Skip to main content Skip to footer

Stucco Detailing for Buildings With Unique Geometry

May 15, 2015

Stucco Detailing for Buildings
With Unique Geometry
Richard W. Mosco, AIA
Wiss, Janney, Elstner Associates, Inc.
225 south lake ave., Pasadena, Ca 91101
Phone: 626-696-4650 • 626-696-4699 • e-mail: rmosco@wje.com
Lee Cope, PE
Wiss, Janney, Elstner Associates, Inc.
2915 Premiere Pkwy., suite 100, Duluth, Ga 30097
Phone: 770-923-9822 • fax: 770-232-9044 • e-mail: lcope@wje.com
3 0 t h RC I I n t e R n a t I o n a l C o n v e n t I o n a n d t R a d e S h ow • M a R C h 5 – 1 0 , 2 0 1 5 M o S C o a n d C o p e • 2 2 7
2 2 8 • M o S C o a n d C o p e 3 0 t h RC I I n t e R n a t I o n a l C o n v e n t I o n a n d t R a d e S h ow • M a R C h 5 – 1 0 , 2 0 1 5
Abstract
Portland cement plaster (stucco) supported by metal lath relies on a properly installed
weather-resistive barrier and drainage plane and properly installed through-wall flashings
to manage water and prevent moisture intrusion from occurring into the wall assembly
and the building interior. Unusual geometric features in building façades present unique
challenges that often affect the performance of the building enclosure. These problematic
features may include sloping walls as well as diagonally set fenestration, wall accessories,
horizontal soffits, shelf conditions, and other projections. The information presented will
assist designers and builders in avoiding the potential for water intrusion in buildings due
to inappropriate detailing.
Speakers
Richard W. Mosco, AIA — Wiss, Janney, Elstner Associates, Inc.
riCHarD mOSCO, who is located in WJE’s Pasadena, California, office, is a licensed
architect specializing in the evaluation and repair of exterior building enclosure components
and assemblies. He has extensive experience in the investigation and repair of water leakage
and distress in Portland cement plaster (stucco) cladding systems, as well as many other
building enclosure systems, including roofing, waterproofing systems, fenestration systems,
air and moisture barriers, and other building envelope components.
Lee Cope, PE — Wiss, Janney, Elstner Associates, Inc.
lEE COPE, who is located in WJE’s Duluth, Georgia, office, is a licensed professional
engineer who has extensive experience in detailing and installation of Portland cement plaster
(stucco) façade systems, air barriers, window systems, waterproofing, and the interfaces
of various envelope components. He has evaluated a variety of structures for causes and/
or distress of their exterior envelope systems. Cope is a voting member of aSTm Committee
C11 on Gypsum and related Building materials and Systems.
3 0 t h RC I I n t e R n a t I o n a l C o n v e n t I o n a n d t R a d e S h ow • M a R C h 5 – 1 0 , 2 0 1 5 M o S C o a n d C o p e • 2 2 9
ABSTRACT
Portland cement plaster (stucco) supported
by metal lath relies on a properly
installed weather-resistive barrier (WrB)
and drainage plane and properly installed
through-wall flashings to manage water
and prevent moisture intrusion from occurring
into the wall assembly and the building
interior. The behavior of water within
the drainage plane in stucco supported by
metal lath is relatively predictable in most
installations. However, unusual geometric
features in building façades present unique
challenges that often affect the performance
of the building enclosure. These problematic
features may include sloping walls,
as well as diagonally set fenestration, wall
accessories, horizontal soffits, shelf conditions,
and other projections.
The information presented, which is
based on the authors’ experience investigating
these issues in real-world installations,
will provide participants with an
understanding of how unusual geometric
features can affect the behavior of water
within the stucco drainage plane and will
assist designers and builders in avoiding
the potential for water intrusion in buildings
due to inappropriate detailing.
INTRODUCTION
Over the past 20 years, the authors
have performed water leakage investigations
on hundreds of buildings throughout
the U.S. that were clad with Portland
cement plaster stucco. The construction
of the buildings under investigation has
included stucco applied to solid bases, such
as concrete or concrete masonry units (i.e.,
directly applied stucco), and stucco applied
to metal plaster bases (metal lath).
For water leakage issues in stucco systems,
it is important to understand how
the stucco cladding resists water penetration.
For directly applied stucco, the stucco
is applied directly to the substrate; there
is no WrB behind the stucco. Therefore,
for these structures, the stucco relies on
proper installation and possibly a coating to
resist water infiltration. Proper installation
requires proper bond between the stucco
and the stucco accessories.
