Skip to main content Skip to footer

Solar-Driven Waves of Water Vapor Within Exterior-Wall Cavities

May 15, 2014

INTRODUCTION
Consider an apartment complex constructed
circa 2002 in a city near San
Francisco, CA, containing about 30 twostory
wood-framed buildings clad with traditional
three-coat exterior plaster cement
(stucco; see Photo 1). Typical for many
large-scale residential projects in California,
the pump-applied stucco cladding system
was applied to oriented strandboard (OSB)
sheathing only at structural shear walls
(Photo 2) and simply over steel line wire at
the nonsheathed walls (Photo 3).
As documented in Photos 2 through 7,
moisture damage, wood decay, and organic
growth were found behind the cladding
and sheathing at certain ground-floor walls
throughout the complex, particularly at
bedrooms. (The general absence of similar
damage at the
same secondfloor
bedroom
walls was, of
course, of great
interest to the investigators.) The results
of RA&A’s extensive investigation, evaluation,
and testing processes did not credibly
explain the localized extent and severity of
the observed condensation damage at these
walls.
8 • I n t e r f a c e J u l y 2 0 1 4
This case study uses photographs and data from an actual building envelope investigation to promote techniques and protocols for using
humidity/temperature dataloggers to acquire new, vital information for the forensic team. (While the word “forensic” may have different
meanings across North America, Richard Avelar & Associates [RA&A] defines it as: the puzzle-solving application of a broad spectrum of
technical knowledge and expertise to answer questions of interest.)
Photo 1 – Typical construction at stucco-clad
apartment complex.
Photo 2 – OSB sheathing supports
the stucco cladding assembly.
SUPPLEMENTAL INVESTIGATION
WITH TEMPERATURE/HUMIDITY
DATALOGGERS
We therefore supplemented our investigation
by positioning, within 23 of the occupied
ground-floor apartments (distributed
throughout the complex), about 100 dataloggers1
that measure temperature and relative
humidity. In general, no prior destructive
testing had occurred at any of the
selected apartments.
Typically, we positioned
four loggers per
apartment to record
ambient conditions
at: a) hallway ceilings, immediately adjacent
to kitchens and bathrooms; b) bedroom
closets; c) plenums above the gypsum board
ceilings at the bedroom
closets (i.e.,
below the subfloor
of the second-floor
units); and d) exterior
wall cavities
directly adjacent to
these bedroom closets. These walls faced all
quadrants of the compass.
As demonstrated in Photo 7, the temperature
and relative humidity (RH) sensors
for the loggers are located at the ends
of 6-ft. cables. This feature allowed us to
record conditions within the plenums and
exterior walls simply by inserting the sen-
J u l y 2 0 1 4 I n t e r f a c e • 9
Photo 3 – Line wire provides support
for the stucco cladding assembly.
Photo 4 – Moisture damage, wood decay, and
organic growth at backside of the OSB sheathing.
Photo 5 – Moisture damage, wood decay, and
organic growth at backside of the OSB sheathing.
Photo 6 – Moisture damage, wood decay, and
organic growth at backside of the OSB sheathing.
sors through small holes drilled through the
gypsum wallboard.
The dataloggers were programmed to
take simultaneous measurements every ten
minutes (i.e., 144 readings per sensor per
day). The accumulated data readily could
be downloaded at any time with the optic
scanners provided with these loggers, which
will continue recording information until
they are turned off (or when their batteries
die after a year or two).
The broad goal of deploying these loggers
was to search the collected data for
patterns that might explain why some of
these ground-floor wall cavities were so
much wetter than others. Beyond considering
the typical construction defects often
found at such large-scale residential projects,
we believed that possible additional
factors for these conditions might include
relative exposure to the elements
(rain, wind, sun, shade, and perhaps
even night-sky cooling2); the
presence or absence of wall penetrations
(e.g., piping, conduit, and
ducting); variable amounts of interior
lifestyle moisture (perhaps due
to differing occupant loads); varying
moisture content of the on-grade
concrete slabs; and multiple other
localized construction, architectural,
and mechanical system features.
