Skip to main content Skip to footer

Forensic Processes For Water Intrusion Investigations

May 15, 2012

While the word “forensic”
has different meanings
throughout North America,
for this article, it is
defined as “the puzzlesolving
application of a
broad spectrum of technical knowledge and
expertise to answer questions of interest.”
The purpose of the following case study is to
consider nonlinear puzzle-solving processes
used during an extended water intrusion
investigation—not to evaluate the merits of
original decisions made by the building’s
contractors.
Preli min ary Inv esti gati on
Our firm was hired to investigate carpet/
flooring failure at the offices of a nonprofit
research facility (Photo 1) near San
Francisco. The
commercial
building was
constructed
in 2005 with
concrete tiltup
panels
(Photo 2) atop
spread concrete
footings
surrounding
an on-grade concrete floor slab directly
adjacent to a tidal estuary (Photo 3) at the
mouth of a river flowing into a saltwater
bay.
N o v e m b e r 2 0 1 2 I n t e r f a c e • 5
Photo 2 – 2005: Concrete tilt-up panels on “spread
footings” surround on-grade concrete slab.
Photo 1 – Nonprofit research facility
near San Francisco.
The on-grade concrete slab addressed below was introduced
to Interface readers in a November 2009 article, “Concrete
Slab-on-Grade Moisture Tests: How Useful Are the Testing
Data When the Vapor Barrier May Be Ineffective?”
6 • I n t e r f a c e N o v e m b e r 2 0 1 2
As seen in Photo 4, our inspection confirmed
deterioration of the latex adhesive
used to secure the vinyl-backed carpet
tiles, which were functioning as a barrier
against the dissipation of water vapor rising
through the floor slab. Such adhesive
failure can result when “moisture traveling
upward through the concrete brings alkalies
to the surface where they can attack
flooring materials.”1 We expedited samples
of the smelly, emulsified adhesive to a laboratory
for assessment of potential health
risks to the building occupants and then,
as directed by indoor air quality (IAQ) specialists,
removed the carpet tiles and deteriorated
adhesive, exposing the underlying
“wet” floor slab.
After safe removal of the failed carpet
tiles, the pressing forensic questions
included these:
a. How wet was the concrete slab at
this point in time?
b. Were some areas substantially wetter
than others?
c. Over time, would the now-exposed
on-grade concrete slab begin drying?
d. Did the humidity data provide clues
to the moisture source(s) wetting the
slab?
Over the course of our investigation, we
used two diagnostic
tests to address such
issues:2
1. An electrical
impedance
test using a
proprietary
meter3 to
d e t e r m i n e
near-surface
moisture content
(Photo 5)
by transmitting a radio-frequency
alternating-current field into the
slab.4
2. An internal relative-humidity test
carried out in conformance with
ASTM F2170.5 Holes are drilled to
a depth of about 40% of the slab’s
thickness to accommodate a tightly
fit sensor that registers the approximate
temperature and relative
humidity (RH)6 within the concrete.7
With the electrical impedance meter,
we found that the near-surface moisture
content of the slab ranged from about 5% to
greater than 6%.8 These high values clearly
demonstrated some form of moistureresistive
performance failure in the design
and/or construction of the on-grade concrete
slab and its surroundings.
In Figure 1, which presents a floor plan
of the building, our preliminary (Phase 1)
and later (Phase 2) electrical impedance
metering is summarized in three approximate
zones of moisture content: “yellow”
(5.0 to 5.7%), “green” (5.8 to 6.0%), and
“blue” (>6.0%). The Phase 1 data suggested
that primary origin(s) of the unintended
moisture infiltration might be located at or
near the western edge of the slab.9
Photo 3 – The building was constructed atop a high water table adjacent to a tidal estuary.
Photo 4 – Latex adhesives are emulsified and
deteriorating, creating smelly IAQ problem.
Photo 5 – Electrical impedance confirms
floor slab is saturated.
By comparison,
the matrix in Table
1 summarizes midslab
“internal RH”
data collected from
six sensors over a
two-year period. The
locations of the six
sensors (S-1, S-2,
S-3, S-4, S-5, and
S-6) are identified in
Figure 1. We see in
Table 1 that five of
the six sensors have
recorded surprisingly
high humidity10
levels within the
concrete slab, while
the other sensor
(S-3) has recorded
“dry” conditions.
Note: With these
sensors, “Hi” indicates
a value greater
than 99% RH. While
both values correspond
to saturation
of the concrete floor
slab, significant
additional moisture
is required to register
“Hi” instead of
99%.