There are a number of conditions that
commonly affect the bond between various
layers in the stucco or between the stucco
and the substrate. These conditions include:
• Variances between the allowable
construction tolerances provided
by the american Concrete institute
(aCi) for formed concrete surfaces
and the tolerances for solid substrates
to receive stucco provided in
aSTm C926, Standard Specification
for Application of Portland Cement-
Based Plaster
• Poor surface preparation
• Poor placement of stucco
• Use of build-out materials
• Improper installation of stucco
accessories
• i ncompatible substrates
any of these conditions or a combination
of these conditions can result in
delamination of the stucco. When delaminations
occur in the stucco, the stucco
becomes unsupported within the delaminated
regions, limiting the ability of the
stucco to transfer thermal or wind loads to
building structure and frequently resulting
in cracking of the stucco. Once cracking
forms, water can migrate through the
stucco and possibly into the building.
For stucco that is supported by metal
lath, the primary method of resisting water
penetration through the stucco cladding
is at the exterior face of the assembly.
However, water should be expected to penetrate
the stucco, either by absorption
through the stucco, through cracks or separations
within the stucco system, or failed
sealants at stucco terminations. Therefore,
stucco systems supported by metal lath
provide a drainage system consisting of
a WrB and flashings to collect and drain
incidental water that penetrates the exterior
surface back to the exterior of the building
and prevent the water from reaching
the interior of the building. reducing the
avenues that enable water to penetrate the
stucco by proper design and installation of
these drainage components is critical to the
success of stucco applied to metal lath.
While the behavior of water within the
drainage plane in stucco supported by
metal lath is relatively predictable in most
installations, the authors often observe several
common mistakes that are made during
the design and construction enabling water
leakage to occur. These mistakes, coupled
with other conditions present when dealing
with façades that have unusual geometric
features, present unique challenges that
often affect the performance of the building
enclosure. Therefore, the focus of this paper
is to discuss the typical performance characteristics
of a stucco-clad wall supported
by metal lath, common issues that result in
water leakage, and the unique challenges
related to unusual geometric features in
building façades.
TYPICAL PERFORMANCE
CHARACTERISTICS OF CLADDING
COMPRISED O F ST UCCO
SUPPORTED BY M ETAL L ATH
Cladding systems consisting of stucco
supported by metal lath generally consist
of one-coat, two-coat, or three-coat systems
ranging from 3/8 to 7/8 in. thick.
The stucco is keyed into lath that is placed
over a WrB and exterior sheathing, which
is attached mechanically to metal or wood
studs. In addition to the metal lath and
WRB, a successful stucco system includes
stucco accessories (control joints, prefabricated
reveal joints, expansion joints, etc.)
through-wall flashings, and flashing around
penetrations and sealant joints. For stucco
supported by metal lath to perform successfully
and properly manage incidental water
that penetrates the stucco, all of these parts
must be designed and installed properly.
Following is a discussion of common design
and construction defects that we have
observed in stucco wall systems supported
by metal lath that often result in water
leakage. We also discuss methods of installation
and design detailing that have been
successfully used to avoid these common
mistakes in a traditional stucco cladding
system supported by metal lath.
Stucco Detailing for Buildings
With Unique Geometry
Weather-Resistive Barriers (WRBs)
The international Building Code (iBC)
requires that a minimum of one layer of #15
asphalt felt, complying with aSTm D226
for Type 1 felt, or other approved materials
be installed as the water-resistive barrier
for exterior veneers, including stucco. For
wood-based sheathing, the iBC requires
that a minimum of two layers of Grade
B building paper be installed. The code
requires each layer to be installed independently
so that each layer provides a
separate continuous drainage plane and in
a manner so that any flashing allows water
to drain.
Today, a wide range of WrBs is available,
from loose-laid sheet products such
as felt paper and building wraps, to fluidapplied
and fully adhered membranes. in
our experience, a single layer of #15 asphalt
felt is generally not adequate to resist water
penetration when the exterior wall has window
openings and other pipe penetrations
or when the exterior sheathing consists of
gypsum sheathing. at these conditions, the
authors typically see poor integration of
flashings around windows and other penetrations,
which often result in water leakage.
We have also observed instances where
the stucco bonds to some loose-laid sheet
products. Therefore, we typically recommend
a loose-laid sheet product or a fluidapplied
membrane that can be wrapped
into the openings, followed by a sacrificial
layer of felt paper. If installed correctly, the
sacrificial layer of felt paper adds to the
water-tightness of the wall assembly and
helps create a clear drainage plane between
the felt paper and the underlying loose-laid
sheet product or fluid-applied membrane.
Through-Wall Flashings and Flashings
Around Penetrations
The iBC also requires flashing to be
installed in veneer claddings such as stucco.
