Skip to main content Skip to footer

High-Performance Building Enclosures Cause Condensation and Indoor Air Quality Problems: The Need for Integrated Design and Improved Investigation Protocols

July 15, 2010

S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • NO V E M B E R 2 0 1 0 HU B B S • 9 9
HIGH-PERFORMANCE BUILDING ENCLOSURES CAUSE
CONDENSATION AND INDOOR AIR QUALITY PROBLEMS:
THE NEED FOR INTEGRATED DESIGN AND
IMPROVED INVESTIGATION PROTOCOLS
BRIAN HUBBS, PENG
RDH BUILDING ENGINEERING LIMITED
224 West 8th Avenue, Vancouver, BC, Canada V5Y 1N5
Phone: 604-873-1181 • E-mail: bch@rdhbe.com
COAUTHORS:
ROBERT ORLOWSKI
GRAHAM FINCH, EIT
1 0 0 • HU B B S S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • NO V E M B E R 2 0 1 0
ABSTRACT
Multifamily buildings in the Lower Mainland of British Columbia and the U.S. Pacific
Northwest have come under increasing scrutiny due to the high incidence of water ingress
and resulting deterioration of exterior wall assemblies. Current trends in architectural and
HVAC design in combination with changes in building enclosure design to improve water
penetration control and energy efficiency often result in increased potential for condensation
related moisture problems. This paper examines these changes through a series of case
studies showcasing typical problems that can occur. Innovative monitoring and modeling
techniques are also presented that shed new light on the multidisciplinary cause of the
problem. Recommendations are provided for integrated architectural and HVAC design to
accommodate the more airtight and insulated wall and window assemblies used on buildings
today, as well as guidance to occupants and building managers to minimize risk of condensation-
related moisture problems in exterior wall assemblies.
SPEAKER
BRIAN HUBBS, PENG — RDH BUILDING ENGINEERING LIMITED
Brian Hubbs is a principal and senior building science specialist with RDH Building
Engineering in Vancouver, BC. He has 19 years of experience working exclusively as a consulting
engineer focused on building enclosure issues in all climate zones across North
America. This work has included the design of new building enclosures as well as forensic
investigation, rehabilitation, maintenance, and litigation support on existing buildings.
Brian has also been a key team member on the many landmark building-science research
and policy projects focused on the West Coast climate zone.
S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • NO V E M B E R 2 0 1 0 HU B B S • 1 0 1
ABSTRACT
Multifamily buildings in the Lower
Mainland of British Columbia, Canada, and
the United States’ Pacific Northwest have
come under increasing scrutiny due to the
high incidence of water ingress and resulting
deterioration of exterior wall assemblies.
The fact that the majority of these moisture
problems have been related to water ingress
has overshadowed other moisture-related
building enclosure issues. With the recent
widespread adoption of rainscreen technology,
improved detailing, and better quality
control, water ingress issues have been
reduced significantly, raising the profile of
other moisture issues such as condensation.
Current trends in architectural and
heating, ventilation, and air conditioning
(HVAC) design, in combination with
changes in building enclosure design to
improve water penetration control and energy
efficiency, often result in increased
potential for condensation-related moisture
problems. This paper examines these
changes through a series of case studies
showcasing typical problems that can
occur. Innovative monitoring and modeling
techniques are also presented that shed
new light on the multidisciplinary cause of
the problem.
Recommendations for integrated architectural
and HVAC design to accommodate
the more airtight and insulated wall and
window assemblies used on buildings
today, as well as guidance to occupants and
building managers to minimize risk of condensation-
related moisture problems in
exterior wall assemblies is provided. A new
test methodology for the investigation and
monitoring of condensation problems is
also presented.
