Skip to main content Skip to footer

Using the New ANSI Roof Edge Standard to Make a Better Roof

February 28, 1999

Using the New ANSI Roof Edge Standard
to Make a Better Roof

 

By John B. Hickman
W. P. Hickman Company
Asheville, North Carolina
Abstract
Originally developed as a design guideline for use by SPRI members, ANSI Standard
ES-1-98 has built upon and expanded the intent of that guideline and is now a National
Standard. This paper shows how the Standard may be used to improve roof design by
assuring a viable edge. The paper also discusses the reasons for developing the stan¬
dard in the first place. Worked examples show the ease with which the Standard can
be used. Useful worksheets, keyed to the Standard, are also provided. Included are
wind calculations, material limitations, corrosion considerations, and photographs to
illustrate the points.
John B, Hickman
John B. Hickman is the Chairman and CEO of the W. P. Hickman Company, headquartered in Asheville,
North Carolina. Mr. Hickman holds a Master’s Degree in Engineering from the University of Michigan.
He is chairman of the Single Ply Roofing Institute’s (SPRI) Edge Detail Subcommittee, and is SPRI’s
delegate to the Edge Detail Committee of the Roofing Industry Committee on Wind Issues (RICOWI).
Mr. Hickman is a member of the Board of Directors of RICOWI, the North Carolina Quality Leadership
Foundation (NCQLF), and of the North Carolina Alliance for Competitive Technologies. He has served
NCQLF as a Senior Quality Examiner. Hickman is a member of CSI, RCI and NRCA and is a former
Director of SPRI.

Using the New ANSI Roof Edge Standard to Make a Better Roof

 

by John B. Hickman
March 15, 1999
The ANSI/SPRI ES-1-98 Standard
After six years of work, SPRI, the association of sheet roofing and component manufacturers achieved
approval of the industry’s first comprehensive standard for roof edge design. ANSI/SPRI ES-1-98, Wind
Design Standard for Edge systems Used with Low Slope Roofing Systems was approved in November 1998
by ANSI, the American National Standards Association. SPRI’s Roof Edge Detail Committee developed the
new standard. That group included of representatives of RCI, The National Roofing Contractors
Association (NRCA), roofing manufacturers, and the insurance industry.
ANSI/SPRI ES-1-98 is the first industry sponsored roof edge design standard. It’s wind force provisions are
based on ASCE 7-95, the National Wind Design Standard. Minimum metal thicknesses and corrosion
considerations are also part of the new Standard. A “Commentary” section explains the engineering behind
its mandatory provisions. The purpose of this paper is to explore this Standard and show how it may be used
for better roof design.
Reasons For Developing the Standard In The First Place
Figure 1: Roof collapse after Hurricane Andrew
[courtesy R. Edwards] Hugo/RICOWI
Nearly ten years ago, Hurricane Hugo
slammed into Puerto Rico and
Charleston, South Carolina. Winds
exceeded 150 mph with torrential rain.
According to Factory Mutual, Hugo
“caused $194 million (1990 dollars) in
damage to 11,075 insured properties?”
Shortly after Hugo, a group,
representing various roof-related
associations, formed RICOWI, the
Roofing Industry Committee On Wind
Issues with Charles Goldsmith, AIA, as
its chairman. RICOWI’s purpose was to foster research and communication aimed at mitigating the effects
of hurricanes and strong winds on roof-related building damage. Immediately, RICOWI established
nineteen priorities for study. “Roof Edge Detailing” was the number two priority on that list. Subsequent
hurricanes and storms have increased awareness of the need for better roof edge design.
Investigators have found that relatively simple steps in edge system securement can potentially head off
millions of dollars worth of windstorm damage. The Institute for Business and Home Safety (IBHS) an
insurance association, has listed “adequate attachment of commercial edge metal” among its top four most
wanted improvements for disaster-resilient structures11 . Each year, about 80% of construction litigation
involves water damage and most of that is a direct result of wind and water leaks at the roof edge.
a Riding Out the Storm, FM P9106, Factory Mutual Corporation, Norwood, MA. 1997.
b IBES, 1998.
Figure 3: Roof Destroyed at Edge
Structural Formulae
Most critical parts of a building are designed using precise structural formulae and codes. In a blow, these
parts generally survive. Edges don’t. Yet they are the first defense the roof has against the wind. Once the
edge goes, so does the rest of the roof.
It doesn’t take a hurricane to rip up a roof edge. Last November, Des Moines was hit by a windstorm that
damaged the roofs of a number of schools. The local paper said: “Some schools scrambled to send students
home because of ripped up roofs. Van Roekel [a school principal] said that the edging along the roofline
blew off, allowing wind under a rubber membrane.c”
Figure 2: Poorly secured coping
destroyed by wind [courtesy Factory
Mutual] apparent to the roofing industry.
Inadequate Standards
Prior to the development of ANSI/SPRI ES-1-98, rules of
thumb, local practices and the suggestions of a few roof
edge manufacturers guided edge design advice. The
Factory Mutual Research Corporation (FMRC) Property
Loss Prevention Data Sheet 1 -49d has been accepted by
some as a standard, but its advice is largely prescriptive
and is not based on the latest wind design standards.
Some have avoided FM 1-49 because it was never
intended to be a national standard outside the FMRC
organization, and it requires that testing be done only at
FMRC’s laboratories. The need for a national design
standard for roof edge details has become acutely
Specifiers Seek Guidance
Many specifiers see the need for better roof edge design. Without a Code or National Standard to back them
up, it is difficult for them to defend a specification when a contractor urges the use of a cheapened detail
because “it is just as good as” the one detailed by the designer. It is even difficult to defend specification of
the edge of a reputable manufacturer. With no standard, it is difficult to compare the merits of different
designs. ES-1-98 is that standard.
How The Standard Can Be Used To Improve Roof
ANSI/SPRI ES-1-98 is a comprehensive work providing rules for wind design, choice of materials, and
other design parameters such as nailer coverage. Its wind pressure provisions, while based on the latest wind
engineering are easy to follow and quickly calculated. Edges designed to comply with the standard will have
adequate metal thickness, good coverage of nailers and appropriate corrosion resistance and will protect the
roof from expected windstorms.
The standard considers such factors as building location, building use, building environment, comer regions,
substrates, and nailer coverage. It also helps a designer to decide which metal pairs to use and what
thicknesses to specify.
c The Des Moines Register, p4A, Des Moines, IA, November 11, 1998.
d Property Loss Prevention Data Sheet 1-49, Roof Edge…, Factory Mutual Corporation, Norwood, MA. 1998.
Hickman-2
Appliances
Frequently, an edge detail that would have served well is compromised by the use of appliances such as
signs or lightning rods that are subsequently attached to the edge. ES-1-98 requires that these be eliminated
or isolated to avoid corrosive and other problems.
Testing
The heart of the document is its test protocols. There are three tests that may be required, depending upon
the edge design. There are two blow-off tests, one for coping
and one for fascia. There is also a membrane pullout test for
those fascia systems that are intended to terminate ballasted or
mechanically attached roofing membrane systems.
Membrane Pull-Out (Test RE-1)
The protocol for this test requires that the membrane be pulled
at a 45° angle. A 100-pound resistance passes this test. See
Figure 3.
Figure 3
Membrane
Tensile Test Base
General Test Layout for Membrane Pullout Test
Membrane Termination Detail —7
Blow-Off Tests (Tests RE-2 and RE-3)
The Standard requires static tests of full-length
sections of roof edge. Full-length assures that all
of the components will be stressed as they would
be in the field. Test RE-1 for fascias is rather
straightforward. Test RE-3 for copings is
complicated somewhat by the requirement that a
coping be tested simultaneously in horizontal and
vertical directions and that the test be run twice,
once against the top and face and once against the
top and back leg. The forces on the coping must
be applied in the exact ratio of design pressures
calculated for the top and the faces. We shall work
examples of these calculations.
Figure 4 shows one embodiment of the testing
apparatus for RE-2 and RE-3. It is a hydraulically
operated device built by W.P. Hickman Company.
Other roof edge manufacturers and at least one
national testing laboratory have similar devices at
this writing.
Worked Examples
Worked examples show the ease with which the
Standard can be used. Worked calculation sheets
appear at the end of this paper. There is also a
blank sheet, which may be reproduced as required.
Figure 4: Device for performing tests
RE-2 and RE-3 [W.P. Hickman Company
photo] Hickman-3
Example 1, Florida High-Rise (Worksheet Appendix 1)
Consider a 100-foot high hospital in downtown Lakeland, Florida. The unit is to have a 16-inch wide coping
with 4-inch face and back legs. Refer to Appendix 1 to follow the calculation steps.
Enter the building identification, date and designer’s initials at the top of the worksheet. Line 02 shows the
average building height at the eaves of 100 feet. Enter the coping width on Line 11 and face height on Line
12. This is the basic information needed to determine the forces on the coping. The calculation steps
follow:
Referring to the Exposure classifications on Page 2 of ES-1, we see that Exposure “B” is appropriate for this
hospital. Since a hospital is an essential facility, the Importance Classification is “IV” (Table 1 on Page 3 of
ES-1). Circle these selections on lines 03 and 04.
Figure 5: Florida high-rise destruction during
Hurricane Andrew [courtesy Roger Edwards] © !992 Roger Ed wards Examining the wind speed map on Page
7, note that Lakeland has a Basic Wind
Speed of 130 miles per hour. Enter the
wind speed on Line 05. Lookup the
Importance Factor (Table 3, Page 4),
based on the Classification circled on
Line 04. The value is 1.15. Enter it on
Line 06. Then multiply line 04 by Line
06 to get Line 07, “Design Wind
Speed.”