Code Section 1405.4 states that flashings
shall be installed to prevent moisture
from entering the wall system and also that
all moisture that enters the wall system is
redirected to the exterior. Section 1405.4
also requires flashing be installed around
door and window assemblies; penetrations
and terminations of exterior wall assemblies;
and exterior wall intersections with
roofs, chimneys, porches, decks, etc.
aSTm C1063 (Section 7.11.5) requires
a foundation weep screed to be installed
at the bottom of all steel-and wood-framed
exterior walls. aSTm C926 (appendix a2,
Design Considerations, Section a2.2.2) recommends
that a drip screed and throughwall
flashings or weep holes or other effective
means to drain away any water that
may get behind stucco be installed at the
bottom of exterior walls supported by a floor
or a foundation. Installation of a means to
permit water to exit the drainage plane is
critical to the success of a stucco wall system.
although these items are frequently
specified, detailing is often inadequate to
ensure proper installation, frequently leading
to water leakage into buildings. in addition,
designers often fail to adequately detail
and specify flashings where the stucco
cladding is interrupted above grade. We
have investigated numerous buildings that
lack appropriate flashings, particularly at
balcony locations. The lack of flashings at
these locations enables water that penetrates
the stucco to enter the building and
often causes significant issues.
in our experience, designers typically
specify through-wall flashings at the head
of the windows, as required by the building
code. This flashing typically terminates
above the window jambs and does not
extend beyond the jambs. Formed end
dams are not normally installed in stucco
construction, primarily due to the propensity
for cracking at the end dam locations.
This method of flashing design and installation
creates several difficulties regarding
integration of the flashings with the WrB
and the windows and in ensuring the integrity
of these systems. Small holes often
occur at the interfaces of these materials,
enabling water to bypass the flashings and
WrB and penetrate the building. One way
to resolve these concerns is to install sealant
on the through-wall flashing when an
accessory casing bead (J-mold) is installed
above the flashing in an effort to create a
sealant end dam. However, in our experience,
the placement of the sealant is often
not watertight or fails prematurely, and
water continues to bypass these sealant
end dams. Our recommendation is to install
continuous flashing around the building
at the elevation of the window heads. The
authors have successfully employed this
method in major stucco repair and reclad
projects on a variety of facilities.
The lack of flashings around pipe penetrations
and other small penetrations are
also common causes of problems in stucco
claddings. These conditions are frequently
not detailed and are often constructed with
only a sealant joint between the stucco
or stucco accessory and the penetration.
Therefore, water traveling down the backside
of the stucco can enter the interior
through the open space between the exte-
2 3 0 • M o S C o a n d C o p e 3 0 t h RC I I n t e R n a t I o n a l C o n v e n t I o n a n d t R a d e S h ow • M a R C h 5 – 1 0 , 2 0 1 5
Figure 1 – Water leakage at screw installed through sheathing (with sheathing
removed for clarity).
rior sheathing and the penetration. To remedy
this condition, we recommend installing
a boot (similar to a roof pipe penetration)
or waterproofing the penetration with selfadhered
flashings in conjunction with the
WrB. Several WrB manufactures have preformed
flashings for these conditions.
Metal Lath Attachment
When installing attachments for metal
plaster bases to wood framing members or
to metal framing members, aSTm C1063,
Sections 7.10.2.5; and 7.10.3.3 require
the fasteners to be installed into the framing
member such that the fasteners pass
through the lath, but do not deform the rib.
Section 7.10.2.2 states that 6d nails, 1-in.
roofing nails, or 1-in. wire staples shall
be installed flush with the lath and into
the wood-framing member. although some
sheathing materials can provide adequate
capacity to resist required lateral loads,
water infiltration often results when fasteners
are not installed in the framing members.
During leakage investigations, the
authors have frequently witnessed water
leakage through the exterior wall system at
locations where fasteners are attached only
to the exterior sheathing and not the framing
members (Figure 1).
Another common condition that we have
observed is water leakage through unsealed
screw holes. This occurs when the installer
misses the framing member, backs the
screw out, and fails to seal the penetration
(Figure 2). This condition typically arises
because the installer of the lath is not the
same installer of the exterior sheathing
or the WRB. Once the WRB is installed,
the installer of
the lath cannot
readily determine
the location of
the framing members.
Therefore,
to ensure that
the lath installer
is able to locate
the framing members,
it is very
important for the
general contractor
to coordinate
between the subcontractors
and
locate the studs
on the WRB as
it is installed so
that chalk lines can be placed to highlight
their locations (Figure 3). if an anchor misses
a stud during the installation of the lath,
the anchor should be removed; the lath and
weather barrier should be cut to expose the
unsealed penetration in the sheathing so
that it can be sealed. Once the penetration
in the sheathing is sealed, the WrB should
be repaired and the lath should be retied.
In addition to unsealed penetrations,
we often observe that the anchors for the
metal lath are installed in such a manner
that the lath is deformed. This is the result
of nails, screws, and staples that are overdriven.
When lath is deformed, the lath is
restrained from moving, which can result in
the stucco cracking. The deformed lath can
also compress the WrB, which obstructs
the drainage plane (Figure 4). When using
screws to attach the lath, the installers
should use guides on their screw guns to
control the depth of the screw.