The purpose of this article is not
to summarize RA&A’s findings for
this ongoing litigation. Instead, we
simply will demonstrate the firm’s
process for evaluating the voluminous
data produced by the loggers.
In addition, this article documents
and describes the daily solar-driven
waves of water vapor that can occur
within exterior wall cavities.
THE HUMIDITY RATIO
Once information was collected from
these loggers, the provided software enabled
us to convert the combined temperature
and RH readings into the humidity ratio,
which represents the actual ambient moisture
content—measured by the total grains3
of water vapor per pound of dry air (GPP)—
within each of the tested spaces at a particular
point in time.4
1 0 • I n t e r f a c e J u l y 2 0 1 4
Photo 7 – Sensors at the ends of 60-in. cables were inserted into closet walls and ceiling plenums.
Chart 1 – Simplified sea-level psychrometric chart (humidity ratio is derived from a nonlinear relationship between RH and temperature).
Chart 1 is a very simplified “psychrometric
chart” demonstrating that the
humidity ratio is derived from a nonlinear
relationship between temperature and RH.
(Psychrometrics is the science of air/water
interaction.) For example, if we know that
the temperature is 80°F (at the vertical red
line) and the RH is 20% (at the curved blue
line), then the point where these two lines
cross (at the horizontal green line) informs
us that the approximate moisture content
of the air is 30 GPP. Using the dataloggers,
comparative analyses of such continually
changing moisture loads can be highly
informative.5
For example, Graphs 1 and 2 show
68 days of ambient moisture load data
recorded 144 times per day (i.e., every
ten minutes) during the winter months of
2013/2014 within two of the ground-floor
apartments at this complex. We can see
that the occupants of Apartment A live a
relatively dry lifestyle (long-term average =
54 GPP), while the tenants in Apartment B
generate 33% more ambient moisture (72
GPP) on average.
It has been our experience with
mass-produced residential units in the San
Francisco Bay area that occupants who
generate a long-term average moisture load
greater than 60 GPP are increasingly prone
to exhibiting mold and moisture problems
at cold gypsum wallboard (i.e., at exterior
walls and corners during winter months
(see Photo 8). Further, these risks appear
to increase exponentially with tenants who
live “wet” (average GPP > 63) or “very wet”
(average GPP > 67) lifestyles.
We generally believe it unreasonable to
criticize residents who choose to live wet
J u l y 2 0 1 4 I n t e r f a c e • 1 1
Graph 1 – Apartment A tenants have a “dry” lifestyle (average GPP = 54) – 144 readings
per day.
* Make sure RCI has your current e-mail address. From the RCI home page (rci-online.org),
click on the “Member Login” link on the right. To log onto your member account for the first
time, click “Create Account” in order to create a user name and password. Do not create a new
account, as members already have existing membership records. Under “Personal,” make sure
you have not marked “exclude e-mail.” Now relax…it’s coming soon.
Check your e-mail inbox* around the 20th of each month.
Have you read tems lately?
Missing Something?
Graph 2 – Tenants at Apartment B live a “wet” lifestyle (average GPP = 72) – 144 readings
per day.
lifestyles.6 It is very important to note that
all such wet versus dry assessments are
highly relative and qualitative; in virtually
all cases, the key factor for potential interior
mold proliferation caused by condensation
of ambient moisture was how poorly the
exterior walls were insulated.7
The moisture spikes seen in Graphs
1 and 2 typically represent cooking and
bathing activities. Similarly, it has been
our experience that extended periods of
low moisture load commonly correspond to
occupant absences. For example, in Graph
1, we see that the tenants at Apartment A
were not at home during a multiday period
(the Christmas holiday) beginning at reading
#7489 (Day 53).
At Graph 3, we see that the moisture
loads within the exterior walls at these various
apartments also differ greatly. With the
wall cavity at Apartment C (average GPP =
63), there is 75% more ambient water vapor
than with the Apartment D wall (average
GPP = 36). The forensic team obviously then
focused extra attention in comparing the
differences between these walls.
Further, close consideration of Graph 3
leads to two other highly interesting questions:
1. What explains the daily cycle of
increasing and decreasing moisture
loads within these exterior walls?
2. What explains the dramatic reduction
in the ambient moisture load
occurring at reading #4753 (Day 33)?