Now we are ready to find the
Theoretical Velocity Pressure (Table 4 on Page 5). Enter the Table for “Exposure B” (Line 03). A building
100 feet high (Line 02) and a Design Wind Speed of 150 mph (Line 07) gives a Velocity Pressure of 57 psf.
Enter 57 on Line 08.
Pressure coefficients are obtained from Table 5, Page 6. These coefficients correct the theoretical velocity
pressures of Table 4 to actual design pressures. No safety factors are needed here. The pressure coefficients
themselves provide the recommended values. Different values are needed for outward force (horizontal)
and upward force (vertical). The building exceeds 60 feet, so we use the right hand column values: -1.8 for
horizontal and -2.3 vertical. The negative sign denotes that the force is away from the building, tending to
tear the edge device off. Enter -1.8 and -2.3 on Line 09.
We may ignore the minus sign if we remember that the force is always acting away from the building.
Multiply the Theoretical Velocity Pressure (Line 08) by the pressure coefficient (Line 09) to get Design
Pressure (Line 10). The pressure is 102.6 psf horizontal and 131.1 psf vertical.
Divide Lines 11 and 12 by 12.0 to convert inches to feet. The 4-inch face is 0.33 feet high and the 16-inch
coping is 1.33 feet wide. Enter the results on Line 13.
The linear resistance we seek is found by multiplying the pressure (pounds per square foot) by the height
and width in feet to get pounds per linear foot (33.9 and 174.4) which are entered on Line 14. Test RE-3 (see
Page 10) must result in at least 33.9 pounds per foot on the face and 174.4 pounds per foot on the top.
Remember that the tests must be performed on a face and the top simultaneously. If the back leg dimension
Hickman-4
differs from the face, recalculate Lines 12-13 for the different back-leg height. That result will be the
performance demanded of the back leg.
The designer may properly place the burden of calculation on the roof edge provider, by simply specifying
that the edge comply with ANSI/SPRI ES-1-98.
Other Provisions of ES-1-98
The designer may specify a minimum thickness, or simply require the roof edge provider to comply with the
Standard. Frequently, dissimilar metals are used for the face and the cleats or retaining devices. Care must
be exercised in selecting these materials. Allowable metal pairs are shown on Page 6. Other pairs may be
chosen, but only if they can be shown to provide satisfactory galvanic compatibility (Sec. 5.3 p.6).
The face of the coping must be wide enough to extend one inch below the top of the wall facing (Sec. 2.4
p.2). This provision of the Standard is to prevent blowing rain from entering the building behind the facing
material. If the coping is secured to a nailer, the attachment of the nailer must be sufficient to carry the
loads calculated above. This requirement can be especially troublesome in retrofitting, because the
condition of the nailer may not be known during the design process.
The following examples will be followed in less detail. Refer to the Appendices for calculation results.
Example 2, Florida Low-Rise (Worksheet Appendix 2)
Assume another Florida building. This time, it is a low-rise motel on the beach near Miami. The
specification is for an 8 inch coping with 3 inch face and back leg. Notice that even though the wind zone is
fiercer, the requirements are much less stringent. The reasons are: The building is not an “essential facility”;
it is not a high-rise; the coping is smaller.
Since the building is on the waterfront, it qualifies as an “Exposure D” location. Being a motel, however, it
is neither low hazard nor critical. For that reason, it qualifies for Importance Category II. The basic wind
speed in Miami, from the map, is 150 mph. These factors lead to 21.0 and 72.4 pounds per ft, roughly half
of the design requirements for Example 1.
Figure 6: Midwest school roof destroyed
after edge failed in storm
[courtesy Beavers & Assoc.] Example 3, Midwest Low Rise
(Worksheet Appendix 3)
Moving away from the hurricane coast,
this example is a hotel in Ann Arbor,
Michigan. It is set in an urban, low-rise
area, so it is “Exposure is B.” Unlike
the motel of the previous instance, large
numbers of people can congregate in a
hotel. Thus, the Importance Category is
III, since it is a building that represents
substantial hazard to human life in the
event of a failure.
The fascia for the building must be
tested to 24.5 pounds per foot.
Furthermore, if the fascia is to retain
Hickman-5
the roofing, it must be tested under the RE-1 protocol to have a gripping power of 100 pounds per foot (Test
RE-1, p.8).
In addition to the face coverage, the designer must be careful to design the edge so that it doesn’t overlap the
back of the nailer (see Sec. 5.3, p3).
Example 4, Equipment shed (Worksheet Appendix 4)
In this example, we have an equipment shed. If it collapsed, there would be scant chance of loss of human
life. Its Importance Category, therefore, is I, “buildings that represent low hazard to human life.” Situated
on a farm, it has an environment of open terrain with scattered buildings. Clearly, “Exposure C.”
Even such a low risk building in America’s “Heartland” requires over 13 pounds per foot of horizontal
resistance on the face and 34 pounds uplift.
Summary
These worked examples can give a sense of
the pressure forces that edge systems must
resist. The forces developed through these
examples require resistances on the faces of
the edge devices of from 26.6 psf to 102.6.
They require uplift resistances of 34.2 to
131.1 psf.
Figure 7: Roof and insulation blown off after
edge system failed during Hurricane Hugo
[W.P. Hickman Company photo] Hickman-6
IS HICKMAN ® ©1999 W.P. Hickman Company,
Appendix 1
ANSI/SPRI ES-1-98 Wind Design Standard for Edge Systems
Used with Low Slope Roofing Systems
Permission is hereby granted to reproduce this page as
The Leading Edge® needed. *Page number of ES-1-98.
Line Building Parameters DATA Page*
01 Building Description
(City, State,
Type of Building,
Local Terrain)
Hospital By:
Lakeland, FL JBH
Downtown location Date:
16” Coping w/ 4” Face 3/15/99
02 Building Height at Eave 100 ft
03 Exposure (Based on Local Terrain) Ci rcl e One Page
A [ B | C D 2
04 Importance Classification (From Table 1) cLrcle One
i i ii i in
Page
3
05 Basic Wind Speed (From wind speed map) 130
mph
Page
7
06 Importance Factor (Select Factor from Table 3 Based on Line
04 Above.
1.15 Page
4
07 Design Wind Speed
= Basic Wind Speed X Importance Factor.
150
mph
Design wind speed
Wfe–
08 Theoretical Velocity Pressure Choose Table 4 Section Based on
Exposure (Line 03). Enter Table 4 with Basic Wind Speed (Line
05) and Building Height (Line 02).
57
Lbs. per sqft
Page
6
09 Pressure Coefficient
Select from Table 5 based on Building Height (line 02).
Hori –
zontal
Verti
-cal
-1.8 -2.3 tSBpWJsB
10 Design Pressure (Ignore negative) Multiply Line 08 by Line 09 102.6
PSf
131.1
PSf
11 Width of Top (Omit if Edge Is Not Coping)
Wife;
16
inch
• ; ‘1
12 Face Height 4
inch
13 Height and Width in Feet
(Divide lines 11&12 by 12.0 to convert to feet.)
0.33
Ft
1.33
ft
14 Design Resistance Multiply Line 10 by Line 13. Edge device
must be tested to meet or exceed this force.
Face Top
ifiK
.: ■ ‘ll.I11′
33.9
tbs. /ft
outward
174.4
lbs. /ft
upward
Hickman-7
Appendix 2
ANSI/SPRI ES-1-98 Wind Design Standard for Edge Systems
Used with Low Slope Roofing Systems
Line Building Parameters DATA Page*
01 Building Description
(City, State,
Type of Building,
Local Terrain)
Motel By:
Miami Beach JBH
Seaside Date:
8” Coping w/ 3” Face 3/15/99
02 Building Height at Eave 45 ft
03 Exposure (Based on Local Terrain) Ci rcl e One Page
A B C pT 2
04 Importance Classification (From Table 1) Circle One
1 [ II ] III 1 IV
Page
3
05 Basic Wind Speed (From wind speed map) 150
mph
Page
7
06 Importance Factor (Select Factor from Table 3 Based on Line
04 Above.
1.00 Page
4
07 Design Wind Speed
= Basic Wind Speed X Importance Factor.
150
mph
Design Wind Speed
08 Theoretical Velocity Pressure Choose Table 4 Section Based on
Exposure (Line 03). Enter Table 4 with Basic Wind Speed (Line
05) and Building Height (Line 02).
60
Lbs. per sqft
Page
6
09 Pressure Coefficient
Select from Table 5 based on Building Height (line 02).
HOM –
zontal
verti
-cal
-1.4 -1.8
10 Design Pressure (Ignore negative) Multiply Line 08 by Line 09 84.0
Psf
108.0
Psf
11 Width of Top (Omit if Edge Is Not Coping)
X
8
inch
:
12 Face Height 3
inch r ^3?
13 Height and Width in Feet
(Divide lines 11&12 by 12.0 to convert to feet.)
0.25
Ft
0.67
ft

14 Design Resistance Multiply Line 10 by Line 13. Edge device
must be tested to meet or exceed this force.
Face Top
L t U fi
21.0
lbs. /ft
I Outward
72.4
lbs. /ft
Upward
13 HICKMAN
The Leading Edge®
©1999 W.P. Hickman Company, Asheville NC.
Permission is hereby granted to reproduce this page as
needed. *Page number of ES-1-98.
Hickman-8
Appendix 3
ANSI/SPRI ES-1-98 Wind Design Standard for Edge Systems
Used with Low Slope Roofing Systems
Line Building Parameters DATA Page*
01 Building Description
(City, State,
Type of Building,
Local Terrain)
Hotel By:
Ann Arbor, MI JBH
Urban-Low Rise Area Date:
6” Fascia 3/15/99
02 Building Height at Eave 120 ft
03 Exposure (Based on Local Terrain) Ci rcle One
A |b I C D
Page
2
04 Importance Classification (From Table 1) circle one
I | II j in | IV
Page
3
05 Basic Wind Speed (From wind speed map) 90
mph
Page
7
06 Importance Factor (Select Factor from Table 3 Based on Line
04 Above.
1.15 Page
4
07 Design Wind Speed
= Basic Wind Speed X Importance Factor.