Attachment of Accessories
Stucco accessories are made of either
vinyl or metal. The flanges on the vinyl
accessories are primarily solid, with smalldiameter
holes that allow for connection
between the accessory and the lath. The
flanges for the metal accessories are solid
and also have small-diameter holes in the
flange (fewer than vinyl accessories), but
also have metal lath that extends off of the
solid portion of the flange. For proper installation
of the stucco accessories, the metal
lath must be attached to the accessory.
The authors believe that proper installation
consists of installing the accessory so that
it is not restrained to the wall. If the accessory
is restrained and not able to move,
cracking and separations can occur in the
stucco. Therefore, for vinyl accessories,
we recommend that the lath is wire-tied
to the accessory through the holes present
in the flange of the accessory. For the
metal accessories, we recommend that the
lath is either wire-tied to the accessory or
3 0 t h RC I I n t e R n a t I o n a l C o n v e n t I o n a n d t R a d e S h ow • M a R C h 5 – 1 0 , 2 0 1 5 M o S C o a n d C o p e • 2 3 1
Figure 2 – View of unsealed screw hole.
Figure 3 – View of chalk lines illustrating locations of studs and floor slab.
mechanically attached through the lath
portion of the accessory. The mechanical
attachment should be installed so that it
does not depress the metal lath. If the metal
lath is depressed, then the accessory will be
restrained from movement.
During construction, contractors often
install the accessories first, followed by
the lath. Mechanical anchors are often
installed through the small holes in the
solid portions of the flanges, followed by
additional anchors used to connect the lath
to the accessory. This installation method
frequently restrains the accessory as well
as obstructs the drainage plane (Figure 5).
In a few instances, the authors have
known designers to specify and installers
to apply sealant behind the flange of the
accessory. In addition to the sealant, a
mechanical fastener is commonly installed
through the flange. This has typically been
observed around openings such as windows
and at pipe penetrations in lieu of proper
flashing. in these cases, a separation often
forms between the stucco and the accessory
because excess sealant interferes with the
key of the stucco to the accessory, resulting
in water leakage through the opening.
Horizontal Shelf Conditions
Horizontal shelf conditions, such as
tops of walls and recessed windowsills,
often allow excessive water to enter the
stucco drainage cavity. The water enters
through cracks or through absorption.
Cracking is common at recessed window
openings and tops of walls due to improper
length-to-width ratios of the stucco panels
in these locations. The length-to-width ratio
often exceeds the 2½ to 1 required by aSTm
C926, Section 7.11.4.2. Once the water
is behind the stucco, it can collect on the
surface of the WRB and potentially leak into
the building at laps and fasteners.
aSTm C926 recognizes this condition,
and in Section a2, Design Considerations
(Section a2.1.1), it states that sufficient
slope shall be provided to prevent water,
snow, or ice from accumulating or standing
on horizontal surfaces.
in addition to providing adequate slope
as required by aSTm C926, we typically
recommend metal flashing be installed over
the horizontal surfaces. in addition, limiting
the fasteners on horizontal surfaces
and wrapping the horizontal surface with
self-adhered flashing helps to protect the
fastener penetrations and laps in loose-laid
sheet WRBs.
UNUSUAL GEOMETRY AND ITS
EFFECT ON THE BEHAVIOR OF
WATER WITHIN THE DRAINAGE
PLANE
as we have described, the behavior of
water within the drainage plane in stucco
supported by metal lath is relatively predictable
when applied to assemblies and details
that are consistent with current recommended
industry standards and practice. In
some cases, alternative detailing that varies
somewhat from these standards and practice—
including those often referred to as
“local custom” details commonly employed
2 3 2 • M o S C o a n d C o p e 3 0 t h RC I I n t e R n a t I o n a l C o n v e n t I o n a n d t R a d e S h ow • M a R C h 5 – 1 0 , 2 0 1 5
Figure 4 – View of over-drilled screw deforming lath.
Figure 5 – View of screw attachment between lath and vinyl accessory.
in specific climate regions—can often adequately
manage water within the drainage
plane. However, unusual geometric features
in building façades present unique
challenges that can significantly affect the
behavior of water in these assemblies.
As is true in most situations, water
within the drainage plane of stucco supported
by metal lath tends to follow the
path of least resistance. Where unusual
geometry occurs in this type of cladding, the
path of least resistance at some conditions
may be significantly altered, circumventing
the traditional flow of water in the assembly.
These conditions may include certain
types of diagonal control or expansion
joints, diagonal door and window heads
and jambs, diagonal soffits and recesses at
door/window heads, diagonal weeps and
drip flashings, diagonal shelf conditions
(including recessed window sills), diagonal
architectural reveal channels, and diagonal
casing accessories.
in a recent litigation case, SGH provided
expert opinion related to the effects of diagonal
accessory installations in a project that
was experiencing significant water intrusion.