INTRODUCTION
The potential for condensation to occur
on the interior surfaces of walls and windows,
in simple terms is related to several
factors:
• Exterior environmental conditions
• Thermal resistance of layers within
the wall assembly
• Thermal characteristics of the window
assembly
• Position of the window within the
wall assembly, as well as details of
the installation
• Location and distribution of heat
within the suite
• Interior source generation of moisture
• Ventilation of interior air to manage
interior relative humidity conditions
These basic influences on condensation
potential have been understood for many
years. However, recent trends within multiunit
residential construction have created a
combination of factors that can lead to
increased potential for condensation and
accumulation of moisture. Moisture accumulation
can result in damaged materials
and mold growth on surfaces. One recent
trend that affects building performance that
stems from the current housing boom and
corresponding increase in housing prices is
the market for very small living spaces. For
architects, this results in a challenge to
design usable living spaces while minimizing
footprint area. Often with limited floor
space, the only available location to place
large furniture such as beds and couches is
adjacent to exterior walls. In addition, the
trend towards maximizing the amount of
glazing area and ceiling height discourages
the use of drop ceilings to enclose perimeter
mechanical ductwork to supply heated dry
air to the building perimeter and adds to the
need for opaque window coverings for privacy.
These three factors reduce the amount
of interior heat getting to the perimeter and
increase the potential for condensation.
Trends toward the use of high-performance
rainscreen wall and window assemblies,
especially those with exterior insulation
over a waterproof air/vapor/moisture
barrier membrane, result in much more
effective airtightness compared to traditional
wall and window assemblies. This
increased airtightness results in a corresponding
reduction in natural ventilation
across the building enclosure. The lack of
natural ventilation must be considered
when designing the building HVAC system,
especially in colder climates where windows
are not likely to be opened during periods of
cold weather. In addition, the increased use
of exposed concrete walls incorporating eyebrows
and concrete curbs increases the risk
of condensation on colder surfaces by creating
thermal bridges. Attachment to these
exposed concrete elements at connections,
in particular at the window-to-wall interface,
also increases the risk of condensation.
In an effort to reduce costs or, in some
cases, increase “Leadership in Energy and
Environmental Design” (LEED) points, some
designers are moving away from traditional
electric or steam-based perimeter heating
systems and moving to more centralized
heating forms such as gas fireplaces, radiant
flooring, and core-based radiant or
forced-air systems. This can result in a
reduction in perimeter heating and thus,
colder surfaces, leading to increased risk of
condensation and associated moisture
problems. Measured relative humidity (RH)
levels within suites have been found to be
higher in newer buildings than is traditionally
assumed in HVAC and building envelope
design. Our design assumptions and,
consequently, our designs need to be
reevaluated.
It is also clear that the way occupants
use their suites and maintain HVAC equipment
can have a profound impact on condensation
performance. In particular, the
typical occupant’s lack of basic knowledge
regarding the factors influencing condensation
potential can result in increased condensation
problems.
This issue represents a very complicated
interaction of architectural design, HVAC
design, and maintenance/occupant use
that together determine success of an exte-
HIGH-PERFORMANCE BUILDING ENCLOSURES CAUSE
CONDENSATION AND INDOOR AIR QUALITY PROBLEMS:
THE NEED FOR INTEGRATED DESIGN AND
IMPROVED INVESTIGATION PROTOCOLS
rior wall assembly with respect to condensation
control. It is not simply a matter of
making assumptions regarding internal and
external environmental conditions and
undertaking a basic vapor-diffusion analysis
of the wall assembly. Before we can
develop solutions, a better understanding of
these complex interactions is required. To
understand the multifaceted cause of the
problems requires improved investigation
techniques that consider all the variables.
Using a series of investigative case studies,
we have summarized the concerns surrounding
these issues and have developed
integrated design considerations for all disciplines
as well as the end users.
NEW INVESTIGATION PROTOCOL
When performing an investigation on a
building that is experiencing condensation
and/or interior air quality problems, it is
important to develop an investigation
methodology that includes all of the critical
variables. Without complete data, interpretation
of the results can easily lead to erroneous
conclusions and incomplete recommendations.
The classic approach to investigating
a building with condensation problems
is to install a few temperature and RH
sensors in a problematic suite for a given
period when condensation occurs within
the unit. Typically, one sensor is used in
each bedroom, with one in the main living
area. Data from the sensors are cross-referenced
with information from the occupants
on their activities that affect the moisture
levels. This helps to explain the various
trends and anomalies found in the data.