103.5
mph
Design wind speed
08 Theoretical Velocity Pressure Choose Table 4 Section Based on
Exposure (Line 03). Enter Table 4 with Basic Wind Speed (Line
05) and Building Height (Line 02).
27
Lbs. per sqft
Page
6
09 Pressure Coefficient
Select from Table 5 based on Building Height (line 02).
Hori –
zontal
verti
-cal
-1.8 -2.3
10 Design Pressure (Ignore negative) Multiply Line 08 by Line 09 48.6
PSf
X
PSf
11 Width of Top (Omit if Edge Is Not Coping)
wife
’I’. ■ : ■’ ■ .
•H i’
X
inch
ills
/pii
12 Face Height 6
inch
13 Height and Width in Feet
(Divide lines 11&12 by 12.0 to convert to feet.)
0.50
Ft
X
Ft
ft”’
* «•
14 Design Resistance Multiply Line 10 by Line 13. Edge device
must be tested to meet or exceed this force.
Face Top
24.3
lbs. /ft
outward
X
lbs. /ft
upward
13 HICKMAN
The Leading Edge®
©1999 W.P. Hickman Company, Asheville NC.
Permission is hereby granted to reproduce this page as
needed. *Page number of ES-1-98.
Hickman-9
Appendix 4
ANSI/SPRI ES-1-98 Wind Design Standard for Edge Systems
Used with Low Slope Roofing Systems _
Line Building Parameters DATA Page*
01 Building Description
(City, State,
Type of Building,
Local Terrain)
Equipment Shed By:
Farm near St. Louis, MO JBH
Agricultural Date:
12” Coping w/ 6” Face 3/15/99
02 Building Height at Eave 32 ft
03 Exposure (Based on Local Terrain) Ci rcl e One
A B [ cj D
Page
2
04 Importance Classification (From Table 1) Ci rcl e One Page
I 1 II 1 III 1 IV 3
05 Basic Wind Speed (From wind speed map) 90
mph
Page
7
06 Importance Factor (Sei
04 Above.
ect Factor from Table 3 Based on Line 0.87 Page
4
nportance Factor.
78
mph
Design wind speed
Of 11
07 Design Wind Speed
= Basic Wind Speed X Ir
08 Theoretical Velocity Pressure Choose Table 4 Section Based on
Exposure (Line 03). Enter Table 4 with Basic Wind Speed (Line
05) and Building Height (Line 02).
19
Lbs. per sqft
Page
6
09 Pressure Coefficient
Select from Table 5 based on Building Height (line 02).
Hori –
zontal
verti
-cal
-1.4 -1.8 .’. ‘v
10 Design Pressure (Ignore negative) Multiply Line 08 by Line 09 26.6
PSf
34.2
PSf
11 Width of Top (Omit if Edge Is Not Coping)
l-aa.’.’-
12
inch
-IZA*; ? BOSOr
12 Face Height 6
inch
13 Height and Width in Feet
(Divide lines 11&12 by 12.0 to convert to feet.)
0.50
Ft
1.00
ft
/I®
14 Design Resistance Multiply Line 10 by Line 13. Edge device
must be tested to meet or exceed this force.
Face Top – c
– > 13.3
lbs. /ft
Outward
34.2
lbs. /ft
Upward
IKI® ®^99 W.P. Hickman Company, Asheville NC.
HI 1^.1 V 1 /Kill Permission is hereby granted to reproduce this page as
The Leading Edge® needed. *Page number of ES-1-98.
Hickman- 10
IS HICKMAN ® ©1999 W.P. Hickman Company, Asheville NC.
Appendix 5
ANSI/SPRI ES-1-98 Wind Design Standard for Edge Systems
Used with Low Slope Roofing Systems
@ Permission is hereby granted to reproduce this page as
Th© Leading Edgo needed. *Page number of ES-1-98.
Line Building Parameters DATA Page*
01 Building Description
(City, State,
Type of Building,
Local Terrain)
By:
Date:
02 Building Height at Eave ft
03 Exposure (Based on Local Terrain) Ci rcl e One Page
A B C 1 D 2
04 Importance Classification (From Table 1) Ci rcle One Page
i 3 11 III | IV
05 Basic Wind Speed (From wind speed map)
mph
Page
7
06 Importance Factor (Select Factor from Table 3 Based on Line
04 Above.
Page
4
07 Design Wind Speed
= Basic Wind Speed X Importance Factor. mph
Design wind speed
08 Theoretical Velocity Pressure Choose Table 4 Section Based on
Exposure (Line 03). Enter Table 4 with Basic Wind Speed (Line
05) and Building Height (Line 02). Lbs. per sqft
Page
6
09 Pressure Coefficient
Select from Table 5 based on Building Height (line 02).
HOM –
zontal
verti –
cal
10 Design Pressure (Ignore negative) Multiply Line 08 by Line 09
psf Psf
11 Width of Top (Omit if Edge Is Not Coping)
r
inch
12 Face Height
inch
13 Height and Width in Feet
(Divide lines 11&12 by 12.0 to convert to feet.)
Ft Ft
14 Design Resistance Multiply Line 10 by Line 13. Edge device
must be tested to meet or exceed this force.
Face Top
lilll
1bs ./ft
Outward
tbs. /ft
Upward
Hickman- 11
Approved November 10, 1998 ANSl/SPRI ES-1-98
. American National Standard
Wind Design Standard for Edge Systems
Used with Low Slope Roofing Systems
1 INTRODUCTION (See Commentary: 1)
The following standard is a reference for those
who design, specify or install edge materials
used with low slope roofing systems. Although
it does address corrosion, this Standard focuses
primarily on design for wind resistance. It is in¬
tended for use with the specifications and re¬
quirements of the manufacturers of the specific
roofing materials and the edge systems used in
the roofing assembly, excluding gutters. The
membrane manufacturer shall be consulted for
specific recommendations for making the roof
watertight at the edge.
This design standard addresses copings and
horizontal roof edges, and the following factors
shall be considered in designing a roof edge.
• Structural integrity of the substrate that an¬
chors the edge
• Wind resistance of the edge detail
• Materials specifications
2 GENERAL DESIGN CONSIDERATIONS AND
DEFINITIONS (See Commentary: 2)
All materials for roof edge construction shall
have sufficient strength to withstand the design
wind load. The following factors apply when de¬
signing a roof edge system: Wind speed, build¬
ing height, corner and perimeter regions, edge
condition, Exposure Factor, topography, galvanic
compatibility and Importance Factor.
2.1 WIND SPEED (See Commentary: 2.1)
Basic wind speed values used in the design cal¬
culations are 3-second gust speeds in miles per
hour (m/s) measured at 33 ft (10 m) above
ground for Exposure Factor C associated with
an annual probability of 0.02 (50 year return).
American national Standards Institute |
These values are taken from the ANSI/ASCE
7-95 1 document (See attachment I) or the au¬
thority having jurisdiction. Section 6.5.5 of
ASCE 7-95 1 shall be used to adjust design wind
speed for the intensifying effects of valleys and
other unique topographic features such as hills
or escarpments. (See Commentary: 2.1 ) The au¬
thority having jurisdiction shall be contacted for
verification of wind data.
2.2 BUILDING HEIGHT
The building height shall be measured from
ground level to the mean height of the roof sec¬
tion under design.
2.3 ROOF EDGE REGIONS
Wind forces near the corner regions are of
greater intensity than in the perimeter regions
between corners. These regions are defined as
follows:
2.3.1 CORNER REGION
For buildings with mean roof height up to 60 feet
(18 m), the corner region is a distance from the
building corner that is 10% of the minimum build¬
ing width or 40% of the building height at the
eaves, whichever is smaller, but not less than
4% of the minimum building width and not less
than 3 feet (0.9 m). For buildings with mean
roof height greater than 60 feet (18 m), the cor¬
ner region is a distance from the building cor¬
ner that is 10% of the minimum building width
but not less than 3 feet (0.9 m).
Copyright © 1998 by SPRI, 200 Reservoir Street, Needham, MA 02494. All Rights Reserved.
1
ANSI/SPRI ES-1-98 Approved November 10, 1998
Figure 1: Edge Flashing Coverage
2.3.2 PERIMETER
The perimeter is the section of roof edge be¬
tween corner regions as defined in Section 2.3.1
(above).
2.4 EDGE CONDITION (See Commentary: 2.4)
The edge condition includes the roof edge de¬
vice (edge flashing or coping) and the nailer or
other substrate to which the edge device is at¬
tached.
Coverage is the location of the lowest vertical
point of the roof edge device or any extension
of it, exclusive of any drip bend or other protru¬
sion. The coverage shall extend a minimum of
1 inch (25 mm) below the bottom of the nailer.
The roof membrane shall not extend below the
coverage.
2.5 EXPOSURE (See Commentary: 2.5)
The building shall be classified into one of the
following Exposures based on surrounding ter¬
rain:
2.5.1. EXPOSURE A.
Large city centers with at least 50% of the build¬
ings having a height in excess of 70 feet (21 .3
m). Use of this exposure category shall be lim¬
ited to those areas for which terrain represen¬
tative of Exposure A prevails in the upwind di¬
rection for a distance of at least one-half mile
(0.8 km) or 10 times the height of the building
or other structure, whichever is greater. Possible
channeling effects or increased velocity pres¬
sures due to the building or structure being lo¬
cated in the wake of adjacent buildings shall be
taken into account.
