Skip to main content Skip to footer

The Correlation Between Wind Resistance and Physical Properties of Fiberglass Shingles

May 15, 2011

2 6 T H RC I I N T E R N A T I O N A L C O N V E N T I O N A N D T R A D E S H OW • A P R I L 7 – 1 2 , 2 0 1 1 K O O N T Z • 2 7
THE CORRELATION BETWEEN WIND RESISTANCE AND
PHYSICAL PROPERTIES OF FIBERGLASS SHINGLES
BY JIM D. KOONTZ, RRC, PE
JIM D. KOONTZ & ASSOCIATES, INC.
3120 N. Grimes St., Hobbs, NM 88240
Phone: 575-392-7676 • Fax: 575-392-7602 • E-mail: jim@jdkoontz.com
ABSTRACT
Fiberglass shingles constitute the primary roofing material used for steep-sloped structures.
During high wind events, shingle performance is critical to building protection.
Shingle failure accounts for millions of dollars of insurance claims every year.
The International Building Code (IBC) requires that the manufacture of fiberglass shingles
comply with physical property standards of ASTM D3462. To test the wind resistances
of shingles, ASTM D3161, the Fan-Induced Method, is used. This method subjects shingle
test decks to varying wind speeds.
This research reviews the relationship between fiberglass shingle physical properties
and the relative wind resistance of the shingle. Test results will be compared to shingle manufacturers
marketing claims and IBC requirements.
SPEAKER
BY JIM D. KOONTZ, RRC, PE — JIM D. KOONTZ & ASSOCIATES, INC.
JIM D. KOONTZ, PE, RRC, has been involved in the roofing industry for 50+ years. Mr.
Koontz obtained a bachelor of science degree in engineering and a master’s in business
administration from Tulane University in New Orleans. He is a registered engineer in multiple
states. Jim began his career as a roofer and roofing contractor in 1960, and in 1976,
he started one of the first roof engineering firms in the United States.
As a researcher, Jim has authored numerous technical articles on roofing, covering a
variety of technical subjects. Mr. Koontz has been a guest speaker for organizations such as
NRCA, ASTM, RCI, international symposia, and others. As a consulting engineer, he has
worked in over 40 states, Canada, Mexico, and the Caribbean. Notable projects include the
Kingdome in Seattle, the Denver International Airport, and the Church Street USPO at
ground zero in New York in the aftermath of 9/11.
2 8 • K O O N T Z 2 6 T H RC I I N T E R N A T I O N A L C O N V E N T I O N A N D T R A D E S H OW • A P R I L 7 – 1 2 , 2 0 1 1
2 6 T H RC I I N T E R N A T I O N A L C O N V E N T I O N A N D T R A D E S H OW • A P R I L 7 – 1 2 , 2 0 1 1 K O O N T Z • 2 9
INTRODUCTION
Fiberglass shingles constitute the primary
roofing material used for steep-sloped
roof structures within North America.
Shingles are used in a wide variety of applications,
including single-family homes,
multitenant structures, commercial- and
institutional-type buildings. There is an
expectation by the designer, installer, and
the user that fiberglass shingles will perform
during wind events according to the
claims of the marketing literature of shingle
roofing manufacturers and the requirements
of local and national building codes.
Failures of shingles during wind events
and subsequent damage to buildings on
which they are installed account for millions
of dollars of insurance industry claims
on a yearly basis. Obviously, during high
wind events such as hurricanes, shingle
performance is critical to the protection of
building structures and their contents. See
Photo 1.
This study reviews the relationship
between fiberglass shingle physical properties
and wind resistance. Several commonly
used new fiberglass shingles from various
manufacturers throughout North America
were initially tested for physical properties
following American Society for Testing and
Materials (ASTM) procedure D3462. The
shingles were installed over plywood test
decks in accordance with the various shingle
manufacturers’ installation instructions.
A large oven was used to heat the test
decks to a test-specified temperature in
order to facilitate self-sealing adhesive strip
activation. The test decks were then subjected
to wind speeds up to 150 mph until
failures occurred. A comparison was then
made between the wind speed resistance
and the physical properties of the shingles.