The information provided by this type of
sensor data is very limited. When analyzing
the data, only theories can be derived as to
the causes of moisture changes because
each source is not monitored individually.
The full impact of the HVAC system on the
problem is often not even considered.
An advanced monitoring protocol was
developed for a recently constructed residential
high-rise complex in the Pacific
Northwest that had been experiencing condensation
problems during periods of cold
weather since construction. The building
was constructed of concrete and incorporated
high-performance rainscreen window
and wall assemblies. The owners of the
building wanted to understand the cause of
the condensation issues and specifically to
determine why condensation was prevalent
on some suites but not on others that had
the same layout and construction. In addition
to the normal temperature and RH data
loggers, the following information was collected
to assist in investigation:
• Logged operation and flow rates of
all HVAC equipment (including all
exhaust fans, furnace fan, and
clothes dryer)
• Measured airflow rates at supply
vents and at windows during furnace
fan operation
• Measured hallway supply air under
all combinations of HVAC equipment
operation
• Logged suite CO2 levels
• Calculated building enclosure air
leakage rates from test data
• Logged window frame and glazing
temperatures at corner and center
of sills, indicating when condensation
was occurring and allowing a
comparison of the effects of furnace
supply air
A complete layout and sensor description
for a sample control/condensation
suite pair is shown in Figure 1. The use of
individual sensors for each source location
allows for clear understanding of the source
of the moisture and what countermeasures
are used to deal with any resulting increase
in RH. For example, the master bedroom
received three sensors in the following locations:
en suite bathroom, bedroom, and
window surface. Correlating the data from
these three sensors will clearly show if the
occupants cause condensation or if other
sources of moisture (such as a shower) contribute.
With sensors also linked to the
exhaust fans, the effectiveness and the
extent of use of each fan could also be
determined. With this monitoring protocol,
a clear picture as to the exact conditions
that led to condensation within the suite
can be concluded from the data. A sample
of the results is included.
Figure 1 — Data logger and sensor setup (control and condensation suite).
Figure 2 — Effect of furnace operation
on window surface temperatures.
1 0 2 • HU B B S S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • NO V E M B E R 2 0 1 0
HVAC FURNACE SUPPLY FAN
EFFECT ON WINDOW TEMPERATURE
During the analysis of the furnace-heated
supply air wash to the windows, it was
observed that the heat-supply vents are
quite far from the windows, and the resulting
flow rate of heated air wash is low and
even nonexistent in many areas. This HVAC
layout is already much more sensitive to
condensation than traditional radiators or
forced air vents at the perimeter and will
result in much colder perimeter window
temperatures.
However, the problem was exacerbated
in one suite pair by the use of a setback
thermostat. Figure 2 shows a typical evening
during periods of cold exterior temperature.
In the control suite with no condensation,
the furnace operates every 15 minutes,
keeping the window temperatures around
65ºF. In the suite with condensation the
window temperature steadily declines during
periods where the furnace is turned off.
This typically occurs at night when exterior
temperatures are at their lowest. The consequence
is window temperatures around
58ºF that result in condensation. One of the
condensation suites’ occupants did not
operate the furnace during the entire monitoring
period resulting in extremely cold
perimeter surface temperatures.
EXHAUST FAN USE VS. SUITE DEW
POINT
In an optimal situation, exhaust fans
would operate during moisture-generating
activities and remain on until the moisture
level in the room returned to its original
value. In general, we found that all occupants
were not consistently and properly
utilizing their exhaust fans during highhumidity-
generating activities. Often,
exhaust fans were not utilized during showers,
and if they were, it was only for the
duration of the shower. In many cases, it
took up to ten hours for the increased
humidity from a single shower to be dissipated
when exhaust fans were either not
used or turned off immediately after a
shower. (Refer to Figure 3.)
IMPACT OF SUPPLY AIR QUANTITY
AND QUALITY ON CONDENSATION
The HVAC design for the building
included a hallway pressurization system
supplying conditioned fresh air to the suites
by means of positive-pressure delivery
under the entry doors. The only other
method of providing fresh air to the suites is
through operable windows that are not
used during periods of cold weather and
through backflow of exhaust vents under
high wind pressures.
