Performance testing of the building enclosure is a common requirement on new construction projects, especially larger projects in the commercial and government sectors. Testing is one of several ways to enact a quality control process to prevent or mitigate the potential for issues after the building is completed and occupied. One of the more common issues that building owners, contractors, and designers hope to avoid is water penetration through the building enclosure to the interior; therefore, performance testing typically includes some form of water penetration resistance testing, such as ASTM E1105-15, Standard Test Method for Field Determination of Water Penetration of Installed Exterior Windows, Skylights, Doors, and Curtain Walls, by Uniform or Cyclic Static Air Pressure Difference.1 While the ASTM E1105-15 test method, which is shown from the building exterior in Fig. 1, can be readily performed and understood, one aspect of performance testing that is markedly not as well understood can be summarized by the following question: How much water penetration performance testing should be required on a new construction project? The short answer to this question is that currently there is no industry-wide consensus or agreement for the extent or quantity of field testing of water penetration performance required for a single project. The lack of a consensus, along with existing and vague guidelines in frequently referenced documents, creates a good deal of confusion and misunderstanding for specifiers and contractors. To clarify the existing confusion, it is first necessary to examine how ASTM E1105 testing is typically specified and what existing trade association documents require for testing quantities. Note that the examination will be limited to quantities for ASTM E1105 testing of windows since, Figure 1. Typical ASTM E1105 test in progress. Photo by Matthias Heil on Unsplash 18 • IIBEC Interface February 2022 This paper was originally presented at the 2021 IIBEC Building Enclosure Symposium. in this author’s experience, this testing is the most common water performance test for new construction. An examination of quantities for other types of building enclosure tests is beyond the scope of this paper. SPECIFICATION TEST REQUIREMENTS One of the biggest misconceptions with respect to ASTM E1105 testing is that simply including ASTM E1105 test requirements in the specifications is sufficient, and no other information is required by the specifying authority. This author has been on multiple projects where the designer’s response to questions such as “How many E1105 tests should be performed?” or “What is the minimum test area size?” was to reference the ASTM E1105 standard. The problem with this response is that ASTM E1105 does not include guidelines that explicitly define testing quantities or extents. This is not a fault in the ASTM standard, as the general intent of the standard is to clearly define the test procedure, provide requirements for the testing equipment, and state information that should be included in a test report. In fact, the standard states that “the specifying authority shall supply the following information…Test Specimen sampling, selection, adjustment, and identification.” The standard purposely does not address test quantities so that the method can be applied to a variety of buildings, from small multifamily projects to large commercial condos such as the one shown in Fig. 2. Given the clear guidelines in ASTM E1105 with respect to the need for the specifying authority to define testing quantities, a reasonable question to ask is why confusion persists among project teams about required testing quantities. The answer to that question leads to another commonly specified trade association document, AAMA 502, Voluntary Specification for Field Testing of Newly Installed Fenestration Products.2 AAMA 502 is a specification created and maintained by the American Architectural Manufacturers Association (AAMA), a trade association that is now part of the Fenestration & Glazing Industry Alliance (FGIA). The AAMA 502 specification includes requirements for field air leakage and water penetration testing of newly installed fenestration products. For the water penetration testing, the AAMA specification basically requires testing per ASTM E1105. Specification writers frequently include field testing per AAMA 502 because, unlike ASTM E1105, the AAMA specification includes guidelines for both test pressures and, more importantly with respect to this paper, information for testing quantities. The short-form field-testing section in AAMA 502 includes the following language, which is intended to be inserted into a Division 08 specification for windows: Test three (unless otherwise specified) of the fenestration product specimens after the products have been completely installed for air leakage resistance and water penetration resistance as specified. As previously noted, AAMA 502 requires that water penetration resistance testing should be performed per ASTM E1105. For any project where AAMA 502 testing is specified and no other testing requirements are included, three water penetration resistance tests should be performed. However, the three default tests are not applicable to every project since the specifier notes in AAMA 502 include the following language: “The number of specimens to be selected for testing on a project should be determined after careful consideration of the following factors.” The specifier note then goes on to list factors including, but not limited, to cost, project size, complexity, and prior experience with the fenestrations. In addition to these factors, the specifier note also includes the following language, which is both helpful and confusing: “ASTM E122 provides guidance on how to establish the number of test specimens in