2.5.2. EXPOSURE B.
Urban and suburban areas, wooded areas, or
other terrain with numerous closely spaced ob¬
structions having the size of single-family dwell¬
ings or larger. Use of this exposure category
shall be limited to those areas for which terrain
representative of Exposure B prevails in the up¬
wind direction for a distance of at least 1,500
feet (460 m) or 10 times the height of the build¬
ing or structure, whichever is greater.
2.5.3. EXPOSURE C. (See Commentary: 2.5.3)
Open terrain with scattered obstructions having
heights generally less than 30 feet (9.1 m). This
category includes flat open country and grass¬
lands.
2.5.4. EXPOSURE D.
Flat, unobstructed areas exposed to wind flow¬
ing over open water for a distance of at least 1
mile (1.61 km). This exposure shall apply only
to those buildings and other structures exposed
to the wind coming from over the water. Expo¬
sure D extends inland from the shoreline a dis¬
tance of 1,500 feet (460 m) or 10 times the
height of the building or structure, whichever is
greater.
2.6 IMPORTANCE FACTOR
(See Commentary: 2.6)
Buildings fitting one of the following criteria shall
have an “Importance Factor* included in the wind
design calculations. Table 1 (page 3) explains
these building classifications. Refer to Section
5.1 and Table 3 for use of Importance Factor.
2
Approved November 10, 1998 ANS1/SPRI ES-1-98
TABLE 1
IMPORTANCE FACTOR
CLASSIFICATION OF BUILDINGS AND OTHER STRUCTURES
FOR WIND, SNOW, AND EARTHQUAKE LOADS :
’ * rux. a j _-u– ~ -n —- _->t-_ 1 V .k— Sar – ‘k_ Xi * J: . ■ ri J jk *
Nature of Occupancy Category
Buildings and other structures that represent a low hazard to I
human life in the event of failure including, but not limited to:
• Agricultural facilities
• Certain temporary facilities
• Minor storage facilities
All buildings and other structures except those listed In Categories I, III, IV II
Buildings and other structures that represent a substantial hazard to human III
life In the event of failure including, but not limited to:
• Buildings and other structures where more than 300 people congregate in one area
• Buildings and other structures with elementary school, secondary school, or day-care
facilities with capacity greater than 250
• Buildings and other structures with a capacity greater than 500 for colleges or
adult education facilities
• Health care facilities with a capacity of 50 or more resident patients but not having surgery
or emergency treatment facilities
• Jails and detention facilities
• Power generating stations and other public utility facilities not included in Category IV
• Buildings and other structures containing sufficient quantities of toxic or explosive
substances to be dangerous to the public if released
Buildings and other structures designated as essential facilities Including, but not limited to: IV
• Hospitals and other healthcare facilities having surgery or emergency treatment facilities
• Fire, rescue and police stations and emergency vehicle garages
• Designated earthquake, hurricane, or other emergency shelters
• Communications centers and other facilities required for emergency response
• Power generating stations and other public utility facilities required in an emergency
• Buildings and other structures having critical national defense functions
From ASCE 7/951
3 SYSTEM REQUIREMENTS
(See Commentary: 3)
3.1 NAILER SECURED SYSTEMS
The basic attachment of the nailer shall be suf¬
ficient to carry the design wind uplift load and
the load specified in Section 4.1. At outside
building corners regions8, nailer securement
shall be designed to carry a load two times the
basic nailer attachment design load. Wood
nailers shall be minimum thickness 1.5 inch (38
mm). For devices used to secure the roofing
(e.g., gravel stops), the nailer shall extend at
least 1/2 inch (13 mm) beyond the back edge
of the horizontal flange of the roof edge device.
The following fastener safety factors shall be
applied to design loading.
a See section 2.3 for definitions of corner regions.
3
ANSl/SPRI ES-1-98 Approved November 10, 1998
4 DESIGN OPTIONS (See Commentary: 4)
Table 2
Substrate Wind Load Safety Factor
Wood2 4.5
Masonry3 3.0
Steel4 1.9
The following minimum securement criteria ap¬
ply for edging systems. When building codes re¬
quire higher wind resistance, the designer shall
calculate and design for the required loads ac¬
cording to local building codes.
4.1 MEMBRANE ATTACHMENT
(See Commentary: 4.1)
Except for Built-Up or fully adhered modified bi¬
tumen roofing, the design of the perimeter at¬
tachment, when terminating the roofing system,
shall provide a minimum holding power of 100
pounds/foot (1 .46 kN/m) holding power. This
force shall be measured in a direction of 45 de¬
grees back onto the roof as tested according to
SPRI Test Method RE-1 (attached). Specifically
for mechanically attached membrane roofing
systems, the perimeter attachment loadings
shall be calculated based on the force required
to hold the roof system’s perimeter sheet in
place for the design wind speed. The fastener
spacing shall be adjusted and the edge detail
shall have sufficient strength to meet and resist
these loads.
4.2 WIND RESISTANCE OF EDGE FLASHING
(Gravelstop) (See Commentary: 4.2 & 4.3)
The vertical face of edge flashing shall be tested
according to SPRI Test RE-2 (attached). Test
results shall meet or exceed design wind pres¬
sures as calculated according to RE-2.
4.3 WIND RESISTANCE OF COPING
(See Commentary: 4.2 & 4.3)
Copings shall be tested according to SPRI Test
Method RE-3 (attached). Test results shall meet
or exceed horizontal and vertical design wind
pressures as calculated according to RE-3.
4.4 FASTENER SPACING
Fastener densities providing satisfactory results
in SPRI Tests RE-2 and RE-3 shall be increased
by a factor of two at corner regions (as defined
in Section 2.3.2) to allow for increased velocity
pressure in these regions.
5 DESIGN PROVISIONS (See Commentary: 5)
5.1 WIND DESIGN (See Commentary: 5.1)
The roof edge design pressure (P) shall be cal¬
culated using the formula
P = GCp x qz x I x kzt
in which:
P = Design Pressure,
GCP = Gust Factor times Pressure Coeffi¬
cient, hereafter referred to simply as
Pressure Coefficient,
qz = Velocity Pressure at building height, z
kzt = Topographic Factor (=1 .0 for flat
terrain, see ASCE 7-95, p. 20 for other
terrain) and
I = Importance Factor Multiplier.
The basic wind speed shall be determined from
Attachment I or the authority having jurisdiction.
Velocity Pressure, “qz” shall be obtained from
Table 4 corresponding to the appropriate Expo¬
sure (see Section 2.5) and the basic wind speed.
Where the design speed, adjusted for topo¬
graphic effects, exceeds 150 miles per hour (237
km/h) or when building height exceeds 150 feet
(45 m), velocity pressure shall be calculated
according to Equation 6-1 from ASCE 7-95.
The importance factor, “I”, shall be obtained us¬
ing Table 3:
ASCE 7-95 1 p. 17.
TABLE 3
IMPORTANCE FACTOR
Building Category Importance
(See Table 1 .Section 2.6 Factor
of this Design Standard) 1
1 0.87
II 1.00
III 1.15
IV 1.15
4
Approved November 10, 1998 ANSUSPRI ES-1-98
TABLE 4
Velocity Pressure (qz)
Exposure A
Exposure B
‘ – Building > \ -‘ “Maximum Wind Spe^;*^ 5<* A A A”;
Height s-85s – 90/XxTAIOD^A ^^50 ’ –
‘”’A ‘A mph \X‘ mph;/i mph mph mph . mph
0-60 ft Use Exposure “C”
>60 -80 ft 12 13 16 19 23 27 31 36
>80 – 100 ft 13 14 17 21 25 29 34 39
>100 – 125 ft 14 15 19 23 27 32 37 43
>125 – 150 ft 15 17 20 25 29 35 40 46
Exposure C
Building Maximum Wind Speed
Height 85 90 ,. 100 110 120 130 140 .150′
mph mph mph mph mph mph mph mph
0-60 ft Use 85% of Loads for Exposure “C”
>60 -80 ft 17 19 24 29 34 40 47 53
>80 -100 ft 18 20 25 31 36 43 50 57
>100 – 125 ft 19 22 27 33 39 46 53 61
>125 – 150 ft 21 23 28 34 41 48 56 64
Exposure D
Building Maximum Wind Speed
Height 85 90 100 110’ 120 130 140 150
mph mph mph mph mph mph mph mph
0-20 ft 17 19 23 28 33 39 45 52
>20 -40 ft 19 22 27 32 38 45 52 60
>40 – 60 ft 21 24 29 35 42 49 57 65
>60 – 80 ft 22 25 31 37 45 52 61 70
>80 – 100 ft 23 26 32 39 47 55 64 73
>100 -125 ft 25 28 34 41 49 57 67 76
>125 – 150 ft 25 29 35 43 51 60 69 79
Building Maximum Wind Speed
Height 85 90 100 110 120 130 140 . 150
mph mph mph – mph ■ mph . imph mph \ mph
0-60 ft Use Exposure “C”
>60 – 80 ft 25 29 35 43 51 60 69 79
>80 – 100 ft 27 30 37 44 53 62 72 83
>100 – 125 ft 28 31 38 46 55 64 75 86
>125 – 150 ft 28 32 39 48 57 67 77 89
5
ANSI/SPRI ES-1-98 Approved November 10, 1998
Tables
Pressure Coefficient-Gust
Factor Product, GCp
Buildings Buildings
60 feet high over
or less 60 feet high
Horizontal GCP (acting
outward from the
building face) -1.4 -1.8
Vertical GC„ (acting
upward at the
building edge) -1.8 -2.3
The Pressure Coefficient, “GCP” shall be obtained
from Table 5: (See Commentary 5.1 )
In Table 5, the negative sign (-) means that the
pressure is away from the building, tending to pull
materials up or off.
