Skip to main content Skip to footer

Cladding and Building Enclosure Component Connections through Foam Plastic Continuous Insulation: Design and Prescriptive Code Compliance

March 20, 2021

IIBEC Interface October 2022
Continuous insulation provides
a means to comply with modern
energy conservation codes
and can provide various other
building code–required functions
for building enclosures.
Continuous insulation is defined as follows in
the International Energy Conservation Code
(IECC)1 and ASHRAE Standard 90.1:2
Continuous insulation (c.i.): insulation
that is uncompressed and continuous
across all structural members
without thermal bridges other than
fasteners and service openings. It is
installed on the interior or exterior
or is integral to any opaque surface
of the building enclosure.
This definition allows some limited thermal
discontinuity to occur for fasteners attaching
components such as the c.i. material, cladding,
fenestration, and even structural ledgers placed
on the surface of a c.i. to avoid major thermal
discontinuities (such as thermal bridging). Even
so, the amount or size of these fasteners should
be specified to minimize their cumulative effect
as relatively small and repetitive point thermal
bridges.3 But these fasteners must also be able
to adequately transfer the weight of cladding,
furring, fenestration, or structural loads from
ledgers that are surface mounted and attached
over a layer of c.i. These two competing design
objectives should be optimized and the content
of this article provides guidance for that purpose.
BACKGROUND
The use of only fasteners to attach cladding
and other exterior architectural or structural
building components through a layer of c.i. is
not without its challenges. First, the c.i. material
must have sufficient compressive resistance
or rigidity to resist fastener draw-down forces
during installation and shear-transfer reaction
forces that may cause compression during
service. For example, if an exterior insulation
material is not sufficiently rigid (that is, it has
low resistance to compressive deformation),
it will tend to compress due to these connection
forces. In such cases, the code definition
for continuous insulation will not be satisfied
because the thermal performance of the insulation
layer is altered (that is, not continuous in
thickness or R-value).
A common example of this compression
condition occurs when metal roofing and siding
panels are installed over blanket insulation
that is placed over purlins and girts in metal
building construction. Consequently, other
means of attachment or support of cladding
and exterior building components through a
layer of compressible exterior insulation may
become necessary to avoid compression, such
as the use of steel shear tabs, metal Z-furring
projecting through the exterior insulation layer,
or specialty thermal break support devices.
Because these attachment methods use elements
that are not fasteners as required by the
definition of continuous insulation (and can
be substantial thermal bridges), the exterior
insulation and cladding support method would
not comply with the energy code’s definition of
and prescriptive R-values for c.i., even though
it solves the compression problem.
These practical difficulties do not mean that
such applications do not have thermal value.
They simply mean that the previously mentioned
application conditions do not permit the exterior
insulation to be considered as c.i. as defined
and intended by energy codes and standards.
They also mean that energy code compliance
and thermal performance for such assemblies
must be demonstrated by use of an assembly
U-factor analysis (including the impact of thermal
transmission through the cladding support
devices penetrating the exterior insulation layer
or compression that occurs at through-fastened
exterior components). For example, Appendix A
of ASHRAE 90.12 provides tabulated U-factors
for masonry walls where masonry veneer ties are
penetrating a layer of exterior c.i., such as foam
plastic insulating sheathing c.i. (FPIS c.i.). As
addressed later in this article, it also is possible
to place a conventional metal brick tie onto the
surface of FPIS c.i. where only the tie fastener
penetrates the FPIS c.i., such that compliance
with the c.i. definition is maintained without
having to determine a U-factor for energy code
compliance. There are also a number of proprietary
brick ties designed for this application with
an “offset” connection to the structure to allow
for a thickness of FPIS c.i.
As a means to avoid the above practical and
energy-code-compliance difficulties or inefficiencies,
this article focuses on designing
fastener connections through c.i. of rigid foam
Cladding and Building
Enclosure Component
Connections through Foam
Plastic Continuous Insulation:
Design and Prescriptive Code Compliance
By Jay Crandell, PE
This paper was originally presented at the 2021 IIBEC International Convention and Trade Show.
October 2022 IIBEC Interface • 17
plastics, particularly FPIS. These
products include expanded polystyrene
(EPS), extruded polystyrene
(XPS), and polyisocyanurate
(PIR). Important to the topic of
this article, FPIS is available in
a wide range of compressive
strengths (for example, 10 psi to
100 psi or more) and is capable
of supporting significant structural
loads of various types. For
example, FPIS can be specified
to support building foundation
loads with design compressive
loads of up to 3000 psf or more,
even including a safety factor of
3 to 5 applied to the material’s
nominal compressive strength to
control deformation and creep.
The conservatism of the safety
factor generally depends on load duration (for
example, sustained dead versus transient live
or snow loads) and duty cycle (for example, lift
truck loads versus column loads on a structural
concrete slab with underlying FPIS insulation for
a refrigerated warehouse). Consequently, with
proper design and specification, FPIS materials
are capable of providing a rigid exterior c.i. layer
through which cladding and building component
attachments can be made to the underlying
structure using only fasteners. Thus, compression
deformation becomes negligible and fasteners
can be used for exterior building component
attachments so that the FPIS complies with the
code definition for continuous insulation and
can satisfy the required R-values for c.i.
