Skip to main content Skip to footer

Demonstrated Energy Savings Of Cool Roof Coatings And Future Directions For Research

November 3, 1997

Demonstrated Energy Savings Of
Cool Roof Coatings And Future
Directions For Research

 

By Dr. Lisa M. Gartland
INTRODUCTION
A relatively new class of
roof coatings has been
shown to save significant
amounts of cooling ener¬
gy. Cool roof coatings reflect away
the bulk of the sun’s energy, allow¬
ing the roof surface to stay cooler
and transferring less heat to the
building underneath. Demonstra¬
tion projects have shown these coat¬
ings can save between 20 and 70%
of the cooling energy used in a
building. These coatings also have
the potential to save money, reduce
air pollution, and lessen the need
for reroofmg. There are still techni¬
cal and industrial challenges in the
way of the widespread adoption of
these coatings as the roofing stan¬
dard.
This paper first reviews the
radiative properties of roof materi¬
als, then summarizes the results
from numerous projects which
demonstrate the effectiveness of
these coatings at saving cooling
energy. The challenges of accurate¬
ly modeling and predicting the
energy savings of cool coatings are
discussed. The non-energy benefits
of cool coatings are described.
Barriers to the implementation of
cool coatings are enumerated and
the challenges facing researchers
and the coating industry are consid¬
ered.
Radiative Properties of Roofing Materials
The radiative properties of roofing materials are best
understood by first studying the energy radiated from the
sun. Solar energy is spectral, which means it varies over
different wavelengths or spectra. Figure 1 shows the solar
energy’ reaching the earth’s surface on a clear summer day.
The amount of energy varies over the wavelength range of
0.3 to 3.0 nanometers, with a peak at around 0.6 nanome¬
ters. Solar energy falls into three distinct classes. Three
percent of solar energy is in the ultraviolet spectrum,
wavelengths responsible for sunburn. Forty percent of
solar energy falls in the form of visible light. The remain¬
ing 57% of the sun’s energy is felt as heat from the
infrared spectrum.
The amount of energy any material can reflect—its
reflectivity—also varies with wavelength. The coolest roof¬
ing materials have high reflectivities over the entire solar
spectrum. An overall measure of a material’s reflectivity to
the sun’s energy, called the albedo, is found by taking a
weighted average of these reflectivities over the solar spec¬
trum.
Figure 2 plots the reflectivity of typical asphalt shingle
roofing materials. 1 Asphalt materials tend to have fairly
low, but generally constant reflectivities over the solar
spectrum, with lighter colored materials having somewhat
Figure 1. Solar energy versus wavelength, for energy reaching the earth’s
surface.
: black asphalt – green asphalt – grey asphalt — ■ white coating
Figure 2. Reflectivity of different roofing materials over the solar spectrum.
8 • Interface November 1997
black asphalt aluminum coating white coating
low albedo high albedo very high albedo
high emissivity low emissivity high emissivity
Figure 3. Combined effects of albedo and emissivity in roofing materials.
Material Overall Albedo
black asphalt shingle 5%
green asphalt shingle 15%
light gray asphalt shingle 25%
typical white coating 75%
Table 1. Overall albedo of the roofing materials shown in
Figure 2.
higher reflectivities. The lightest colored
asphalt shingles—very light grays sometimes
classified as whites—reflect no more than 25%
of the sun’s energy from the roof.
Figure 2 also shows the reflectivity of a high¬
ly reflective coating. This coating has a peak
reflectivity of 0.87 in the visible spectrum, mak¬
ing it a very bright white. The reflectivity of
this coating tends to fall off in the infrared spec¬
trum, but the overall albedo of the coating is still 75%,
much higher than the albedo of traditional asphalt materi¬
als.
The reflectivity and albedo of roofing materials are not
the only radiative properties of interest. In order to stay
cool, roofing materials must also have high emissivities.
The emissivity is the percentage of absorbed energy a
material can radiate away from itself. Materials with low
emissivities tend to trap any heat they collect. Most roof¬
ing materials have emissivities of 0.90 or above, but roof¬
ing materials made of metal or metal particles tend to have
much lower emissivities, ranging between 0.05 and 0.60,
depending on their surface conditions.