Roof edge designs shall pass tests RE-1 , RE-2 and
RE-3 as appropriate for the application: Edge de¬
vices designed to act as membrane terminations
shall pass SPRI Test RE-1 . Edge flashings and
other edge devices for which the exposed vertical
component area exceeds the ex-posed horizontal
component area (edge flashings, etc.) shall pass
SPRI Test RE-2.
Copings and other devices for which the exposed
horizontal area exceeds the exposed vertical area
shall pass SPRI Test RE-3. To allow for higher wind
loads at corners, double the fastening in the cor¬
ner region instead of testing corner assemblies
when the straight length assembly passes RE-3.
Exposed areas in the above requirements shall be
those elements upon which the wind forces act di¬
rectly.
5.2 METAL THICKNESS (See Commentary: 5.2)
Minimum gauges for exposed faces5 shall be de¬
termined from Table 6:
5.3 GALVANIC COMPATIBILITY AND
RESISTANCE (See Commentary: 5.3)
Metal edge devices (face, clip and fastener) shall
be of the same kind of metal, or shall be gal¬
vanically compatible metal pairs. Compatible
metal pairs shall be selected from the following
list:
Aluminum-Galvanized Steel
Aluminum-Stainless Steel
Copper-Stainless Steel
or other pairs that can be shown to provide sat¬
isfactory galvanic compatibility.
Copper shall not be used In combination
with steel, zinc or aluminum.
Fasteners shall be galvanically compatible with
the other roof edge system components.
5.4 APPLIANCES
Appliance attachments, such as lightning rods,
signs or antennae that penetrate the water seal,
induce a galvanic reaction or otherwise compro¬
mise the effectiveness of the roof edge system,
shall be eliminated or isolated to prevent prob¬
lems.
TABLES
Minimum Metal Thicknesses for Flatness
Exposed Face Galvanized Steel Cold Rolled Copper Formed Aluminum
Up to 4“
(to 100 mm)
26 ga
(0.022″ 0.6 mm)
16 oz
(0.022″ 0.6 mm)
0.040″
0.8 mm
>4″ -8″
(>100-200 mm)
24 ga
(0.028″ 0.7 mm)
16 oz
(0.022″ 0.6 mm)
0.050″
1.3 mm
>8″ -10″
(>200 – 250 mm)
22 ga
(0.034″ 0.9 mm)
20 oz
(0.027″ 0.7 mm)
0.063″
1.6 mm
>10″ -16″
(>250 – 400 mm)
20 ga
(0.040″ 1.0 mm)
‘■ 0.080″
2.8 mm
6
Approved November 10, 1998 ANSI/SPRI ES-1-98
7
ANSI/SPRI ES-1-98 Approved November 10, 1998
SPRITest Method RE-1
Test for Roof Edge Termination of
BALLASTED OR MECHANICALLY ATTACHED
ROOFING MEMBRANE SYSTEMS
(See Commentary: SPRI Test Method RE-1)
The termination shall withstand a minimum force of
100 Ibs/ft (134 kg/m) according to Section 4.1 of
the Standard when tested using the following
method.
A minimum 12 inch (300 mm) wide mock-up of the
termination system shall be constructed and
mounted on the base of a tensile testing device so
the membrane is pulled at a 45° angle to the roof
deck to simulate a billowing membrane (see Fig¬
ure 3). For devices in which fasteners are part of
the membrane securement, at least two such fas¬
teners shall be included in a balanced sample.
The jaws of the tester shall be connected to two
bars that clamp the membrane securely between
them so that the load is distributed uniformly along
the width of the membrane (see Figure 3). The
tester is loaded until failure occurs. Failure is de¬
fined as any event that allows the membrane to
come free of the edge termination or the termina¬
tion to come free of its mount. The roof edge ter¬
mination strength is deemed satisfactory if the test
force at failure on a 12 inch (300 mm) wide sample
meets or exceeds 100 pounds per foot (1 50 kg/m).
8
Approved November 10, 1998 ANSI/SPRI ES-1-98
SPRI Test Method RE-2
Pull-Off Test for Edge flashings
(See Commentary: SPRI Test Method RE-2)
1. Apparatus
The description of the apparatus is general in
nature. Any equipment capable of performing
the test procedure within the allowed tolerances
shall be permitted. A schematic drawing of this
apparatus is shown in Figure 4. The test appa¬
ratus shall be constructed so that the perfor¬
mance of individual components is unaffected by
edge or end constraints on the test sample.
2. Safety Precautions
Proper precautions shall be taken to protect the
operating personnel and observers in case of
any failure.
4. Procedure
4.1 Gravity
Any undue influence from gravity that does not
occur during actual installation shall be omitted
from the test specimen. If the test specimen is
inverted, a gravity correction shall be made in
the determination of the allowable superimposed
loading. Tests run in an inverted position shall
include data from pressure reversal or an upright
specimen to show that unlatching at the drip
edges will not occur in the normal orientation.
4.2 Stabilization
Fascia Blow-Off Test Set Schematic
(Force at Failure x Face Area =
Blowoff Resistance)
Fascia
Figure 4: Fascia Test Schematic
3. Test Specimens
All parts of the test specimen shall be full size
in width and all other dimensions, using the
same materials, details and methods of con¬
struction and anchoring devices (such as clips
or cleats) as used on the actual building.
Sample length shall be the average length de¬
signed for field use on the project with a mini¬
mum of 8 feet (2.4 m). When the longest length
designed for the project is less than 8 feet
(2.4 m) the longest design length shall be used.
When the anchoring means at the ends of the
edge flashing are normally used to restrain other
additional lengths of edge flashing, then the an¬
choring means shall be modified so that only
that percentage that might restrain rotational
movement in the test specimen is used.
A dial gauge shall be attached to the centerline
of each loaded surface to detect movement.
Stabilization of the test shall be when the gauge
ceases to show movement.
4.3 Loading
Loading shall be applied uniformly on centers no
greater than 12″ (300 mm) to the vertical face
of the edge flashing. Loading shall be applied
on the horizontal centerline of the face. Loads
shall be applied incrementally and held for not
less than 60 seconds after stabilization has been
achieved at each incremental load. Between
incremental loads, the loading shall be reduced
to zero until the specimen stabilizes, or for five
minutes, whichever happens first. After a recov¬
ery period of not more than five minutes at zero
load, initiate the next higher incremental load.
Loading to the face of the edge flashing shall
be applied in increments not to exceed 25 Ib/sq.
ft. (120 kg/m2) until approximately 60 Ib/sq. ft.
(300 kg/m2) is obtained. Thereafter, increments
of load shall not exceed 10 Ib/sq. ft. (5 kg/m2).
Loading speed shall be such that each incre¬
mental load up to and including 60 Ib/sq. ft. (300
kg/m2) shall be achieved in 60 seconds or less.
Above 60 Ib/sq. ft. (300 kg/m2), incremental load¬
ing shall be aohieved in 120 seconds or less.
Loading shall proceed as indicated until the test
specimen either fails or exceeds the required
design pressure. The increments of load appli¬
cation shall be chosen so that a sufficient num¬
ber of observations are made to determine the
exact load at failure. The last sustained 60-second
load without failure is the maximum load
recorded as the design value.
9
ANSl/SPRI ES-1-98 Approved November 10, 1998
4.4 Failure:
Failure shall be loss of securement of any com¬
ponent of the roof edge system.
4.5 Test Results
The total force at the conditions described in 4.3
above shall be recorded. This force shall be
converted to pressure by dividing the force by
the area of the face: Force is measured in
Pounds
Outward Force
Pressure = – — –
Face Height x Face Length
Force, Length is the test sample length in feet,
Height is in Feet (inches/12), Pressure is in
Pounds per Square Foot. If test results exceed
the design outward wind pressure, the edge
flashing has acceptable wind blow-off resis¬
tance.
SPRITest Method RE-3
Pull-Off Test for Copings
(See Commentary: SPRI Test Method RE-3)
1. Apparatus
This description of the apparatus is general in
nature. Any equipment capable of performing
the test procedure within the allowed tolerances
shall be permitted. A schematic drawing of this
apparatus is shown in Figures 5 and 6. The test
apparatus shall be constructed so that the per¬
formance of individual components is unaffected
by edge or end constraints on the test sample.
Figure 5: Coping Bi-Directional Test
Schematic: Top and Face Leg.
2. Safety Precautions
Proper precautions shall be taken to protect the
operating personnel and observers in case of
any failure.
3. Test Specimens
All parts of the test specimen shall be full size
in width and all other dimensions, using the
same materials, details and methods of con¬
struction and anchoring devices (such as clips
or cleats) as used on the actual building.
Sample length shall be the average length de¬
signed for field use on the project with a mini¬
mum of 8 feet (2.4 m). When the longest length
designed for the project is less than 8 feet
(2.4 m) the longest design length shall be used.
When the anchoring means at the ends of the
edge flashing are normally used to restrain other
additional lengths of edge flashing, then the an¬
choring means shall be modified so that only
that percentage that might restrain rotational
movement in the test specimen is used.
4. Procedure
4.1 Gravity
Any undue influence from gravity that does not
occur during actual installation shall be omitted
from the test specimen. If the test specimen is
inverted, a gravity correction shall be made in
the determination of the allowable superimposed
loading. Tests run in an inverted position shall
include data from pressure reversal or an upright
specimen to show that unlatching of the drip
edges at the cleats will not occur in the normal
orientation.
4.2 Stabilization
A dial gauge shall be attached to the centerline
of each loaded surface to detect movement.
Stabilization of the test shall be when the gauge
ceases to show movement.