The data from
our moisture me-ters
and RH sensors
demonstrated
that the on-grade
concrete slab was unusually wet. The
primary purpose for our ensuing puzzlesolving
investigation was to explain why,
how, and where this excess moisture infiltrated
the slab. The foundation for this
forensic process is the highly perceptive
guidance published by architect William
Rose: “Most moisture problems can be
diagnosed by looking at the condition and
asking how much water it took to create
Figure 1 – Partial plan view identifies the “internal RH” sensors (S),
the concrete test cuts (C), four inspected planters (P), and approximate
moisture content (MC) measurements at the concrete slab.
Table 1 – Internal relative humidity readings per ASTM F2170.
610.579.9075
www.Durapax.com
Rugged &
ReCYCLed
Durapax Coal Tar
Delivers Roofing
Reliability
Coal tar is the most reliable and
long-lasting membrane roofing
technology for flat and low-slope
commercial roofs, due to its
superior resistance to weather
extremes, extended exposure to
ponded water, and low total cost
of ownership.
As a pre-consumer recycled
product, coal tar contributes
to your LEED certification
(Credit #4); and may qualify
as a locally-produced material
(Credit #5). Durapax coal tar
roofing systems are ideal under
vegetated roofs, which are
subject to constant moisture. And
coal tar’s exceptionally long life
span represents the ultimate in
sustainability, with less landfill
volume generated.
Specify your next “green roof”
with a Durapax coal tar roofing
system.
N o v e m b e r 2 0 1 2 I n t e r f a c e • 7
8 • I n t e r f a c e N o v e m b e r 2 0 1 2
that problem. Solving the problem amounts
to asking where that amount of water could
have come from and where it should go.”11
Even though we already had identified
a variety of exacerbating sources of water
leakage into the building and onto the slabon-
grade concrete, including improperly
installed aluminum-framed storefront windows
and widespread cracking of the concrete
tilt-up panels (Photo 6), these defects
could not have produced sufficient amounts
of water to make the floor slab so wet.
Conditions under the concrete floor
slab were investigated
destructively
at three locations
(C-1, C-2, and
C-3) identified in
Figure 1. In test
cut C-1 (Photo 7)
near the S-3 sensor,
we found multiple punctures in the
10-mil polyethylene vapor retarder12 (Photo
8) installed between the compacted granular
base and granular subbase. No evidence
of free water was found in this hole.
At test core C-2, near the western
edge of the concrete floor slab, pooling
water (Photo 9) was found directly under
the floor slab. Similarly, at test cut C-3,
after excavation below the sidewalk, water
began seeping outward
(Photo 10) from
under the concrete
tilt-up panel, indicating the existence of a
pool of water under the slab at its western
perimeter.
Upon digging into planters P-1 and
P-2 (see Figure 1) between the front of
the building and the sidewalk, we found
corroded rebar and the exposed edge of a
blackish 10-mil polyethylene vapor retarder
(also punctured). In other words, as seen in
Photo 11, the contractor had not closed off
(or “turned down”) the edge of the concrete
slab to provide a water migration barrier
between the planter soil and the granular
base and subbase under the concrete slab.
However, within these two planters, we
found no evidence of ponding or trapped
water, and we observed that the granular
fill supporting the sidewalk promoted good
Photo 7 – Test cut C-1 exposes the overlap joint
of the 10-mil polyethylene vapor retarder.
Photo 6 – Widespread cracking of concrete tilt-up panels
was an exacerbating source of water infiltration.
Photo 8 – The polyethylene vapor retarder
was found to have numerous punctures.
Photo 9 – Test core C-2: Pooling water was
found directly under the floor slab.
drainage away from the building.
At this point in the forensic analysis,
it seemed reasonable to hypothesize that a
primary moisture source for the wet floor
slab was some form of upward “percolation”
of unintended moisture (water and/
or vapor) through the underlying clay soil13
from the high water table14 (Photo 3) traveling
vertically through the punctured vapor
retarder15 (Photo 8) into the on-grade concrete
slab.
In retrospect, we had reached this seemingly
reasonable—but erroneous —hypothesis
by overly focusing on the heavily punctured
vapor retarder due to our past experiences
with failed or missing underslab
vapor retarders at other projects.16
Phase 2 Inv esti gati on
Upon subsequent review, our theory
was found to suffer from a fatal flaw: the
concrete floor slab and its subslab granular
layers had been installed onto a 30-in.-thick
lime-treated soil
(LTS)17 pad constructed
atop
the locally common
adobe clay
soil, which can
be highly expansive
(i.e., has
a high shrink/
swell potential
when its moisture content decreases or
increases). Our destructive testing (with a
jackhammer) supplemented research indicating
such dense LTS pads are resistant to
water and vapor infiltration.