Code-compliant FPIS products are manufactured
in accordance with ASTM C5784 and
ASTM C1289.5 These standards provide a foundation
for complying with various building code
and energy code provisions governing the use
of FPIS in residential and commercial building
construction.1,2,6,7 In particular, these ASTM
standards provide a basis for specifying types
of FPIS materials on the basis of compressive
resistance properties.
FPIS materials are water resistant and have
relatively high R-values per inch ranging from
about R-4 per inch to more than R-6 per inch.
For this reason, FPIS products are often used as
c.i. for building foundations, walls, floors, and
roofs as a means to comply with modern energy
conservation codes and standards. Because of
the relatively high R-value per inch, they also
minimize the thickness of c.i. required to meet
energy code requirements and this also helps
with designing and specifying cladding and
building component attachments through FPIS
(as will become evident later in this article). In
addition, FPIS products can provide several
building enclosure functions beyond just c.i.
when they are properly integrated with a building
enclosure assembly, including water-resistive
barrier, air barrier, and water-vapor control.
These various applications and functions of
FPIS, including other code-compliance considerations
such as fire safety and wind resistance,
have been addressed in greater detail in two prior
IIBEC conference papers and presentations.8,9
For additional information on these matters,
including technical guidance, design resources,
research, and code-compliance listings, refer to
https://www.continuousinsulation.org.
Two common wall assembly applications
with c.i. are shown in Fig. 1. One is considered
a “hybrid” wall with a combination of exterior
FPIS c.i. and cavity insulation. The other uses
exterior c.i. only and is known as the “perfect
wall” because it maximizes the protection of the
structure from thermal and moisture cycling
by substantially decoupling it from the exterior
environment. As mentioned, FPIS can serve
multiple “control layer” functions when used in
either of these assembly approaches. In both of
these approaches, cladding, furring, and other
structural or architectural building components
are ideally placed on the surface of the rigid foam
sheathing insulation and attached through it
with an appropriate fastener schedule to minimize
thermal-bridging effects and maintain
compliance with the energy code’s definition
of continuous insulation.
For support of gravity loads, such as those
caused by the weight of cladding or structural
live and dead loads on a roof or deck ledger, the
fasteners through the FPIS layer to the primary
structural system must provide sufficient shear
capacity and stiffness. As a bonus, the use of
stainless steel fasteners can add durability to
exterior component connections through FPIS
while also reducing heat transfer through the
fasteners (stainless steel has about one-third the
thermal conductivity of a regular carbon steel
fastener).
CLADDING AND BUILDING
COMPONENT CONNECTIONS
THROUGH FPIS
Regardless of the number of functions that
FPIS c.i. may be used to provide for a given building
enclosure assembly, one thing is certain:
exterior wall coverings and even structural
building components must be fastened or supported
through it to the underlying structure.
The remainder of this article focuses on how to
properly attach such components through FPIS
to the underlying structure while minimizing
thermal bridging and maintaining conformity
with the energy code’s definition of continuous
insulation. The following two approaches to code
compliance are addressed:
1. Prescriptive requirements for cladding and
furring connections through FPIS to wood,
cold-formed steel framing, or wood structural
panels (WSPs).
2. Engineering design procedures for various
types of building component connections
through FPIS to the structural frame or substrate.
The technical basis of the prescriptive
solutions and design procedures that follow
is described in Applied Building Technology
Group research report no. 1503-02, “Attachment
of Exterior Wall Coverings Through Foam
Plastic Insulating Sheathing (FPIS) to Wood
or Steel Wall Framing.”10 That report and the
data and references described therein serve as
Figure 1. Example wall assemblies with continuous insulation.
Source: Reproduced by permission from Applied Building Technology Group (ABTG), “Model Moisture Control
Guidelines for Light-Frame Walls: A Building Code Supplement for Builders, Designers, and Building Officials,” 2017,
http://www.appliedbuildingtech.com/rr/1701-01; and J. H. Crandell, “Assessment of Hygrothermal Performance
and Design Guidance for Modern Light-Frame Wall Assemblies,” in Advances in Hygrothermal Performance of
Building Envelopes: Materials, Systems and Simulations, ed. P. Mukhopadhyaya and D. Fisler. West Conshohocken,
PA: ASTM International, 2017, 362—394, http://dx.doi.org/10.1520/STP159920160097. Note: AB = air barrier;
FPIS = foam plastic insulating sheathing; VR = vapor retarder; WRB = water-resistive barrier.