order to estimate a measure of quality of a production lot with prescribed precision.” This language is helpful to specification writers because when questions arise about test quantities, the writer can point back to AAMA 502 and state that test quantities can be determined per ASTM E122.3 At the same time, the language is confusing because now another ASTM standard must be reviewed and understood to establish the number of ASTM E1105 tests required for a project. ASTM E122 is where the test quantification process gets even more muddled. ASTM E122 GUIDELINES ASTM E122-17, Standard Practice for Calculating Sample Size to Estimate, with Specified Precision, the Average for a Characteristic of a Lot or Process, includes multiple methods for determining how large a sample size needs to be to provide a precise estimate of quality for all units in a lot of material or process. The methods in ASTM E122 are mostly applicable to material properties of production lots, as evidenced by the examples in the standard that discuss average transverse strength of a lot of bricks. However, the standard does include a section that relates to the fraction that does not conform to a process, and this section is how we will attempt to examine how to calculate the quantity of ASTM E1105 tests required for a project. February 2022 IIBEC Interface • 19 Figure 2. Commercial building that could require more water penetration resistance testing. Given the complexity of calculating sample size with ASTM E122, we must first frame and define the language and terminology in ASTM E122 in terms of fenestration installation and ASTM E1105 testing. The terms and symbols in Eq. (1) will be needed to calculate a sample size for an example building. Each term or symbol is first defined by the general definition provided in ASTM E122 and then discussed in terms of ASTM E1105 testing for a new construction project. Note that the equation is taken directly from ASTM E122. Equation (1) will be critical for calculating the number of ASTM E1105 tests required, and the calculation process and challenges are best illustrated and explained with a practical example. ASTM E122 EXAMPLE CALCULATION Before we provide any information for our example new construction project, we should note that Eq. (1) is not actually affected by our example building. If E is prescribed and previous data are available that allow for a good estimate of the window failure rate p0 when subjected to ASTM E1105 testing, the sample size or number of windows that should be tested can be readily calculated. Realistically, however, prescribing an E value is difficult, and a good estimate of p0 is likely not available; therefore, an example building is needed to understand how we can discuss and assume these values. For our example new construction project, let us say that 500 identical windows will be installed. This example building is obviously a simplification when compared to any new construction process, but simplification is needed if we are to understand the ASTM E122 calculation process and demonstrate the assumptions needed to determine our sample size. Determining Window Failure Rate p0 The first piece of information that is required is p0, which, as previously defined, is an estimate of the fraction of installed windows on the project that would fail ASTM E1105 testing, or the failure rate of the windows. The best way to estimate window failure rate is to examine empirical window failure rates of similar processes. Unfortunately, such empirical data are likely not available since reliable window failure rate calculations would require that 100% of windows on similar projects were tested per ASTM E1105. In this author’s experience, few, if any, projects exist where 100% of the windows have been tested. Another approach for estimating failure rate is to calculate and average the percentage of ASTM E1105 failures on similar projects where some, but not all, of the windows were subject to ASTM E1105 testing. While this approach seems advantageous, it is not a reliable estimate of failure rate for at least two reasons: (1) failure rates of small sample sizes on similar projects are not necessarily equivalent to failure rates of the entire lot or process; and (2) data from previous projects are not likely applicable to our example project since several factors (including, but not limited to, flashing methods, crew experience, and nature of installation) are not the same from one project to the next. Given the limitations of methods for estimating p0 from empirical data, the author suggests an alternate strategy to define this value. This strategy involves defining an acceptable failure rate of the windows for our building in terms of what the project team is willing to accept. For this example, let us say that the project team is willing to accept a failure rate of 4%, meaning 20 windows could fail ASTM E1105 testing. Such a strategy is obviously problematic since most project teams will likely demand a 0% failure rate; however, any demand for zero failures would necessitate testing and repairing all windows, which is even less likely than accepting a failure rate greater than 0%. Prescribing Acceptable Difference E Like our failure rate process, determining an acceptable difference between the failure rate of the sample and the failure rate of the entire process is not a straightforward process. ASTM E122 actually requires that Equation 1. Equation 2. n = size of a sample taken from a lot or process Sample size is the number of installed fenestrations—specifically windows—that will be subject to ASTM E1105 testing. The lot or process is best described as the total number of installed windows on a new construction project. Note that for this paper, we will use the terms “fenestrations” and “windows” interchangeably. And for the example, we