Many areas in North America18 have
expansive clay soils with high shrink/
swell properties that can be stabilized with
hydrated lime treatment, which causes
the clay surface mineralogy to be altered,
producing reduced
plasticity, reduced
moisture-holding
capacity, reduced swell potential, improved
stability, and the ability to construct a solid
working pad.19
While it is far more common to encounter
these relatively expensive LTS stabilization
programs during roadway construction
and at large commercial projects than
at small office/warehouse buildings, with
20/20 hindsight (considering the adobe clay
soils and the river mouth location), it makes
N o v e m b e r 2 0 1 2 I n t e r f a c e • 9
Photo 10 – Test cut C-3 at sidewalk: Water began seeping outward
from under the concrete tilt-up panel.
Photo 11 – Soil in planter directly abuts the
granular subgrade under the concrete slab.
The punctured polyethylene vapor retarder is
visible under the corroded rebar.
Photo 12 – Overview of P-3 planter.
Photo 13 – Close view of P-3 planter.
1 0 • I n t e r f a c e N o v e m b e r 2 0 1 2
great sense that the construction site first
had been prepared with a thick, dense, and
relatively water-impenetrable LTS pad.
During our initial forensic surveys, perhaps
blinded by our focus upon the punctured
vapor barrier and the high water
table, our incomplete surveys at the P-1 and
P-2 planters and the C-1, C-2, and C-3 test
cuts caused a failure to consider the underlying
LTS pad (not shown on the provided
construction drawings). In hindsight, it is
obvious that we also should have inspected
the other planters sooner.
The thick LTS pad extends beyond the
building’s footprint, under the adjacent
sidewalk. Beyond the sidewalk, the at-grade
hardscape slopes away from the concrete
slab and sidewalks. These conditions certainly
seemed to discredit any theory that
the wet floor slab was indicative of vertical
“percolation” of moisture from the underground
water table.
The puzzle-solving process for complex
water intrusion investigations can be a
highly nonlinear maze. When arriving at a
roadblock or dead end, the next step is to reassess
previously collected observations and
data for evidence of alternate pathway(s).
Again, the advice of architect William Rose
is fundamental: Solving complex moisture
problems always entails asking where that
amount of water could have come from.20
For this particular puzzle, if the problematic
water apparently was not migrating vertically,
then we needed to reconsider potential
routes for horizontal intrusion atop the
newly recognized LTS pad.
Our initially collected moisture data had
indicated the wettest (“saturated”) areas of
the wet concrete floor slab were at its western
edge. Upon
excavation into
the infill planter
(P-3) seen in
Photos 12 and 13,
we found wet soil,
the exposed edge
of the polyethylene
vapor retarder, and
water trails leading
under the concrete
slab and granular
base and subbase
atop the LTS pad.
And, even though
some, but not all,
of these planting
areas were serviced
by landscaping
drains, the inlets for these through-thesidewalk
drain pipes were located about two
inches above the LTS pad, thus serving no
functional purpose.
Finally, even though our excavation at
the P-1 and P-2 planters at the front of the
building had revealed a drainable granular
base under the adjacent sidewalk, here at
the P-3 sidewalk, we found native clay soil
that was highly sticky and water-saturated,
providing minimal drainage,
if any, from the planter. In
short, at the four sides of the
P-3 planter, only the granular
base and subbase under
the slab provided drainage
routes.
Meanwhile, we had received
permission to take
moisture content readings of
the concrete floor slab inside
south-facing Unit 12 (see
Photo 14), which had become
vacant. As shown in Figure 1,
the entire floor in Unit 12 was
found to be very wet, with
the wettest readings at the
southern edge adjacent to the
planters.
We excavated into the P-4
planter (Photo 15), again finding
wet soil, the exposed edge
of the polyethylene vapor
retarder, and visual evidence
that water migration under
the concrete slab was occurring
atop the LTS pad, which
was found to have an undulated
surface that could pond
water. Then, under the P-4
sidewalk, we again found native clay soil
that was highly sticky and water-saturated,
providing minimal drainage, if any, from the
planter. (Also note the plastic piping for the
landscaping irrigation in Photo 15.)
Summary Disc ussi on
In many litigation cases, forensic analyses
of building envelope performance move
forward sporadically due to legal, logistical,
access, and/or budgetary constraints.
This article does not attempt to describe or
explain the timeline of the extended investigation
carried out at this building.
