Skip to main content Skip to footer

Air Infiltration and Its Consequences for Building Enclosures in Hot/Humid Climate Zones

November 16, 2022

IIBEC Interface November 2022
Air Infiltration and Its
Consequences for Building
Enclosures in Hot/Humid
Climate Zones By David Finley and Manfred Kehrer
This paper was originally presented at the 2022 IIBEC International Convention and Trade Show. To maximize the efficacy and
performance of building
enclosure walls, the four major
building enclosure control
layers (liquid water, air, water
vapor, and thermal) should be
designed and installed with continuity. The position
of these control layers within a wall assembly
can also significantly affect the hygrothermal
performance (movement of heat and moisture)
of an exterior wall. In a previous study,1,2 we
reviewed the risk of microbial growth within
energy code—compliant exterior walls that use
a split insulation arrangement, both exterior
continuous insulation and batt insulation within
the stud cavities, located in Climate Zones 4 and
higher, as defined in the International Energy
Conservation Code (IECC).3
In this study, we focus on quantifying the risk
of microbial growth and potential deterioration of
the interior gypsum wallboard for energy code—
compliant exterior walls in hot and humid climate
zones (such as Climate Zones 1 and 2) because of
unintentional exterior air infiltration.
EFFECTS OF INSULATION
Because the introduction of insulation in
any exterior wall system reduces the heat flow
through the wall assembly, the surface temperatures
of materials inboard of the insulation are
reduced in hot and humid climates (especially
when air conditioning is used). In addition to the
temperature drop in the interior space caused by
the insulation, a subsequent and greater reduction
in the saturation vapor pressure Pws occurs,
as shown in Eq. (1), which can cause the development
of condensation.
Saturation vapor pressure is the maximum
pressure of water vapor, or absolute humidity,
that can exist within the air. Relative humidity
(RH) is the ratio of actual water vapor in the air
to the maximum amount of water vapor at saturation
(Eq. [2]). Therefore, the RH of saturated
air (that is, actual vapor pressure equal to the
saturation vapor pressure) is 100%.
Because of the relationship between the
significant drop in saturation vapor pressure
associated with thermal gradients via insulation,
increased RH as well as the inherent reduction
in surface temperatures inboard of the insulation
layer is expected. Therefore, it is important
and ideal to place the thermal control entirely
outboard of the other building enclosure control
layers, thereby protecting the structure
and moisture-sensitive finishes from elevated
RH and potential condensation development.
However, the energy codes allow either splitting
the thermal control layer so that it sandwiches
some of the other control layers or placing it
entirely inboard of the control layers within the
stud cavity. If the insulation is placed in a split
or inboard position, it is imperative to control
or reduce the vapor and air transport into and
through the insulation layer to avoid condensation
development or increased surface RH that
can promote microbial growth.
Condensation can occur on surfaces when
the surface temperature drops below the dew
point temperature of the ambient air, which
occurs when the vapor pressure reaches the
saturation vapor.
where
T = temperature (°K)
Note that Pws will drop exponentially relative to T.
Equation 1
Equation 2
where
Pw = vapor pressure
where
Tdp = dew point temperature (°C)
Ti = interior temperature (°C)
A = 17.62
B = 243.12
Equation 3
For interstitial spaces, such as within a wall
system, the necessary moisture (vapor) for
condensation or elevated surface RH typically
comes from two sources: vapor diffusion and
air leakage. Both of these mechanisms should
be considered when evaluating the anticipated
hygrothermal performance of a proposed exterior
wall assembly.
Equation 1
Equation 2
Equation 3
where
November 2022 IIBEC Interface • 29
DIFFUSIVE CONDENSATION
Diffusive condensation occurs when moisture
migrates from air with a higher vapor pressure
to air with a lower vapor pressure. Diffusion
is a much slower method of transferring moisture
than airflow. As a result, it is typically a less
significant contributor to moisture migration
associated with condensation problems than
airflow. Nonetheless, the placement of vapor
retarders within an exterior wall assembly with
respect to the location of the insulation warrants
careful consideration.
As previously discussed, insulation causes a
significant change in the thermal gradient and
a corresponding drop in saturation vapor pressure.
If the predicted vapor pressure at any point
across the moisture-sensitive portion of the wall
assembly were to exceed the saturation vapor
pressure, condensation would be predicted to
occur to satisfy equilibrium (Fig. 1). It should be
noted that the rate of condensation development
is typically extremely low.
To control diffusive condensation, a vapor
retarder (typically the water-resistive air barrier),
should be generally placed on the warm side of all
CONVECTIVE CONDENSATION
Because airflow through discontinuities can
carry moisture into a wall assembly at a much
greater rate than diffusion through materials
can, air leakage is often the primary source of
moisture transfer associated with condensation
within a wall assembly.
