Skip to main content Skip to footer

A Tale of Two Stones: Evaluation Of A Stone Wall Cladding System

May 15, 2008

S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • OC T O B E R 2 0 0 8 FA R M E R & K E N N E Y • 1
A TALE OF TWO STONES:
EVALUATION OF A STONE PANEL CLADDING SYSTEM
MATTHEW C. FARMER
WISS, JANNEY, ELSTNER ASSOCIATES, INC., FAIRFAX, VA
CLARISSA S. KENNEY
WISS, JANNEY, ELSTNER ASSOCIATES, INC., FAIRFAX, VA
ABSTRACT
Looks are not always what they seem. The evaluation and analysis of problems associated
with a natural stone cladding system involving two distinctly different types of natural
stone will be presented. What began as a response to a single isolated panel failure of one
of the stone types led to some surprising test results with respect to both stones. Our discussion
will highlight the details of our investigative findings, the results of material
strength testing, and the impact of each stone’s unique characteristics on our perceptions
of these cladding materials, and the resulting challenges to developing appropriate recommendations
for this unique set of project conditions.
SPEAKER
MATTHEW C. FARMER — WISS, JANNEY, ELSTNER ASSOCIATES, INC., FAIRFAX, VA
MATTHEW C. FARMER joined the New Jersey office of Wiss, Janney, Elstner in 1986.
Since then, he has been involved with numerous evaluations of concrete, steel, and timber
structures, as well as those involving clay, concrete, stone, and cast-stone masonry. He has
concentrated his practice in the area of building envelope cladding systems design, investigation,
analysis, and repair, including numerous engagements as an expert witness. Mr.
Farmer served as manager of the Fairfax office from 1994 until 2006, when he became a
principal with WJE. Farmer is a graduate of the University of Colorado and Cornell University.
He is licensed as a professional engineer in the District of Columbia, Virginia, and
Maryland.
COAUTHOR
CLARISSA S. KENNEY — WISS, JANNEY, ELSTNER ASSOCIATES, INC., FAIRFAX, VA
After completing an undergraduate dual degree program in both architecture and civil
engineering at The Catholic University of America, CLARISSA KENNEY joined the
Washington, DC, office of Wiss, Janney, Elstner in 2004. Since then, Ms. Kenney has been
involved with the investigation and repair design of existing structures, including several
landmark buildings listed on the National Register of Historic Places, which have required
the development of repair drawings and specifications as well as on-site construction observation
and field-testing services. Her investigative experience includes a wide range of building
façade materials, including clay brick, concrete masonry, cast stone, concrete, metal
panel systems, and numerous stone veneer panel systems.
2 • FA R M E R & K E N N E Y S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • OC T O B E R 2 0 0 8
INTRODUCTION
Looks can be deceiving; the presence of
visible defects and deficiencies do not
always represent the true character and
durability of a material, nor does the
absence of defects necessarily indicate a
material with no flaws.
After owner-implemented building
expansions were conducted several times in
the past 70 years, the subject building,
located in the mid-Atlantic Coast region,
underwent revitalization efforts during
which a natural stone cladding system was
applied in the 1970s to unify the appearance
of the adjoining buildings of different
vintages. Two distinctly different stone panels,
serpentine and white marble, were used
to architecturally unite the building as well
as modernize its appearance. What began
as an investigative response to a single isolated
failure of an approximately 35-yearold
serpentine cladding panel led to some
surprising findings and test results as well
as a realization that opinions of stone
cladding quality after a visual assessment
and initial assumptions may not be the
same after a more in-depth evaluation. In
this instance, the results of materialstrength
testing resulted in contradictory
perceptions of the stone used and caused
modification of the approach taken to develop
appropriate recommendations for this
unique cladding system and its unusual
project conditions.
BACKGROUND
History of Construction
The building is five stories tall, but
approximately 105 feet in height. The original
building has a concrete structural frame
with an exterior composed of limestone and
brick masonry. Several expansions have
occurred that both widened the building
and increased its height. The expanded portions
of the structure are constructed of an
expressed concrete frame infilled with concrete
masonry units.
A façade comprised of 2-cm-thick stone
panels was installed as a barrier system
over the new combined structure (with the
exception of a portion of the east elevation)
approximately 35 years ago, in an effort to
unify the appearance
of the multiple buildings
and additions.