HISTORY
Three-tab fiberglass shingles were first
introduced into the roofing market in the
late 1970s and early 1980s as a substitute
for conventional three-tab organic shingles.
The newer three-tab fiberglass shingles
relied upon the use of fiberglass mats to be
an equal-to or better-than product when
compared to the use of conventional organic
mats.
In the early 1990s, splitting problems
were reported with fiberglass shingles.1 As a
result, numerous
technical articles were published and
seminars held that discussed these shingle
failures. Splitting failures were attributed to
a variety of factors that included workmanship,
lack of proper below-deck ventilation,
tab adhesion, thermal expansion/
contraction of the shingles and the
deck, and insufficient tensile strength and
tear resistance. Analysis of the relationship
of these physical properties of shingles to
wind resistance has been limited.
Several factors that can affect the wind
resistance of fiberglass shingles include
installation errors, the design of a shingle,
and the quality control of the shingle when
manufactured. The International Building
Code (IBC) requires that fiberglass shingles
be manufactured to comply with various
physical property standards set forth in
ASTM D3462. Typical physical properties
include the following: masses of the shingle,
the matt, asphalt, and filler in a per unit
area. Other minimum physical properties
include: nail pull-through and tear resistance.
Consumers, contractors, and roof
designers take for granted that fiberglass
shingles are manufactured in compliance
with code requirements, and they rely upon
manufacturers’ marketing representations
and claims.
The test wind speeds for shingles, once
deemed adequate to predict performance,
have changed dramatically since Hurricane
Andrew in August of 1992. In the late 1980s
and early 1990s, the maximum wind speed
used in shingle testing was 60 mph. This
was recognized as inadequate and unrealistic
compared to real-world wind events.
Today’s standards require testing at speeds
ranging from 60 to 150 mph.
SHINGLE INSTALLATION
The number and placement of fasteners
attaching the shingle to the substrate is
critical to the performance of fiberglass
shingles. Nails installed in the shingle too
high or at improper locations can affect a
shingle’s wind resistance. Obviously, nails
placed too high, engaging only one layer of
a shingle as opposed to two layers, are more
THE CORRELATION BETWEEN WIND RESISTANCE AND
PHYSICAL PROPERTIES OF FIBERGLASS SHINGLES
Photo 1 – Shingle failure.
likely to fail at lower wind speeds. The pullthrough
resistance of a nail installed in only
one layer of a shingle is obviously less than
that of a properly placed nail. Thomas
Smith studied the subject of acceptable fastener
location variation in 1999.2 One of
Smith’s recommendations was for shingle
manufacturers to provide clear “nail lines”
so that contractors could secure shingles at
the proper locations.
Shingle placement and exposure can
also be important to the wind resistance of
fiberglass shingles. Shingles installed with
too much exposure and, therefore, a lack of
headlap, are more vulnerable to failure during
wind events. See Figure 1.3
Properly driven fasteners are critical for
suitable performance of shingles during
wind events. Improperly installed nails can
be underdriven, overdriven, installed
crookedly, or outside the nail zone. Tab
adhesion by way of the self-sealing adhesive
strip can be affected by fasteners either
underdriven or installed crookedly. See
Figure 2.4 Overdriven fasteners and fasteners
installed crookedly can break the fiberglass
matt at or near the nail head, resulting
in a loss of nail pull-through resistance.
Typically, a minimum of four nails,
evenly spaced and just below the self-sealing
adhesive strip, is required for conventional
three-tab fiberglass shingles. Specific
recommendations in high wind zones are
somewhat vague. Several manufacturers
require and show up to six fasteners per
shingles in “high wind areas. The decision
of what is considered a high wind area is
left up to the contractor, consumer, and the
design professional. The building codes
refer back to recommendations of the shingle
manufacturer for proper installation.
The timing of installation of shingles can
also be critical. The self-sealing adhesive
strip may not activate until spring for shingles
installed in the late fall or winter
because of cold weather. In some areas of
the country, windstorms can deposit dust
beneath shingle tabs before sealing occurs,
resulting in imperfect bonding strength.5
BUILDING CODES
Designers, contractors, and consumers
assume that fiberglass shingles will provide
a reasonable degree of performance during
expected wind events as required by local
building code. Maps found in the IBC depict
expected basic wind speed for a 50-year
mean recurrence interval for all areas of the
United States and territories. Refer to Figure
3, IBC R301.2(4).