SOLAR HEATING AND SOLAR-DRIVEN
DIFFUSION AT EXTERIOR WALLS
At every cladding system that is “hygroscopic”
(i.e., has an ability to absorb and
desorb water), some of these water molecules
will be driven inward into the wall
assembly when this cladding material is
heated by the sun.
Sun-driven moisture is a phenomenon
that occurs when walls are wetted
and then heated by solar radiation.
Upon solar heating, a large
vapor pressure difference may occur
between the exterior and interior
leading to the inward diffusion of
moisture.8
While some degree of solar-driven diffusion
will occur at all hygroscopic cladding
materials, its effects are most noticeable at
reservoir systems (e.g., stucco and concrete)
that can safely hold larger amounts of free
water.9
Similarly, solar heating of exterior walls
also will free some of the water molecules
adhered to the surface of (or contained
within) the hygroscopic wood framing and
sheathing materials within the wall cavity:
“It is clear that any wet material…that is
heated by the sun will generate large inward
vapor drives.”10
Then, at night, when these wall assemblies
cool, this excess moisture will be
adsorbed11 and absorbed12 into the solardried
cladding, framing, and sheathing as
the water vapor condenses. Further, during
cold weather, even in the mild climate
zones near San Francisco, this nighttime
adsorption/absorption process also will be
affected by an outward vapor drive from the
heated interior: “The common assumption
is that drying occurs predominately to the
outside in cool and cold climates. …This
assumption becomes less true as the climate
becomes warmer and as the enclosure
is exposed to more solar heating.”13
In short, the daily moisture cycles seen
in Graph 3 simply document the effects of
1 2 • I n t e r f a c e J u l y 2 0 1 4
Photo 8 – Mold growth at poorly insulated exterior walls (at corner of building).
Graph 3 – Why is the exterior wall cavity at Apartment C 75% wetter (on average) than
Apartment D?
solar heating and nighttime cooling on the
ambient moisture loads within the exterior
wall cavities. Proof of this concept is provided
in Graph 4, which charts:
a) Red dashed line: daily moisture load
(GPP) within the stucco-clad exterior
wall cavity at Apartment E, measured
144 times per day
b) Black solid line: exterior temperature
(°F), also measured 144 times
per day (by a logger from a different
manufacturer, positioned in a distant
portion of the complex)
The remarkably close correspondence
between these two lines (which represent
very different values) is strong evidence that
the daily spikes of ambient moisture within
this exterior wall are a function of solar
heating of the exterior wall—which creates
an inward vapor drive during the heat of the
day that is countered at night by condensation
(due to cooling) of excess moisture and
by an outward vapor drive from the warmer
apartment toward the colder exterior.
The long-term average ambient moisture
load (red dashed line) within the exterior
wall cavity at Apartment E is 47 GPP. Now
consider the solid blue line at Graph 5,
which records the humidity ratio within a
bedroom closet at Apartment E. Due to the
tenants’ unusually wet lifestyle, the average
ambient moisture load within the bedroom
is 72 GPP. (Note: the hallway logger next to
the kitchen and bathroom recorded a longterm
average of 73 GPP.)
From a forensic perspective, an interesting
feature of Graph 5 is that the shape of
the daily rise and fall (consistent with the
effects of solar heating) of the ambient moisture
load within the bedroom at Apartment
E roughly corresponds to the shape of the
solar-driven moisture load within the exterior
wall (Graph 4), seemingly indicating a
direct interaction (via vapor diffusion and/
or unintended air convection) between the
two bodies of water vapor separated by a
layer of gypsum drywall.
One reason that the rough correspondence
between the two moisture loads
(within the bedroom closet and within the
exterior wall cavity) strongly interests the
investigative team is that it has been our
experience at other stucco-clad projects
that interior moisture loads have not exhibited
the daily rise and fall of solar-driven
vapor—perhaps due to the reasonably airtight
barrier formed when the interior wallboard
is installed in compliance with the
California Energy Code.
WHAT IS THE EFFECT OF LIFESTYLE
MOISTURE?