A critical goal of the forensic process is
tying together cause(s) and effect(s). “Within
the limits of the investigator’s commission: a)
the consequences of leakage are established;
b) the severity, consistency, and distribution
of these consequences are determined;
and c) leakage pathways from construction
defects and other types of building envelope
failures are identified. This investigative process
commonly is both inductive and deductive
and should be carried out with methodological
competence, intellectual rigor, and
professional integrity.”22
While our preliminary Phase 1 survey
led us to hypothesize vertical percolation
Photo 14 – Phase 2 investigation occurred at Unit 12.
Photo 15 – The pour strip (or pour-back strip) 21 within Unit
12 was saturated. The planter drains under the slab via
the LTS pad.
from the natural water table as a primary
explanation for the wet slab and resultant
flooring failure, subsequent evidence,
including the Phase 2 survey, led us to
conclude that a primary source was horizontal
migration—via the granular base and
subbase under the slab—from the poorly
drained planters, creating a perched water
table23 atop the LTS pad.24
In retrospect, the early information
gained from the moisture content values
summarized in Figure 1 and the subgrade
conditions (see Photo 11) exposed
at the interface between the P-1 planter
and the slab easily could have been
sufficient to solve this moisture-migration
puzzle. However, even if our conclusions
perhaps came slowly, our forensic process
remained consistent with the investigative
methodology prescribed in ASTM E2128,25
which includes the following guidance: “The
information systematically accumulated in
a leakage evaluation is analyzed as it is
acquired. The new information may motivate
a change in approach or focus for subsequent
steps in the evaluation process.”
Even though E2128 specifically addresses
leakage evaluations of building walls, its
forensic principles are valid for all building
envelope evaluations.26 As the investigation
progresses, new conditions and sampling
questions may emerge that confirm, enrich,
modify, or challenge the investigator’s
understanding of the observed phenomena:
“The evaluation of water leakage…is a
cognitive process in which technically valid
conclusions are reached by the application
of knowledge, experience, and a rational
methodology.”27 The hallmark of good building
envelope forensics is a willingness to
remain open to new information, no matter
what it reveals.
References
1. Reference Howard Kanare’s excellent
manual, Concrete Floors and Moisture,
published by the Portland Cement
Association (www.cement.org).
2. The uses and potential limitations
of such testing meters and equipment
were explored in this writer’s
article in the November 2009 issue
of Interface. We also recommend
ACI 302.2R-06, “Guide for Concrete
Slabs That Receive Moisture-
Sensitive Flooring Materials,” published
by the American Concrete
Institute (www.concrete.org).
3. Tramex Concrete Encounter CME4
meter (www.tramexltd.com).
4. Kanare. “Such instruments can provide
useful information on relative
differences in moisture conditions to
a depth of 50 mm (2 in.).”
5. ASTM F2170-1, Standard Test
Method for Determining Relative
Humidity in Concrete Floor Slabs
Using in-situ Probes, ASTM International
(www.astm.org).
6. Kanare. “Moisture moves through
concrete in a partially adsorbed or
condensed state by diffusion, not
simply as unbound, free water vapor
or liquid. The rate of moisture transmission
depends on the degree of
saturation, which is a function of the
relative humidity on each side of the
concrete. Therefore, the driving force
for water vapor movement through
a slab is the relative humidity differential
through the slab’s depth,
not simply the vapor pressure differential…
RH probes are a method of
directly measuring this property.”
N o v e m b e r 2 0 1 2 I n t e r f a c e • 1 1
7. For this project, we used the Rapid
RH® sensors marketed by Wagner
Meters (www.wagnermeters.com).
8. While the porosity (and thus the
maximum possible moisture content)
of concrete can vary, when evaluating
on-grade concrete slabs in the
San Francisco Bay area, we often
find it reasonable to roughly categorize
such moisture content measurements
as follows: “typical” (3.0 to
3.7%); “potentially problematic” (3.8
to 4.3%); “wet” (4.4 to 5.0%); “very
wet” (5.1 to 6.0%); and “saturated”
(> 6.0%). These categories, which differ
from those defined for this article,
also are qualitative and comparative
and intended solely to aid the forensic
evaluation process.
9. However, as discussed in this writer’s
article, “Anatomy of a Leakage
Investigation at a Concrete Floor
Slab,” published in the July 2008
issue of Interface, it should be noted
that widespread lateral migration
of moisture within a concrete slab
can occur from undetermined point
source(s) of water infiltration—
potentially complicating the puzzlesolving
process.
