Skip to main content Skip to footer

Understanding Low-Sloped (Hydrostatic) Standing-Seam Metal Roofs

May 15, 2015

Understanding Low-Sloped (Hydrostatic)
Standing-Seam Metal Roofs
Stephen L. Patterson, RRC, PE
Roof Technical Services, Inc.
1944 Handley Dr., fort Worth, TX 76112
Phone: 800-256-6693 • fax: 817-496-0892 • e-mail: spatterson@rooftechusa.com
Charles L. Smith Jr.
McElroy Metal/Architectural Building Components
1500 Hamilton Rd., bossier City, la 71111
Phone: 281-931-3996; fax: 281-931-3989 • e-mail: csmith@archmetalroof.com
3 0 t h RC I I n t e R n a t I o n a l C o n v e n t I o n a n d t R a d e S h ow • M a R C h 5 – 1 0 , 2 0 1 5 p a t t e R S o n a n d S M I t h • 1 2 5
Abstract
This presentation will address performance issues associated with low-slope (hydrostatic)
standing seam metal roofs (SSmrs) and the industry standards related to these roofs.
Examples will be provided of new insights into their failures, and standards applying to
them will be clarified. SSmrs are increasingly being used in applications once reserved for
built-up and single-ply roofing, and many of these roofs are blowing off, leaking, and failing
prematurely. The objectives of this presentation are to:
• Explain the differences between hydrostatic and hydrokinetic SSmrs
• Explain the performance requirements of hydrostatic SSmrs
• Explain the mechanisms of failures of hydrostatic SSmrs
• Provide the attendee an understanding of the industry standards and the nuances
in the standards for hydrostatic and hydrokinetic SSmrs
• Provide the reader guidelines for specifying and constructing hydrostatic SSmrs that
perform
This presentation brings together the unique collaboration of a consultant/engineer and
manufacturer who collectively have designed countless SSmrs, as well as investigated hundreds
of hydrostatic SSmr failures. This collaboration brings together manufacturing, field
performance, testing, and design experiences to address the serious performance issues and
design challenges associated with hydrostatic SSmrs.
Speakers
Stephen L. Patterson, RRC, PE — Roof Technical Services, Inc.
STEPHEn l. PaTTErSOn is a licensed engineer and registered roof consultant with 40
years of experience in the roofing industry, including work in manufacturing, as a contractor,
and as a roof consultant. Patterson founded roof Technical Services, inc., an architectural
and engineering firm specializing in roofing and waterproofing, in 1983. He coauthored
Roof Design and Practice, a roof design textbook published by Prentice Hall in 2001, as
well as two design monographs published by the rCi Foundation: Roof Drainage and Wind
Pressures on Low-Sloped Roofs. Patterson has consulted on some of the most complex lowsloped
metal roofs in the Southwest, including the american airlines Wide-Body Hanger at
alliance airport and Terminal D at DFW.
Charles L. Smith Jr. — McElroy Metal/Architectural Building Components
CHarliE SmiTH founded architectural Building Components in 1989, when he purchased
the equipment of a small Houston, Texas-based metal roofing manufacturing business.
Over the next 23 years, the company grew into an industry-leading metal roofing and
wall system solution provider specializing in the use of metal to recover existing low-slope
roofs. in 2012, architectural Building Components became a part of mcElroy metal, which
enabled Charlie to focus on educational and product development efforts to help the roofing
industry design creative solutions with metal. He recently cowrote the new rCi metal roofing
course with Brian Gardiner. He is a member of nrCa and rCi.