In general, we observed that the supply
air volume was lower and the relative
humidity higher on the condensation suites
in comparison with the control suites (Table
1). This lack of supply air is also reflected in
the CO2 measurements that show considerably
higher CO2 levels in suites with lower
ventilation rates and higher levels of condensation,
as shown in Figure 4.
Figure 3 – Effect of shower on Suite RH
and condensation without exhaust fan
operation.
Table 1 — Supply airflow rates.
S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • NO V E M B E R 2 0 1 0 HU B B S • 1 0 3
Air-flow
measurements
had no increase
when fans were
activated; the
hallway
pressurization
was not working.
ASHRAE
recommendations
based on suite
area (accounts for
5-6 occupants).
ASHRAE
recommendations
at 15 cfm per
person for actual
occupant loads.
N6011 N301
Baseline 24 0
Master bathroom 55 8
Guest bathroom 53 11
Common bathroom 55 14
Kitchen level 1 55 11
Kitchen level 2 55 16
Kitchen level 3 59 29
Dryer w/ booster fan 55 14
ASHRAE recommended (based on suite size = 0.3 ACH) 82 82
% of ASHRAE recommended @ baseline 29% 0%
% of ASHRAE recommended w/continuous master bath fan 67% 10%
ASHRAE recommended (based on # of occupants, 15 cfm/person) 30 30
% of ASHRAE recommended @ baseline 79% 0%
% of ASHRAE recommended w/continuous master bath fan 183% 27% 1Control suite
Airflow
IMPACT OF ENCLOSURE AIR
LEAKAGE
As part of the quality assurance testing
of new building envelope assemblies—the
American Standard Test Method (ASTM)
E783, Standard Test Method for Field
Measurement of Air Leakage Through
Installed Exterior Windows and Doors—
results were known for the wall and glazing
assembly used on this project.1 The major
envelope assemblies consisted of sliding
balcony doors, floor-to-ceiling window-wall,
and exterior insulated rainscreen metal
panels.
The results of this air leakage testing
revealed that overall air leakage rates
across the building envelope assembly were
on the order of 0.09 L/(s m2) @75 Pa, which
is within the recommended level outlined by
the building code2 [Max 0.10 L/(s m2) @75
Pa]. The measured air leakage rate @75 Pa
was converted to an equivalent leakage area
(ELA75) using Bernoulli’s equation:
Q = CA[(2/p)DP]1/2
(Q = flow rate, C = contraction coefficient,
A = area, p = air density, and DP =
pressure differential)
with the following assumptions:
C = 0.6, p =1.20, suite wall area = 80m2
Based on these assumptions, the ELA75
was found to be 11.4 cm2. Utilizing ELA75
and a DP of 4 Pa for the average measured
pressure across the enclosure, the equivalent
air leakage rate of 3.6 cfm was estimated
for the entire exterior wall area of the
unit tested. Table 5 of ASHRAE’s
Fundamentals Handbook3 and Standard 62
suggests that a two-occupant unit should
have a total ventilation rate greater than 30
cfm. With the building enclosure only capable
of providing on the order of 10% of the
recommended ventilation air for the suite
with all windows closed, it is clear that
modern high-performance building envelope
enclosures should not be relied upon to
provide a significant portion of the required
ventilation for the unit.
FIELD SURVEY OF PERFORMANCE
OF HVAC SYSTEMS
A survey of buildings was undertaken as
part of the development
of an HVAC
guideline for multiunit
residential buildings
in the U.S.
Pacific Northwest
(Portland and Seattle
areas).4 The purpose
of this survey was to
examine the actual
in-service performance
of HVAC systems
a few years after
c o n s t r u c t i o n .
Information was gathered
through visual
observations, measurements
of pressure
differentials and
airflow, as well as
through discussions
with on-site maintenance personnel and
occupants. A summary of performance
issues and observations follows. Fieldwork
was performed only on calm days in May
2004 to minimize wind effects and stack
effect, respectively.
HEATING
• In several instances, furniture was
located in front of cadet heaters,
lowering their effectiveness and/or
creating a fire risk. See Figure 5.