Once a wind speed is determined from
the IBC R 301.2(4) map, reference is then
Figure 1 — Proper and improper
nailing.
Figure 2 — Improperly
driven fasteners.
Figure 3 — IBC map.
Figure 4: Table 905.2.4.1(1)
Maximum Basic Classification ASTM Type, Class
Wind Speed Requirement Wind Speed (mph)
Figure 301.2(4) (mph)
85 D, G, or H D = 90, G = 120, H = 150
90 D, G, or H D = 90, G = 120, H = 150
100 G or H G = 120, H = 150
110 G or H G = 120, H = 150
120 G or H G = 120, H = 150
130 H H = 150
140 H H = 150
150 H H = 150
3 0 • K O O N T Z 2 6 T H RC I I N T E R N A T I O N A L C O N V E N T I O N A N D T R A D E S H OW • A P R I L 7 – 1 2 , 2 0 1 1
CLASSIFICATION OF ASPHALT SHINGLES PER ASTM D7158
made to determine the proper shingle classification
based upon the basic wind speed.
Refer to IBC Tables 905.2.4.1 (1) and (2),
Figures 4 and 5. Depending upon the test
procedure followed, a letter classification is
then designated for a shingle: D, G, or H for
ASTM D7158; or A, D, or F for ASTM
D3161. The test wind speed is then listed
within the ASTM standards. Depending
upon performance characteristics, shingles
are consequently marketed by manufacturers
with specific wind-resistance classifications,
e.g., A = 60 mph, D = 90 mph, or F =
110 mph.
WIND TESTING, ASTM D7158 AND
D3161
The wind resistances of shingles are
tested in accordance with ASTM D7158,
which involves measuring pressure differences
above and below shingles and performing
mechanical uplift resistance using
a tensile-testing apparatus described in
ASTM D6381. Calculations are then
required to determine the relative uplift
resistance of a shingle. The test procedure
described was developed by the Asphalt
Roofing Manufacturers Association (ARMA)
in 1991 at a time when the prior shingle
testing that was performed at wind speeds
up to 60 mph was
believed to be
inadequate.6 See
Photo 2.
The Fan-
Induced Method,
ASTM D3161,
involves building shingle test roof decks
and then subjecting the shingles to various
wind speeds. The test decks are conditioned
at a temperature of 57° to 60°C (135° to
140°F) for a continuous period of 16 hours
at a slope of 2 in per ft or 17%. The temperature-
conditioned test decks are then
placed in front of the fan outlet on an
incline of 2 in per horizontal ft (17% slope).
The fan delivers a horizontal stream of air
through a rectangular opening 3-ft wide by
1-ft high, placed 7 in from the leading edge
of the third course of shingles. See Photo 3.
The test decks are then subjected to
various wind speeds. Failure is defined in
ASTM D3161 as the inability to restrain any
portion of a shingle lifting that would prevent
the shingle from standing upright or
bending back on itself. Depending upon
performance characteristics, shingles are
consequently marketed by manufacturers
with specific wind resistance classifications:
A = 60 mph, D = 90 mph, or F = 110 mph.
Shingle manufacturers will typically
represent, in writing, that their shingles
meet certain ASTM and IBC standards;
however, shingle manufacturers’ warranties
may actually be written for a lower wind
speed than the wind speed listed in the IBC
or ASTM classification.
Prior research7 utilizing pressure-sensing
taps has studied the wind flow mechanism
that produces uplift on shingles. This
research has shown that as wind flows up
and over the surface of a shingled roof,
forces exerted by the wind vary depending
upon location. Refer to Figure 6.8 Negative or
uplift pressure develops just above and
behind the leading edge of the tab of the
shingle. In front of the butt edge of the shin-
Photo 2 — Wind testing.
Photo 3 — Fan.