Figure 3 shows the effect of albedo and emissivity on
roof surface temperature. Black asphalt roofs tend to have
the hottest peak temperatures (~180°F) despite their high
emissivity, since their low albedo value means they absorb
most of the sun’s energy. White coatings tend to stay the
coolest (MOOT at peak) since they reflect away most of
the sun’s energy’. Aluminum coatings tend to fall some¬
where in between. These coatings have albedos of around
40%—higher than traditional asphalt materials, but still
quite a bit lower than the highest albedo coatings.
Aluminum coatings have fairly low emissivities which
don’t allow them to radiate away absorbed heat.
Aluminum coated roofs tend to be about 20°F cooler than
the darkest asphalt roofs, but can still be classed as “hot”
roofs.
The most effective way to reduce the surface tempera¬
ture of a roof is to use a material which has both high albe¬
do and high emissivity. Many publications use the terms
“white” or “high-albedo” to describe this type of roofing
material. These misnomers can be very confusing. Use of
the term “white” implies that all white roofs will have
reduced surface temperatures. This is not the case since
visible properties of a roof do not indicate its albedo or
emissivity. Calling a roof “high-albedo” says nothing about
a roofs emissive properties. I have adopted the nomencla¬
ture “cool” to describe roofs with very high albedo (over
50%). and high emissivity (90% or higher).
Demonstration of Cool Roof Savings
Numerous projects have been undertaken to study the
effects of cool roof coatings on roof surface temperature
and cooling energy use. All studies confirm the ability of
cool coatings to reduce roof surface temperatures dramati¬
cally—by 50 to 80°F, and to save significant amounts of
cooling energy during the summer months.
Table 2 summarizes the results of five studies per-
Location „ Description
Insulation, Roof
Slope
Uncoated
Albedo
^Coated
Albedo
Cooling
Energy Savings
Sacramento, CA 1-story residence R-ll, flat roof 18% 77% 67%
Sacramento, CA 1-story school R-19, flat roof 8% 68% 40%
Cocoa Beach, FL 1-story residence R-ll, 22° roof slope 21% 70% 25%
Cocoa Beach, FL 1-story residence uninsulated, flat roof 20% 73% 43%
Cocoa Beach, FL 1-story school R-19, flat roof 23% 67% 35%
Table 2. Cooling energy savings from five demonstration projects.
November 1997 Interface • 9
formed in California and Florida.2
The albedos of all rooftops were
K Location ^GilrovTCAWI Davis.CA/W^ Wgan Jose, CA^
Building use Medical Office Medical Office Drug Store
Square footage -61,000 -31,000 -26,000, plus
-7000 mezzanine
Insulation R19 in ceiling
below roof plenum
R8 in roof above plenum foil barrier below
roof in plenum
Original roof type It. gray sheet It. gray sheet tan sheet
Original albedo 25% 24% 16%
Coated albedo 60% not yet coated not yet coated
raised by 40 to 60 percentage
points, well into the range of “very
high albedo” (over 50%).
Regardless of the level of insula¬
tion in the roof, all buildings
showed significant reductions in
the amount of cooling energy
used—reductions from 25% to
67%. These studies were all per-
Table 3. Building information for LB XL ‘s ongoing EPA demonstration project.
formed on residences or small
school buildings.
Figure 4. Infrared photograph of the roof of the Gilroy, CA building at
the edge of the white coating.
Figure 5. .Measured temperature of the coated rooftop and estimated
temperature of the roof without coating for the Gilroy. CA building dur¬
ing the week of Aug. 26 to Sept. 1. 1996.
An ongoing project funded by
the Environmental Protection Agency and administered
by Lawrence Berkeley National Laboratory is studying the
effect of cool coatings on three large, single-story commer¬
cial buildings in California.3 Table 3 gives information
about the use, size and roof conditions of these buildings.
As yet only one of the building rooftops has been given a
cool coating. The rooftop of the Gilroy, California building
was coated during the first week of August 1996, raising its
albedo from 25 to 60%. Coatings similar to the white elas¬
tomer used on this roof have albedos of 75 to 85% when
measured on smooth surfaces in the laboratory. The
roughness of the capsheet surface reduces the albedo by
increasing the absorption of the reflected solar radiation.