Airflow occurs when there is an air pressure
differential across an assembly. The differential
may be caused by wind, mechanical pressurization,
stack effect, or other factors, and the airflow
travels from a higher to a lower air pressure.
Depending on the direction of airflow, ambient
air temperatures, and the RH of the air and wall
system materials, airflow may cause either wetting
of the assembly’s materials via condensation
or drying of the materials through evaporation.
For example, if hot and humid exterior air
flows into the exterior wall assembly due to a
pressure differential, moisture can condense on
surfaces of wall components that are below the
dew point of the infiltrating interior air. With airpermeable
batt insulation within the stud cavity,
it can be expected that some infiltrating exterior
air will be able to reach the inboard face of the
gypsum wallboard, which may have a surface
temperature below the dew point temperature
of the outdoor air, and that could promote condensation.
Paths for this type of airflow include
discontinuities within the water-resistive air barrier
and exterior sheathing; such discontinuities
are commonly found around penetrations and
along terminal edges at interfaces with floors,
roofing assemblies, and fenestration.
In general, there are two primary air leakage
paths: direct and circuitous. Direct paths, like
the one shown on the left in Fig. 2,4 are typical
of a through-wall connection or penetration,
Figure 1. Predicted vapor pressure profile of a typical split insulation system in a hot and
humid climate. The dashed lines represent the predicted vapor pressure, and the solid lines represent
the saturation vapor pressure. The green shaded region indicates the area where the predicted
vapor pressure exceeds the saturation pressure or where the predicted relative humidity
exceeds 100% (left). The pressure profile for the same assembly but with a vapor-impermeable
water-resistive air barrier (right).
Figure 2. Diagram showing direct airflow paths (left) and circuitous airflow paths (right) for
a cold weather situation. Figure: Reprinted from reference 4.
insulation, outboard of the inherent drop in saturation
vapor pressure, to locally reduce vapor pressure;
however, split insulation assemblies make
this challenging in hot-humid climates (Fig. 1).
30 • IIBEC Interface November 2022
where the air flows directly from the outside
to the inside or vice versa. In this case, the air
usually carries enough thermal energy to warm
up or cool down the component surfaces along
the flow path. This typically keeps the surface
temperature of the contacted elements within
the flow path above the dew point, which means
that there will be no condensation along the
path. Depending on climatic conditions, liquid
condensation may develop on either the interior
or exterior surface of the wall assembly. The
primary concern with direct leakage paths is
typically thermal shorts (“energy leaks”) within
the building enclosure.
Conversely, circuitous flow patterns, as shown
on the right in Fig. 2, do not sufficiently warm
or cool the greater area of the crossed surfaces;
therefore, there is a potential for moisture-laden
air to contact surfaces that are below the dew point
temperature of the air. This type of air leakage
path can result in the deposition of significant
amounts of condensate within the wall system.
To prevent direct and circuitous air paths, all
materials, components, and assemblies should
be integrated to provide a continuous air-control
layer. However, even with a “continuous” aircontrol
layer, construction practices and general
operation and service of the building will allow
some unintended air leakage, which will likely
increase during the service life of the building
as materials age and weather. But how much is
too much, and are there energy code—compliant
wall assemblies that fare better when some
air leakage occurs?
To provide insight on these questions for hot
and humid climates, we conducted transient
hygrothermal analyses that considered several
combinations of partially unknown parameters,
namely air infiltration rates depending on airtightness,
actual indoor temperatures, perm
ratings of interior paints and exterior waterresistive
air barriers, and their impact on the
hygrothermal performance.
HYGROTHERMAL MODELING
In our study, we used WUFI Pro 6 (WUFI),
which is modeling software that can assess the
response of a multilayered system in terms of
one-dimensional simultaneous heat and moisture
transport. Using historical climatic conditions
for a given geographic location, WUFI
can model trends in the moisture content and
wetting and drying cycles of each component
in the system over a period of multiple years.
The model we developed—which is similar
to the air exfiltration model in cold climate
zones that is incorporated in WUFI—can
account for the effects of air leakage. Our
approach takes pressure difference due to stack
effect and global building air leakage rates,
which can be derived by blower door measurements,
into account. It should be noted that
this air infiltration model is not yet validated,
although the authors of the air exfiltration
model agree that it is viable.