While there were other factors that
contributed to the water
intrusion, many of the
sources of the building
enclosure failures were,
in our opinion, related
to the unusual geometric
conditions outlined in
this paper. Due to limitations established
by the terms of the litigation case, the specific
project and owner are not identified,
and photographs of the actual project could
not be used. Figures used in this document
include graphic recreations of the conditions
encountered during our investigation
and photographs of laboratory mock-ups
constructed for testing during the litigation
case.
For most conditions identified in this
document, the laboratory mock-up was
constructed to replicate both as-designed
and as-constructed conditions. This allowed
for independent consideration of both construction
errors and design issues. The
mock-up specimen—shown as a threedimensional
drawing in Figure 6 and photographically
in Figure 7—included many of
the unusual geometric conditions encountered
at the project; however, it was not an
exact reproduction of any specific portion of
the actual project.
Water testing was performed on the
mock-up in the laboratory using the procedures
outlined in aSTm E2128, including
the use of the calibrated spray rack, but
without a pressure differential between
interior and exterior conditions (Figure 8).
Control and Expansion Joints
Control joints are intended to control
shrinkage and other minor movement cracks
in the stucco and are not designed to weep
water to the exterior from the drainage plane.
However, when horizontal control joints are
installed in a manner that secures the joint
flanges tightly against the WrB—such as is
the case with mechanically attached joints
with solid flanges—the flow of water downward
within the drainage plane becomes
obstructed, and trapped water may even-
3 0 t h RC I I n t e R n a t I o n a l C o n v e n t I o n a n d t R a d e S h ow • M a R C h 5 – 1 0 , 2 0 1 5 M o S C o a n d C o p e • 2 3 3
Figure 6 – Three-dimensional drawing of mock-up.
Figure 7 – Photograph of actual laboratory mock-up.
tually find its way out of the assembly by
slowly seeping between the stucco and control
joint material, with the help of gravity.
When these types of control joints are
installed in a diagonal manner, however,
that same force of gravity creates an altered
path of least resistance for water to travel
along within the assembly. Where the joint
installation obstructs the downward vertical
movement of the water, the drainage
plane cavity itself provides a clearer and
unobstructed path compared to the small
gap between the plaster and the control joint
accessory, allowing water to flow diagonally
downward along the top of the joint within
the drainage plane. as the water flows diagonally,
it joins with more water flowing down
toward the control joint, accumulates, and
gains in volume until it intersects another
obstruction such as a similarly installed
vertical control joint, or until it encounters
a weep or other escape mechanism. Where
an obstruction interrupts the diagonal flow,
a dam effect can cause an increased accumulation
of water that may overwhelm the
drainage plane, allowing water to penetrate
the WRB at vertical and sometimes even
horizontal laps.
at the example project in the litigation
case, the as-designed condition at diagonal
control joints included solid-flange “double-
J” accessories, mechanically attached
through a layer of self-adhered flashing
membrane and sheathing to double studs
at vertical framing members and to solid
backing at horizontal or diagonal conditions
(Figure 9).
lath was cut at the joints and nested
over the control joint flanges. all fasteners
in the control joint flanges, as well as all
fasteners for the lath were sealed. Vertical
joints were installed in a continuous manner,
and horizontal or diagonal control
joints were cut and sealed to the vertical
joints in conformance with the manufacturer’s
installation instructions. During
water testing of the as-designed construction
in the mock-up at diagonal control
joints, water was found to collect within
the drainage plane where the diagonal joint
intersected the vertical joint, overloading
the drainage plane between the plaster and
the WrB, increasing in depth within the
assembly until (in some locations) eventually
passing through the unsealed laps in
the WRB.
Diagonal expansion joints that obstruct
the free flow of water within the drainage
plane present similar problems unless they
also include separate weeps. The addition of
weeps, however, may not provide complete
relief from problems, as we will discuss later.
Channel reveals are popular with many
designers and can be used to enhance
visual accents. These channels are most
commonly fabricated from extruded aluminum;
however, some formed sheet metal
channels are also available. These accessories
typically utilize solid flanges and are
usually mechanically attached to the building
structure through the WrB. Similar to
the conditions associated with mechanically
fastened control joints, these installations
can obstruct the free flow of water on the
WrB to weep flashings, and channel reveals
installed diagonally can present similar
concerns as those identified for control and
expansion joints.
in the laboratory mock-up test specimen,
the as-designed construction for the
channel reveal installation was replicated.
This installation was similar to that for the
control joints in that the solid flanges were
2 3 4 • M o S C o a n d C o p e 3 0 t h RC I I n t e R n a t I o n a l C o n v e n t I o n a n d t R a d e S h ow • M a R C h 5 – 1 0 , 2 0 1 5
Figure 8 – Water testing of laboratory mock-up.