Of the three buildings in this study, the Gilroy building
had the highest initial rooftop albedo as well as the great¬
est amount of roof/ceiling insulation, and its coated albedo
was also not extremely high. Nonetheless, this building
still showed impressive roof surface temperature reduc¬
tions and cooling energy savings. Figure 4 shows an
infrared photograph of the Gilroy rooftop taken on a hot
summer afternoon during the coating process. This photo
shows the coated surface temperature is about 40 to 60°F
cooler than the uncoated surface.
Figure 5 shows measured surface temperatures over the
week of Aug. 26 to Sept. 1, 1996 together with estimates
of the temperatures that would have occurred without
coating. ‘The uncoated temperatures were calculated from
a regression equation relating pre-coating surface tempera¬
tures to weather and other variables. Peak temperatures of
the coated surface are 40-60°F below estimated peaks of
Figure 6. Measured cooling energy use with coated rooftop and estimated
cooling energy use without coating for the Gilroy. CA building during the
week of Aug. 26 to Sept. 1. 1996.
the uncoated surface.
Figure 6 plots the measured and estimated cooling ener¬
gy use of the Gilroy building during the week of Aug. 26
to Sept. 1. Estimates were again made from a regression
equation relating uncoated energy use to weather and
other variables. The decrease in energy use docs not look
dramatic, but the daily cooling energy load shapes for the
coated roof are shorter and narrower than the uncoated
shapes, adding up to 21% savings. Table 4 lists the total
cooling energy used for the remaining summer weeks after
the coating was applied, along with the estimated cooling
energy use for these weeks. The overall summertime cool¬
ing energy savings was 5300 k\Vhr, or 22% of the total
estimated uncoated energy use.
10 • Interface November 1997
Figure 7. Improvements needed in the DOE-2 building energy model.
Energy Prediction
Problems and Solutions
The demonstration projects described in the
previous section show the enormous potential of
cool coatings to reduce the cooling energy used by
buildings in warm climate regions. Further work is
being done to predict the wintertime penalties
and energy savings of cool roofs in various climate
regions.4 Most of this work focuses on using build¬
ing energy models to make these predictions.
Unfortunately, most of these models are not
equipped to accurately represent the heat transfer
processes that occur in the roof and ceiling.
An example of this inadequacy is found by
revisiting the study of the Sacramento, California
school bungalow referenced in Table 2.5 The roof
of this bungalow began as a galvanized metal roof
which was first painted brown (8% albedo), then a couple
of weeks later painted white (68% albedo). The cooling
energy use of this bungalow was measured through each
period, and then compared to determine how much cool¬
ing energy was saved by use of the white coating. The
measured daily total and daily peak energy savings are
recorded in Table 5.
Predictions of energy use were also made using the
DOE-2 building energy simulation model. DOE-2 is the
most widely used tool for building energy predictions.
Careful simulations were made using information about
indoor temperatures, building occupancy, and the actual
weather data in Sacramento
there is no radiative exchange in the plenum, between
the underside of the roof and the topside of the ceiling.
This means the model does not transfer enough heat to
the building conditioned space.
The second problem with DOE-2 is it treats the con¬
ductivity of the roof insulation as a constant. In reality,
the conductivity of fiberglass insulation varies with tem¬
perature,6 and as we have seen, roof temperatures vary
quite a bit. A 60°F change in insulation temperature
increases its conductivity by 25%. Since DOE-2 ignores
this effect, it once again can underpredict the building
load.
during the period of inter¬
est. The DOE-2 predictions
are also recorded in Table 5.
DOE-2 is seen to underpre¬
dict both the daily total and
daily peak cooling energy
savings due to use of a cool
coating.
The cause of this under¬
prediction is due to three
shortcomings in the DOE-2
model, illustrated in Figure
7. All three of these model¬
ing problems reduce the
heat load from the roof to
Table 4. Measured cooling energy used by the Gilroy building after the roof was coated, compared to cooling
energy use estimated without a roof coating, for the summer weeks after the roof was coated.
t Week
Measured
Cooling. kWhr
(coated)
Estimated
Cooling. kWhr
(uncoated)
Cooling
Energy
Savings, kWhr
Percent
Savings
Aug 5-11 2827 3485 658 19
Aug 12-18 3769 4587 818 18
Aug 19-25 2397 3211 814 25
Aug 26-Sept 1 3242 4102 860 21
Sept 2-8 1796 2418 622 26
Sept 9-15 2035 2734 699 26
Sept 16-22 2344 3176 832 26
Total 18410 23713 5303 22.4%
the building’s condi¬
tioned space, and
lead to DOE-2’s
underprediction of
cooling energy use.