18 • IIBEC Interface October 2022
the basis for prescriptive cladding attachment
provisions found in the International Building
Code6 (IBC) and the International Residential
Code7 (IRC). Refer to 2021 IBC Sections 2603.12
and 2603.13 and 2021 IRC Sections R703.15
and R703.16. These prescriptive cladding and
furring attachment requirements have been
included in the IBC and IRC since the 2012
editions. In addition, Table R703.3.3 of the 2021
IRC provides for attachment of lightweight cladding
through up to 2-in.-thick FPIS to minimum
7/16-in.-thick WSP sheathing; thus, it does not
require fastening to studs for this limited condition.
Alternatively, such connections directly
to WSP installed over a layer of FPIS c.i. also
are permissible, but placing WSP over FPIS c.i.
must consider the impact to shear wall bracing
capacity of the WSP (as done for some proprietary
sheathing panels with FPIS c.i. laminated
to the interior side rather than the exterior side
of a structural panel).
Prescriptive Cladding and
Furring Attachment through FPIS
Several important general requirements for
use of the codified prescriptive cladding and
furring attachments through FPIS are addressed
in this article:
1. All of the codified prescriptive provisions
are engineered to work with and require use
of minimum 15 psi compressive resistance
FPIS as specified in accordance with ASTM
C578 or ASTM C1289. They address FPIS
thicknesses up to 4 in., depending on the
fastening schedule and cladding weight.
2. The provisions address support of cladding
weight by a fastener transferring shear through
a layer of FPIS to the structure. Therefore,
these provisions are intended to supplement
fastening requirements for each type of cladding
found in the code or the specific cladding
manufacturer’s installation instructions
(unless those instructions specifically address
installation over FPIS). The more stringent
fastening schedule should apply.
3. To maintain wind or seismic out-of-plane load
resistance—that is, fastener design withdrawal
strength—the fastener must have sufficient
length to penetrate through the FPIS layer and
maintain the required minimum embedment
in wood framing or engagement of fastener
threads in cold-formed steel framing.
4. Fasteners must be installed in a manner to
adequately draw all intervening material layers
together without over- or underdriving
resulting in problems such as warping of
materials or gaps between material layers.
However, more recent research has shown
that a drainage plane gap up to 3/8 in. thick,
provided by an intervening drainage mat
rather than furring placed behind lath for
stucco (one-coat and three-coat varieties
inclusive), can be tolerated with use of the
prescribed attachments and design procedure
discussed later in this article.11 This is
important to be able to address new stucco
drainage requirements in the 2021 editions
of the IRC and IBC for moist climates
(much of the United States). Back ventilation
or improved drainage behind other
types of cladding is also a recommended
practice, particularly for moist climates.
5. The fastener schedules and permissible
FPIS thicknesses will vary according to the
cladding weight supported (including all
materials outbound of the FPIS layer). The
cladding weight categories are as follows.
• 3 psf: vinyl siding, wood lap siding, most
fiber cement siding
• 11 psf: three-coat stucco
• 18 psf: medium-weight adhered masonry
veneer
• 25 psf: heavy adhered masonry veneer
These examples are not inclusive of all cladding
types or weights. Refer to cladding
manufacturer data for actual unit weight
Figure 2. Illustration of cladding and furring attachments through FPIS to CFS framing.
Note: CFS = cold-formed steel; FPIS = foam plastic insulating sheathing.
and, for absorptive claddings, a “wet” weight
should be used.
6. Fasteners, framing materials, and FPIS materials
must comply with the specifications and
minimum properties referenced in the tables
and table notes.
For masonry or concrete structural substrates,
the IRC and IBC require an engineered
design or use of fastener manufacturer data
because commonly used concrete/masonry
fasteners are proprietary. While the code provisions
use commodity (standardized) fasteners
for wood and steel framing, proprietary fasteners
may also be used, but must be analyzed in accordance
with the engineering procedure addressed
below. Where the scope limitations of the design
procedures are not satisfied, design lateral (shear)
values for a given fastener or connection scenario
should be determined in accordance with a suitable
test methodology consistent with that used
to develop the design procedure and IRC and
IBC code provisions derived from that procedure;
refer to ABTG research report no. 1503-
0210 for a description of the test methodology
and performance criteria, which were based on
applying ASTM D1761 connection shear tests
October 2022 IIBEC Interface • 19
including also long-term shear tests to evaluate
creep stability under constant load.
Prescriptive Cladding and Furring
Attachment through FPIS to Cold-Formed
Steel Framing
Figure 2 illustrates cladding direct attachment
over FPIS (no furring) and also furring attachment
over FPIS. The requirements for direct cladding
attachment and furring attachments over FPIS are
shown in Tables 1 and 2, respectively.
It is important to note that the figures included
in this article focus only on detailing connections.
The wall assembly details will require additional
components or materials for code compliance,
depending on design conditions.
Prescriptive Cladding and Furring
Attachment through FPIS to Wood Framing
Figure 3 illustrates cladding direct attachment
over FPIS (no furring) and also furring attachment
over FPIS. The requirements for direct cladding
attachment and furring attachments over FPIS are
shown in Tables 3 and 4, respectively.