In our study, we used WUFI simulations
to characterize the influence of air leakage
rates and elevated surface RH on a prototype
wall assembly in an example location. A brick
masonry—clad, framed wall section with a
vapor-impermeable (0.1 perm) water-resistive
air barrier over glass-matt-faced gypsum board
as the exterior sheathing was assumed to be
oriented south in Houston, Texas, which is in
Climate Zone 2. Further, R-20 batt insulation
placed between 2 × 6 wood studs and interior
gypsum wallboard was modeled. The combination
of the following conditions resulted in more
than 500 combinations simulated with WUFI:
• Interior temperatures from 65°F
to 72°F
• Interior RH 50% and 60%
• Building airtightness at 75 Pa from
0 to 1 ft3/min/ft2
• Interior finish: latex paint (7 and
1 perm), vinyl wallpaper
The output data were analyzed and are conveyed
in terms of ANSI/ASHRAE 160-2016,
Criteria for Moisture-Control Design Analysis in
Buildings,5 at the interior paper-faced gypsum
board. The main criterion is based on a mold
growth model developed by TEKES (the Finnish
Funding Agency for Technology and Innovation)
and VTT (the Technical Research Council of
Finland),6 which has been validated on actual
laboratory and field measurements on mold
growth and takes the temperature, RH, time, and
substrate class into account. This main criterion
is based on the mold index values in Section 6
of ASHRAE 160 (Table 1), and it defines values
equal to greater than 3 as unacceptable.
RESULTS
We compiled the resulting mold growth
index (MGI) to provide a more detailed assessment
of the hygrothermal performance of
code minimum R-values in ASHRAE 90.1,
Energy Standard for Buildings Except Low-Rise
Residential Buildings,7 and the IECC.3 For example,
Figs. 3 through 8 illustrate the results after
Table 1. Mold indices
Index Description of growth
0 No growth
1 Small amounts of mold on surface (microscope), initial stages of local growth
2 Several local mold growth colonies on surface (microscope)
3 Visual findings of mold on surface, <10% coverage, or <50% coverage of mold
(microscope)
4 Visual findings of mold on surface, 10%–50% coverage, or >50% coverage of
mold (microscope)
5 Plenty of growth on surface, >50% coverage (visual)
6 Heavy and tight growth, coverage about 100%
Source: Adapted from reference 6.
Depending on climatic
conditions, liquid
condensation may
develop on either the
interior or exterior
surface of the wall
assembly. The primary
concern with direct
leakage paths is typically
thermal shorts (“energy
leaks”) within the
building enclosure.
November 2022 IIBEC Interface • 31
a 10-year simulation on the exterior surface
of the interior paper-faced gypsum wallboard
example wall with either a 7-perm
latex paint or vinyl wallpaper finish under
60% interior RH. The diagrams show the
predicted maximum MGI, maximum RH,
and maximum water content (percent by
weight) depending on the air leakage rate
and the indoor temperature. The figures
also identify the air leakage requirements
from the IECC and from the following
organizations and programs: the Passive
House Institute, the US Department of
Energy Net Zero Energy Buildings, and
the US General Services Administration
Level Tier 3. Sources can be found in references
8 and 9. Other results can be found
in Figs. A.1 through A.6 in the Appendix.
All the diagrams show a similar basic
and predictable behavior: Wall assemblies
at higher airtightness levels and higher
interior temperatures are at lower risk for
development of mold (as represented by
the green colors in the lower right corners
of the diagrams). Altering conditions
toward the upper left corners of the diagrams,
meaning higher airtightness levels
and lower interior temperatures, results
in higher risk for development of mold,
as represented by the colors turning from
yellow/orange to red.
It is obvious from the results in the
Appendix that decreasing air leakage leads
to better-performing assemblies. Further,
increased interior operating temperatures
also help the exterior wall perform better:
Because the interior drywall will be
at a higher temperature, the risk of condensation
for the example wall assembly
in Climate Zone 2 is lower, assuming the
levels of airtightness are at least code compliant
(0.4 ft3/min/ft2 at 75 Pa) to achieve
acceptable ASHRAE 160 criterion.
Finally, from the results in the
Appendix, we can establish that use of a
Class I or II vapor retarder (less than 1
perm) is associated with a significantly
higher risk for mold development in all the
combinations when compared with the use
of variable latex paint permeances (greater
than or equal to 1 perm). This validates the
code restriction on the use of Class I vapor
retarders on the interior side of framing in
Climate Zones 1 and 2.
CONCLUSION
Figures 4 through 8 show that even if
construction follows the energy code, a
hygrothermal safe performance is associ-
Figure 3. Maximum mold growth index values for variable air leakage rates and interior temperatures
with 7-perm latex paint. DOE NZE = US Department of Energy, Net Zero Energy
Buildings; IECC = International Energy Conservation Code; Phius = Passive House Institute;
US GSA Tier 3 = US General Services Administration, Level Tier 3.