1 2 6 • p a t t e R S o n a n d S M I t h 3 0 t h RC I I n t e R n a t I o n a l C o n v e n t I o n a n d t R a d e S h ow • M a R C h 5 – 1 0 , 2 0 1 5
3 0 t h RC I I n t e R n a t I o n a l C o n v e n t I o n a n d t R a d e S h ow • M a R C h 5 – 1 0 , 2 0 1 5 p a t t e R S o n a n d S M I t h • 1 2 7
OVERVIEW
There are serious performance problems
with and a general lack of understanding
of the design and construction standards
associated with low-sloped standing-seam
metal roofs (SSmrs). Historically, SSmrs
were used for steep-sloped (hydrokinetic)
roof applications, and these roofs performed
extremely well. Today, SSmrs are
commonly used in low-slope (hydrostatic)
applications with widely varying results.
These roofs often leak, blow off, and fail
prematurely.
The industry standards for SSmrs used
in low-sloped, hydrostatic applications are
generally misunderstood. Surprisingly,
many of the SSmr systems that are commonly
specified for hydrostatic roof applications
do not meet the basic industry standards
for hydrostatic roofs. The objectives
of this paper are to provide an overview
of low-sloped SSmr systems, a thorough
discussion of the problems associated with
them, an understanding of the industry
standards for these roofs, and guidelines
for specifying and constructing low-sloped
SSmrs that will perform.
INTRODUCTION
metal roofing has a long history. Copper
and lead roofing have been successfully
used for centuries in a variety of styles.
Copper roofing was used on the new York
City Hall in 1763 and on the maryland State
House in 1774.1 Copper roofing has had a
long and successful history and is one reason
metal roofing is considered to be one of
the best roofing systems available. Doublelock
standing-seam copper roofs were the
standard for many years. Historically, these
roofs were formed into pans from sheets of
metal, and the side-laps were formed into
vertical or standing-seam seams; hence,
the name standing-seam. These roof panels
were formed from standard sheet metal
panels that varied in size but were commonly
3 by 10 ft. in size. The end laps were
lapped and hemmed, and the panels were
attached to the structure (normally wood)
with cleats.
Historically, SSmrs were used for steep
roofing situations, generally referred to as
hydrokinetic roofing applications where
water sheds off quickly enough to prevent
penetration through the roof system
when subjected to low-sloped, hydrostatic
roofing applications. low-sloped metal
roofs were typically flat-seam
roofs—sometimes referred
to as flat-lock seam roofs.
Historically, these roofs were
formed into relatively small
panels with hemmed edges
that were interlocked into
place and soldered to provide
the waterproofing required to
prevent water penetrations
from hydrostatic water pressure
common to low-sloped
roofs. Figure 1 is an excerpt
from Roof Design and Practice
showing typical standingseam
and flat-seam metal roof
details.
Tin plating and galvanization
of steel roofs were important
innovations in metal
roofing that lead to a reduction
in the cost of metal roofs
and increased the popularity
of metal roofing. SSmrs were
first adapted to low-sloped
applications when sealants
were introduced within the
seam to provide waterproofing
to prevent water from
penetrating the system when
subjected to hydrostatic water
pressure associated with low-
Understanding Low-Sloped (Hydrostatic)
Standing-Seam Metal Roofs
Figure 1 – Excerpt from Roof
Design and Practice.
sloped applications. Metal
building and metal building
component manufacturers
began promoting and manufacturing
standing-seam roofs
specifically for low-sloped
applications in the 1960s.
Butler introduced the trapezoidal
SSmr in 1969, which
led to the common use of
SSmrs in low-sloped roof
applications. Today, there are
a variety of low-sloped SSmrs,
and the purpose of this paper
is to discuss the issues related
to low-slope SSmrs.
Standards for Low-Sloped Metal Roofs
There are two general categories of
roof systems: hydrokinetic and hydrostatic.
Hydrokinetic roof systems are watershedding
systems that rely upon water running
off quickly enough to prevent leaks.