The first problem
comes about when
the roof and ceiling
are modeled as a sin¬
gle layered compo¬
nent. In this case
B …» Daily Total Energy Savings
(kWhr/dav) . .
’’Daily Peak Energy
Savings (kW) .
Measured savings 4.6 0.56
DOE-2 predicted savings 2.9 0.28
Difference -37% -50%
Table 5. Measured and DOE-2 predicted savings of a white versus a brown roof in a Sacramento, CA school bunga¬
low during the summer of 1992.
12 • Interface November 1997
Figure 8. Measured and DOE-2 predicted values of cooling energy use
in the Sacramento school bungalow during two days in the summer of
1992 while the roof was painted brown.
; —■— measured base D0E2 -W5- radiation -O- ex. film -36- conduction -air- alt
Figure 9. Measured and DOE-2 predicted values of cooling energy use
in the Sacramento school bungalow during two days in the summer of
1992 while the roof was painted white.
The third problem is the use of a convection coeffi¬
cient at the roofs surface that is potentially too high. A
high convection coefficient means more heat is carried
from the roof surface to the outside air, which in DOE-2
may keep the roof surface temperature artificially cool,
again reducing the building heat load.
A function was written to correct all three problems,
and was tested using the 1992 Sacramento, GA school
bungalow data.7 Figure 8 shows both the measured and
the DOE-2 predicted cooling energy use over a two day
period while the roof was painted brown. The best match
to the measured energy use came when the function
incorporated all three solutions into the DOE-2 model.
Figure 9 plots the same information during a period while
the roof was painted white. Changes to the DOE-2
model have little effect in this case since the high albedo
of the roof dominates the heat transfer mechanisms by
keeping the roof surface temperature low.
Figure 10 plots daily values of cooling energy use ver¬
sus the values predicted by DOE-2 using all three model
improvements. The DOE-2 cooling energy predictions
are higher than the measured values, but the predicted
brown and white values are now higher than the mea¬
sured values by about the same amount. This means the
prediction of the difference between the brown and white
energy use (the prediction of cooling energy savings) is
now much more accurate.
Knnual Cooling
Energt Ik\Mir>
Annual Heating
Energy (kWiir)
Overall Savings
(kWhri
Standard
DOE-2
brown roof 1943 2192
+122
white roof 1776 2237
savings +167 -45
Improved
DOE-2
brown roof 2750 2325
+494
white roof 2108 2473
savings +642 -148
Table 6. Annual energy savings predictions for a cool roof using standard DOE-2 and the improved
version of DOE-2 for the Sacramento, CA school bungalow.
The analysis of the
Sacramento school bungalow was
extended past the summer cool¬
ing season to determine the
effect of these modeling
improvements on annual build¬
ing energy use. Table 6 lists the
annual cooling and heating ener¬
gy values predicted by the stan¬
dard DOE-2 model and the
DOE-2 model with improve¬
ments. Both the cooling energy
savings and the heating energy
penalties are increased with
the improved model. But the
overall effect of these
Table 1. Cost comparison of cool coatings versus the use of conventional roofing.
Cool Coating Cuintntion.il Roofing
Initial Cost + $0.50/sq ft + $3.5O/sq ft
Energy Savings over 10 Years – $0.20 to $0.70/sq ft none
Recoat/Relayer after 10 Years + $0.50/sq ft + $1.50/sq ft
Total $0.30 to $0.80/sq ft $5.00/sq ft
improvements is a fourfold
increase in annual energy sav¬
ings. This means the stan¬
dard DOE-2 model, as well
as other similar building ener¬
gy models, may be grossly
underpredicting the energy
savings due to cool roofing.
14 • Interface November 1997
Non-Energy Benefits of Cool Coatings
There are clearly demonstrated reductions in cooling
energy use as well as increasingly reliable predictions of
annual energy savings due to the use of cool roof coatings.
These coatings also have the benefits of lower cost,
reduced air pollution, and reduced waste.