The stone cladding
panels vary in size,
but the most common
panel dimensions
are 27 inches
wide by 54 inches
tall. The cladding
panels are made of
two types of stone: a
locally quarried
green/black serpentine
(see Figure 1),
and a white marble
quarried domestically
(see Figure 2).
Minimal documentation
was retained
over the years regarding building
repair and maintenance;
however, we found that the
sealant at joints between stone
panels was in poor condition at
the time of our investigation,
and supplementary anchors
were installed along the lowest
row of marble panels at each
elevation.
To support the new stone
cladding over both the original
1930s limestone masonry
structure and the newer walls
with concrete masonry unit
infill and expressed concrete
floor slabs, a supplemental
metal framing system consisting
of steel “unistruts” was
used (see Figure 3). The vertical
members generally align with
vertical stone panel joints and
are attached to the concrete
floor slabs or supplemental
steel backup structure where
required, using steel clips. The
steel back-up is attached to the original
façade using a combination of throughbolts,
mechanical expansion anchors, and
chemical fasteners. “Continuous” horizontal
aluminum anchor rails span the unistruts
and engage the stone cladding at kerfs
(slots cut into the stone panel edges to
receive an anchor) to transfer the lateral
and gravity loads from the stone cladding
into the unistruts using bolts and clamping
washers.
A TALE OF TWO STONES:
EVALUATION OF A STONE PANEL CLADDING SYSTEM
Figure 2 – Overall view of marble stone panels.
S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • OC T O B E R 2 0 0 8 FA R M E R & K E N N E Y • 3
Figure 1 – Overall view of serpentine stone panels. Note the
extent of pronounced veining.
Initiation of Investigation: Panel Failure
After over 30 years of service, one of the serpentine (dark green, almost
black) marble panels fractured. The upper portion of the panel slipped
downward and was retained behind adjacent panels; the remaining lower
portion of the panel fell to the ground. The fracture occurred along a horizontal
vein partially filled with a brittle epoxylike material, likely applied as
a surface treatment. The owners became concerned that other serpentine
panels with similar horizontal veining might disengage, so they initiated an
investigation to evaluate the cladding and anchorage system.
POSTFAILURE OBSERVATIONS
After addressing any immediate safety concerns by limiting
pedestrian access, a visual survey of the serpentine stone was
conducted from the ground in an attempt to assess if there were
any additional panels that might be unstable. The marble panels
were also surveyed from the ground for any visible damage. In
addition, both types of stone cladding panels were observed at
close range from a personnel lift, and selected panels were
removed to examine the backup and cladding support conditions.
Samples of the stone were also taken for material-strength testing
in the laboratory.
Stone Cladding Anchorage System
Of some concern was the lack of any compressible fill in the
stone panel kerfs that serve to evenly distribute lateral and gravity
loads from the panel to the aluminum rail. Without any material
in the kerfs, the loads can be unequally distributed throughout
the kerf, causing uneven loading and stress concentrations at contact
points between the anchor and the stone panel (see Figure 4).
Small shims were observed between the anchor rail and the
stone, presumably used to level the stone cladding panels and
transfer the gravity load into the anchor rails. These shims were
composed of a thin fiber board that was deteriorated, allowing
direct contact between the stone cladding panels and the anchor
rails (see Figure 5). The thickness of the shims varied, as well,
Figure 3 – Unistrut support structure for stone
cladding. Note horizontal anchor rail spanning
between vertical unistruts.
Figure 5 – Spotted serpentine panel (left), and veined
serpentine panel (right).
4 • FA R M E R & K E N N E Y S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • OC T O B E R 2 0 0 8
Figure 4 – Stone panel kerf engaging horizontal
anchor rail (circle). Note lack of sealant and
damaged shims (arrows).
resulting in reduced engagement
of the stone cladding panel kerf
with the anchor rail and a subsequent
reduction in load capacity.
Serpentine
Serpentine or serpentinite is
part of the marble class of stone;
however, ASTM distinguishes it
from marble with respect to its
physical properties. It is a metamorphic
rock formed by the recrystallization
of carbonate-based
rock, but unlike typical marbles
with calcite or dolomite mineral
content, the stone is largely composed
of the mineral serpentine,
which gives the stone a greenish
hue. The stone is typically known
for its numerous crossing veins
and rifts created by the entrapment
of other minerals during its
geologic formation.