• In many instances, the electric
cadets are located towards the unit
interior rather than at or near an
exterior wall. Also, interiorly located
heat sources are often situated
directly beneath thermostats. In
some suites, the occupants reported
feeling cold even when the heaters
were used. Since heat was not being
provided at the exterior walls, the
relatively cold walls reduce occupant
thermal comfort and increase the
likelihood of condensation-related
issues at the exterior walls and windows.
See Figure 5.
• In some suites, the occupants do not
use the electric heating systems, as
they are perceived to be expensive.
Occupants also complain that the
cadet heaters (electric fan coils) are
noisy. At some buildings, plug-in
style, oil-filled radiators are used in
lieu of the electric baseboard or
cadet heaters. See Figure 6.
Figure 4 – Correlation of effect of CO2 levels on condensation.
Figure 5 — Electric cadet wall heater located behind couch,
away from exterior wall, and directly below the thermostat,
leading to poor temperature control within the room.
1 0 4 • HU B B S S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • NO V E M B E R 2 0 1 0
VENTILATION
• The airflow at many bath fans was
measured with a flowmeter. Some
exhaust fans designed for humidity
control operate continuously. These
were found in poor operating condition,
due to a lack of being maintained.
In other locations, the fan
was ineffective, due to an insufficient
gap under the doorsill, which
suffocated the fan.
• In corridor buildings, many suites
were positively pressurized relative
to the corridor. Of the units that
were negatively pressurized, most
were 1 to 5 Pa negative relative to
the corridor. One suite was 25 Pa
negative relative to the corridor.
• Also in corridor buildings, the supply
airflow rate varied between floors
of the same building. Supply air
seemed insufficient in some cases to
balance the sum of the continuous
exhaust of the suites at that particular
floor.
• In many suites with continuous
exhaust fans, significant lint has
built up.
• Some suites are provided with recalculating
fans in lieu of exhausting
vents.
• There is inadequate ducting and
booster fan used for clothes dryers.
MAKEUP AIR
• There is little to no gap beneath hallway
doors to allow makeup air to
flow to units (supply from corridor).
There is also little gap at the base of
bathroom doors, suffocating continuous
bath fans.
(The suite layout is
such that bathroom
doors remain
closed most
of the time.
• Closures are installed
at the base
of hallway doors to
stop drafts and
odors from transferring
from the
hall under the
door, cutting off
the “fresh” air supply.
See Figure 7.
• The trickle vents
in windows are often closed.
• In some corridor buildings, stairwell
doors are propped open, weakening
the hallway pressure needed to supply
fresh air to suites and disrupting
mechanical system balancing. See
Figure 8.
• The hallway pressurization system
causes inherent draft under entry
doors.
• There are complaints of odors from
suite occupants in many buildings.
• Manual-operating point-source
exhaust fans are not used in many
kitchens and baths.
• Fans are disconnected if or when
they become noisy rather than
replacing or maintaining them.
S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • NO V E M B E R 2 0 1 0 HU B B S • 1 0 5
Figure 6 — Use of oil-filled radiators in
same room as shown in Figure 5.
Figure 7 — Undercut door intentionally blocked to resist
drafts and control odors from hallway into suite.
Figure 8 — Stairwell
doors propped open,
frustrating attempts
to control airflow
within building.
Figure 9 — Cover to close exhaust grill.
• Exhaust grills are fitted with covers
by occupants to shut off flow
because of the perception of heat
loss from the exhaust systems. See
Figure 9.
• Exhaust ducts are terminated within
attic spaces vs. being vented.
• Heavy curtains at some exterior
walls insulate the walls from heated
air. See Figure 11.
• Insufficient makeup air to utility
rooms affects clothes dryer performance,
reducing capacity to exhaust
moist air.
The field survey clearly illustrated that a
combination of architectural, HVAC, and
occupant factors act together to cause
HVAC systems to not function as intended.
The case studies that follow illustrate some
examples in more detail where this dysfunction
has led to condensation and moisture-
related damage.