Table 1. Siding minimum fastening requirements to cold-formed steel framing for direct cladding attachment over FPIS to support cladding
system weight
Note: Tabulated values are based on minimum 33 ksi steel for 33 mil and 43 mil steel and 50 ksi steel for 54 mil steel or thicker. Screws shall comply
with the requirements of ASTM C1513. FPIS shall have a minimum compressive strength of 15 psi in accordance with ASTM C578 or ASTM C1289.
DR = design required; FPIS = foam plastic insulating sheathing; o.c. = on center. 1 in. = 25.4 mm; 1 psf = 0.0479 kPa; 1 psi = 6.895 kPa; 1 ksi = 6.895 MPa.
Figure 3. Illustration of cladding and furring attachments through FPIS to wood framing.
Note: FPIS = foam plastic insulating sheathing.
20 • IIBEC Interface October 2022
Lightweight Cladding Prescriptive
Connection through FPIS to WSP
Sheathing
In accordance with Section R703.3.3 of
the IRC, direct connection of lightweight
claddings (maximum 3 lb/ft2 unit weight)
through FPIS (maximum 2 in. thick) to
WSPs (minimum 7/16-in. thickness) can
be done in accordance with Fig. 4 and
Table 5. The cladding fastener must be of
sufficient length to penetrate a minimum
of ¼ in. beyond the back side of the WSP
sheathing. Also, fastener minimum size
and maximum spacing must comply with
the cladding manufacturer’s installation
instructions, especially where the instructions
require a more stringent fastening
Table 2. Furring minimum fastening requirements to cold-formed steel framing for application over FPIS to support cladding system weight
Note: Table values are based on the following:
• Wood furring of Spruce-Pine-Fir or any softwood species with a specific gravity of 0.42 or greater per NDS.
• Minimum 33 mil steel hat channel furring of 33 ksi steel. Steel hat channel shall have a minimum 7/8 in. depth, 11/4 in. web width, and ½ in.-wide flanges with web
or flanges bearing on FPIS surface.
• Cold-formed steel framing of indicated nominal steel thickness and minimum 33 ksi steel for 33 mil and 43 mil steel and 50 ksi steel for 54 mil steel or thicker.
Screws shall comply with the requirements of ASTM C1513.
Furring shall be spaced a maximum of 24 in. o.c. in a vertical or horizontal orientation.
• In a vertical orientation, furring shall be located over wall studs and attached with the required fastener spacing.
• In a horizontal orientation, furring shall fastened at each stud with a number of fasteners equivalent to that required by the fastener spacing. If the required fastener
spacing is 12 in. o.c. and the studs are 24 in. o.c., then two fasteners would be required at each stud (24/12 = 2). In no case shall fasteners be spaced more than 24
in. apart.
FPIS shall have a minimum compressive strength of 15 psi, in accordance with ASTM C578 or ASTM C1289.
DR = design required; FPIS = foam plastic insulating sheathing; NDS = American Wood Council (2018); o.c. = on center. 1 in. = 25.4 mm; 1 psf = 0.0479 kPa;
1 psi = 6.895 kPa; 1 ksi = 6.895 MPa.
Figure 4. Illustration
of lightweight cladding
attachment through
maximum 2-in.-thick
FPIS to minimum 7/16-in.-
thick wood structural
panel sheathing.
Note: FPIS = foam plastic
insulating sheathing.
October 2022 IIBEC Interface • 21
schedule. Where applicable, this is one of the
simplest means of connecting cladding through
foam sheathing where a steel- or wood-frame
wall is sheathed with WSPs.
Supplemental Prescriptive Furring
Requirements for Wind Load Resistance
For furring materials and their attachment
to a structure, prescriptive wind pressure resistance
requirements are typically not available in
the locally applicable building code and design
values for typical 1×4 wood members used as
furring are not available because they are only
appearance graded. This concern affects wall
assemblies using furring, with or without the
presence of FPIS under the furring. Therefore,
Tables 6 and 7 are provided to supplement the
prescriptive or designed furring connection
requirements through FPIS as addressed in the
previous tables for support of cladding weight.
The more stringent fastening schedule for cladding
weight support or wind load should apply.
The tabulated allowable wind pressure resistance
values in Tables 6 and 7 must be equal
to or greater than the components and cladding
allowable stress design (ASD) negative
(suction) pressure wind load required by the
locally applicable building code. Because these
tables are only representative of an appropriate
furring design for wind pressure resistance, the
applicability for a specific use should be verified
for suitability prior to use. The tabulated
design values are based on analysis to determine
which of the following limits the design: furring
bending, fastener withdrawal, or fastener head
pull-through.
Allowance for Brick Tie Attachments
through FPIS Continuous Insulation
Section R703.8.4 of the IRC permits typical
brick ties, such as corrugated straps, to be
attached with only the fastener penetrating the
FPIS c.i. layer where it is of sufficient length
to maintain the embedment into framing or
minimum 7/16-in.-thick WSP sheathing for withdrawal
resistance. This applies to only the scope
of the IRC where wall components and cladding
ASD wind loads are 30 psf or less (refer
to IRC Section R703.3.2, “Wind Limitations”).