will assume all the windows on the building are the same size. This simplification is not ideal since the term “fenestration” does apply to more than windows; however, simplification is required to demonstrate the calculation procedure. E = maximum acceptable difference between the true average or fraction nonconforming of the lot or process and the sample average or fraction nonconforming This value is the difference, expressed as a decimal, between the fraction or percentage of all fenestrations on the building that fail or would fail ASTM E1105 testing and the fraction or percentage of fenestrations in the sample size that fail ASTM E1105 testing. Note that this value must be prescribed or assumed, which can be difficult and will be discussed in the example. pO = advanced estimate of the fraction of a lot or process whose units have the nonconforming characteristic under investigation The nonconforming characteristic is ASTM E1105 test failure of any installed fenestration or window. This value is best described as the fraction or percentage of windows on the new construction project that would experience ASTM E1105 test failure, or the failure rate of the installed windows. The fraction nonconforming estimate should be based on knowledge of similar lots or processes. Estimating this value is difficult, as will be discussed in the example. 20 • IIBEC Interface February 2022 the approximate precision desired for the estimate must be prescribed. That is, it must be decided what maximum deviation, E, can be tolerated between the estimate to be made from the sample and the result that would be obtained by measuring every unit in the lot or process. In the author’s opinion, the acceptable precision or maximum deviation value should be provided by the specifying authority. Realistically, the entire reason we are calculating a sample size via ASTM E122 is because the specifying authority is not likely to provide or even understand this value, so we will again need to assume this value. Returning to our value for p0, we know that the project team accepted a failure rate of 4%, so let us define the acceptable difference E between the sample size failure rate and process sample rate as 3.5%, or 0.035. This E value means that a sample failure rate of anywhere between 0.5% and 7.5% is acceptable and is a reliable indicator of the failure rate of the entire process. Calculating Sample Size n Since the values for p0 and E have been established, calculating the sample size, or the number of windows that should be tested per ASTM E1105, is now straightforward as we only need to substitute these values into Eq. (1), as shown in Eq. (2). The n value represents the number of installed windows that should be tested per ASTM E1105 to ensure that the fraction nonconforming, or failure rate, of the sample is a precise measurement of the fraction nonconforming of the entire process of installed windows on our example building. Since our example building has 500 windows, testing 282 of those windows equates to testing approximately 56% of all windows. Testing this many windows would be a substantial effort for any project team, so the sample size calculation warrants further analysis and discussion. February 2022 IIBEC Interface • 21 ASTRUTExtruded Aluminum Pipe Support protects roofs.And pipes.l One-piece designl Integrated shallow strut allows use of any standard accessoryl Multiple, custom lengths— cut-to-order from 6″ to 20″ longl 150 lb. load; 5 lb. per square inch compressive strengthInnovative rooftop supports since 1998www.MAPAproducts.com(903) 781-6996The new A-Strut Aluminum Pipe Supports from MAPA elevate pipes above roofs, protecting the roof from abrasion and punctures, and the pipes from deterioration caused by movement and rough roofing material.You’re protected from headaches and expenses.TM®Model MA-6F4Patent Pending Since databases and statistical education and acceptance do not yet exist, the determination of testing quantities should continue to be a collaborative process where all parties involved discuss, debate, and ultimately settle on a testing regimen. SAMPLE SIZE DISCUSSION As shown in our example, using ASTM E122 to calculate a sample size can result in large sample sizes relative to the size of the entire lot or process. The resulting sample size is a function of both the fraction nonconforming and acceptable difference values. Both values can vary based on empirical data, project team requirements, and assumptions, so it is worth noting how variations in these values will affect the resulting sample size, as shown in Fig. 3. The key pattern in Fig. 3 is that the sample size increases from top to bottom and from right to left. This pattern means that as the fraction of nonconforming windows increases and the acceptable difference decreases, the resulting sample size increases. This relationship between sample size, fraction of nonconforming windows, and acceptable difference is shown graphically in Fig. 4 and 5. The wide variety in possible sample sizes based on the variability of the fraction of nonconforming windows and acceptable difference values makes it difficult to routinely calculate a sample size for a given project per ASTM E122 guidelines. For comparison’s sake, let us assume that the values for our example building are reasonable for any given project and that testing approximately 56% (282 out of 500) windows is the norm for a new construction project. How would this value compare with typical testing rates for actual projects? Testing rates vary widely from one project to the next; however, in this author’s experience and based on limited published information, testing anywhere from 1% to 2% of the total number of installed fenestrations is not uncommon. Returning to our example project, testing 1% to 2% would require 5 to 10 tests, and this range