The serpentine panels varied
greatly in color, texture, and veining. Two
primary types of serpentine cladding were
identified. The first was greenish-black serpentine
with lighter (almost gray) spots
evenly distributed on the surface. This
stone material was found to be sound and
generally free of defects. The second is a
green-black serpentine with pronounced
brown-red veins running throughout the
panel. The minerals that comprise the veins
weathered more rapidly than the base
material, such that the fillers and surface
treatments were no longer present. The surfaces
of the veins were rougher and more
eroded than the surrounding stone matrix
(see Figure 6). This roughness and material
loss made the veins appear to be cracked
when observed from the ground, and stability
was difficult to ascertain (see Figure 7).
From a distance, it was nearly impossible to
distinguish between veining and fully developed
cracks.
Upon close examination, several panels
did exhibit cracks along the veins and were
displaced along the cracks, indicating
potential instability (see Figures 8 and 9).
Several of the veins and cracks were filled
S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • OC T O B E R 2 0 0 8 FA R M E R & K E N N E Y • 5
Figure 6 – Example of eroded,
intersecting veins in serpentine
panel.
Figure 7 – View of serpentine
panels from the ground.
Note veins can easily be
mistaken for cracks.
(likely at the time of fabrication) with an
epoxylike substance to conceal the more
eroded veins and create a smooth, polished
surface (see Figure 10).
The serpentine panel that most recently
failed had fractured along a cross-panel
vein that cracked previously or cracked
recently as a result of wind loading against
the panel section weakened at the vein. Our
survey identified numerous panels that had
a similar potential for failure due to crosspanel
veins or preexisting cracks. Given the
long vertical span of the panels relative to
their width and thickness, these veins create
opportunities for future fractures when
the panel is loaded, particularly if the veins
run across the width of the panel or if the
veins are present in zones where panel flexural
stresses are highest. The varying conditions
of the veining and
the potential for cracks to
form along the veins also
made individual panel
performance and stability
highly unpredictable
without examination of
each panel at close range.
Marble
Marble is a metamorphic
rock formed from
preexisting rocks (typically
limestone) that have
been exposed to increases
in pressure and/or temperature. The recrystallization
of the rocks (composed mostly
of carbonate) and their impurities create
marble with its intrinsic veining or “inclusions”
and its
crystalline structure.
The purest
white marbles
have very few
impurities, while
colored marbles
assume the color
gradation of their
mineral impurities.
Observations
of the marble
cladding panels
revealed that they
were very uniform
in color and overall
texture, creating
a homogeneous
appearance
with no significant
physical distress evident (see Figure
11); however, nearly 100% of the marble
panels were visibly bowed and generally
curved inward (see Figure 12). The only
imperfections observed were some small,
short cracks oriented in a perpendicular
direction from the panel edges. Sealant
joints were removed at the corners of several
panels to determine the effect of the curvature
on the kerf and anchorage system,
revealing that the interior legs adjacent to
the kerfs of many of the panels were broken
at their ends where the kerf anchor was in
direct contact with the stone (see Figures 13
and 14). This critical damage that directly
reduces the load capacity of the stone
cladding and anchor system was not evident
from the exterior and could have gone
unnoticed until a more apparent failure
occurred.
When viewed under a microscope, this
marble is composed of a series of tightly
interlocked crystalline calcite grains that
adhere to each other with a calcite binder.
This complex arrangement of calcite grains
Figure 8 – Crack that is coincident with a vein in a
serpentine stone panel.
Figure 9 – Example of a displaced serpentine
stone panel with a crack along a vein.
Figure 10 – Polymer surface filler present in serpentine vein.
Note heavy concentration of veins.
6 • FA R M E R & K E N N E Y S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • OC T O B E R 2 0 0 8
within the crystalline
structure of
the stone, although
relatively uniform in
its geometry, can be
subject to the formation
of intergranular
fractures,
or microcracking,
within the calcite
binder of the stone
when the marble is
exposed to changes
in temperature.
After these cracks
have formed, the
calcite grains in the
marble tend to disassociate
or come
apart within the calcite
binder of the
stone. Once loosened,
these grains
are then free to
move slightly and
reorient themselves
within the crystalline
structure of
the stone. They typically
will not return to their original position within the calcite
binder once this process has begun.