This connection strategy works only because
anchored masonry veneers are separately supported
and do not rely on the brick tie for support
of the veneer weight. Therefore, resisting
out-of-plane loads is of primary concern. For
this reason, use of corrosion-resistant screws for
Table 3. Siding minimum fastening requirements to wood framing for direct cladding attachment over FPIS to support cladding system weight
Note: Table values are based on wood framing of Spruce-Pine-Fir or any wood species with a specific gravity of 0.42 or greater in accordance with NDS.13
Required fastener minimum penetration shall be permitted to include thickness of wood structural panel sheathing materials. Nail fasteners shall comply with ASTM
F1667, except nail length shall be permitted to exceed ASTM F1667 standard lengths. Fasteners of equivalent or greater diameter and bending strength shall be
permitted. FPIS shall have a minimum compressive strength of 15 psi in accordance with ASTM C578 or ASTM C1289.
DR = design required; FPIS = foam plastic insulating sheathing; o.c. = on center. 1 in. = 25.4 mm; 1 psf = 0.0479 kPa; 1 psi = 6.895 kPa.
22 • IIBEC Interface October 2022
Table 4. Furring minimum fastening requirements to wood framing for application over FPIS to support cladding system weight
Note: Table values are based on wood framing and furring of Spruce-Pine-Fir or any wood species with a specific gravity of 0.42 or greater in accordance
with NDS.13 Nail fasteners shall comply with ASTM F1667, except nail length shall be permitted to exceed ASTM F1667 standard lengths. Wood screws
and lag screws shall comply with NDS Appendix L and ANSI/ASME B18.6.1. Other approved fasteners of equivalent or greater diameter and bending
strength shall be permitted. Required fastener minimum penetration shall be permitted to include thickness of wood structural panel sheathing materials.
A minimum 2× wood furring shall be used where the required siding fastener penetration into wood material exceeds ¾″ and is not more than 11/2″, unless
approved deformed shank siding nails or siding screws are used to provide equivalent withdrawal strength, allowing the siding connection to be made to
a 1× wood furring.
Furring shall be spaced a maximum of 24″ o.c. in a vertical or horizontal orientation.
• In a vertical orientation, furring shall be located over wall studs and attached with the required fastener spacing.
• In a horizontal orientation, furring shall be fastened at each stud with a number of fasteners equivalent to that required by the fastener spacing. If the
required nail spacing is 12″ o.c. and the studs are 24″ o.c., then two (2) nails would be required at each stud (24/12 = 2). In no case shall fasteners be spaced
more than 24″ (0.6 m) apart.
FPIS shall have a minimum compressive strength of 15 psi, in accordance with ASTM C578 or ASTM C1289.
DR = design required; FPIS = foam plastic insulating sheathing; o.c. = on center. 1 in. = 25.4 mm; 1 psf = 0.0479 kPa; 1 psi = 6.895 kPa.
Table 5. Lightweight cladding minimum fastening requirements for attachment through maximum 2-in.-thick FPIS to minimum 7/16-in.-thick
wood structural panel
Note: Horizontal spacing of fasteners along siding is based on a siding width (distance between horizontal rows of fasteners) of 12 in. For other siding widths,
multiply required horizontal spacing by 12/w, where w is the siding width in inches. Use of this table is limited to the wind load scope limits for cladding attachments
in accordance with Section R703.3.2 of the International Residential Code (that is, maximum 30 psf negative design wind pressure). FPIS = foam plastic insulating
sheathing; o.c. = on center.
1 in. = 25.4 mm; 1 psf = 0.0479 kPa.
October 2022 IIBEC Interface • 23
tie attachment may be preferable, especially
when attaching to minimum 7/16-in.-thick
wood sheathing underneath. When fastened
through FPIS, use of stainless steel fasteners
will not only maximize durability but also
reduce the thermal conductivity impact of the
tie fastener as mentioned previously.
Engineered Design of Cladding
and Building Component
Connections through FPIS
Where applicable, the calculation procedures
in this section should be used by a
registered design professional to determine
the lateral (shear) and withdrawal design values
for fastener connections through FPIS to
the underlying structure or substrate. The
lateral design value calculation procedures
provided below are applicable to FPIS having
a maximum 4-in. thickness and a minimum
15 psi compressive strength in accordance
with ASTM C578 or ASTM C1289. They
also apply only to attachment of cladding, linear
components or members such as furring
or ledger, and panel products installed over
FPIS. In addition, the general requirements
for the prescriptive provisions listed previously
also apply to use of these engineering
procedures.