IMPACT OF
ARCHITECTURAL
SPACE
LAYOUT
Si gni f i cant
levels of mold
and deterioration
were observed
within a vinylclad
townhouse
complex in Washington State.5 The damage
occurred along the base of the walls, both at
the exterior sheathing and on the interior
surface of the interior gypsum sheathing.
The investigation of the cause of the moisture
problems identified issues related to
exterior water penetration as the cause of
deterioration of the sheathing. However, the
high levels of mold and deterioration on the
interior gypsum board (Figure 12) could not
be explained by exterior moisture sources
alone. In many cases, all of the visible mold
was located on the interior of the polyethylene
vapor
retarder, while
insulation and
framing to the
exterior of the
polyethylene was observed to be in good
condition (Figure 13).
The investigation revealed the following
issues:
• Electric cadet heaters and thermostat
controls were located at a significant
distance from the exterior
walls and were often not directed at
the exterior walls (Figure 14).
• The interior space layout dictated
that many of the obvious locations for
large furniture, such as beds and
couches, were adjacent to exterior
walls. The location of large furniture
in these areas had the dual effect of
adding insulation to the interior of
the wall and blocking heat flow from
the cadet heaters (Figures 12 and 14).
Figure 10 — Exhaust duct terminated in attic space.
Figure 11 — Curtains prevent air from
circulating at exterior wall and window/wall.
Conditioned air is being directed to the outside
walls from an interior location almost 7m away.
Figure 12 — Mold on interior surface
of exterior wall in bedroom.
Figure 13 — Insulation and studs in good
condition on exterior of vapor barrier.
1 0 6 • HU B B S S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • NO V E M B E R 2 0 1 0
• Units were constructed
over an
unheated parking
garage, and
the interior floor
consisted of a
structural concrete
slab covered
with polystyrene
insulation,
gypcrete,
and carpet. The
detail at the base
of the exterior
walls incorporated
a perimeter
concrete curb that was attached to
the suspended structural slab, creating
a thermal bridge through the
insulation in the sandwich slab
(Figure 15).
• Humidity in many of the units was
higher than expected, and clothing
and other personal effects were
found piled up against the exterior
walls in a number of units.
A simulation of the base-of-wall detail
was performed using Therm 5.26 to better
understand the contribution of the thermal
bridging to the condensation and mold
problem. The model used an exterior temperature
of 0ºC (32ºF) and an interior temperature
of 20ºC (60ºF). At this temperature
and interior relative humidity of 50%, the
dew point of the air is 9ºC (48ºF). The simulation
in Figure 15 models the wall interface
without interior furniture. The coldest
interior temperature is 12.5ºC (54.5ºF),
indicating that the risk of condensation
would be quite low under the modeled conditions.
When the same detail was modeled
with a sofa on the interior of the wall in
Figure 16, the results showed surface temperatures
of 6.7ºC (44ºF), which is significantly
below the dew point of the modeled
conditions. The temperature region between
6.7ºC and 9ºC (44ºF and 48ºF), the dew
point, (shown on Figure 16) is approximately
the same location where interior mold
was observed on the walls during the investigation.
The results of the investigation indicate
that the interior condensation and mold
sources on this building were a result of a
combination of HVAC design, interior space
planning, architectural detailing, and occupant
lifestyle.
Figure 14 — Location/orientation of cadet heater, furniture, and resultant mold.
Figure 15 — Temperature isotherm at base of wall.
Figure 16 — Temperature isotherm at base of wall with sofa adjacent to interior
surface.
S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • NO V E M B E R 2 0 1 0 HU B B S • 1 0 7
RECOMMENDATIONS
The subsequent sections provide recommendations
for architectural design, HVAC
design, and instructions that need to be
communicated to the building occupants
and/or managers to help them better
understand the factors that influence condensation
control. It is important to note
that any one of these items is not likely to
be critical by itself. There generally need to
be several contributing factors to create a
condensation problem. As a result, each of
these recommendations must be viewed in
the overall building context. Concessions
can be made without necessarily compromising
condensation control.