10
Approved November 10, 1998 ANSI/SPRI ES-1-98
4.3 Loading
Face and top loadings shall be applied simulta¬
neously in the ratio of (Face Height x Horizon¬
tal Cp) to (Top Width x Vertical Cp) in which the
Face Height is the height of the face (front or
back leg) being tested. Loading shall be applied
uniformly on centers no greater than 12″ (300
mm) to the top of the coping and to one of the
faces of the coping at the same time. Loads
shall be applied on parallel horizontal centerlines
of the surfaces tested. Loads shall be applied
incrementally and held for not less than 60 sec¬
onds after stabilization has been achieved at
each incremental load. Between incremental
loads, the loading shall be reduced to zero until
the specimen stabilizes, or for five minutes,
whichever happens first. After a recovery pe¬
riod of not more than five minutes at zero load,
initiate the next higher incremental load. Load¬
ing to the top of the coping shall be applied in
Figure 6: Coping Bi-Directional Test
Schematic: Top and Back Leg.
increments not to exceed 25 Ib/sq. ft. (120 kg/
m2) until approximately 150 Ib/sq. ft. (730 kg/m2)
is obtained. Thereafter, increments of load shall
not exceed 10 Ib/sq. ft. (5 kg/m2). Loading speed
shall be such that each incremental load up to
and including 150 Ib/sq. ft. (730 kg/m2) shall be
achieved in 60 seconds or less. Above 150 lb/
sq. ft. (730 kg/m2), incremental loading shall be
achieved in 120 seconds or less.
Loading shall proceed as indicated until the test
specimen either fails or exceeds the required
design pressure. The increments of load appli¬
cation shall be chosen so that a sufficient num¬
ber of observations are made to determine the
exact load at failure. The last sustained 60-second
load without failure is the maximum load
recorded as the design value.
Both face and back legs shall be tested in this
manner. Separate test samples shall be used
for testing the face and back legs: One sample
to test the face while loading the top (See Fig¬
ure 5), and the other to test the back leg while
loading the top (See Figure 6).
4.4 Failure
Failure shall be loss of securement of any com¬
ponent of the roof edge system.
4.5 Test Results
The total of upward and outward forces at the
conditions described in 4.3 above shall be re¬
corded. Each total force shall be converted to
pressure by dividing the force by the area of the
surface upon which it acts:
Outward Pressure =
Outward Force
Face Height x Face Length
Upward Pressure =
Upward Force
Coping Width x Coping Length
Pressure is measured in pounds per square foot,
• Force is measured in Pounds Force,
• Length is the test sample length in feet,
• Height is in Feet (inches/12).
• “Face” refers to back leg or front leg of the cop¬
ing specimen.
If the test results meet or exceed the design up¬
ward and outward wind pressures on both front and
back leg tests, the coping has acceptable wind
blow-off resistance.
11
ANSI/SPRI ES-1-98 Approved November 10, 1998
COMMENTARY to
WIND DESIGN STANDARD for EDGE SYSTEMS USED with
LOW SLOPE ROOFING
This Commentary consists of explanatory and
supplementary material designed to help design¬
ers, roofing contractors and local building authori¬
ties in applying the requirements of the preceding
Standard.
This Commentary is intended to create an under¬
standing of the requirements through brief expla¬
nations of the reasoning employed in arriving at
these requirements.
The sections of this Commentary are numbered to
correspond to sections of the Standard to which
they refer. Since having supplementary material for
every section of the Standard is not necessary, not
all sections are referenced in this Commentary.
1 INTRODUCTION
This Design Standard was developed for use
with Built-Up (BUR), Single-Ply and Modified Bi¬
tumen roofing systems. While the Standard is
intended as a reference for designers and roof¬
ing contractors, the design responsibility rests
with the “designer of record.”
Roof edge systems serve aesthetic as well as
performance functions for a building. Aestheti¬
cally, they provide an attractive finish and some¬
times even a key feature to the exterior of a
building. Of course, no matter how aesthetically
pleasing, a roof edge system must act primarily
as an effective mechanical termination and tran¬
sition between the roof and other building com¬
ponents such as parapet walls, vertical walls,
corners, soffits, edge flashing boards, etc.
A high performance roof edge system provides
many benefits. It acts as a water seal at the
edge. When it is also the means by which the
membrane is attached to the building at the
edge, it must also exhibit sufficient holding
power to prevent the membrane from pulling out
at the edge under design wind conditions. Fur¬
thermore, the edge system itself must not come
loose in a design wind. A loose edge system
not only endangers surrounding property or per¬
sons, but it also exposes the roofing to blow-off,
starting at the edge.
Perimeter systems considered for this Standard
are differentiated into two general types:
EDGE FLASHINGS: These are products or de¬
signs that complete the horizontal deck or mem¬
brane plane at its transition to a vertical wall
drop, typically at a 90° angle. Normally the roof¬
ing membrane is restrained by the edge by
means of a mechanical gripping of the roofing
between metal flanges or by a bond between the
roofing and edging.
Termination devices against vertical walls in¬
board of the roof edge are not considered by this
Guideline.
GUTTERS: Gutters and other rain-carrying de¬
vices are beyond the scope of this Standard.
However, the designer should be aware that
their securement is important to the proper func¬
tioning of the building.
Two general classes of materials cover nearly
all perimeter systems. They are:
EXTRUSIONS: Shapes or designs made by
forcing heated metal or polymeric material
through pre-cut custom dies. These designs are
usually of a heavier gauge than formed prod¬
ucts, but many extrusions must have their fin¬
ish applied after manufacturing.
FORMED METAL: Sheets of metal, usually
steel, aluminum or copper, bent on press brakes
or roll-forming equipment to match a desired de¬
sign or configuration. Available in many thick¬
nesses and frequently with a variety of finishes.
MAINTENANCE
The design engineer should consider maintenance
of the roof edge. See the ARMA/NRCA/SPRI Re¬
pair Manual for Low-Slope Roof Membrane Sys¬
tems6.
SUMMARY
This document addresses factors that should be
considered in the specification and design of roof
edge systems for low slope roofing systems. Good
design practice requires consideration of nailer, roof
edge and membrane securement, and also selec¬
tion of materials and finishes to minimize corrosion,
and metal gauges to assure strength and flatness.
12
COPINGS/CAPS: These are designs that cover
the tops of parapet walls, usually with the roof¬
ing membrane terminated under them.
Approved November 10, 1998 ANSI/SPRI ES-1-98
COMMENTARY
2 GENERAL DESIGN CONSIDERATIONS AND
DEFINITIONS
Determination of the appropriate wind force cat¬
egory shall be based on wind speed, Exposure,
building height, topography and the edge detail
location on the building. Location of the edge
detail on the building is also important, since
blow-off forces increase near the corners.
2.1 WIND SPEED
Special wind regions (mountains or valleys):
Refer to Section 6.5.5 of the ANSI/ASCE
7-951 Commentary.
The intensifying effects of topography (hills or
escarpments) are to be accounted for. Speedup
over hills and escarpments is accounted for in
ASCE 7-95 by means of a topographic factor,
k^ that depends on the height of the building,
the height and slope of the hill or escarpment,
the distance of the crest upwind of the building,
and whether the terrain is a hill or an escarp¬
ment.
2.3 CORNER REGION
The angle at which the walls meet to constitute
a corner is undefined here and in ASCE 7-95.
It has been suggested that an airflow separa¬
tion effect begins to take effect when walls meet
at 150°. Therefore, since most walls meet at
angles more acute than this, the meeting angle
in not a practical consideration for this Stan¬
dard7.
2.4 EDGE CONDITION
The roof edge may also function as an air seal,
when combined with an air-retarder throughout
the field of the roof, by preventing air infiltration
under the roofing membrane. To resist air infil¬
tration, nailers should be sealed to the building
with appropriate sealant materialb. Where mul¬
tiple courses of nailers are used, these nailer
courses should also be sealed to each other.
Butt-joints should also be sealed.
2.5 EXPOSURE
2.5.3 EXPOSURE C
Consistent with ASCE 7-95, the Standard uses
Exposure “C” for all buildings with heights 60 ft.
(18 m) or less. For building heights of 60 feet
or less in Exposure “B,” use 15% lower load than
for Exposure “C.”
2.6 IMPORTANCE FACTOR
The Importance Factor, I, accounts for the de¬
gree of hazard to human life and damage to
property. The Importance Factor, I, is used to
modify the wind speed and, in effect, assign dif¬
ferent levels of risk based upon intended use of
the structure. Category I Exposure gives a 25
year mean recurrence value while Categories III
and IV give 100 year mean recurrence values.
Other recurrence values can be found in the
Commentary of ASCE 7-951.
3 SYSTEM REQUIREMENTS
Resistance to blow-off depends not only upon
the attachment of the roof edge device to the
edge of the building, but also upon the integrity
of the nailer or other substrate to which the edge
device is attached. It is important to consider
the load path from the nailer to the foundation
of the building to assure proper wind load pro¬
tection.
Table?
Substrate
Safety Factor
Static Load Wind Load
Wood8 6.0 4.5
Masonry9 4.0 3.0
Steel 10 2.5 1.9
Common fastener safety factors follow. Note
that when designing for wind, static load safety
factors may be reduced by 25%.
WOOD MEMBERS
The terrain surrounding a building will influence
the exposure of that building to the wind.
Nailers should be pressure treated wood11 se¬
cured by corrosion resistant12 anchor bolts coun¬
tersunk into the wood nailer and attached to the
nailer with nuts and washers. Anchor bolts
should be of sufficient size and spacing to rebAn
appropriate sealant is a single or multi-component elastomeric material used to weatherproof construction joints.