While it is reasonable to speculate that a
primary source of the water vapor recorded
within these various walls could be lifestyle
moisture from tenant activities, Graph 6
demonstrates that vacating an apartment
may not greatly impact the daily waves of
solar-heated moisture within the exterior
wall.
Graph 6 summarizes 17 days of ambient
moisture load data, recorded 144 times per
day at Apartment F. As seen, the tenants
vacated the unit midway through this testing
period. There was no rain; every day was
sunny. The sensor for Logger 1 (blue line)
was inserted into the exterior wall cavity
at the master bedroom closet. The sensor
for Logger 2 (red line) recorded the ambient
moisture load in the hallway (near the
kitchen and bathroom).
When the apartment was occupied, the
average moisture load within the exterior
wall was only 9% greater than when vacant,
seemingly demonstrating that while lifestyle
moisture may have contributed to the daily
waves of solar-heated ambient moisture
measured within this exterior wall, it was
not the driving source.
Further, after the apartment was vacat-
1 4 • I n t e r f a c e J u l y 2 0 1 4
Graph 4 – Exterior temperature (F°) at the residential complex and ambient moisture load
(GPP) within the exterior wall at Apartment E; 144 readings per day.
Graph 5 – Ambient moisture load (GPP) within bedroom (blue solid line) and exterior wall
(red dashed line) at Apartment E; 144 readings per day.
ed, the average moisture load within the
exterior wall was 16% greater than the average
moisture load within the unit, leading
us back to a key forensic question: What
are the sources of water vapor within the
exterior wall cavity?
STATIC “DEW POINT METHODS”
ARE USELESS FOR MOST STUCCO
CONDENSATION INVESTIGATIONS
Despite the impressive advances in
hygrothermal analysis made during the past
two decades (e.g., WUFI14), many consultants
still carry out forensic analyses of condensation
damage with the static “dew point
methods” detailed many years ago by the
American Society of Heating, Refrigerating,
and Air-Conditioning Engineers (ASHRAE).
Given specific interior and exterior temperatures,
these ASHRAE procedures calculate
a theoretical dew point within the wall
assembly by analyzing each component’s
vapor permeance and thermal resistance
(R-value). However, it is clear that even the
relatively simple processes of solar heating
and solar-driven diffusion into and through
stucco-clad walls are more than enough
to render these static methods virtually
useless.
Consider that leading experts on such
dew point analyses write:
These methods are often misused,
especially when condensation is
present. Some people advocate abandoning
these design tools because of
J u l y 2 0 1 4 I n t e r f a c e • 1 5
Graph 6 – Red line is ambient moisture load (GPP) near kitchen, and blue line is ambient
moisture load (GPP) inside stucco-clad exterior wall cavity at Apartment F — 144 readings
per day.
their severe limitations. …Another
weakness is that these methods
exclude all moisture transfer mechanisms
other than [static] vapor diffusion
and neglect moisture storage in
the building materials. This severely
limits the accuracy of the calculations,
especially in the case of wet
materials.15
Also:
Furthermore, since the method only
considers steady-state transport
under heavily simplified boundary
conditions, it cannot reproduce individual
short-term events or allow for
rain and solar radiation. It is meant
to provide a general assessment of
the hygrothermal suitability of a
component, not to produce a simulation
of realistic heat and moisture
conditions in a component exposed
to the weather prevailing at its individual
location.16
It is RA&A’s opinion that these static
methods are outdated and almost always
useless for most forensic analyses of moisture
condensation damage found within the
existing building envelope.
PRINCIPLES FOR INVESTIGATION
AND EVALUATION
For building envelope investigations,
determining the humidity ratio (ambient
moisture load) is closely comparable to
using a traditional meter to measure the
moisture content ratio of wood framing
and sheathing. In either case, a common
goal for field-level professionals simply is to
determine which components or areas are
substantively wetter (or dryer) than others.
The great value of these data loggers is
that it can automate the moisture sampling
process. The deployment of 100 loggers at
this project enabled RA&A to collect 28,800
simultaneous readings (temperature and
RH) every day over a five-month period. By
the end, more than 2,000,000 humidity
ratio (i.e., ambient moisture load) measurements
were available for evaluation and
processing with Microsoft’s Excel® program.