Figure 9 – Detail of as-designed control joint.
mechanically attached to framing through
a layer of self-adhered flashing membrane
and sheathing, the lath was cut and nested
into the channel flanges, and all fasteners
were sealed. Unlike the control joints,
however, the design required the channel
reveals to be continuous and not interrupted
by vertical joints. in addition, some
conditions at the project included diagonal
reveals terminating at recessed vertical
window jambs, as shown in the mock-up
depicted in Figure 6. During water testing
of the as-designed mock-up, water was
found to have collected along the top of the
channel, growing in volume as it progressed
down the diagonal. Where the channel
intersected a window jamb, water intrusion
occurred at the interface between the window
head soffit (where the bulk of the drainage
plane water was discharged from the
channel) and the window frame, and also
along the channel path beginning about 24
inches from the window. Deconstruction of
the assembly showed that water was accumulating
within the drainage plane and
passing through laps in the WrB and also
through fasteners, even though they were
sealed at the WrB face (Figure 10).
avoiding problems associated with diagonal
control joints, expansion joints and
channel reveals can be accomplished by
using fabricated products in a manner
consistent with that intended by the manufacturer.
For assemblies requiring a drainage
plane, ensure that control joints are
installed over a continuous WRB and have
expanded metal flanges wire-tied to lath
that is discontinuous at joint locations and
fully embedded in the plaster. This installation,
which is consistent with aSTm C1063,
will provide a free and unobstructed drainage
plane. Weeps or drip flashings designed
to evacuate water from the assembly should
be provided at appropriate intervals; however,
control joints should not be expected
to weep water from the drainage plane.
Weeps and Drip Flashings
Weeps or drip flashings are critical to
the drainage plane performance in a stucco
assembly supported by metal lath. These
accessories are generally used in a horizontal
application, spaced at designated vertical
intervals along a stucco wall, at transitions
to horizontal soffit conditions, and at
door and window head conditions. There
are numerous products available that are
designed, fabricated, tested, and marketed
by the manufacturer to facilitate weeping of
water from the drainage plane. These products
generally perform best when installed
in horizontal applications, and their performance
may be adversely affected by
installations having unusual geometry. at
diagonal installations, the concept of the
path of least resistance
again alters
the behavior of the
water within the
drainage plane.
Where drip flashings
are not provided
at diagonal soffit
and recessed dooror
window-head
conditions, water
follows the path
of least resistance
and tends to wrap
from the vertical
wall drainage plane
into the horizontal/
diagonal soffit portion
of the assembly.
The water then
flows downward
along the horizontal/
diagonal drainage
plane, accumulating
in volume as
more water enters
the assembly with no adequate path to
weep from the assembly (Figure 11).
This water accumulation can exceed
the capacity of the drainage plane, causing
the water to fill the cavity and leak through
the laps in the WrB or through-flashings
at adjacent assemblies. large quantities of
3 0 t h RC I I n t e R n a t I o n a l C o n v e n t I o n a n d t R a d e S h ow • M a R C h 5 – 1 0 , 2 0 1 5 M o S C o a n d C o p e • 2 3 5
Figure 10 – Evidence of water penetration at diagonal aluminum channel.
Figure 11 – Diagram showing path of water within the
drainage plane at diagonal recessed window head without
drip flashing.
water that reach the end of the diagonal run
may exceed the capacity of the flashings, if
provided, at the termination.
Where diagonal drip flashings or weeps
are provided, some water will weep out;
however, some water flowing in the drainage
plane tends to travel along the path of least
resistance, remaining within the drainage
plane and flowing along the diagonal head
rather than weeping out at the flashings.
This water again accumulates and can
exceed the capacity of the drainage plane,
potentially causing the water to fill the cavity
and leak through the laps in the WrB
or through-flashings at adjacent assemblies
(although to a lesser extent, compared to
assemblies without drip/weep flashing).
This condition is commonly encountered
where steep-slope roofing intersects a vertical
stucco assembly extending upward. in
these cases, where water is expected to flow
within the drainage plane along a diagonal
path, “kick-out” flashings have traditionally
been used to evacuate water from the
assembly.
Potential problems related to weeps
and drip flashings in stucco assemblies
with diagonal accessories and terminations
can be mitigated following some basic
principles. in tall stucco wall assemblies,
provide weeps or drip flashings at appropriate
vertical intervals. The intervals may
vary depending on region, climate, and
other factors; however, it is generally recommended
that weeps be provided at each
floor line, or at every 20 ft., whichever is
less. Drip flashings should be provided at
the head condition for doors, windows, and
other similar penetrations. Where possible,
these weeps should be horizontal; however,
where diagonal weeps or drip flashings are
to be installed, kick-out flashings should be
provided. at conditions where long diagonal
drip flashing or weep runs occur, it may
be necessary to provide multiple kick-out
flashings spaced at intervals appropriate to
the specific conditions. in addition, accessories
that include a 45-degree termination,
similar to typical foundation weep screeds,
may improve performance compared to
standard drips or casing beads, including
perforated casings.
in the as-designed laboratory mock-up,
weeps and drip flashings were not included
at recessed window-head conditions; therefore,
none of these conditions was tested on
the mock-up during our investigation.