This change in the material properties of the marble effectively
disrupts the otherwise uniform and tightly bound crystalline
structure of the stone, resulting in a “net,” or a permanent volumetric
expansion of the marble itself due to the reorientation of
the grains within the calcite binder that results in bowing. This
process of net growth as a result of cyclic influences is known as
“hysteresis.” A coarse-grained marble will typically experience a
more pronounced level of deformation or bowing as compared to
the finer-grained marbles available for the same application. As the marble
structure increases in volume, it also decreases in strength, due to
Figure 11 – Consistent, uniform appearance of the marble
stone panels.
Figure 12 – Curvature of marble stone
panels due to hysteresis and associated
strength loss.
Figure 14 –
Rear kerf leg
damaged due
to marble
curvature or
hysteresis.
Figure 13 – Concealed damage of interior kerf
leg, due to curvature of marble stone panels.
S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • OC T O B E R 2 0 0 8 FA R M E R & K E N N E Y • 7
the breakdown of the original crystalline
structure. Strength loss resulting from the
effects of hysteresis is both progressive and
irreversible, with no known treatment or
cure.
As bowing becomes more pronounced,
moisture ingress into the stone increases as
the cracks and microfractures at the
exposed panel surfaces begin to open and
become more directly exposed to weather.
The calcite binder is dissolved more quickly,
resulting in an increase in the rate of
disaggregation of the stone. This disaggregation,
commonly referred to as “sugaring”
(due to the presence of loose, powderlike
calcite grains on the exposed marble panel
surfaces resulting from disaggregation), will
then lead to edge cracking and similar distress
in the body of each panel. This is
indicative of strength loss in the stone, and
permanent change in the material properties
of the marble.
MATERIAL STRENGTHS
In both new construction and building
repairs, stone testing using ASTM1
International Standards for dimension
stone is recommended to establish the
physical properties and typical characteristics
of a stone, such as porosity, density,
and strength (flexural and compressive
strengths and modulus of rupture, etc.).
Due to the presence of cracks in the serpentine
and the evidence of the marble losing
strength due to hysteresis, both the
white marble and the serpentine stones
were tested for flexural strength, or bending
strength of the stone. This is the most critical
physical characteristic for thin-stone
cladding systems, since their design is typically
controlled by flexural capacity and its
ability to resist laterally applied loads, such
as wind. ASTM C880, “Standard Test
Method for Flexural Strength of Dimension
Stone,” was performed to determine the
flexural strength. The values obtained
through testing allow us to determine the
overall flexural capacity of the stone panels
as well as the adequacy of the kerf anchoring
system.
Based on ASTM recommendations, each
sample was tested in the vertical and horizontal
directions of the bedding plane (or
grain structure), allowing us to distinguish
which spanning direction was weaker. This
is particularly important in stones whose
bedding planes may not be immediately evident.
According to the standard, samples
should be tested in both wet and dry conditions;
however, in an effort to minimize
costs, all of the samples were tested in a wet
condition that typically governs for design
and evaluation purposes. Table 1 summarizes
the results of the C 880 Flexural Tests
for the white marble, veined serpentine, and
spotted serpentine.
Based on the test results, both the
veined and the spotted serpentine far exceeded
the recommended flexural strength,
indicating a high quality of stone; however,
the coefficient of variation for the veined
serpentine was extremely high, indicating a
lack of consistency in the material due to
the pronounced veining. Our visual observations
of cracking along veins and variations
in vein condition supported this finding.
By comparison, the coefficient of variation
for the spotted serpentine data was
very low, implying that the absence of veining
results in a more uniform cladding
material.
While the original strength values for
the marble cladding were not available, our
experience suggests that this material
would normally have had a flexural
strength on the order of 1,200 to 1,500 psi.
The flexural strengths obtained from the
marble cladding panels were well below this
value, even below the minimum for a stone
to be classified as a marble. Though outwardly
appearing undamaged, the low-flexural
test results confirmed strength loss
consistent with the effect of hysteresis over
a prolonged period, reducing the capacity of
the marble cladding to resist applied lateral
loads.
STRUCTURAL ANALYSIS OF THE
STONE CLADDING
The ASTM minimum specification
requirements for stone are typically used as
guidelines for choosing a material and as a
basis for design when stone-testing data
may not be readily available. Numerous
other factors such as the anchorage system,
panel height-to-width ratio, span direction,
loading, and safety factors must be considered
when designing or evaluating a
cladding system. As a result, a structural
analysis of both the marble and the serpentine
using the documented test strengths
and project-specific conditions was necessary
to determine the adequacy of the panel
and anchorage system in the existing application.