10. Actual “moisture content” values
within a concrete slab are a function
of both RH and temperature. For
our puzzle-solving purposes, it was
sufficient to observe that the RH data
indicate the slab is much “wetter”
at Sensors 1, 2, 4, 5, and 6 than at
Sensors 3. It is this writer’s experience
that some investigators tend to get
bogged down with data quantification
in lieu of rapidly proceeding forward
with simple qualitative comparisons
of differing data sets. Similarly, while
the precise accuracy of some moisture
content readings can be important,
for many forensic surveys the investigator
only needs to consider the broad
differences between “wet” and “lesswet”
data from identical sensors.
11. W.A. Rose, Water in Buildings – An
Architect’s Guide to Moisture and
Mold, John Wiley & Sons, Inc., 2005.
12. Reference: ASTM E1745, Standard
Specification for Plastic Water Vapor
Retarders Used in Contact With Soil Or
Granular Fill Under Concrete Slabs;
and E1643-11, Standard Practice
for Selection, Design, Installation, and
Inspection of Water Vapor Retarders
Used in Contact With Earth or
Granular Fill Under Concrete Slabs.
13. ASTM E1643 notes, “Soils with comparably
higher clay contents are
particularly troublesome because
the relatively high capillary action
within the clay allows moisture to
rise under the slab.”
14. Kanare: “Although moisture vapor
causes most floor problems, sometimes
a high water table provides a
direct source of liquid water in contact
with the underside of a concrete
slab.”
15. Ibid: “A properly designed vapor
retarder must be installed without
gaps, punctures, or tears in order
for it to function as intended.”
16. Ibid: “It is important to note that a
capillary break will not stop the free
movement of water vapor. The actual
depth of the water table below a slab
is not important insofar as moisture
vapor movement is concerned.
Whether the water table is one meter
(3.3 feet) or many meters below the
slab, the subgrade and subbase will
have close to 100% relative humidity;
it is the presence of an infinite supply
of water vapor that often causes
flooring systems to fail. The slab
must be protected by an adequate
vapor retarder under the concrete.”
17. www.lime.org/uses_of_lime/construction/
soil.asp.
18. See map at http://geology.com/articles/
soil/.
19. Lime-Treated Soil Construction Manual,
National Lime Association (www.
lime.org): “Lime can modify almost
all fine-grained soils, but the most
dramatic improvement occurs in clay
soils of moderate-to-high plasticity.
Modification occurs because calcium
cations supplied by hydrated lime
replace the cations normally present
on the surface of the clay mineral,
promoted by the high pH environment
of the lime-water system.”
20. W.A. Rose.
21. Kanare: “Concrete tilt-up wall construction
is often used for large
area buildings, such as warehouses
and manufacturing facilities, where
the finished floor surface is used
as a casting bed for the walls….A
900- to 1500-mm (3- to 5-ft.-) wide
strip around the perimeter of the
floor is usually left out of the initial
floor pour; this is called a pourback
strip, leave-out strip, perimeter
strip, or fill-in strip.”
22. L. Haughton & C. Murphy, “Qualitative
Sampling of the Building
Envelope
for Water Leakage,” Journal
of ASTM International (www.astm.
org), Vol. 4, No. 9 (10/2007) – republished
by ASTM in 2009 in STP 1493
(Repair, Retrofit, and Inspection of
Building Exterior Wall Systems).
23. Kanare: “A ‘perched’ water table
forms when surface water, such as
precipitation, cannot percolate downward
through a relatively impermeable
layer to the natural water table.”
24. It still remained possible that vertical
infiltration of groundwater onto
the LTS pad was occurring where
the pad was penetrated by a trench
serving the main sewer line; however,
this alternative was ruled out
after additional destructive testing.
25. ASTM E2128-12, Standard Guide
for Evaluating Water Leakage of
Building Walls, ASTM International
(www.astm.org).
26. L. Haughton & C. Murphy.
27. ASTM E2128-12.
1 2 • I n t e r f a c e N o v e m b e r 2 0 1 2
Lonnie Haughton, CDT, is a principal codes/construction
consultant with Richard Avelar & Associates in Oakland,
CA. He is a member of RCI, the Forensic Expert Witness
Association, the Construction Specifications Institute,
Western Construction Consultants Association (Westcon),
Construction Writers Association, and is an EDI-certified EIFS
Third Party Inspector. Lonnie is one of about 800 individuals
nationwide who has been certified by the International Code
Council as a Master Code Professional. He is the primary
author of the paper “Qualitative Sampling of the Building Envelope for Water Leakage,”
published in the Journal of ASTM International, and has a passion for solving complex
moisture intrusion puzzles.
Lonnie Haughton, CDT