As seen in the graphs for this article, highly
informative patterns will emerge from wide
variations in hourly and daily data.
Our previously published principles for
this process of investigation and analysis
include:17
1) Find the location(s) of unexpectedly
high quantities of water (including
ambient moisture):
Most moisture problems can
be diagnosed by looking at
the condition and asking how
much water it took to create
that problem. Solving the
problem amounts to asking
where that amount of water
could have come from and
where it should go.18
2) Consider the common origins of
unintended water (vapor and liquid)
accumulation within exterior walls
and buildings.
a. Liquid water from precipitation
(rain and melting snow)
b. Liquid water from plumbing
leaks
c. Water vapor from the exterior
d. Water vapor from activities and
processes within the building
e. Liquid and vapor from the soil
adjoining the building
f. Moisture built-in with the materials
of construction
g. Moisture brought in with goods
and people.19
3) Then, consider the two main mechanisms
of ambient moisture transport
into and through the building
envelope: diffusion (higher concentrations
of water vapor move toward
lower concentrations) and convection
(water molecules are transported
by air movement created by pressure
differentials).
4) Then, consider the potential routes of
unintended moisture movement into
and through the building envelope.
For a moisture-related problem
to occur, it is necessary
for at least four conditions
to be satisfied: 1) A moisture
source must be available, 2)
there must be a route or
means for the moisture to
travel, 3) there must be some
driving force to cause moisture
movement, [and] 4) the
material(s) involved must be
susceptible to moisture damage.
20
5) Don’t forget the Second Law of
Thermodynamics, which requires,
as a fundamental law of the universe,
that when two unequal reservoirs
of energy (including disparate
concentrations of water vapor) are
connected, the greater pool will flow
into the lesser pool until equilibrium
is reached.
This process has been summarized
by North America’s
leading building science
experts as: Moisture tends
to move from warm to cold
(driven by the magnitude of
the thermal gradient) and
from more to less (driven by
the concentration gradient).21
6) Further, as demonstrated above,
remember that daily waves or spikes
of water vapor that tend to increase
on hot sunny days and decrease
during cool nights (or cloudy days)
are caused by solar heating of moisture
reservoir(s).
7) Finally, if the general timing, shape,
and/or amplitude of ambient moisture
loads recorded by one logger
correspond to the cycles of moisture
load (or temperature) from a separate
logger within a different space,
then very likely there is a close,
direct relationship between the measured
conditions.
SUMMARY DISCUSSION
As noted, a key purpose of this article
is to introduce and discuss unseen effects
of solar heating of hygroscopic cladding
materials, including reservoir systems (such
as stucco and concrete) that can safely hold
large amounts of free water.
Exterior wall assemblies with alternate
claddings will perform differently on an
hourly and daily basis due to varying material
properties (e.g., permeability, absorptivity,
and drainage/drying potential). From
a general perspective, these differences do
not mean that any particular system (e.g.,
stucco) is inherently better or worse than
any other (e.g., fiber-cement lap siding). The
varying degrees of solar-heated water vapor
occurring within our traditional well-proven
exterior wall systems are natural phenomena
that, in and of themselves, are not
problematic. Instead, the key to successful
long-term performance of these walls is to
prevent the accumulation of unintended
moisture from atypical sources.
However, if problematic condensation
is discovered (perhaps years after original
construction), then a full evaluation of these
conditions might require consideration of
the potential effects of solar-diffused vapor
1 6 • I n t e r f a c e J u l y 2 0 1 4
being added to an exterior wall’s existing
moisture load. To this end, modern temperature/
RH loggers that can track minute
changes to the humidity ratios within
both the building and its envelope can be
an invaluable addition to an investigator’s
toolkit.
While it is well beyond the scope of
this article to identify specific design or
construction deficiencies that may have
contributed to the localized condensation
damage seen at this project, we can report
that our data analyses implicate air flow
(convection) of warm humid air from the
heated interiors into and through certain
segments of the exterior wall system via
unintended voids in the interior and exterior
envelopes.
REFERENCES
1. For this testing, we used the HOBO
U23-002 Pro v2 data loggers manufactured
by Onset Corporation
(http://www.onsetcomp.com).