Table 1 compares the cost of using a cool coating on a
roof versus using conventional roofing. The comparison
studies 10 years of a roofs life with the assumption that
initially, under the conventional route, the roof is torn off
and replaced while in the cool coating path, the roof can
be coated without removal. The cool coated roof can real¬
ize an energy savings of 20 to 70% over the next ten years
for a monetary savings of 20 to 70<f a square foot. After 10
years, the conventional roof needs a new layer of roofing,
while the coated roof can be recoated at one-third the cost.
At the end of only ten years, the cool roof saves more than
$4.00 a square foot.
The monetary benefits of the energy savings of cool
coatings are not insignificant, but they are much smaller
than the potential savings due to reduced roof mainte¬
nance costs. Theoretically, these cool coatings can be
applied over any roof surface which does not leak. The
coatings are assumed to greatly slow down, if not stop, the
aging process of the underlying roof materials. Since they
are much lighter than a new layer of asphalt, the coatings
can be applied indefinitely for decades before having to
tear off the old roof materials and replace them.
If these claims about the longevity of roof materials
under cool coatings are true, then a substantial amount of
waste can be avoided by the use of cool coatings. There
are an estimated 11 million tons of asphalt roofing waste
going into U.S. landfills every year. Over the last 40 years,
7 to 10% of the landfill space used has been filled with
roofing waste from both commercial and residential build¬
ings. 8 Use of cool coatings can greatly increase the life of
roof materials, and reduce the amount of torn-off roofing
waste going into landfills. The roofing waste that still
remains can be recycled into road mixes using existing
processes already operating, such as in the RamCo recy¬
cling facility in Fort Myers, Florida. 9 These technologies
can help turn the roofing industry to a more “green” or
“sustainable” path.
Direct and indirect reductions in air pollution can also
be attributed to the use of cool roofing materials. Direct
reductions come about because less cooling energy is
used, so fewer emissions are produced for energy genera¬
tion. Indirect reductions can result if cool surfaces are used
widely throughout an urban area. Cooler surfaces transfer
less heat to the air, keeping urban air temperatures lower.
Lower urban temperatures again call for less cooling ener¬
gy, and reduced energy generation emissions.
Lower urban temperatures also reduce smog formation.
Ozone formation is highly dependent on temperature, so
air temperature reductions slow down the “cooking” of
smog on hot summer afternoons. A computer simulation of
Los Angeles added cool surfaces and trees to 15% of the
possible areas. 10 This simulation indicated summer peak
temperature drops of 6°F and smog decreases of 10%. This
smog reduction is equivalent to ozone reductions obtained
by taking 3 to 5 million cars from the roads of Los
Angeles.
Barriers to Implementation of Cool Coatings
Cool rooftop coatings have many benefits, but their
implementation is still going slowly. There are many rea¬
sons contributing to their slow adoption, including techni¬
cal confusion, market barriers, and aesthetic barriers.
There is a lot of scientific misinformation leading to a
general technical confusion and skepticism about cool
coatings. As discussed earlier in this report, the visible
properties of a roof material do not necessarily indicate
how cool they will stay or how much ener¬
gy they will save. Materials with higher
reflectivities, like aluminum coatings, do
not necessarily stay cool. The only way to
know if a material will be cool is to know
its reflectivity and emissivity. This infor¬
mation is not generally available to roofers
or consumers, and its significance would be
understood by few people even if it were
available. Efforts are underway to adopt a
standard called the “solar reflectivity
index,” a rating combining the reflectivity
and emissivity to indicate how cool a mate¬
rial will stay in the sun. The Environ¬
mental Protection Agency is also working
on rating the energy properties of roofing
materials through their EnergyStar program.
Until one or both of these standards is in
common use, the confusion about roofing
products will remain.
■I metal ▲ brown O white
Figure 10. Measured versus predicted values of the daily cooling energy use for the
Sacramento, CS school bungalow during the summer of 1992, using all 3 improvements to
the DOE-2 model predictions.
November 1997 Interface • 15
Figure 11. Reflectivity of experimental colored coatings and white residential shingles.