is much smaller than testing 282 windows. Again, we should note that testing 282 windows per ASTM E122 is only one of many possible sample sizes, but if a wide variety of sample sizes are possible per ASTM E122, then the ASTM E122 guidelines may be of little value when attempting to implement and specify a testing regimen for any new construction project. SUMMARY ASTM E122, which is referenced in AAMA 502 as containing guidelines for establishing the number of test specimens for a project, does not provide simple, repeatable procedures for establishing sample sizes for building enclosure field performance testing. The ASTM E122 guidelines require the use of empirical data that are not readily available for common water penetration testing, such as ASTM E1105 testing. Without this empirical data, the assumptions Figure 3. Sample size variations with highlighted result from the example project. Figure 4. Sample size versus acceptable difference at selected fraction nonconforming values. Figure 5. Sample size versus fraction nonconforming at selected acceptable difference values. 22 • IIBEC Interface February 2022 that are needed to complete the ASTM E122 calculations have too much impact and result in a wide variation in potential sample sizes for performance testing. In lieu of the ASTM E122 guidelines, for the time being, this author suggests that a reasonable strategy is to water test 1% to 2% of all windows installed on a project. The 1% to 2% guideline may be viewed by the project team as too much testing. However, if nothing else, the guideline can be used as a starting point for project team discussions, and testing quantities can be adjusted based on the needs and constraints of the individual project. Returning to our example one last time, testing 1% to 2% of the windows would result in 5 to 10 water tests, which, again in this author’s experience, can be a reasonable testing quantity. If ASTM E122 continues to be referenced as a guideline for determining sample sizes, databases will need to be established and maintained that contain results from previous enclosure testing so these results can be used to estimate fraction nonconforming values for future projects. Additionally, the industry will need to embrace statistical analysis as a means for calculating sample sizes so that the demand for zero nonconforming items on a project can be avoided. Since databases and statistical education and acceptance do not yet exist, the determination of testing quantities should continue to be a collaborative process where all parties involved discuss, debate, and ultimately settle on a testing regimen. The testing regimen should be based on numerous factors such as budget, product complexity, building risk profile, and project team experience. All these factors, among others, should be weighed and reviewed to arrive at a testing quantity for the building enclosure that provides the appropriate level of quality control and assurance. REFERENCES 1. ASTM International. 2015. Standard Test Method for Field Determination of Water Penetration of Installed Exterior Windows, Skylights, Doors, and Curtain Walls, by Uniform or Cyclic Static Air Pressure Difference. ASTM E1105- 15, West Conshohocken, PA: ASTM International. 2. American Architectural Manufacturers Association (AAMA). 2012. Voluntary Specification for Field Testing of Newly Installed Fenestration Products. AAMA 502-12. Schaumburg, IL: AAMA. 3. ASTM International. 2017. Standard Practice for Calculating Sample Size to Estimate, With Specified Precision, the Average for a Characteristic of a Lot or Process. ASTM E122-17. West Conshohocken, PA: ASTM International. February 2022 IIBEC Interface • 23 Jeff Crowe, PE, has been with Pie Consulting & Engineering since 2010. As a member of and technical director for Pie’s Building Science Group, he is part of a team that regularly reviews building enclosure drawings and details and frequently performs building enclosure field testing. He has provided consultation for architects, contractors, and owners for appropriate testing and has also presented on several technical topics with respect to building enclosure testing. He was a contributing author to the U.S. Army Corps of Engineers Air Leakage Test Protocol for Building Envelopes. Jeff Crowe, PE What It Takes to Get Back to Work As 2022 begins, COVID-19 uncertainty remains, as does the staffing shortage that the pandemic has exacerbated. The Building Owners and Managers Association International asked attendees at one of its recent meetings about what kept them up at night. Leading the field: staffing concerns, which extend to other industries. “The talent shortage was the top concern across the board, and it in turn connects directly to other issues, such as staff burnout, operational efficiency and growth,” John Salustri wrote in Looking to 2022: Property Professionals Accelerate on Their Positives (boma.org/DeepDives). “A recent Bisnow report puts the overall staffing shortfall as impacting 60 to 70 percent of all commercial real estate firms, and certainly all disciplines.” What can building enclosure professionals do to attract and keep talent? One senior executive advised moving away from passive hiring techniques, such as posting job listings, and toward greater emphasis on the promotion of company resources and training programs. But the building itself and the working environment could be just as important. “In an era when that talent can pick and choose where they want to work, the building itself plays a vital role in attraction and retention,” Salustri wrote. “‘The way to distinguish a building from its peers is how much more it offers employees,’ said one contributor. People make employment decisions based, at least in part, on the physical environment.” S P E C I A L I N T E R E S T Photo by Chris Gray on Unsplash