2. On cloudless nights, heat is radiated
into space from the surface of the
earth. At buildings, the magnitude
of this nighttime heat-loss phenomenon
from roofs and exterior walls is
reduced when obstacles (e.g., other
buildings and large trees) impede
this night-sky radiation.
3. There are 7,000 grains in a pound.
4. Donald P. Gatley, Understanding
Psychrometrics, Second Edition,
ASHRAE, Inc., Atlanta, GA 2005:
“Humidity ratios provide a simple,
effective, and most convenient
means of accounting for the mass
of water vapour in a psychrometric
process…by relating it to the nonvarying
mass of dry air.”
5. Lonnie Haughton, “Using Humidity/
Temperature Loggers for Moisture
Investigations – Case Studies,”
http://www.rci online.org/interface/
2009-BES-haughton.pdf.
6. Heinz R. Trechsel and Niklas Vigener,
“Investigating Moisture Damage
Caused by Building Envelope Problems,”
Moisture Control in Buildings:
The Key Factor in Mold Prevention,
Manual 18. 2nd edition, Heinz R.
Terchsel and Mark T. Bomberg,
editors. ASTM International, 2009:
“Requiring careful moisture management
by the occupant is no substitute
or excuse for inadequate moistureresistant
design.”
7. Peter Trotman, Chris Sanders, and
Harry Harrison, Understanding
Dampness, BRE, Garston, Watford,
UK, 2004: “In winter, the internal
surfaces of external walls are colder
than the air in the room, with
the temperature drop depending on
how well the wall is insulated. The
relative humidity at the wall surface
will, therefore, be higher than in the
room.”
8. Wahid Maref et al, “Laboratory Demonstration
of Solar-Driven Inward
Vapour Diffusion in a Wall Assembly,”
National Research Council
Canada, 11th Canadian Conference
on Building Science and Technology,
Banff, Alberta, 2007.
9. Lonnie Haughton, “Buildings That
‘Leak’ Only On Sunny Days – Case
Study and Investigative Guidelines,”
http://www.rci-online.org/interface/
2010CTS-Proceedings-haughton.
pdf.
J u l y 2 0 1 4 I n t e r f a c e • 1 7
Blah, Blah, Blah, Blah, Blah, Blah,
Blah, Blah, Blah, Blah, Blah, Blah,
Blah, Blah, Blah, Blah, Blah, Blah,
Blah, Blah, Blah, Blah, Blah, Blah,
Blah, Blah, Blah, Blah, Blah, Blah,
Blah, Blah, Blah, Blah, Blah, Blah,
Blah, Blah, Blah, Blah, Blah, Blah,
Blah, Blah, Blah, Blah, Blah, Blah,
Blah, Blah, Blah, Blah, Blah, Blah,
Blah, Blah, Blah, Blah, Blah, Blah,
Blah, Blah, Blah, Blah, Blah, Blah,
Blah, Blah, Blah, Blah, Blah, Blah,
Blah, Blah, Blah, Blah, Blah, Blah,
Blah, Blah, Blah, Blah, Blah, Blah,
Why are we still debating
the merits of cool roofs?
Thermoplastic white roofs have proven
performance in all climates. Bust the myths:
vinylroofs.org/cool-roofing-myths
10. John F. Straube, “The Influence
of Low-Permeance Vapor Barriers
on Roof and Wall Performance,”
Proceedings of Thermal Performance
of Building Envelopes VII, Clearwater,
Beach, Florida, 2001
11. Adsorption is the process where
some previously free-flying water
vapor molecules stick to the surface
of a material due to cooling temperatures.
12. Absorption is capillary movement of
moisture within hygroscopic materials.
13. John F. Straube, “The Influence
of Low-Permeance Vapor Barriers
on Roof and Wall Performance,”
Proceedings of Thermal Performance
of Building Envelopes VII, Clearwater,
Beach, Florida, 2001
14. http://web.ornl.gov/sci/btc/apps/
moisture/
15. Anton TenWolde, “Manual Analysis
Tools,” Moisture Analysis and
Condensation Control in Building
Envelopes, (Manual 40, Heinz R.