13
ANSl/SPRI ES-1-98 Approved November 10, 1998
COMMENTARY
sist the design load and a minimum 200 Ibf/ft
(300 kg/m) vertical load. For wood nailers wider
than 6″ (152 mm), bolts should be staggered to
avoid splitting the wood. Each wood nailer
member should have at least two fasteners. A
fastener should be located approximately 4“
(100 mm) and minimum 3″ (75 mm) from each
end of the wood. Additional wood members,
such as edge flashings, cant strips and stacked
nailers should be fastened with corrosion resis¬
tant fasteners having sufficient pullout resis¬
tance. Fasteners should be staggered, spaced
at a maximum 12 inches (305 mm) on centers,
and should penetrate the wood sufficiently to
achieve design pullout resistance. Spacing
should be on maximum 6 inches (152 mm) cen¬
ters in corner regions0.
MASONRY
When imbedded in masonry, anchor bolts as de¬
fined above should be bent 90° at the base or
have heads designed to prevent rotation and
slipping out. When hollow block masonry is
used at the roof line, cores and voids in the top
row of blocks should be filled with concrete hav¬
ing a minimum density of 140 Ibs/cu ft (10,900
g/m3 ). When imbedded in light aggregate block,
bolts should be embedded minimum 12 inches
(300 mm) into concrete fill. When heavy aggre¬
gate blocks are used, bolts should be embed¬
ded minimum 8 inches (200 mm).
LIGHTWEIGHT CONCRETE AND
GYPSUM DECKS
Nailers should not be fastened to light weight
concrete or gypsum decks. Instead, anchor
nailers directly to wall structural members using
fasteners whose size and locations meet the
Standard under 3.1 above.
STEEL DECK
The steel deck should be designed to withstand
the design forces specified under 3.1. Nailer at¬
tachment should be strong enough to resist 200
Ibf/ft (300 kg/m) vertical load.
NAILERLESS SYSTEMS
When the roof edge is attached directly to ma¬
sonry or steel without the use of a nailer, its at¬
tachment configuration should be tested to re¬
sist wind loading, using tests specified in Sec¬
tion 4 of this Standard.
REROOFING
For nailer security when reroofing, the contrac¬
tor should check to be sure the nailer or other
substrate is in good condition and well secured
to the building. Questionable members should
be removed and replaced according to the
above guidelines. Note that it is much more dif¬
ficult to be sure that the load path (connection
of roof members ultimately to the building foun¬
dation) is secure for an existing building than it
is for new construction. The roofing contractor
should notify the designer if unexpected condi¬
tions or deteriorated substrate materials are dis¬
covered during the reroofing process.
4 DESIGN OPTIONS
Holding power of the edge detail is divided into
two considerations. The first is the resistance
of the edge to outward and upward forces that
tend to blow or peel the edge system off the
substrate. The second is the ability of the edge
to resist the pull of the roofing inwardly.
Edge details may be selected from manufactur¬
ers who certify certain minimum performance to
meet design requirements, based upon testing.
Other designs may be used, provided they are
tested and certified by an independent testing
laboratory to meet the wind and pullout resis¬
tance design standards suggested in this docu¬
ment.
4.1 MEMBRANE ATTACHMENT
The edge flashing may be the only restraint pre¬
venting a roof blow-off. In ballasted systems,
ballast may be scoured away from the edge.
Mechanically attached membranes may be at¬
tached only by the edge flashing at the building
edge. The 100 Ib/ft (1 .46 kN/m) may not be suf¬
ficient if there is a large amount of scour, expos¬
ing a wide span of roofing.
Consideration should be given to sealing the
edge against air infiltration. Air infiltration may
affect the loads on the roofing and the perim¬
eter edge detail 13 by adding a positive pressure
under the roofing, thus compounding the effect
of negative pressure above the roofing.
cSee section 2.3 of the standard for the definition of corner regions.
14
Approved November 10, 1998 ANSI/SPRI ES-1-98
COMMENTARY
4.2 & 4.3 WIND RESISTANCE OF EDGE
FLASHINGS & COPINGS
Although all edge devices are to be tested ac¬
cording to the tests outlined in the Standard and
its attachments, the following guidelines may be
used to establish designs for testing. The guide¬
lines may be modified to achieve desired test
results.
Edge flashings, copings and the like should be
secured with continuous cleats of 24 ga steel,
0.050 (2 mm) aluminum or metal of equivalent
strength at the bottom of the face edge. Cleats
should be secured with annular threaded or
screw-shank nails long enough to penetrate the
wood nailer at least 1-1/4″ (3 cm). Nail heads
should be at least 3/16″ (5 mm) in diameter.
Alternatively, cleats may be secured with mini¬
mum No. 8 (4 mm) screws long enough to pen¬
etrate the nailer 3/4″ (20 mm) or penetrate metal
3/8″ (10 mm). Where velocity pressures are less
than 45 Ibs/ft2 (220 kg/m2), cleat fasteners
should be placed no farther than 24* (600 mm)
apart. Where velocity pressures are greater
than 45 Ibs/ft2 (220 kg/m2) they should be
spaced 16″ (400 mm) or closer. Fastener fre¬
quency should be doubled in corner regions.
Nail heads should be larger than the narrowest
dimension of the slotted holes. Where velocity
pressures exceed 45 psf (220 kg/m2), add a
screw through the back section of the edge
flashing near the center of each section and at
the center of the joint cover. Edge flashing sec¬
tions should be spaced to allow for expansion
around this screw.
Metal coping should be secured by a cleat at the
wall exterior. Where velocity pressures exceed
45 psf (220 kg/m2), the coping should be se¬
cured on the inside with No. 10 (5 mm) galva¬
nized screw fasteners through neoprene wash¬
ers on 30″ (760 mm) or narrower centers. At
higher velocity pressures, the centers should be
20″ (500 mm) or narrower. Screws should be
long enough to penetrate the wood nailer at
least 1 “ (25 mm). The effects of thermal expan¬
sion should be considered. Screw holes in the
coping should be pre-punched or drilled oversize
to allow for thermal expansion if aluminum
thicker than .063″ (1 .6 mm) is used.
To ensure adequate holding, edge designs
should also include a drip edge that securely
engages the cleat. Inadequate securement may
lead to a release of the edge, resulting in the
ultimate failure of the roof edge device.
Fastener spacing is doubled in corner regions
to account for the increased wind forces in these
regions.
5 DESIGN PROVISIONS
5.1 WIND RESISTANCE
TABLE 4 values have been calculated using
Equation 6-1 from Section 6.5.1 of ASCE 7-951,
for 1=1.0 and ^=1.0:
cu = 0.00256 x Kz x Kzt x V2 x I
in which:
ch = Velocity Pressure (the Velocity Pres¬
sures shown in Table 4 of this Standard
is actually “q/r as defined in ASCE 7-
95 and therefore are to be multiplied by
“I” to obtain qz),
Kz = Velocity Pressure Exposure Coefficient
from Equation C-3 in the Commentary
Section of ASCE 7-95 (Also shown as
Table 6-3 in ASCE 7-95),
= Topographical factor for buildings built
on hills or escarpments (from Equation
6-2 of ASCE 7-95),
V = Basic Wind Speed, mph, from Attach¬
ment I of this Standard and
I = Importance factor defined in Table 3.
Velocity Pressure “ch” is the pressure imparted
by the energy of the wind. In practice, aerody¬
namics will cause actual wind pressures to dif¬
fer from theoretical values at certain locations
on the building. A building with a flat, level (or
slightly sloped) roof will experience greater
forces at the corners and eaves than on interior
roof surfaces because of eddy effects at the
eaves. These effects are accounted for by us¬
ing the products of Pressure Coefficient and
Gust Factor, GCP obtained from Table 5 (Sec¬
tion 5.1) which is taken from ASCE 7-951, Fig¬
ures 6-5 and 6-8, assuming an “effective wind
area” of 10 square feet or less. The vertical
component was taken from the values for Sur¬
face 2 on those Figures. ASCE-7-95 does not
address the horizontal component of GCP at the
roof edge. Therefore, the horizontal value of
GCP was taken from the values for Surface 5,
which is the vertical corner region. That surface
15
ANSI/SPRI ES-1-98 Approved November 10, 1998
was selected because it presents nearly the
same geometry to the wind as would the roof
edge.
ASCE 7-95 suggests different pressure coeffi¬
cients in corner regions. Instead of using ASCE
7-95 pressure coefficients for corner regions in
this Standard, the design method was simplified
by requiring doubled fastening in these regions.
5.2 METAL THICKNESS
Increased metal thickness improves the flatness
reduces the “oil-can” effect of the roof edge
metal. The required minimums do not address
other important design factors such as fasten¬
ing pattern and frequency, continuous or inter¬
mittent cieating, stiffening ribs or brakes in the
edges. Metal thickness may need to be in¬
creased for higher wind areas unless Tests RE-
2 or RE-3 have been performed.
5.3 GALVANIC COMPATIBILITY AND
RESISTANCE
Corrosion and strength should be considered in
the choice of materials. This Standard focuses
primarily on metal edge systems. When plastic
materials are used, corrosion is not usually a
factor (although environmental deterioration
must be considered), however, strength of the
materials must be considered.
Corrosive potential can be roughly predicted by
knowing the placement of the two metals in the
Galvanic Series. The farther apart the metals
are in the Galvanic Series, the greater is this
potential for corrosion. Metals adjacent to each
other in the Series have little potential for cor¬
rosion. In the following list (Galvanic Series), the
metals high on the list are potentially corroded
while those low on this list are protected. Fre¬
quently, the corrosion rate of “sacrificed” metals
will be low, even if there is a potential for corro¬
sion. Thus there will generally be little corrosion
between metals that are close to each other on
the list, however, when they are in contact, the
lower of a pair will be protected by the higher
even if no perceptible corrosion is taking place.