Horizontal Shelf Surfaces
Horizontal shelf conditions occur at a
variety of locations, including tops of walls
and recessed windowsills. These conditions
pose an increased risk of water intrusion
at any configuration; however, this risk is
increased when the shelf slopes diagonally
parallel to the plane of the wall. Rainwater
falling on these shelf conditions can penetrate
the stucco more easily through cracks
and at inadequately sealed terminations
to adjacent materials compared to vertical
walls. While the substrate and WrB at shelf
conditions should always slope to the vertical
face below for drainage, aesthetic decisions
often result in this slope being minimized.
Water on diagonal shelves will follow
the path of least resistance, often along the
more steeply sloped diagonal direction rather
than toward the vertical face. When water
on the shelf WrB intersects an obstruction
such as a vertical wall or jamb condition,
the water may accumulate and exceed the
capacity of the WrB, entering the assembly
through laps in the WrB.
Diagonal shelf conditions occur at the
example project in the form of recessed
windowsills, and this condition was replicated
in the as-designed mock-up. During
the water testing, no evidence of water
intrusion was encountered; however, our
review of field water testing and investigative
deconstruction documentation of these
conditions at the actual building revealed
that water was entering the wall cavities at
laps in the building paper and at the sealant
interface between the sill shelf and the
window frame seal, mostly at the location
where the sill intersects the recessed jamb.
Due to space limitations, the as-designed
mock-up presents smaller samples of the
various conditions. in the actual project,
the windowsills where water intrusion was
identified extended as much as 45 ft. in
length, which likely increased the accumulation
of water compared to our mock-up,
which may account for failure in the actual
project, but not in the mock-up testing.
Where diagonal shelf conditions are
installed, proper detailing can minimize
risks. Shelves should be sloped toward the
vertical face below as much as possible. at
these critical conditions, the WRB should
always be installed over a more-reliable
water barrier such as a metal flashing, selfadhered
flashing material, or both. Where
the shelf WrB intersects an obstruction
such as a vertical wall or jamb, a welldetailed
flashing should be provided. This
flashing should be fully sealed so that
it does not rely on normal weather-laps
to resist water intrusion. Always provide
well-detailed sealant installations at the
interface between the diagonal shelf and
adjacent materials, especially at the bottom
termination.
Casing Beads
Casings are typically used as a termination
for stucco. most standard casings for
exterior stucco have a component defining
the depth, which we will call the projection,
of ¾ or 7/8 in. to match the thickness of the
stucco. They also have a return at the face
of the stucco, which typically measures 1/8
or ¼ in. Flanges may consist of expanded
metal lath or solid metal. While expanded
flanges wire-tied to lath and encased in
the plaster provide the best opportunity
for the stucco panel to move and resist
cracking, in many areas of the country, casing
accessories with mechanically attached
solid flanges are commonly used. Having
solid flanges, however, does not necessarily
allow these accessories to perform as flashings
for the purposes of sealing the stucco
cladding to an adjacent assembly. When a
sealant application is used and sealed to
the return face of the casing, establishing
a good seal is difficult, since the face of 1/8
to ¼ in. is often insufficient to accept the
minimum sealant-joint depth required for
adhesion. Casing beads used in a flashing
application inherently include a reverse
lap at joints, leading to potential leaks.
Casings by their design cannot be “nested”
within each other; therefore, they cannot be
fully weather-lapped in vertical or diagonal
applications. Typical joint conditions for
casings include a cut in each piece allowing
for the lap; however, this ensures that a
portion of the lap will not be shingled in a
weather-lapped manner. Problems with casing
accessories in any orientation, including
diagonal, can be avoided by incorporating
a separate, properly lapped and sealed
flashing. allowance for movement in the
stucco assembly can also be enhanced by
using casing accessories with expanded
flanges that can be wire-tied to the lath and
encased in the plaster material.
at the example project from the litigation
case, the designer’s details showed
no casing or termination accessory of any
kind. The sealant was shown adhered to the
window frame and to the face of the finished
2 3 6 • M o S C o a n d C o p e 3 0 t h RC I I n t e R n a t I o n a l C o n v e n t I o n a n d t R a d e S h ow • M a R C h 5 – 1 0 , 2 0 1 5
stucco, which is not part of the weatherresistive
barrier assembly. The shop drawings
of the window included a metal flashing
or casing with a relatively large return
(Figure 10); however, this was not further
detailed or specified in the project documentation,
and the actual installation included
a standard casing with a 1/8-in. return. As
constructed, the sealant was adhered to the
finish coat of the stucco, engaging only 1/8 in.
of metal at the best-case conditions, and in
many case, no metal due to tolerance limitations.
in the as-designed mock-up, which
utilized the standard 1/8-in. casing return,
water was also observed penetrating into
the cavity of the windows through the laps
on the projection of the casing.