Terchsel editor) ASTM International,
2001
16. http://btric.ornl.gov/wufi/tool.
shtml
17. Lonnie Haughton, “Buildings That
‘Leak’…”
18. William A. Rose, Water in Buildings –
An Architect’s Guide to Moisture and
Mold, John Wiley & Sons, Inc., 2005
19. John F. Straube, “Moisture Control
in Buildings,” ASHRAE Journal,
January 2002. Also reference Section
11 of ASTM E 241, “Standard Guide
for Limiting Water-Induced Damage
to Buildings,” ASTM International,
West Conshohocken, PA
20. John F. Straube, “Moisture in
Buildings,” ASHRAE Journal (January
2002), www.ashrae.org
21. Joseph Lstiburek, “Investigating
and Diagnosing Moisture Problems,”
ASHRAE Journal (December 2002),
www.ashrae.org
1 8 • I n t e r f a c e J u l y 2 0 1 4
Lonnie Haughton,
MCP, LEED AP,
CDT, is a principal
codes/construction
consultant
with Richard
Avelar & Associates
in Oakland,
CA, and one of
about 800 individuals
nationwide
who have been
certified by the
International Code Council as a Master
Code Professional. He is the primary author
of the seminal paper “Qualitative Sampling
of the Building Envelope for Water Leakage,”
published in 2007 in the Journal of ASTM
International and now cited in ASTM E2128-
12, Standard Guide for Evaluating Water
Leakage of Building Walls. Many of his
published articles and papers since 2009
have advocated the use of temperature/RH
data loggers for field-level evaluation of condensation
damage found within the exterior
envelope.
Lonnie Haughton,
MCP, LEED AP, CDT
The RCI Foundation (U.S.) and the RCI Foundation Canada have agreed to
donate $20,000 to the Single Ply Roofing Industry (SPRI) as part of an industry-wide
research effort on 2012 International Energy Conservation Code (IECC) continuous
air barrier requirements. The project is being funded by SPRI, the Canadian Roofing
Contractors Association (CRCA), the National Roofing Contractors Association
(NRCA), and The Roofing Industry Alliance for Progress. The actual research work is
being conducted by the National Research Council of Canada (NRCC).
SPRI has agreed to contribute $100,000 with the help of industry partners like
the RCI Foundations. The total cash cost for the program is to be $310,000, with
SPRI donating an additional $100,000 of in-kind support, including materials and
labor to be used in the test program.
Effective with the 2012 edition of the IECC, a continuous air barrier around the
entire building envelope is required, including the roof assembly, the connection
between the roof and wall air barrier, and around all roof penetrations. The objective
of the NRCC research program is to develop data and test procedures that can be
used to demonstrate compliance with the air barrier requirements of the IECC for
mechanically attached roof systems.
Mechanically attached roof systems represent approximately 40% of the lowslope
commercial roofing market. The NRCC’s research is expected to:
1. Develop test data for prescriptive construction details that would meet the air
barrier requirements of the code
2. Develop an assembly test procedure and get it referenced in the code
The RCI Foundation Board of Directors agreed to the funding during its March
22, 2014, meeting in Anaheim, CA. The U.S. Foundation’s support will be $15,000,
and the Canadian Foundation is contributing $5,000.
RCI Foundation Supports
Air Barrier Research
Guardian Fall Protection, Kent,
Washington, has recalled certain
self-retracting lifelines after discovering
a potential performance problem
in complying with ANSI/ASSE
Z359.14-2012, Safety Requirements
for Self-Retracting Devices for
Personal Fall Arrest and Rescue
Systems, for cold-conditioning tests.
There have been no reported injuries
resulting from the issue, but
serious injury or death could result.
Part numbers being recalled are
#109010 (20-ft., 3/16-in. galvanized
cable edge series self-retracting lifeline)
and #109015 (30-ft., 3/16-in.
galvanized cable edge series selfretracting
lifeline). This recall does
not affect other Guardian products. If
a unit’s serial number starts with the
letter “A” and there is not a stamped
“G” on the front cover,” the unit
must be returned. For more information,
visit www.guardianfall.com.
Self-Retracting
Lifelines Recalled