Hydrokinetic roofs are also referred to as
steep roofs. Generally, hydrokinetic roofs
are considered to be roofs with slopes of
3:12 or more. Hydrokinetic standing-seam
roofs include a wide variety of SSmrs, all
snap-together architectural panels, snaptogether
trapezoidal metal panels, and
mechanically seamed panels. The category
for low-sloped roofing is “hydrostatic” roofs,
which are roofs that must be waterproof
and must be able to withstand hydrostatic
water pressure, defined as submersion of
the roof under water. Unfortunately, there
are Smmr systems with snap-together
seams being marketed for use in lowslope
hydrostatic applications, yet which
do not meet the standards for hydrostatic
roofs. The metal Building manufacturers
association (mBma) establishes standards
for metal buildings that utilize low-sloped
metal roofs. Below is a quotation from the
MBMA Metal Roofing Design Manual (1st
Edition)3 identifying the hydrostatic requirements
for low-sloped applications:
low-slope applications are also
sometimes called hydrostatic metal
roofing systems. This term is also
appropriate, as “low slope” within
the context of metal roofing generally
means very low slope—almost
flat, hence details and joinery must
tolerate periods of submersion (or
hydrostatic exposure). The term
“functional” implies that the purpose
of the roof is solely that of
waterproofing and not one of aesthetic
enhancement—more or less
reciprocal to steep-slope metal roofing
where “form” is of equal importance
to “function.”
The american Society of Testing and
materials (aSTm) is the recognized organization
that establishes standards for building
materials and systems. aSTm established
testing procedures for building components
of metal roof panel systems, which include
low-sloped SSmrs. aSTm E2140-014 is the
Standard Test Method for Water Penetration
of Metal Roof Panel Systems by Static Water
Pressure Head. This is the recognized standard
for low-slope (hydrostatic) metal roofs,
including low-sloped SSmrs. Following is
a quotation from paragraph 1 of aSTm
E2140, identifying the aSTm hydrostatic
requirements:
1. Scope
1.1 This laboratory test method
covers the determination
of the resistance to water
penetration of exterior metal
roof panel system sideseams,
endlaps, and roof plane penetrations
when a specified
static water pressure head is
applied to the outside face of
the roof panel.
n ote 1—This test method is
intended to evaluate waterbarrier
(not water-shedding)
roof system joints and
details. These systems are
also referred to as hydrostatic
roof systems.
The test procedure for aSTm E2140
involves the submersion of the test assembly
of the roof system under 6 in. of standing
water for six hours. in order to pass,
no water may penetrate through the roof
during the test. Figure 2 is an excerpt from
aSTm E2140 showing test apparatus. The
circled notation was added for clarity.
The 2012 international Building Code5
provides minimum slope standards for
metal roofing, as well. Below is a quotation
from the 2012 international Building Code
(iBC), Section 1507.4, metal roof Panels:
1507.4.2 Deck slope. Minimum
slopes for metal roof panels shall
comply with the following:
1. The minimum slope for lapped,
nonsoldered seam metal roofs
without applied lap sealant shall
be three units vertical in 12
units horizontal (25-percent
slope).
2. The minimum slope for lapped,
nonsoldered seam metal roofs
with applied lap sealant shall
be one-half unit vertical in 12
units horizontal (4-percent
slope). lap sealants shall be
applied in accordance with the
approved manufacturer’s installation
instructions.
3. The minimum slope for standing-
seam of roof-systems shall
be one-quarter unit vertical in
12 units horizontal (2-percent
slope).
The performance standards for lowsloped
metal roofing are consistent and
well established. low-sloped roofs must be
waterproof and able to resist hydrostatic
water pressure in order to function as lowsloped
roofs. While it is unlikely that these
roofs will become submerged, there are
1 2 8 • p a t t e R S o n a n d S M I t h 3 0 t h RC I I n t e R n a t I o n a l C o n v e n t I o n a n d t R a d e S h ow • M a R C h 5 – 1 0 , 2 0 1 5
Figure 2 – Excerpt from ASTM E2140 showing test apparatus.
circumstances when they will leak as a result of hydrostatic
water pressure due to capillary action; wind-associated pressure
differences; and intense rains, ice, and snow. Figure 3 is a photograph
showing the unusual circumstance when a SSmr becomes
submerged. in this instance, 10 in. of hail fell in a short period in
June on a roof in Colorado. The result was the hail melted faster
than the water could run off the roof and there was a significant
period of time where the water was well above the height of the
standing-seam, resulting in hundreds of leaks in an 18-year-old
roof that had previously been problem-free.