Installation of WRB
In most cases, the installation of sheetapplied
WrB materials is relatively straightforward.
Manufacturers specify the required
overlap dimensions at horizontal and vertical
lap joints in the material. To achieve
a reliable weather lap, the installation of
the WrB progresses vertically from the low
point to the high point, providing a shingle
effect. in most cases, decisions regarding
where the WRB installation starts and in
which direction the installation proceeds
are determined by the contractor, based on
construction schedule-related issues; WrB
decisions are not typically addressed by the
designer.
For the most common installations,
vertical lap joints can be lapped from
right to left or from left to right with little
consequence to the performance of the
building enclosure. Where diagonal accessories
affect the path of water within the
drainage plane, however, the orientation of
vertical lap joints can play a significant role
in maintaining the water-resistance of the
assembly. When the path of water within
the drainage plane is diverted by a diagonal
accessory and flows downward along
the diagonal, WrB sheet materials that are
installed beginning at the high point of the
accessory and progress to the low point
create a reverse lap that can allow water
to penetrate the WRB. These conditions
become even more problematic at recessed
shelf and soffit conditions, since the reverse
lap has a greater surface area exposed to
water travelling along the diagonal drainage
plane at the shelf or soffit.
An example of how the installation
sequence of the WrB at diagonal accessories
and other features must be carefully
considered would be obvious at a trapezoidal
window having head and sill conditions
that slope on a diagonal in different directions.
In cases such as this, the installation
of the WrB above the window head must be
installed from the left to the right, while the
installation of the WrB below the sill must
be installed from the right to the left.
While the use of self-adhered membrane
flashings in these conditions can provide
additional protection in sealing the open
laps, the potential exists for accumulation
of water within these assemblies to leak
through inadequately sealed lap joints,
and through sealant installations that were
intended to shed water rather than to resist
longer-term immersion.
While the design documents for the
project did not address this reverse lap
potential, for the purposes of fabricating the
as-designed mock-up, we elected to provide
a proper weather-lap. We do note, however,
that our review of documentation from testing
and destructive investigations at the
actual building showed that these reverse
laps did exist in the building and were a
major source of water intrusion.
managing the potential for water intrusion
at diagonal accessories and lapping
of the WRB requires the installer to have a
thorough understanding of the behavior of
water in the drainage plane at these conditions;
however, in our experience, this is
often not the case. While the installation
sequencing will almost always be a contractor’s
“means-and-methods” decision,
designers can also influence the installation
by including specific installation instructions
related to installing the WrB at diagonal
accessories on the construction drawings
and in the project manual.
CONCLUSION
Façades comprised of stucco supported
by metal lath are popular throughout the
United States and in many other parts of
the world. These systems are relatively
economical, durable, and require minimal
maintenance, in addition to being aesthetically
pleasing. a successful installation of
this type of wall cladding requires an understanding
of the aSTm standards developed
to help designers and builders, which
include aSTm C926 and aSTm C1063.
in this paper, we have described the
basic performance characteristics of the
drainage plane and how following the
requirements of the aSTm standards can
reduce the potential for water leaks in the
building. For buildings that have unusual
geometric features, however, those engaged
in the design and construction of these
assemblies must also have a more advanced
understanding of how unusual geometry
can alter the behavior of water within
this drainage plane. We have described
some of the unusual conditions we have
encountered in our investigations, and have
provided some suggestions for addressing
these conditions in a manner that will minimize
the potential for leaks. in addition to
understanding and adhering to the requirements
of the aSTm standards, designers
and installers should follow some other
basic principles, including:
• Use plaster accessories in the manner
intended by the manufacturer.
For example, do not expect control
joints to perform as weeps or drip
screeds.
• Provide weeps and drip screeds at
appropriate intervals on walls, at the
head condition of penetrations such
as doors and windows, and at transitions
from vertical walls to soffits.
• Do not install accessories in a manner
that obstructs the vertical flow
of water in the drainage plane,
especially diagonal accessories, like
mechanically attached control joints
or channel reveals, unless effective
weeps are also provided.
• Slope horizontal and/or diagonal
shelf conditions to drain to the outside
face of the wall.
• When installing stucco with diagonal
accessories, follow the “path of
least resistance,” which may direct
water diagonally; and provide active
measures like kick-out flashings
to evacuate water before excessive
accumulation can occur.
• Install WRB materials with vertical
joints weather-lapped in a manner
that anticipates diagonal or horizontal
movement of water when wrapped
onto shelf or soffit conditions.
Ultimately, the success of these installations
depends on all parties involved in
the design and construction of stucco supported
by metal lath having an adequate
understanding of the behavior of water
in the drainage plane, particularly where
unusual geometry occurs.
3 0 t h RC I I n t e R n a t I o n a l C o n v e n t I o n a n d t R a d e S h ow • M a R C h 5 – 1 0 , 2 0 1 5 M o S C o a n d C o p e • 2 3 7