2 6 T H RC I I N T E R N A T I O N A L C O N V E N T I O N A N D T R A D E S H OW • A P R I L 7 – 1 2 , 2 0 1 1 K O O N T Z • 3 1
CLASSIFICATION OF ASPHALT SHINGLES PER ASTM D3161
Figure 5: Table 905.2.4.1(2)
Maximum Basic Classification ASTM Type, Class
Wind Speed Requirement Wind Speed (mph)
Figure 301.2(4) (mph)
85 A, D, or F A = 60, D = 90, F =110
90 A, D, or F A = 60, D = 90, F =110
100 A, D, or F A = 60, D = 90, F =110
110 F F = 110
120 F F = 110
130 F F = 110
140 F F = 110
150 F F = 110
gle, a stagnation region develops that creates
downward pressure. Prior research
was instrumental in the development of
ASTM D7158, which calculates wind resistance
of asphalt shingles.
SHINGLES’ MARKETING
LITERATURE
Each shingle of every manufacturer
used in this research represented compliance
with a letter classification listed in
ASTM D3161, ASTM D7158, or both. Seven
out of eight manufacturers indicated compliance
with ASTM D3462. The manufacturers
also listed a wind speed warranty in
miles per hour (see Figure 7).
LABORATORY TESTING, PHYSICAL
PROPERTIES – ASTM D3462
Jim D. Koontz & Associates, Inc.
acquired new, three-tab fiberglass shingles
from five different commercially available
retail or supplier sources. Prior to the
installation of the shingles on the decks for
wind testing, the physical properties of the
shingles were determined.
• Mat weight
• Tensile strength
• Tear strength
• Fastener
p u l l –
through:
s i n g l e
l a y e r ,
double layer
Small samples from
the fiberglass shingles
were placed in a bath of
hot, circulating, organic
solvent. The asphalt
and granules were
extracted from each
sample until a clean
mat was obtained. The
samples of the desaturated
fiberglass mat
were dried and weighed.
The desaturated dry
fiberglass mat weights
ranged from a low of
1.71 lbs/100 ft2 to a
high of 2.07 lbs/100 ft2. All of the shingle
samples tested contained fiberglass mats
that exceeded the ASTM D3462 minimum
desaturated mat weight requirement of 1.35
lbs/100 ft2. The shingles tested had a gross
weight ranging from a low of 74.7 lbs/100
ft2 to a high of 101.9 lbs/100 ft2. All of the
shingles exceeded the ASTM D3462 total
minimum weight requirement of 70.0
lbs/100 ft2. See Photo 4.
The shingles were also tested for tensile
strength. Tensile strength is not listed as a
requirement under ASTM D3462. The tensile
strength test was performed for purposes
of information and comparison. The tensile
strengths ranged from a low of 84.0 lbf
to a high of 126.0 lbf. See Photo 5.
Fastener pull-through testing was performed
with a single layer and two layers of
shingles. The purpose of employing two
methods of testing was to simulate improper
and proper fastener placement.
Obviously, if a shingle were nailed above the
recommended nail zone, only one layer
would be penetrated. The single-layer pullthrough
resistance ranged from a low of
20.0 lbf to a high of 33.0 lbf. The ASTM
D3462 pull-through requirement for a single
shingle layer is a minimum of 20.0 lbf.
The double shingle layers’ pull-through
resistance ranged from 40.0 lbf to 70.0 lbf.
Figure 6 — Shingle separation.
Figure 7
Shingle ASTM ASTM D3161 ASTM D7158 Manufacturer
Manufacturer D3462 Classification Classification Warranty
(mph)
1 Yes A, F H 60
2 Yes F H 60
3 — A H 54
4* Yes F — 100
5 Yes F H 60
6 Yes F H 60
7 Yes F H 60
8 Yes F H 60
3 2 • K O O N T Z 2 6 T H RC I I N T E R N A T I O N A L C O N V E N T I O N A N D T R A D E S H OW • A P R I L 7 – 1 2 , 2 0 1 1
Photo 4
— Mat
weight.
Photo 5 — Tensile strength.
*Modified Asphalt Shingle A = bundle; F = literature
ASTM D3161: A = 60 MPH, F = 110 MPH; ASTM D7158: H = 150 MPH
See Photos 6A and 6B.