low-sloped metal roofs should also meet standards similar to
other low-sloped roofing systems, including those for wind and
fire. Wind resistance for low-sloped roofs is also an issue, and the
roof system must be able to resist wind uplift pressures as well as
remain watertight. The standards for established wind uplift pressures
are provided in the american Society of Civil Engineering
(aSCE) and Structural Engineering institute’s (SEi) aSCE/SEi 7,
Minimum Design Loads for Buildings and Other Structures. The
low-sloped metal roof assembly should be able to resist these
uplift pressures. The standard wind uplift test for aSCE/SEi 7
is aSTm-E1592. There are also recognized testing agencies like
Factory mutual (Fm) and Underwriters laboratories (Ul) that
provide testing of metal roofing assemblies to show that these
systems meet established wind uplift pressures. Fire-rating
requirements are established in the iBC, and agencies like Fm
and Ul also provide testing to the established standards.
Types of Low-Sloped Metal Roofs
There are three basic types of low-sloped metal roofs. There
are low-sloped metal roofs that are lapped and sealed, commonly
referred to as exposed fastener systems. There are SSmr
systems which come in a variety of shapes; and there is the
flat-seam metal panel, which is not discussed in this paper. The
most commonly used exposed fastener systems panels are corrugated,
r-panels, and U-panels. Figure 4 shows examples of
the three different types of metal panels.
There is a wide variety of SSmr profiles used on low slopes.
Examples of three types of standing-seam panels are in the following
illustrations. Figure 5 is an illustration of a double-lock
standing-seam metal panel roof, sometimes referred to as an
asymmetrical vertical rib panel.
3 0 t h RC I I n t e R n a t I o n a l C o n v e n t I o n a n d t R a d e S h ow • M a R C h 5 – 1 0 , 2 0 1 5 p a t t e R S o n a n d S M I t h • 1 2 9
Figure 3 – Submerged SSMR after hailstorm.
Figure 4 – Examples of three common types of metal panels.
Figure 5 – Double-lock standing-seam metal panel roof.
Figure 6 is an example of a standingseam
T-panel roof, which is sometimes
referred to as a symmetrical T-shaped vertical
rib. This panel provides continuous
sealant beads and eliminates the area of
discontinuity in the sealant bead, which will
be discussed later.
Figure 7 is an illustration of a fieldseamed
trapezoidal double-lock standingseam
metal panel roof. This is the standard
hydrostatic trapezoidal metal panel.
There is another style of trapezoidal
standing-seam metal panel that utilizes
a snap-together seam. The snap-together
trapezoidal standing-seam roofs are hydrokinetic
roofs, and seams typically do not
meet aSTm E2140, the standard for hydrostatic
metal roofs. it is extraordinarily difficult
to maintain a watertight seam that will
withstand hydrostatic water pressures with
any snap-together standing-seam metal
panels. Figure 8 is an illustration showing a
typical snap-together trapezoidal standingseam
metal panel.
Waterproofing Issues With Low-Sloped
Metal Roofs
as stated above, these roof systems
must be resistant to hydrostatic water
pressure in order to be used in low-sloped
applications, which are defined as slopes
less than 3:12. The aSTm standard that
applies to metal roofs requires metal roofs
to resist water penetration when submerged
in 6 inches of water for six hours. Below is
a quotation from aSTm E2170 describing
the test procedure. This is a rigorous test
that simulates conditions that may occur
on low-sloped roofs during certain intense,
wind-driven rains or during ice and snow
events.