Design of Connections through FPIS to
Cold-Formed Steel Framing
The installation and design of screw-type
connections shall comply with AISI S100,12
Section J4, with the additional requirements
indicated in (a) and (b) as follow for connections
including a layer of FPIS sandwiched between
the connected parts. Where screw fasteners are
installed through FPIS, the fastener length shall
be sufficient to provide a minimum of three
threads of penetration through the cold-formed
steel member receiving the fastener tip.
a. Tension allowable design values. Nominal
tension design values for screw connections
shall be determined in accordance with AISI
S100, Section J4.4, and divided by a safety factor
of not less than 3.0 to derive an allowable
design tension value.
b. Shear allowable design values. Nominal
shear strength design values for screws shall
be determined in accordance with AISI S100,
Section J4.3.1, and divided by a safety factor
of not less than 3.0 to derive an allowable
shear design value. Where the connection
includes a layer of FPIS sandwiched between
the connected parts, the following additional
requirements and limitations shall apply:
i. For connections using #8 or #10 screws,
AISI S100, Eq. J4.3.1-1 [Pns = 4.2 (t2
3d)1/2Fu2] shall be multiplied by one of the following
gap effect reduction factors Gr as applicable:
• For #10 screw in 54 mil (0.054 in. [1.370
mm]) and 50 ksi (345 MPa) steel:
Gr = 0.17—0.0048r
• For #10 screw in 43 mil (0.043 in. [1.09
mm]) and 33 ksi (228 MPa) steel:
Gr = 0.19—0.0066r
• For #8 or #10 screw in 33 mil (0.033 in.
[0.838 mm]) and 33 ksi (228 MPa) steel:
Gr = 0.16—0.0064r
where
Gr = gap effect reduction factor for use
with AISI S100, Eq. J4.3.1-1
r = dsep/d
dsep = separation between connected steel
parts caused by thickness of FPIS, in.
(mm)
d = nominal screw diameter
= 0.164 in. (4.17 mm) for #8 screws
= 0.190 in. (4.83 mm) for #10 screws
ii. The value of r shall not exceed 21.
iii. For 0 < r < 2, calculated Gr in accordance
with item i does not need to be less than
1-r/2.
iv. A larger steel thickness and screw size than
indicated in item i for the respective Gr
equations shall be permitted, provided the
Table 6. Furring minimum fastening requirements for application over FPIS to resist allowable stress wind pressure (wood frame structure).
Note: FPIS = foam plastic insulating sheathing; o.c. = on center. 1 in. = 25.4 mm; 1 psf = 0.0479 kPa.
24 • IIBEC Interface October 2022
Pns value calculated in accordance with
AISI S100, Eq. 4.3.1-1, uses the screw size
and steel thickness as indicated in item i
for the respective Gr equations.
v. The material against the screw head shall be
minimum 33 mil and 33 ksi steel, minimum
3/8-in.-thick wood or wood-based material
with a specific gravity of not less than 0.42,
or equivalent.
The gap reduction factors provide control
of long-term deflection (creep) and limit shortterm
deflection to 0.015 in. based on evaluation
of test data to develop and confirm the design
methodology.10 With application of the gap
reduction factors to control joint deflection, the
resulting safety factors are typically much greater
than the minimum safety factor of 3 required by
the AISI S100 standard for connections without
FPIS or a gap in the joint. The minimum 15
psi compressive resistance and maximum 4-in.
thickness for FPIS are associated with the test
data upon which the gap reduction factor equations
are based.10 Higher compressive resistance
FPIS may provide improved performance, but
the design provisions are based on this typical
minimum value.
Design of Connections through
FPIS to Wood Framing
The installation and design of connections
using dowel-type fasteners (that is, nails and
screws) shall comply with the American Wood
Council’s National Design Specification for Wood
Construction13 (NDS), including the additional
requirements indicated in (a) and (b) as follow
for connections including a layer of FPIS sandwiched
between the connected parts.
a. Allowable withdrawal design values.
Withdrawal design values for dowel-type fasteners
shall be determined in accordance with
NDS, Section 12.2. Where dowel-type fasteners
are installed through FPIS, the specified
fastener length shall be sufficient to provide
the design penetration into wood framing.
b. Reference lateral design values. Reference
lateral (shear) design values for dowel-type
fasteners shall be determined in accordance
with NDS, Section 12.3, with the following
modifications and limitations where the connection
includes a layer of FPIS sandwiched
between the connected parts:
i. The reduction term Rd, in accordance with
NDS, Table 12.3.1B, shall not be less than 3.0.
ii. The yield limit equations in accordance
with Table 1-1 of AWC Technical
Report 12, “General Dowel Equations for
Calculating Lateral Connection Values,”14
which include a gap parameter g equal to
the thickness of FPIS sandwiched between
connected parts, shall be used in lieu of
the yield limit equations in NDS, Table
12.3.1A.
iii. The minimum fastener penetration in the
main member (member receiving the fastener
tip), including the thickness of WSPs
attached to the main member, shall comply
with NDS and shall not be less than 1 in.
for screws or 1¼ in. for nails.
iv. The minimum specific gravity of wood
materials being connected shall be 0.42.