Serpentine
Based on the flexural strength results
obtained, the physical panel dimensions,
and current industry-accepted safety factors,
it was determined that the veined serpentine
cladding panels were not adequate
to resist anticipated lateral loads as originally
designed. A reduction in the industryaccepted
safety factor for flexural strength
was considered in this case, due to the
acceptable performance of the cladding in
service; however, the reduced safety factor
Table 1
ASTM C 880 STANDARD TEST METHOD
FOR FLEXURAL STRENGTH OF DIMENSION STONE
STONE TYPE VERTICAL HORIZONTAL
Marble Min. (ASTM C503) 1,000 psi 1,000 psi
Average 751 psi 724 psi
Maximum 860 psi 868 psi
Minimum 552 psi 521 psi
Standard Deviation 117 psi 140 psi
Coefficient of Variation 16 % 19 %
Serpentine Min. (ASTM C1526) 1,000 psi 1,000 psi
Veined Average 3,773 psi 3,504 psi
Maximum 4,751 psi 4,628 psi
Minimum 2,053 psi 1,598 psi
Standard Deviation 1,026 psi 1,195 psi
Coefficient of Variation 27 % 34 %
Serpentine Min. (ASTM C1526) 1,000 psi 1,000 psi
Spotted Average 3,430 psi 2,341 psi
Maximum 3,811 psi 2,477 psi
Minimum 3,118 psi 2,201 psi
Standard Deviation 261 psi 102 psi
Coefficient of Variation 8 % 4 %
8 • FA R M E R & K E N N E Y S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • OC T O B E R 2 0 0 8
S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • OC T O B E R 2 0 0 8 FA R M E R & K E N N E Y • 9
was rejected due to concerns with the high
variability in panel conditions and the
unpredictability of the impact of the veining
on panel flexural capacities. Consideration
of a reduced safety factor was deemed more
appropriate for the spotted serpentine, due
to its more uniform test results, but far
fewer of these panels were installed on the
building.
Marble
Upon review of the test data and panel
geometry, the marble cladding panels were
also found to be structurally inadequate,
due to their lower flexural strengths, with
no applied safety factor. The marble
cladding panel flexural capacities were well
below those required to sustain current
code-mandated loading; however, no evidence
of major structural distress (cracks,
displacement) was observed or noted during
the service life of the cladding. This may be
partially explained by examination of
weather data for the period during which
the cladding was installed. The highest
recorded wind speeds during this period
were only two-thirds of currently accepted
design wind speeds, resulting in actual
loading well below the code-mandated minimums.
The marble panels were also of structural
concern, due to the loss of capacity at
the kerfs resulting from bowing-induced
kerf fractures. These were particularly worrisome
because there was no outward evidence
of the fractures, so compromised
panels (or the extent of the damage) could
not be readily detected. It was calculated
that approximately 70 percent of the kerf
length was required to transfer the codemandated
design loads. Our observations
suggested that no more than ten percent of
the kerf lengths were damaged at the time
of our examination, but this figure could
increase as the panels continue to bow and
lose strength in the future.
SUMMARY
Anchorage Conditions
The original stone-panel installation is
problematic overall because the kerfs were
not filled with any material that allowed for
the loads to be spread along their length;
the panels were, in effect, loose between the
kerf anchor rails, allowing movement and
causing unpredictability with respect to
load transfer from the panel to the backup
support structure. Current practice includes
filling the continuous kerfs with a
flexible material such as elastomeric
sealant so that the kerf anchor is not rigidly
fixed in the kerf but also is not able to
move freely.
The vertical load of the stone panels
(panel self-weight) was transferred into the
continuous kerf anchors through shims
installed below the panels, and these shims
were deteriorated or missing. If the panels
are not properly supported, then the panel
can contact the kerf anchor in unanticipated
ways that cause stress concentrations
and eventual cracking. Future stone installations
should include more durable setting
blocks or shims in a length and size that are
optimal for distributing the load to the
backup structure and maintaining reliable,
consistent kerf/anchor rail engagement.
Stone Cladding Panels
The appearance of the façade elements
and stone cladding at first glance gave the
impression that these materials were in
good condition generally, despite using a
stone panel thickness for both the marble
and serpentine of less than the current
industry recommended minimum of 3 cm.