9. Procedure
9.1 remove any sealing material
or construction that is not
normally a part of the typical
panel assembly.
note 5—When full-length
brake-forming is available,
the test panels at the side
rails can be bent upward to
form effective side seals.
n ote 6—nonhardening mastic
compounds or pressuresensitive
tapes can be used
effectively to seal the test
panel assembly to test chamber.
n ote 7—The perimeter seals
between test panel specimen
and test chamber do
not have to duplicate actual
building perimeter details.
9.2 load the test specimen to
approximately 3 in. (75 mm)
of water pressure head.
Maintain water level for a
minimum of 5 min.
n ote 8—The use of roomtemperature
water is recommended
to avoid condensation,
which may interfere
with the observations of
water leakage.
9.2.1 Examine perimeter seals and
repair as necessary. Restore
water pressure head to
approximately 3 in. (75 mm)
if required and maintain for
a minimum of 5 min.
n ote 9—a small amount of
perimeter seal leakage is permitted,
provided that it does
1 3 0 • p a t t e R S o n a n d S M I t h 3 0 t h RC I I n t e R n a t I o n a l C o n v e n t I o n a n d t R a d e S h ow • M a R C h 5 – 1 0 , 2 0 1 5
Figure 6 – Standing-seam T-panel roof or symmetrical T-shaped vertical rib.
Figure 7 – Field-seamed trapezoidal double-lock standing-seam metal panel roof.
not impede the determination
of water leakage on the
inside face of the roof panel
specimen.
9.3 increase the water pressure
head to 6 in. (150 mm).
9.3.1 maintain the 6-in. (150-mm)
± .2-in. (5-mm) water pressure
head for a period of 6
hr.
9.3.2 record the water pressure
head and observe for water
leakage on the inside face of
the roof panel specimen 1 hr.
after the start of the test, 3
hr. after the start of the test,
and immediately prior to test
termination.
9.3.3 The test procedure shall be
terminated after 6 hr. or
upon observation of water
leakage on the inside face of
the roof panel specimen.
9.4 remove all water from test
specimen area. Observe and
record condition of panels,
panel endlaps, and panel
sideseams.
The minimum slope of exposed fastener
systems allowed in the iBC is 0.5:12.
Exposed fastener systems are typically comprised
of panels that provide 36 in. of coverage
and are attached to the underlying
structure using fasteners that penetrate the
panels and are lapped and sealed. The key
to waterproofing these systems is to have
sealant between the laps in the panels and
gaskets on the fasteners. Tape
sealant is applied between the
side and end laps and on the dry
side of the lap. The key is to prevent
water from entering at the
lap and through the screw holes.
Figure 9 is an illustration showing
the appropriate lap in a metal panel.
SSmrs can be used on slopes as low as
0.25:12, which is generally the minimum
slope allowed by the iBC. Four conditions
that make waterproofing a low-slope
standing-seam roof a challenge are the end
laps, seam sealant, valleys, and curbs. End
laps are one of the most common sources
of leaks on low-sloped metal roofs. The
waterproofing issues related to the end lap
are essentially the same as on the exposed
fastener systems. The profile of a standingseam
panel makes sealing the end lap more
difficult due to the geometry. Figure 10 is an
illustration showing the end lap in a trapezoidal
metal panel.
The end lap has to be 100% waterproof
and able to resist hydrostatic water pressure.
Even a relatively small depth of water
results in hydrostatic water pressure that
forces water under a lap. For example, the
hydrostatic water pressure from ¼ in. of
water will back water up a foot under the
lap of a panel on a ¼-in./ft. slope. Water
also tends to pond behind the lap on low-
3 0 t h RC I I n t e R n a t I o n a l C o n v e n t I o n a n d t R a d e S h ow • M a R C h 5 – 1 0 , 2 0 1 5 p a t t e R S o n a n d S M I t h • 1 3 1
Figure 8 – Snap-together trapezoidal standingseam
metal panel.
Figure 9 – Appropriate lap in a metal panel.
Figure 10 – The end lap in a trapezoidal metal panel.
sloped metal roofs, exacerbating the problem
with leaks at end laps.