Figure 4. Maximum mold growth index for variable air leakage rates and interior temperatures
with vinyl wallpaper. DOE NZE = US Department of Energy, Net Zero Energy Buildings;
IECC = International Energy Conservation Code; Phius = Passive House Institute; US GSA
Tier 3 = US General Services Administration, Level Tier 3.
Figure 5. Maximum relative humidity for variable air leakage rates and interior temperatures
with 7-perm latex paint. DOE NZE = US Department of Energy, Net Zero Energy Buildings;
IECC = International Energy Conservation Code; Phius = Passive House Institute; US GSA
Tier 3 = US General Services Administration, Level Tier 3.
32 • IIBEC Interface November 2022
Figure 6. Maximum relative humidity for variable air leakage rates and interior temperatures
with vinyl wallpaper. DOE NZE = US Department of Energy, Net Zero Energy Buildings; IECC
= International Energy Conservation Code; Phius = Passive House Institute; US GSA Tier 3 =
US General Services Administration, Level Tier 3.
Figure 7. Maximum water content for variable air leakage rates and interior temperatures
with 7-perm latex paint. DOE NZE = US Department of Energy, Net Zero Energy Buildings;
IECC = International Energy Conservation Code; Phius = Passive House Institute; US GSA
Tier 3 = US General Services Administration, Level Tier 3.
Figure 8. Maximum water content for variable air leakage rates and interior temperatures
with vinyl wallpaper. DOE NZE = US Department of Energy, Net Zero Energy Buildings;
IECC = International Energy Conservation Code; Phius = Passive House Institute; US GSA
Tier 3 = US General Services Administration, Level Tier 3.
ated with higher interior temperatures and
lower air leakage rates. Our findings suggest
that compliance with the energy code does
not guarantee condensation—or mold-free
wall performance.
Hygrothermal performance of wall
assemblies is exceptionally complex, a function
of numerous variables and assumptions.
Thus, simplified empirical design guides
may not provide prudent direction.
This study focused on a single city in
Climate Zone 2. Additional simulations to
include more geographic locations and prototype
wall assemblies would provide a more
encompassing design guideline for designers
to comply with the current energy codes and
avoid moisture accumulation and microbial
growth due to condensation.
REFERENCES
1. Finley, D., and M. Kehrer. 2019. “ASHRAE 90.1
and Cold Weather Condensation.” In: Proceedings
of the 2019 IIBEC Building Enclosure Symposium,
Louisville, KY, pp. 64—72.
2. Finley, D., and M. Kehrer. “ASHRAE 90.1:
Codified Condensation for Cold Climates.” In:
2020 Residential Building Design & Construction
Conference Proceedings, pp. 39—54. https://www.
phrc.psu.edu/assets/docs/Publications/2020RBD
CCPapers/2020-RBDCC-Whole-Proceedings.
pdf.
3. International Code Council (ICC). 2021.
International Energy Conservation Code. Country
Club Hills, IL: ICC.
4. Künzel, H. M., D. Zirkelbach, and B. Schafaczek.
2012. “Modelling the Effect of Air Leakage in
Hygrothermal Envelope Simulation.” National
Institute of Building Science 2012—Proceedings
BEST3 Conference, Atlanta (2012). https://wufi.
de/literatur/K%C3%BCnzel,%20Zirkelbach%20
et%20al%202012%20-%20Modelling%20the%20
Effect%20of%20Air.pdf.
5. American Society of Heating, Refrigerating and
Air-Conditioning Engineers (ASHRAE). 2016.
Criteria for Moisture-Control Design Analysis in
Buildings. ANSI/ASHRAE 160-2016. Peachtree
Corners, GA: ASHRAE.
6. Ojanen, T., H. Viitanen, R. Peuhkuri, K.
Lähdesmäk, J. Vinha, and K. Salminen. 2010. “Mold
Growth Modeling of Building Structures Using
Sensitivity Classes of Materials.” In: Proceedings of
the Thermal Performance of the Exterior Envelopes
of Whole Buildings XI Conference, Clearwater,
Florida. https://web.ornl.gov/sci/buildings/confarchive/
2010%20B11%20papers/104_Ojanen.pdf.
7. ASHRAE. 2019. Energy Standard for Buildings
Except Low-Rise Residential Buildings. ASHRAE
90.1-2019. Peachtree Corners, GA: ASHRAE.
November 2022 IIBEC Interface • 33
8. Lstiburek, J. 2006. “BSD-104: Understanding Air
Barriers.” Building Science Corporation website,
October 24, 2006. https://www.buildingscience.com/
documents/digests/bsd-104-understanding-air-barriers.