Another area of technical confusion is the
effort to classify the benefits of cool coatings
into the same terms as the R-value rating for
insulation. This is an incorrect analogy which
can lead to very wrong conclusions about the
behavior of white coatings. If you try to
explain the decreased cooling load due to a
cool coating in terms of an increased R-value,
then you incorrectly assume this coating also
decreases the heating load during the winter.
The insulation R-value reduces conductive
heat transfer through the roof, while cool coat¬
ings reduce radiative heat transfer to the roof.
Market barriers to the adoption of cool
coatings also exist. Conventional roofing tech¬
niques have been used for decades, so there is
a relative lack of experience with and avail¬
ability of cool coatings. Roofing contractors are
somewhat skeptical of the claims made about
cool coatings and still have many questions
about their reliability and longevity. Contractors who must
guarantee their work are not about to apply a coating they
do not trust. The business of contractors also depends
heavily on the relayering, tearing off and replacement of
conventional roofing materials. The new cool coating tech¬
nologies have the potential to upset the market and
reduce the demand for these labor- and material-intensive
roofing services.
There are also aesthetic concerns to the adoption of
cool roofing materials. These materials at this point are all
white, which is considered unattractive. White roofs are
unacceptable even on some flat rooftops, where the
rooftop will not be seen by the majority of people. There
are sometimes building codes restricting what can be seen
from surrounding hills or taller buildings. There is also a
fear of creating glare for airline pilots, which is largely
unfounded. The worst glare is created by specular reflec¬
tions, which bounce off a surface at an angle equal and
opposite to the one they came in on. Today’s cool surfaces
are very bright and reflect the majority of visible light. But
they reflect light diffusely, meaning they spread light out
in all directions instead of concentrating it in one direc¬
tion.
Cool white roofing materials also have the problem of
showing the buildup of dirt and any biological growth.
Most of these products contain agents to make them “self¬
washing,” i.e., to encourage the action of rainwater to
remove dirt particles, as well as chemicals to reduce the
formation of any algae or mildew. The question of
reduced albedo remains, especially in areas of high dust
and pollen and low rainfall. 11
Ongoing and Future Work on Cool Coatings
There are significant research and industry challenges
regarding cool coatings which still need to be undertaken.
Research challenges include performing systematic
demonstrations of the energy savings of cool roofing mate¬
rials with different roof insulation and constructions, and
in varying climate regions. Improvements also need to be
made to modeling and prediction programs to get accurate
predictions of summertime energy savings and wintertime
heating penalties. Research into cool coating materials is
now underway at two national laboratories—Lawrence
Berkeley National Laboratory and Oak Ridge National
Laboratory.
Research at Lawrence Berkeley National Laboratory
has been covering many areas. Researchers have been
administering demonstration projects of cool coatings in
California and Florida (through the Florida Solar Energy
Center). Improvements in roof heat transfer modeling are
being made to the next generation of DOE-2, the DOE-
2.2 and EnergyBase programs. Work is underway to adopt
standards rating reflectivity, emissivity and the “solar
reflectance index” through ASTM, ASHRAE and the
California Energy Commission. Research with the
Environmental Protection Agency is ongoing to provide
input for EnergyStar standards for roofing materials. A roof¬
ing materials database has been added to the World Wide
Web. Urban climatological and air quality modeling is
underway to evaluate the effects of cool surfaces in cities
throughout the United States.
Work at Oak Ridge National Laboratory includes test¬
ing at a comprehensive roof and attic facility, detailed
modeling of the heat transfer mechanisms of roof and attic
systems, and investigation of the effects of moisture
buildup on roofing materials.
The coatings industry also faces many challenges.
Vendors must ascertain the durability and longevity of
their products, determine expected failure mechanisms,
and quantify the lifetime albedo of their products. To
market these products as truly “green” and environmen¬
tally friendly, they must evaluate the life cycle costs and
externalities of coating products and prove their benefits
16 • Interface November 1997
over traditional materials.
The coatings industry could also potentially profit from
the development of new cool materials. Researchers at
Lawrence Berkeley National Laboratory have examined
colored coatings and residential shingles with albedos of
about 0.50 (see Figure ll). 12 These products may have
appeal to a broader segment of the roofing market. The
development of coatings for residential shingles (probably
applied to shingles before they are installed), may also be
another profitable area of investigation.