The standing seam must also be watertight,
and there must be continuous sealant
in the seam in order to resist hydrostatic
water pressure without leaking. The sealant
is normally factory-applied to the inside
of the rib, and the sealant is held in place
when the rib is formed. it is critical for the
sealant to be continuous and fill the void
in the rib in order to maintain the rib in a
watertight condition over the life of the roof.
aSTm E1514, Standard Specification for
Structural Standing-Seam Steel Roof Panels,
provides standards for metal panel roofs,
and Section 9.3.1.1 deals with the sealant
requirements. Below is an excerpt from
aSTm E1514, Section 9.3.1.1:
9.3.1.1 The sealer shall be of sufficient
size and shape to fill the
maximum void to be sealed
and to assure compression
after engagement. The minimum
compression shall be
30% by volume, or the adhesion
plus webbing characteristics
shall be as required to
maintain watertightness.
Section 9.3.1.2 in aSTm E1514 deals
with resilience of the sealant; below is an
excerpt from 9.3.1.2:
9.3.1.2 The sealer shall be sufficiently
resilient to maintain the seal
after movement of joints due
to fluctuation in external load,
or expansion and contraction,
or combination thereof.
The conventional standing-seam rib has
a cleat or clip in the rib that holds the
panel in place and allows for expansion and
contraction. This clip creates a discontinuity
in the rib that can result in voids in the
sealant. Figure 11 is a photograph showing
a portion of the rib cut away exposing the
clip.
Figure 12 is a close-up of the gap in
the adhesive. In this case, the sealant was
not of sufficient size and shape to fill the
maximum void to be sealed and to assure
compression after engagement. The result
of this void is a leak in the seams of the
trapezoidal panel.
The symmetrical T-shaped panel eliminates
this discontinuity in the rib and
allows for a continuous uninterrupted sealant
bead on either side of the rib.
Perhaps the biggest challenge in preventing
water penetration through low-sloped
metal roof systems involves valleys. This is
particularly true with the trapezoidal panels.
The geometry of the rib makes it difficult to
seal the opening of the panel at the valleys.
The opening at the end of the panel is large
and irregular, making it difficult, if not virtually
impossible, to waterproof the panels at
a valley. The hip flashing is also a difficult
condition, in a manner similar to the valley.
It is also important to understand that
the slope of the valley is less than the slope
of the roof. a 0.25:12 slope is a slope of
approximately 2.1%, and the slope of a valley
on a roof with a 0.25:12 slope is only
1 3 2 • p a t t e R S o n a n d S M I t h 3 0 t h RC I I n t e R n a t I o n a l C o n v e n t I o n a n d t R a d e S h ow • M a R C h 5 – 1 0 , 2 0 1 5
Figure 11 – A portion of the rib is cut away, exposing the clip.
Figure 12 – Close-up of the gap in the adhesive.
1.5%, which is almost 30% less slope in the
valley. Water also tends to build up in the
valleys because water is flowing into the valley
from two directions, resulting in a larger
drainage area than with a typical panel. The
water flow from two directions also increases
turbulence that adds to the water buildup
in the valleys. For this reason, it is always a
good idea for the valley to be below the plane
of the roof panels on lower-sloped roofs.
Generally, all penetrations and transitions
are difficult issues for low-sloped
metal roofs. large penetrations typically
have a large drainage area on the upslope
side of the roof, which results in substantial
water flowing into the back of the penetration.
These types of penetrations also can
result in expansion and contraction issues.
roof panels are generally fixed on one end
and allowed to float on the other end to
eliminate excess stresses in the panels from
expansion and contraction. In many cases,
the panels are attached on both sides of
the penetration (upslope and downslope
side of the penetration), which results in
the panels’ being fixed on both ends and
resulting in excess stress from expansion
and contraction in the panels. like a panel
end lap, most curb penetrations rely upon
exposed fasteners and tape sealant to join
the roof panels to the curb, providing many
opportunities for leaks.