The use of a minimum Rd value of 3.0 controls
long-term creep and limits initial deflection
to not more than 0.015 in. for dowel-type fasteners
of ¼-in. diameter or less, FPIS of minimum
15 psi compressive resistance and maximum
4-in. thickness, wood materials of 0.42 specific
gravity or greater, and the fastener penetration in
the main member as indicated previously.10 With
application of the Rd value of 3.0 under these
conditions of use, the resulting safety margins
relative to ultimate lateral capacity are typically
greater than 5.
Design Procedure Applications
The previously detailed engineering procedures
provide for calculation of fastening solutions
beyond the limited prescriptive solutions
and fastener schedules for cladding and furring
connections presented earlier. For example, they
can be used to evaluate the following:
• Cladding and furring connections that use
alternative fastener schedules and even pro-
Table 7. Furring minimum fastening requirements for application over FPIS to resist allowable stress wind pressure (cold-formed steel
frame structure).
Note: FPIS = foam plastic insulating sheathing. 1 in. = 25.4 mm; 1 psf = 0.0479 kPa.
Higher compressive resistance FPIS may provide improved performance, but the design provisions are based on this typical minimum value.
October 2022 IIBEC Interface • 25
prietary types of fasteners, such as self-tapping
wood lag screws, which may have better yield
strength and stiffness than commodity fasteners,
resulting in improved performance
(that is, able to accommodate heavier loads
or thicker FPIS)
• Load-bearing structural building component
connections through FPIS, such as deck or
roof ledgers, for code-compliant structural
capacity and joint stiffness (Fig. 5)
• Various architectural building components
attached to a structure through FPIS, such as
window and door awning frames or shading
device support systems
• Structural sheathing connections through a
layer of FPIS (where FPIS is used as “undersheathing”—
that is, structural sheathing
placed over top of FPIS—not the more typical
case of “oversheathing”—that is, FPIS placed
over top of structural sheathing)
• Window and door frame anchorages through
FPIS or through plastic or wood shims in a
rough opening gap to enable calculation
of shear capacity to support fenestration
weight (or transverse wind loads) as a means
to achieve or demonstrate compliance with
fenestration industry standards for anchorage
design, such as AAMA 2501.115 This design
need, however, may only arise for anchorage
and support conditions not prescriptively
addressed in the fenestration manufacturer’s
installation instructions or where equivalent
substitute anchors are considered as permitted
by the code.
CONCLUSION
This article has reviewed code-compliant
prescriptive solutions and design procedures
for attachment of cladding, furring, and various
architectural and structural building components
through FPIS c.i. The primary goals of
these prescriptive requirements, design procedures,
and details are to provide a means to
maintain structural integrity while also promoting
thermal continuity and efficient construction
of a building enclosure when FPIS is
specified as c.i. Some of the key takeaways from
this article include the following:
• The connection provisions addressed herein
offer many options to provide structurally efficient,
energy-efficient, practical, and durable
means of constructing and designing codecompliant
and high-performance building
enclosures that use FPIS c.i.
• The prescriptive connection options and
design approaches presented are necessary
to meet the intent of model energy codes and
standards (for example, IECC and ASHRAE
90.1), particularly their shared definition
for continuous insulation, thereby allowing
compliance to be achieved by simply meeting
required prescriptive insulation R-values for
c.i.
• The presented connection provisions also
meet the intent and requirements of model
building codes (for example, IRC and IBC)
for proper attachment of cladding and furring
on walls with FPIS c.i.
• The same provisions can also be used to design
structural connections through a layer of FPIS
c.i., such as roof and deck ledgers.
• Finally, the use of connection provisions
addressed in this article helps support compliance
with improved water vapor control
provisions in modern building codes, whereby
FPIS c.i. can provide a uniform, stable, and
dry environment within building enclosure
assemblies.
REFERENCES
1. International Code Council (ICC), International Energy
Conservation Code. Country Club Hills, IL: ICC, 2021.
2. American Society of Heating, Refrigerating and Air-
Conditioning Engineers (ASHRAE), Energy Standard for
Buildings Except Low-Rise Residential Buildings, ANSI/
ASHRAE/IES Standard 90.1. Atlanta, GA: ASHRAE,
2019.
3. Applied Building Technology Group (ABTG), “Repetitive
Metal Penetrations in Building Thermal Envelope
Assemblies,” ABTG Research Report No. 1510-03, 2016,
http://www.appliedbuildingtech.com/rr/1510-03.
4. ASTM Subcommittee C16.22, Standard Specification for
Rigid, Cellular Polystyrene Thermal Insulation, ASTM
C578-18 (West Conshohocken, PA: ASTM International,
2018).
5. ASTM Subcommittee C16.22, Standard Specification for
Faced Rigid Cellular Polyisocyanurate Thermal Insulation
Board, ASTM C1289-17. West Conshohocken, PA:
ASTM International, 2017.
6. ICC, International Building Code. Country Club Hills,
IL: ICC, 2021.
7. ICC, International Residential Code. Country Club Hills,
IL: ICC, 2021.