Coatings industry members are challenged to work
together to promote the use of their products. Together
they can more effectively set and voluntarily adopt stan¬
dards for classifying their materials, develop a broad
research agenda, and pool financial support. There is also
a need to educate people about the science behind cool
roof coatings, as well as their great potential benefits. The
roof construction industry also needs to learn to apply
coatings effectively and consistently and must be given
the equipment and training to measure coating albedo to
ensure they are achieving the targeted value.
Summary
Cool roofing is not a simplistic concept. The develop¬
ment of products and markets for cool coatings faces sig¬
nificant technical and industrial challenges, as well as mar¬
ket and sociological barriers. But cool roof coatings can
also provide great benefits. These coatings have the
potential to save large amounts of money and energy, and
to significantly reduce air pollution and roofing waste.
About Tbe Author
I Dr. Lisa Gartland is currently a |
post-doctoral fellow in the |
Building Energy Analysis j
Program at Lawrence Berkeley
National Laboratory, where she I
has investigated the effects of high j
albedo roofing on building cooling ‘«
and heating loads. Prior to obtaining a doctorate in /
mechanical engmeeringfrom the University of Washington |
in 1995, she designed and analyzed cooling systems for jet |
engjnes and nuclear reactors. *
Publish A Business Card Ad In
Interface For Only $150.
Phone RCI Headquarters.
FOOTNOTES
1. Berdahl and Bretz, “Pre¬
liminary Survey of the
Solar Reflectance of
Cool Roofing Materials,”
Lawrence Berkeley Nation¬
al Laboratory Report #
LBL-36020, October
1995.
2. Akbari, Bretz, Hanford,
Kurn, Fishman, Taha
and Bos, “Monitoring
Peak Power and Cooling
Energy Savings of Shade
Trees and White Sur¬
faces in the Sacramento
Municipal Utility Dist¬
rict (SMUD) Service
Area: Data Analysis,
Simulations and
Results,” Lawrence
Berkeley Laboratory
Report # LBL-34411,
December 1993.
Parker, Barkaszi,
Chandra, and Beal,
“Measured Cooling
Energy Savings From
Reflective Roofing
Systems in Florida:
Field and Laboratory
Research Results,” Ther¬
mal Performance of the
Exterior Envelopes of
Buildings VI, pp. 489-500,
jointly sponsored by
U.S. DOE, ASHRAE,
ORNL and the Building
Environment and Ther¬
mal Envelope Council,
December 4-8, 1995,
Clearwater, FL.
3. Gartland, “EPA Demon¬
stration Project: Energy
Savings of Cool Roof
Coatings,” draft report
for Lawrence Berkeley
National Laboratory,
January 1997.
4. Konopacki, Akbari,
Gabersek, Pomerantz,
Gartland and Moezzi,
“Energy and Cost Bene¬
fits from Light-colored
Roofs in 11 U.S. Cities,”
Lawrence Berkeley Nation¬
al Laboratory Report #
LBL-39433, October
1996.
5. Akbari et al.
6. Levinson, Akbari and
Gartland, “Impact of the
Temperature Depen¬
dence of Fiberglass In¬
sulation R-Value on
Cooling Energy Use in
Buildings,” Lawrence
Berkeley National Labor¬
atory Report # LBL-
38678.
7. Gartland, Konopacki
and Akbari, “Modeling
the Effects of Reflective
Roofing,” Lawrence
Berkeley National Labor¬
atory Report # LBL-
38580, August 1996.
8. “Disposal Costs Go
Through the Roof,” RSI,
pp. 30-32, October 1993.
9. “Roofing Debris Recy¬
cling, Ten Years and
Counting,” Roofer
Magazine, pp. 22-24, July
1996.
10. Akbari, Rosenfeld,
Taha and Gartland,
“Mitigation of Summer
Heat Islands to Save
Electricity and Reduce
Smog,” Proceedings of the
AMS Annual Meeting,
Atlanta, GA, Jan. 28-
Feb. 2, 1996; also,
Lawrence Berkeley
National Laboratory
Report #LBL-37787.
11. Bretz and Akbari,
“Durability of Highalbedo
Roof Coatings
and Implications for
Cooling Energy
Savings,” Lawrence
Berkeley National
Laboratory Report # LBL-
34974, June 1994.
12. Berdahl and Bretz.
November 1997 Interface • 17