9. Salonvaara S., and A. Karagiozis. 2015. “Acceptable
Air Tightness of Walls in Passive Houses.” Phius website.
https://www.phius.org/sites/default/files/2022-
04/201508-Airtightness-Karagiozis.pdf.
ABOUT THE AUTHORS
David Finley is
involved in a wide
range of architectural
investigations. His
building enclosure
experience includes
water infiltration testing
of windows, curtainwalls,
masonry
facades, and plaza
and below-grade
waterproofing, as well
as condensation and air leakage testing of glazed
fenestrations and masonry facades. Finley is
well versed in performing hygrothermal analyses
using steady- and transient-state techniques.
Additionally, he is capable of analyzing window
and wall systems for two-dimensional thermal
conduction.
Manfred Kehrer is
a senior associate at
Wiss, Janney, Elstner
Associates Inc. (WJE),
who has been active in
the field of building science
for more than 30
years. After more than
20 years at Fraunhofer
IBP, Germany, where
he was active in the
laboratory and leading
development of WUFI software, he worked
for the Oak Ridge National Laboratory for 5
years as a senior researcher and then served for
1 year as president of the start-up consulting
company justSmartSolutions LLC. At WJE,
Kehrer is in charge of building science solutions
for a variety of problems in construction
practice. He is a voting member, chair, and vice
chair for several American Society of Heating,
Refrigerating and Air-Conditioning Engineers
and ASTM International committees, serves on
the editorial board of the journal Frontiers in
Built Environment, and has won several awards.
Appendix: Hygrothermal Modeling Results
Figure A.1. Interior gypsum wallboard with vinyl wallpaper under 50% relative humidity: (a)
mold growth index, (b) maximum relative humidity, and (c) maximum water content (percent
by weight). DOE NZE = U.S. Department of Energy, Net Zero Energy Buildings; IECC =
International Energy Conservation Code; Phius = Passive House Institute; U.S. GSA Tier 3 =
U.S. General Service Administration, Level Tier 3.
David Finley
Manfred Kehrer
34 • IIBEC Interface November 2022
Appendix: Hygrothermal Modeling Results
Figure A.2. Interior gypsum wallboard with 1-perm latex paint under 50% relative humidity: (a) mold growth index, (b) maximum relative
humidity, and (c) maximum water content (percent by weight). DOE NZE = U.S. Department of Energy, Net Zero Energy Buildings; IECC =
International Energy Conservation Code; Phius = Passive House Institute; U.S. GSA Tier 3 = U.S. General Service Administration, Level Tier 3.
November 2022 IIBEC Interface • 35
Appendix: Hygrothermal Modeling Results
Figure A.3. Interior gypsum wallboard with 7-perm latex paint under 50% relative humidity: (a) mold growth index, (b) maximum relative
humidity, and (c) maximum water content (percent by weight). DOE NZE = U.S. Department of Energy, Net Zero Energy Buildings; IECC =
International Energy Conservation Code; Phius = Passive House Institute; U.S. GSA Tier 3 = U.S. General Service Administration, Level Tier 3.
36 • IIBEC Interface November 2022
Appendix: Hygrothermal Modeling Results
Figure A.4. Interior gypsum wallboard with vinyl wallpaper under 60% relative humidity: (a) mold growth index, (b) maximum relative
humidity, and (c) maximum water content (percent by weight). DOE NZE = U.S. Department of Energy, Net Zero Energy Buildings; IECC =
International Energy Conservation Code; Phius = Passive House Institute; U.S. GSA Tier 3 = U.S. General Service Administration, Level Tier 3.
November 2022 IIBEC Interface • 37
Appendix: Hygrothermal Modeling Results
Figure A.5. Interior gypsum wallboard with 1-perm latex paint under 60% relative humidity: (a) mold growth index, (b) maximum relative
humidity, and (c) maximum water content (percent by weight). DOE NZE = U.S. Department of Energy, Net Zero Energy Buildings; IECC =
International Energy Conservation Code; Phius = Passive House Institute; U.S. GSA Tier 3 = U.S. General Service Administration, Level Tier 3.
38 • IIBEC Interface November 2022
Appendix: Hygrothermal Modeling Results
Figure A.6. Interior gypsum wallboard with 7-perm latex paint under 60% relative humidity: (a) mold growth index, (b) maximum relative
humidity, and (c) maximum water content (percent by weight). DOE NZE = U.S. Department of Energy, Net Zero Energy Buildings; IECC =
International Energy Conservation Code; Phius = Passive House Institute; U.S. GSA Tier 3 = U.S. General Service Administration, Level Tier 3.