The Elmendorf Tear Test, ASTM D1922, was performed on each of
the eight new shingle samples. ASTM D1922 is one of the ASTM
Standards referenced in D3462. The tear strength ranged from a low of
1,290.0 g to a high of 2,400.0 g. Under ASTM D3462, the minimum tear
strength requirement is 1,700.0 g. Seven of the eight shingle samples
tested did not meet the minimum ASTM requirement. See Photo 7.
Seven of the eight shingles that fell below the 1,700 g tear resistance
requirement were packaged in wrappers that stated the shingles were
manufactured in accordance with ASTM D3462 standards. Most importantly,
the IBC requires that shingles meet the minimum standards of
ASTM D3462, and that includes D1922.
A summary of the physical property test is included within Figure 8.
LABORATORY TESTING, WIND RESISTANCE – ASTM D3161
Eight test roofs/decks were carefully constructed consisting of ½-in
plywood covered with a Type 15 organic felt
underlayment and overlaid with different,
new fiberglass shingles. Each shingle was
attached to the test deck with four roofing
nails at the manufacturer’s specified usual
locations just below the self-sealing adhesive
strip. Each test roof was then conditioned
following ASTM D3161 in a large
oven for 16 hours at a temperature of 57° to
60°C (135° to 140°F) in order to activate the
self-sealing adhesive strip.
Initial testing showed that the conditioning
time and temperature did not result
in an adequate activation of the self-sealing
adhesive strip. This resulted in a poor bond
of the shingle layers, typically found in field
inspection of real-world projects. The shingles
conditioned for 16 hours at a temperature
of 57° to 60°C (135° to 140°F) failed at
60 mph.
The test samples were then reheated for
16 hours at 160°F, and tested after reheating.
Prior research by William Cullen9 also
found that conditioning the shingles at
higher temperatures over a longer period of Figure 8
Shingle Tear Tensile Net Desaturated Pull Pull
Sample Strength Strength Weight Mat Weight Through Through
Single Double
Layer Layer
(g) (lbf) (lbs/sq) (lbs/sq) (lbf) (lbf)
1 1,670 99 74.7 1.77 25 48
2 1,450 91 84.6 2.04 25 55
3 1,290 87 81.8 1.96 23 45
4* 2,400 87 101.9 2.00 26 54
5 1,960 126 80.5 1.89 33 70
6 1,430 84 93.1 2.07 22 40
7 1,870 87 83.6 1.83 23 49
8 1,430 84 82.3 1.71 20 49
Average 1,688 9893 85.3 1.91 25 51
ASTM 1,700 — 70.0 1.35 20 —
Minimum
2 6 T H RC I I N T E R N A T I O N A L C O N V E N T I O N A N D T R A D E S H OW • A P R I L 7 – 1 2 , 2 0 1 1 K O O N T Z • 3 3
Photos 6A and 6B — Fastener pull-through.
Photo 7 — Elmendorf tear test.
*Modified Asphalt Shingle
time enhances self-sealing adhesive strip
bond strength.
The ASTM D3161 basic test procedure
requires that a test deck be exposed to one
wind speed for two hours; however, it is not
prohibited to use different test velocities
and different time intervals. In this
research, each test deck was placed in front
of a blower, and it was then tested at wind
speeds that began at 60 mph and increased
in 30 mph increments every thirty minutes,
up to a maximum of 150 mph. The mode of
failure of the different shingles on each test
deck was recorded (Figure 9).
According to ASTM D3161, failure is
defined as follows:
The end point for failure shall be
taken as the time at which the sealing
feature fails to restrain one or
more full shingle tabs. In addition,
no free portion of a shingle shall lift
so as to stand upright or bend back
on itself during the test.
For purposes of this research, failures of
the shingles were described by two different
modes:
Mode 1 — Tab loose, unbroken,
meets the ASTM D3161 minimum
Mode 2 — Full shingle detachment,
exposure of felt underlayment, wood
deck, or both
Seven of eight shingles tested complied
with the wind speed rating as required
under ASTM D3161. Two of eight shingles
rated under ASTM D7158 performed well at
a wind speed of 150 mph; six shingles, however,
failed. The shingles tested performed
at wind speeds that exceeded the velocities
listed in the warranties.