The design of low-slope metal roofs
must take into consideration hydrostatic
water pressure at all conditions, including
the end laps, seams, valleys, and penetrations.
The industry standard test is to
submerge the system in 6 inches of water
for six hours. The seams, laps, valleys,
and penetrations are the “achilles heels” of
the low-slope SSmr. The roof designer can
dramatically improve the performance of
low-slope metal roofs by eliminating all of
the conditions or as many of these conditions
as possible. a properly designed and
installed low-slope metal roof can provide
years of maintenance-free roofing, but conversely,
an improperly designed or installed
low-sloped metal roof can be among the
biggest problems in roofing. Figure 13 is a
photograph showing a roof design that has
zero end laps and zero fasteners penetrating
into the building envelope. The penetrations
have been redesigned using transversemounted
panels uphill of the curbs to eliminate
the issues with water draining into the
back of the penetrations.
Wind Uplift Issues With Low-Sloped
Metal Roofs
low-sloped metal roofs must be
designed and installed to meet the wind
uplift requirements included in the IBC.
The wind uplift requirements in the IBC are
based on aSCE’s Minimum Design Loads
for Buildings and Other Structures (aSCE
7). These standards have evolved over the
years and are quite rigorous. it is important
to understand that the wind uplift pressures
are greatest in the corners and along
the perimeter of the roof. Often, the roof
panels meet the wind uplift in the field but
do not meet the wind uplift along the perimeter
or ridge without decreasing the purlin
spacing. The snap-together trapezoidal panels
are prone to unsnapping during wind.
The panels tend to lift in the middle, causing
the seams to rotate and unsnap. Figure
14 is an illustration showing the rotation of
a trapezoidal panel during wind. Over time,
the seams can loosen and leak.
Wind uplift for low-sloped standingseam
metal panels is dependent on the clip,
the seam design, the width of the panel,
the gauge of the panel, and—in the case of
structural panels—the purlin spacing. The
typical 24-gauge, 24-in.-wide trapezoidal
panel installed over purlins spaced 5 ft.
on center will come apart at around 60 to
75 psf. a typical 16-in.-wide double-lock
standing-seam panel on purlins spaced 5
ft. on center will come apart at around 90
psf. These are probably the most commonly
used configurations for low-sloped metal
3 0 t h RC I I n t e R n a t I o n a l C o n v e n t I o n a n d t R a d e S h ow • M a R C h 5 – 1 0 , 2 0 1 5 p a t t e R S o n a n d S M I t h • 1 3 3
Figure 13 – A design with no end laps or fasteners penetrating the envelope.
Figure 14 – The rotation of a trapezoidal panel during a wind event.
roofs; yet, in many cases, these configurations
will not meet the higher wind uplift
requirements, particularly in the higher
wind uplift zones on the roof.
There are several ways to increase the
wind uplift capacity on a SSmr. The more
common methods include increasing the
gauge of the panels, decreasing the panel
width, or adding purlins to decrease the
clip spacing. For example, increasing the
thickness to 22-gauge will increase the
uplift capacity approximately 20 to 25%.
However, in cases where there are relatively
high wind uplift requirements, it may be
necessary to go to a system that incorporates
a continuous clip.
Thermal Movement Issues
Expansion and contraction due to
changes in temperature is a significant
issue in all metal roofs. The failure to
properly allow for expansion and contraction
can result in premature failure of the
system. The first edition of Copper and
Common Sense was published in 1945 following
a joint study of copper roofing failures
going back to the early 1900s.8 Copper
and Common Sense provided design and
construction guidelines for copper roofs,
including standing-seam copper roofs.
Fundamental in these design and construction
guidelines were provisions for expansion
and contraction.
Historically, SSmrs were fabricated
from sheets of metal that were 10 ft. long,
and there were far fewer issues with expansion
and contraction with these roofs than
the modern low-sloped SSmrs. This is
particularly true of the continuous-length
metal panels, which can be formed in
extremely long panels. Care must be taken
to allow for the expansion and contraction
in the design and construction of these
roofs.
