systems, 1993.
Mason Knowles is the president of Mason Knowles
Consulting, LLC, providing technical services and educational
programs for the spray polyurethane industry. He has
more than 40 years’ experience in the SPF industry as a contractor,
material supplier/manufacturer, equipment manufacturer,
and trade association professional. Knowles is the
former executive director of the Spray Polyurethane Foam
Alliance (SPFA); chairman of ASTM D08.06, Subcommittee on
Spray Polyurethane Foam Roofing; chairman of the ASTM task group for the spray
polyurethane foam standard specification (ASTM C1029); a member of the National
Institute of Building Science’s Building Envelope Thermal and Energy Committee; a
member of the RICOWI Hurricane Investigation Team; and a roofing/building envelope
inspector.
Mason Knowles
14 • I N T E R FA C E S E P T E M B E R 2010