The test data show very little correlation
between the wind resistance and the desaturated
mat-weight of the shingle. There is
also very little correlation between the gross
shingle weight and the wind resistance of
the shingle. The only exception was Shingle
Sample No. 4, the modified asphalt shingle,
which had the highest total gross shingle
weight.
Once the self-sealing adhesive strip has
failed by separating, it is clear that shingles
with higher fastener pull-through resistance
and higher tear strength have a higher
destructive wind-speed resistance (refer
to Figures 10 and 11).
Shingle Mode 1 Mode 2 Class Class Warranty
Tab Loose Underlayment D3161 D7158 mph
mph or Deck mph mph
Exposure mph
1 110 130 60/110** 150 60
2 130 130 110 150 60
3 90 110 60 150 54
4* 150+ 150+ 110 — 100
5 150 150 110 150 60
6 90 110 110 150 60
7 130 130 110 150 60
8 130 130 110 150 60
Figure 9
Figures 10 and 11 — Tear strength/wind speed and pull-through/wind speed.
3 4 • K O O N T Z 2 6 T H RC I I N T E R N A T I O N A L C O N V E N T I O N A N D T R A D E S H OW • A P R I L 7 – 1 2 , 2 0 1 1
*Modified Asphalt Shingle **Data on Wrapper / Marketing Literature
ADDITIONAL TESTING,
WORKMANSHIP ERRORS
Test decks were also constructed with
often-seen workmanship errors: high nailing
(above the required nailing zone), installation
with less than four nails, and excessive
tab exposure. Samples built with excessive
exposure and nails improperly placed
failed at wind speeds of 60 mph.
ADDITIONAL TESTING, SHINGLE TAB
RESEALED
Shingles were subjected to various wind
speeds until one tab failed but did not crack
or bend back from the test deck, according
to ASTM D3161. The shingle tabs that
became loose at 60 mph were resealed with
asphalt roof cement. The repaired roof deck
was then retested. The roof with repaired
shingles performed up to 110 mph.
SHINGLES INSTALLED USING SIX
NAILS VERSUS FOUR NAILS
Before the advent of self-sealing shingles,
the installation of organic shingles
using six nails per shingle was a common
practice and was required by the Corp of
Engineers on military installation projects.
The shingle tabs were hand sealed with
asphalt roof cement. Manufacturers currently
refer to the use of six nails in areas of
high wind zones.
Shingle samples were tested on test
decks using both six and four nails per
shingle. The initial tab failures were found
to be similar on both sets of decks.
Catastrophic failures (seen as fully bent
back or broken tabs), however, were minimized
when six nails were utilized for
attachment. Moreover, the catastrophic failure
mode was delayed, requiring a longer
exposure to wind before failure.
Prior research conducted by Carl Cash
indicated that at wind speeds of up to 60
mph, the number of nails used to secure
shingles to a deck was not found to be particularly
critical. Thomas Smith stated,
however, that shingles installed with six
nails provided additional wind resistance
over shingles installed with four nails.10
DISCUSSIONS
Under the current 2009 Edition of the
International Building Code, all of the
United States falls within a minimum wind
speed zone of 90 mph. The IBC also
requires that all shingles comply with ASTM
D3462. It would appear that Class-A shingles,
only tested to 60 mph under ASTM
D3161, cannot be code-compliant.
The 2012 Edition of the IBC will adopt
2010 American Society of Civil Engineers
(ASCE) 7. Significant increases in the basic
wind speeds that shingles need to resist will
occur, with the minimum standard
throughout the United States becoming 115
mph.11 Classifications of shingles at 60
mph, 90 mph, and 110 mph may no longer
be adequate for code compliance.
There is an assumption that the marketing
literature representing a shingle’s
physical characteristics and performance
attributes is accurate. Prior research has
shown that representations of shingle manufacturers
claiming shingle compliance
with ASTM D3462 are not necessarily accurate.
12
The letter classification, particularly
under ASTM D7158 where a wind speed
resistance is calculated, may also provide
inaccurate information. As Thomas Smith
notes, “Research studies13 by others have
concluded that shingles [sic] performance
during wind events is related to the variability
in the physical properties of shingles.”