During design, consideration should
also be given to expansion and contraction
at rooftop equipment and large penetrations,
as the attachment of the panels at
these penetrations can result in a roof panel
being restricted on both ends. Typically, a
panel is fixed at one end and is allowed to
expand and contract at the other end. All
too often, the panels are fixed on both ends
of the equipment, resulting in a section of
roof panel being fixed at both ends.
CONCLUSIONS
SSmrs can provide long-term economic
performance on low-sloped applications
typically reserved for conventional
built-up, modified-bitumen, and single-ply
installations. However, it is important to
understand the dynamics of SSmrs and
to avoid the pitfalls associated with many
of the typical industrial applications of
low-sloped metal roofs. It is essential that
the roof be properly designed to meet the
hydrostatic requirements of low-slope applications
and to make sure the roof meets
the code requirements, including the wind
uplift requirements. The designer should
be aware that there are significant limitations
on many of the most commonly used
standing-seam metal panels when designed
for low-slope, hydrostatic conditions. Below
are some keys to properly designing lowsloped
metal roofs.
Panel Selection
Use only panels that meet the aSTm
E2140 requirements for hydrostatic applications.
The longer the run, the more likely
the panels will develop problems. Panels
with areas of discontinuity within the rib
are more likely to leak than panels with
continuous sealants.
End Laps
Eliminate end laps wherever possible.
Use continuous length panels where possible.
Expansion/Contraction
all standing-seam roof panels will undergo
some level of expansion and contraction
from changes in temperature. The longer
the panels are, the greater the amount of
movement that occurs. all perimeter flashings
and trim must be designed to provide
for thermal movement. On lower slopes, it
is best to fix the panel at the eave with a
watertight, compression-sealed connection
to the structure. Panels that are hooked
on the eave trim like an architectural eave
detail will have a high propensity to leak on
a low slope or come unhooked if the panels
are long. Expansion is then directed toward
the ridge and along the sidewall or gable
conditions. The ridge and curb conditions
must allow for thermal movement of the
panels.
Large Penetrations
Eliminate large penetrations wherever
possible or design the roof to eliminate long
runs of panel that terminate into the back
of these penetrations. Always provide for
free flow of water around penetrations, and
do not restrict the movement of the panels
by fixing the panels on both sides of penetrations.
Ponding Water/Hydrostatic Water
Conditions
The designer must be aware of and
avoid conditions where water can build up
on a SSmr, whether it is behind a penetration,
at a lap, at a valley, or at a transition.
Valleys
Eliminate hips and valleys wherever possible.
in cases where valleys are required,
design the valleys so that the valley is
recessed to eliminate hydrostatic water pressure.
a metal roof may not be appropriate on
complex low-sloped applications.
Wind Uplift
Make certain the panels meet the wind
uplift requirements for the eaves, rakes,
and ridges.
Understanding the requirements for
low-sloped SSmrs is critical in designing
low-sloped metal roofs. Properly designed
and installed low-sloped metal roofs can
provide many years of low-cost, low-maintenance,
and leak-free roofing protection for
building owners.
REFERENCES
1. One Hundred Years of Roofing in
America, nrCa, 1986.
2. Roof Design and Practice, Prentice
Hall, 2000.
3. MBMA Metal Roofing Design Manual
(1st Edition), mBma, 2000.
4. a merican Society of Testing and
materials, aSTm E2140.
5. 2012 international Building Code,
IECC.
6. a merican Society of Testing and
materials, aSTm E1514.
7. a merican Society of Civil Engineers,
minimum Design loads for Buildings
and Other Structures, aSCE 7-10.
8. Copper and Common Sense, Revere
Copper Products, inc., 2005.
1 3 4 • p a t t e R S o n a n d S M I t h 3 0 t h RC I I n t e R n a t I o n a l C o n v e n t I o n a n d t R a d e S h ow • M a R C h 5 – 1 0 , 2 0 1 5