For this reason, steel, being lower on the list
than zinc will be protected by the zinc, which is
“sacrificed” to save the steel. Fortunately,
though there is a potential for corrosion between
zinc and steel, under most conditions, the rate
of corrosion is minuscule so that the zinc lasts
many years while electrolytically protecting the
steel.
Similarly, pairs of metals such as aluminum and
zinc or aluminum and stainless steel will show
no perceptible corrosion between them, because
of their proximity to each other on the list. On
the other hand, pairing copper with zinc or alu¬
minum or even steel must be avoided because
copper is far from them on the Galvanic Series
and the potential for corrosion is great.
In extremely corrosive environments such as salt
water environments, chemical plants or paper
mills, corrosion resistant materials such as stain¬
less steel shall be used.
Table 8
Galvanic Series14
Anodic or Least Noble (Corroded End)
Magnesium
Zinc
Aluminum
Cadmium
Steel
Stainless Steel
Lead
Tin
Copper
Titanium
Silver
Gold
Cathodic or Most Noble (Protected End)
TEST METHOD RE-1
The method with which the edge of the roofing
membrane is terminated (edge flashing, nailer,
or other) is the last anchor point to hold the
membrane in place should the membrane hap¬
pen to separate from the roof deck during a high
wind. When this happens, the roof system will
put a load on the termination. Therefore, the
termination must withstand a minimum force of
100 Ibs/ft (134 kg/m) when tested using the
method. This value has been adopted from the
ANSI RP-4 Standard.
This is a new procedure. The precision and bias
of the test measure has not been determined.
16
Approved November 10, 1998 ANSI/SPRI ES-1-98
TEST METHODS RE-2 and RE-3
4.2 Stabilization
Stabilization is necessary during loading to in¬
sure that the specimen has reached equilibrium
before considering a sustained load for a period
of 60 seconds. As the specimen approaches its
ultimate capacity, stabilization of the specimen
will generally take longer to achieve.
4.3 Loading
These test methods consist of applying loads on
surfaces of a test specimen and observing de¬
formations and the nature of any failures of prin¬
cipal or critical elements of the coping or edge
flashing system profiles or members of the an¬
chor systems. Loads are applied to simulate the
static wind loading of the members. Test RE-2,
for edge flashings, requires loads on only the
vertical face since the uplift wind loading on a
edge flashing member is considered to be neg¬
ligible. Since corners are difficult to test with
these methods, corner areas are best handled
by designing a device to pass RE-2 or RE-3 as
appropriate and doubling the number of fasten¬
ers in corner regions.
A recovery period between increases in incre¬
mental loading is allowed for the test specimen
to attempt to assume its original shape prior to
applying the next load level.
The rate of loading can be a critical issue when
specimens are subjected to continuously in¬
creasing load until failure is achieved. Loading
rate has little meaning in RE-2 and RE-3 be¬
cause these methods employ incrementally in¬
creased loads sustained for relatively long times
followed by brief recovery periods. This incre¬
mental method is more stringent than continu¬
ous loading because of the requirement of hold¬
ing a load for 60 seconds.
The Standard requires full length specimens be¬
cause end conditions of discreet sections of
copings and edge flashings can play a profound
role in the failure mode of the materials. Fur¬
thermore, those products having noncontinuous
cieating can exhibit different performance under
testing than in the field if the cleats do not act
upon the products as they would in the field. For
example, if a product requiring two cleats in a
144 inch (5669 mm) length were tested as a
36″ (914 mm) sample with one cleat, the cleat
would act over a larger percent of the product
than would be experienced in the field, render¬
ing the results difficult to translate to the field.
These are new procedures. The precision and
bias of these test measures have not been de¬
termined.
4.4 Failure
Some examples of “component failure that will
not enable the edge flashing to perform as de¬
signed” would be:
• Full nail pull-out at some point
• Collapse of a cleat, fascia or cover
• Disengagement of a face or coping at the
drip-edge
5.2 Metal Thickness
Table 6 was developed from NRCA and Factory
Mutual recommendations. The table has been
constructed to simplify its use over the Factory
Mutual table and to extend the range of fascia
widths beyond that given by NRCA.
EXAMPLE
Consider a 95 foot (30 m) high suburban confer¬
ence-type hotel building in Suburban Atlanta. At¬
tachment I is a map showing basic wind speeds for
most of the United States.
Basic Wind Speed from the Map is 90 mph.
The “Exposure” for such a building according to the
definitions given on Page 3 of the Design Standard
is Exposure “C.” Consulting Table 4 for Exposure
“C,” at 90 mph, the velocity pressure, qz, for a 95
foot structure at 90 mph is 26 pounds per square
foot (psf).
Velocity Pressure = 26 psf
The Importance Factor (see Table 1 and Table 3)
would be that of a Category II building (occupancy
by more than 300 people in one room). The im¬
portance factor I, is 1.15 for this building.
Importance Factor Multiplier (I) = 1.15
Velocity Pressure is multiplied by the Importance
Factor Multiplier to obtain an Adjusted Velocity
Pressure:
Adjusted Velocity Pressure =
26 x 1.15 = 30 psf
Using a Pressure Coefficient (GCp) from Table 5 of
-2.3 for the vertical direction and -1 .8 horizontally,
the following design force is calculated:
Vertical Design Pressure:
-2.3 x 30 Ib/sq. ft. = -69 Ib/sq. ft
17
ANSl/SPRI ES-1-98 Approved November 10, 1998
Horizontal Design Pressure:
-1.8 X 30 Ib/sq. ft. = -54 Ib/sq. ft
In this case, a coping must be tested to withstand
54 psf (Ib/sq. ft.) outward force and 69 psf uplift
force.
If the cooing had 4″ legs and a cap width of 18
inches, the cap would be required to withstand an
upward force of:
1.5 sq. ft/ft x 69 Ib/sq. ft. = 104 Ib/ft
and outward forces of:
.33 sq. ft./ft x 54 Ib/sq. ft. = 18 Ib/ft
on each face.
The coping is to be tested according to SPRI Test
RE-3 run on straight lengths. Doubling fasteners
in the comer region will be sufficient instead of test¬
ing corner assemblies if the straight length assem¬
bly passes RE-3. Note that in testing the edge de¬
vice, upward forces and outward forces on a face
are to be applied simultaneously and both face leg
and back leg tests are to be run.
If the perimeter were an edge flashing instead of a
coping, it would need to withstand an outward de¬
sign force of 54 psf.
If the edge flashing had a 6“ (0.5 sq. ft./ft) face, the
design resistance would need to be
0.5 sq. ft ./ft x 54 Ib/sq. ft = 27 Ib/ft.
The edge flashing is to be tested according to SPRI
Test RE-2 run on straight lengths. Doubling fas¬
teners in the corner region will be sufficient instead
of testing corner assemblies if the straight length
assembly passes RE-2. Furthermore, the edge
flashing must be tested according to SPRI Test RE-
1 to restrain a 45° pull of 100 pounds per foot if it
is the termination of Single-Ply or Modified Bitumen
Membrane.
A roof edge may be designed and tested to meet
the above criteria, or one may be selected that has
been previously certified to meet the minimum de¬
sign requirements of this Standard.
18
Approved November 10, 1998 ANSl/SPRI ES-1-98
REFERENCES
1. Minimum Design Loads for Buildings and
Other Structures, ASCE 7-95, American So¬
ciety of Civil Engineers, New York, 1996.
2. National Design Specifications for Wood Con¬
struction, NFPA, Washington, 1991.
3. Drilling and Anchoring Systems Design
Manual, Rawlplug Company, Mississauga,
ON.
4. Cold formed Steel Manual, AISI, 1986.
5. Adapted from NRCA Roofing and Waterproof¬
ing Manual, National Roofing Contractors As¬
sociation, Rosemont, IL, 1996, and Loss Pre¬
vention Data Sheet 1-49, Factory Mutual Re¬
search Corporation, Nonwood, MA. 1985.
6. Repair Manual for Low-Slope Roof Membrane
Systems. ARMA/NRCA/SPRI, 1997.
7. James R. McDonald, Texas Tech University,
Private communication with John Hickman,
August, 1997.
8. National Design Specifications for Wood Con¬
struction, NFPA, Washington, 1991.
9. Drilling and Anchoring Systems Design
Manual, Rawlplug Company, Mississauga,
ON.
10. Cold formed Steel Manual, AISI, 1986.
11. Standard C15-96 Wood for Commercial-Resi¬
dential Construction, Preservative Treatment,
American Wood-Preservers Association,
Granbury, TX, 1996
12. Procedure for Evaluation of Corrosion Resis¬
tance of Steel Fasteners, SPRI, Needham MA,
1988.
13. A Guide to Achieve the Secured Single Ply,
Technical Note No. 20, Dow Chemical Com¬
pany, Granville, Ohio, 1986.
14. Perry ed. Chemical Engineers Handbook,
McGraw-Hill, New York, 1963. Table 23-1.
An American National Standard implies a consensus of those substantially concerned with its scope and provisions. An
American National Standard is intended as a guide to aid the manufacturer, the consumer, and the general public. The
existence of an American National Standard does not in any respect preclude anyone, whether he has approved the stan¬
dard or not, from manufacturing, marketing, purchasing or using products, processes, or procedures not conforming to the
standard. American National Standards are subject to periodic review and users are cautioned to obtain the latest edi¬
tions.
The American National Standards Institute does not develop standards and will in no circumstances give an interpretation
of any American National Standard. Moreover, no person shall have the right or authority to issue an interpretation of an
American National Standard in the name of the American National Standards Institute.
CAUTION NOTICE: This American National Standard may be revised or withdrawn at any time. The procedures of the
American National Standards Institute require that action be taken to reaffirm, revise or withdraw this standard no later
than five years from the date of approval. Purchasers of American National Standards may receive current information on
all standards by calling or writing the American National Standards Institute
19