However, upon closer examination, the
stone claddings (both serpentine and marble)
had characteristics that undermined
their stability, and compromised their
structural integrity. The pronounced veining
in the serpentine concealed cracks and
represented potential planes of weakness
that could fail over time. While strength of
the serpentine was high relative to ASTM
standards, it was not adequate if this system
were to be installed under current code
requirements. Even taking into account
past “incident-free” performance of the
cladding system, the inherent variability
and unpredictability of the veined serpentine
make it a poor choice for an exterior
cladding application that carries an
increased risk of performance-related problems.
The marble cladding panels have suffered
from hysteresis, resulting in a reduction
of flexural strength below the industry
minimum for marble and below values necessary
to resist code-mandated lateral loads
but with no readily observable distress that
reveals the dramatic strength loss it has
undergone. The bowing inherent with the
hysteresis process also led to localized kerf
damage that is concealed and therefore not
easily monitored, further compromising the
ability of the marble panels to resist lateral
loads. Strength loss, as well as the associated
bowing, kerf failure, and formation of
additional cracks in the marble cladding
panels, will continue to occur over time, further
reducing their ability to resist in-service
loading.
RECOMMENDATIONS
Recommendations for corrective action
to address deficiencies with a cladding system
are always difficult because past performance
may not necessarily warrant
drastic action. Often, deficiencies are discovered
by accident, not through occurrence
of a failure. For example, cladding
systems may be underdesigned but perform
well due to a lack of exposure to maximum
design loading, conservative safety factors,
or unanticipated structural redundancy. It
is simple to arbitrarily dictate that such a
cladding system must be removed because
it does not meet current code, but if past
performance has been satisfactory, then the
decision to do away with the cladding may
represent a substantial economic waste. In
such a situation, other options should be
explored to manage the risk associated with
the deficient cladding system. This might
include enhanced inspection or monitoring
protocols, partial replacement, repairs,
strengthening, even reevaluation of potentially
overly conservative analytical assumptions
or code requirements. Often, managing
the risk associated with underdesigned
or underperforming cladding systems can
be more desirable and less disruptive than
removing the risk altogether.
In the case of this project, failure of a
single cladding panel triggered an investigation
that concluded that both the existing
serpentine and marble cladding panels were
theoretically underdesigned. Upon closer
inspection, several other serpentine panels
were indeed cracked or otherwise unstable;
however, the majority of serpentine panels
contained heavy veining but were performing
with no evidence of structural distress.
In addition, the marble panels appeared to
be performing well under in-service loads,
despite experiencing strength loss and kerf
fractures. We presented several recommendation
options to the client with a range of
costs and associated risks.
Because of the immediate need to
replace damaged and unstable panels, we
recommended a complete, 100 percent
close-range visual examination to be performed
in conjunction with joint sealant
replacement to take advantage of available
access and staging. Removal of the sealant
also helps to eliminate any redundant support
provided by the sealant itself and
allows stability of the cladding panels to be
evaluated directly. Any panels found to be
unsound, unstable, displaced, cracked, or
otherwise structurally compromised, were
to be replaced with material that matched
the original and complied with ASTM minimum
material properties. In addition to
replacement of damaged-panels, a program
of frequent inspections was required to
ensure that any future panel damage could
be identified and addressed quickly on an
ongoing basis as part of a maintenance program.
This option carried the least nearterm
cost but the most risk of future problems.
A second option was presented that
included the same close-range examination
of the cladding and replacement of any
damaged panels. In addition, we recommended
modifying the anchorage system in
a manner that reduced the flexural stresses
below the code-required maximums by
reducing the spans between anchor points.
While more costly to implement, the risk of
additional panel failure was reduced by
modifying the conditions that could lead to
a future failure, and the existing cladding
panels that are sound could be reused.
Continued inspection of the cladding was
required but at less frequent intervals than
the previous option. This option was more
costly, but reduced the risk of future problems
by addressing the stone cladding
structural deficiencies directly.
The third option presented for consideration
was replacement of the stone cladding
with alternative materials such as metal
panels or an exterior insulation finish system
(EIFS) and reusing the existing stone
cladding support system. This was the most
expensive option presented but also carried
the least future risk of failure by removing
the underdesigned and/or deficient cladding
material altogether. Due to the least
amount of risk and reduced long-term
impact to the owners, this option was chosen
over the first two; recladding design is
currently underway.
FOOTNOTE
1. Formerly, the American Society for
Testing and Materials.
1 0 • FA R M E R & K E N N E Y S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • OC T O B E R 2 0 0 8