8. J. H. Crandell, “Continuous Insulation: Research,
Applications, and Resources for Walls, Roofs, and
Foundations” (paper presented at RCI International
Convention and Trade Show, Orlando, FL, March 14–19,
2019), https://iibec.org/wp-content/uploads/2019-ctscrandell.
pdf.
9. J. H. Crandell, “Applying Recent Building and Energy
Code Advancements for Durable and Energy-Efficient
Building Enclosures” (paper presented at IIBEC 2020
Virtual International Convention and Trade Show, June
Figure 5. Porch roof ledger and soffit ledger connection detail through 4-in.-thick FPIS.*
Source: Building Science Corp., National Institute of Standards and Technology (NIST) project no. NI
ST NZERF, CAD (computer-aided design) DWG file A-PLOT-DETL-NZERTF, 2009, https://www.
nist.gov/system/files/nzertf-architectural-plans3-june2011.pdf.
* Using the previous design procedure for connections to wood framing through FPIS, two 3/8-in.
lag screws (or similar-capacity proprietary self-drilling wood screws) were used for the roof ledger connections
to each stud at 24 in. on center. Soffit ledger connections are less substantive (smaller or fewer
fasteners) due to lower connection forces and this distinction minimizes thermal bridging and cost.
Note: FPIS = foam plastic insulating sheathing. 1″ = 1 in. = 25.4 mm; 1′ = 1 ft = 0.305 m.
26 • IIBEC Interface October 2022
13, 2020), https://iibec.org/iibec-events/applying-building-
energy-code-durable/.
10. Applied Building Technology Group (ABTG),
“Attachment of Exterior Wall Coverings Through Foam
Plastic Insulating Sheathing (FPIS) to Wood or Steel
Wall Framing,” ABTG Research Report No. 1503-02,
March 2015, http://www.appliedbuildingtech.com/
rr/1503-02.
11. P. Gunderson and K. Kaufmann, “Attachment of Heavy
Claddings over Foam with and without Drainage Gaps”
(prepared for USDA Forest Products Laboratory by
Home Innovation Research Labs, Upper Marlboro, MD,
March 2020), https://www.homeinnovation.com/~/
media/Files/Reports/Attachment-of-Heavy-Claddings-
Over-Foam-With-and-Without-Drainage-Gaps.pdf.
12. American Iron and Steel Institute (AISI), North
American Specification for the Design of Cold-Formed
Steel Structural Members, AISI S100-16 (Washington,
DC: AISI, 2016).
13. American Wood Council (AWC), National Design
Specification for Wood Construction. Leesburg, VA:
AWC, 2018.
14. AWC, “General Dowel Equations for Calculating Lateral
Connection Values,” Technical Report 12. Leesburg, VA:
AWC, 2015.
15. American Architectural Manufacturers Association,
Voluntary Guideline for Engineering Analysis of
Anchorage Systems for Fenestration Products Included
in NAFS, AAMA 2501-20. Schaumburg, IL: Fenestration
and Glazing Industry Alliance, 2020.
Please address reader comments to chamaker@
iibec.org, including “Letter to Editor” in the subject
line, or IIBEC, IIBEC Interface Journal, 434
Fayetteville St., Suite 2400, Raleigh, NC 27601.
Jay Crandell has over 30
years of experience in
construction, engineering,
and innovative
building technology
research for private- and
public-sector clients. He
has conducted benchmark
studies of major
natural disasters as well
as research to address
significant structural,
energy, and building science challenges. His work
has helped to propel many innovative technologies
into the International Code Council’s codes and
consensus standards. He has published on various
engineering, construction, and building science topics.
For additional information visit www.aresconsulting.
biz and www.appliedbuildingtech.com.
Quickly and easily
detect air and water
leaks in air barriers
and roof membranes.
Leak Tester
Conforms to
ASTM E1186
1-800-448-3835
www.defelsko.com
n Single and two-ply membranes
n Liquid applied membranes & paint
n Sprayed Polyurethane Foam (SPF)
n Exterior Insulation and Finish Systems (EIFS)
n EPDM roofing systems
n Waterproofing & more
+1-315-393-4450 n 1-800-448-3835
techsale@defelsko.com n www.defelsko.com
1081745_Editorial.indd 1 8/13/22 6:13 PM
special interest
Jay Crandell, PE
Do You Work with
Your Best Friend?
You’ve heard about the perils of office
romances. What about office friendships?
A Gallup survey of nearly 4000 workers in
June of this year showed that the percentage of
employees who reported having a best friend at
work has declined in the past three years. The
survey showed that:
• Among hybrid workers, 17% said they had a
best friend at work, down from 22% in 2019.
• Among all workers (including fully remote or
fully on-site employees), 19% reported having
a close friend at work, down from 20% three
years ago.
Those declines can be a problem because
employees with a best friend at work are more
likely to report being extremely satisfied with
their jobs—and therefore less likely to leave.
Source: The Wall Street Journal
IZKES/SHUTTERSTOCK.COM