CONCLUSIONS
• Successful performance of fiberglass
three-tab shingles is clearly dependent
upon three interdependent
properties: proper installation, adequate
activation of the self-sealing
adhesive strip, and shingles manufactured
actually to meet or exceed
the industry-adopted standards of
ASTM D3462.
• The ratings determined under ASTM
D7158, in some cases, list a wind
speed of 150 mph. The representation
that some shingles can perform
at this wind speed may not always
be accurate.
• Testing shingles in strict accordance
with ASTM D3161 procedures may
not reflect real-world conditions.
Conditioning shingles for 16 hours
at a temperature of 57° to 60°C
(135° to 140°F), in most cases, did
not properly activate the self-sealing
adhesive strip. Heating the test
decks at higher temperature was
required to properly activate the
self-sealing adhesive strip.
• Shingles with a higher nail pullthrough
resistance and a tear resistance
of 1,700.0 grams or greater, as
required by ASTM D3462, exhibit a
higher degree of wind resistance.
Shingles that do not meet ASTM
D3462 are not code-compliant.
• Depending upon the type of damage
and the extent of such damage,
some repair can be performed on
three-tab shingles with an expectation
of shingle performance in compliance
with code requirements.
• Based upon the testing performed, it
is clear the first line of defense from
high wind speeds is the performance
of the self-sealing adhesive strip.
Once the self-sealing adhesive strip
fails, the physical properties of the
shingles come into play. Shingles
with enhanced tear strength and
fastener pull-through strength tend
to have a greater resistance to catastrophic
failure.
END NOTES
1. Jim D. Koontz, “Fiberglass Shingles,”
Western Roofing Magazine,
1990.
2. Thomas L. Smith, Matt Millen,
“Influence of Nail Locations on Wind
Resistance of Unsealed Asphalt
Shingles,” North American Conference
on Roofing Technology,
Ontario, Canada, Sept. 16, 1999,
98-111.
3. Redrawn from The National Roofing
Contractors Roofing and Waterproofing
Manual – Fourth Edition,
1,049.
4. Ibid., 1,048.
5. J.A. Peterka, J.A. et al., “Wind Uplift
Model for Asphalt Shingles,” Journal
of Architectural Engineering,
December 1997, 147-155.
5. Donald E. Shaw, “ARMA’S New
Approach for Evaluation of Asphalt
Shingle Wind Resistance,” International
Symposium on Roofing
Technology, 1991, 216-218.
7. J. Peterka, G.D. Lamb, J.E. Cermak,
“Wind Resistance of Asphaltic Roofing
Shingles,” Proceedings of the
Seventh International Conference on
Wind Engineering, Volume 3, 1987,
21-30.
8. Redrawn from an illustration from
Carl G. Cash and Frank W. Kan,
“Finite Element Analysis of Racked
vs. Traditionally Applied Three-Tab,
Seal-Tab, Strip Shingles, and Blister
Tests for Asphalt-Glass Felt Shingles,”
ASTM STP 1349, Roofing
Research and Standards Development,
4th Vol., May 1999,
123–131.
2 6 T H RC I I N T E R N A T I O N A L C O N V E N T I O N A N D T R A D E S H OW • A P R I L 7 – 1 2 , 2 0 1 1 K O O N T Z • 3 5
9. William C. Cullen, “Research and
Performance Experience of Asphalt
Shingles,” 10th Conference on
Roofing Technology, National Institute
of Science and Technology,
National Roofing Contractors
Association, April 1993, 6-12.
10. Thomas L. Smith, “Improving Wind
Performance of Asphalt Shingles:
Lessons From Hurricane Andrew,”
11th Conference on Roofing
Technology, Gaithersburg, Maryland,
September 21 – 22, 1995.
11. Thomas L. Smith, “Mapping the
2010 Wind Changes,” Professional
Roofing, NRCA, August 2010, 35-39.
12. Jim D. Koontz, “Performance Attributes
of Fiberglass Shingles,” Interface,
July 2007.
13. Thomas L. Smith and Matt Millen.
3 6 • K O O N T Z 2 6 T H RC I I N T E R N A T I O N A L C O N V E N T I O N A N D T R A D E S H OW • A P R I L 7 – 1 2 , 2 0 1 1