ARCHITECTURAL DESIGN
RECOMMENDATIONS
There are a variety of architecturally
related items that can influence condensation
potential:
• The suites should be compartmentalized
with an airtight perimeter
maintained between the suite and
the corridor and between adjacent
suites. This recommendation
addresses many of the airflow control
issues that were identified in the
field survey.
• Space layout should be designed to
encourage locating large pieces of
furniture away from exterior walls
and windows.
• Poorly ventilated spaces such as
closets should not be located on outside
walls.
• Windows should be located toward
the interior portion of wall assemblies
to encourage “washing” of the
window with interior heated air. This
maintains warmer temperatures at
the surface of the window assembly.
This window placement is also better
from a water-penetration-control
perspective, since the windows are
somewhat protected when recessed.
• Walls should be designed and constructed
with a continuous insulating
layer located somewhere within
the assembly to minimize thermal
bridging and maintain warmer interior
surface temperatures.
• Details should be designed and constructed
to avoid thermal bridging
such as continuous metal sill pans
or anchors.
• Dryers should be closer to exterior
walls to provide shorter exhaust
length.
HVAC DESIGN RECOMMENDATIONS
The majority of multiunit residential
buildings use heating systems that do not
require ducts. Although they have higher
initial costs, ducted systems do have some
advantages, since they permit a wider variety
of fuel sources, easier addition of cooling,
and often better delivery of fresh air
and conditioned air throughout the suite.
We have assumed that nonducted systems
are used. The recommendations for both
heating and ventilation reflect this assumption.
A primary goal of ventilation is to provide
good indoor air quality, which includes
comfortable interior humidity levels.
However, what constitutes good indoor air
quality is not well defined, nor do we customarily
measure it. It is assumed that by
providing sufficient ventilation, good indoor
air quality will be maintained. The recommendations
for ventilation also reflect
ASHRAE Standard 62.2, Ventilation and
Acceptable Indoor Air Quality in Low-Rise
Residential Buildings,7 which requires
whole-house ventilation, local exhaust, and
source control.
Note that some of the recommendations
are directly related to factors that may
affect the intended function and thus condensation
potential, while other recommendations
are directed at managing owner/
occupant impact or intervention.
HEATING
• Locate heating at the exterior walls
or so that heat is directed to and
reaches the exterior walls. For this
purpose, baseboard heating is
preferable to cadet heaters. This is
particularly important when designing
small living spaces, since wall
space for shelving and storage is at
a premium. Heaters that are located
on opaque wall areas will reduce
this space and will likely be modified
or covered over by some occupants
in order to meet their space needs.
• Locate thermal controls on a zoned
basis usually in each room and
located away from the exterior walls
and heaters.
• Use quiet systems to discourage
occupants from disabling them.
Baseboards may be preferable to
cadets for this reason.
• Use systems that require minimal
maintenance since occupants are
likely neither to do the maintenance
nor to notify the owner or manager
that it is required.
• Provide the owner or manager with
comprehensive maintenance and
renewal recommendations for the
heating components.
VENTILATION
• Meet ventilation requirements on an
individual suite basis. This effectively
means that each suite is treated
as an independent dwelling unit
from an HVAC perspective.
• Use low-noise source exhaust fans
(<1.5 sonnes) to encourage proper
use and discourage occupant tampering.
• Use constant, low-volume, wholehouse
fans to provide basic air
exchange for suites.
• Provide fresh air to each suite.
Locate/detail inlets so that they are
not readily blocked by occupants.
Provide adequate makeup air to run
all exhaust fans and dryers effectively.
• Provide the owner/manager with
comprehensive maintenance and
renewal recommendations for the
heating components.
• Take steps to minimize occupant
control over source fans. (Use
humidistat controls, connect to light
switch so that fan is operational
whenever light is on, or set to run
automatically for periods of time
each day.)
Figure 17 provides a conceptual illustration
of the recommendations for an arbitrary
suite in a multiunit residential building.
OCCUPANTS / BUILDING MANAGER
Given the limited understanding that
occupants can be expected to have regarding
the interaction of factors to create condensation
problems, there is a need to reinforce
good operational procedures on an
annual basis through educational initiatives
(flyers delivered to each suite, short
presentations at owner meetings). In addition,
there is a need for building managers
to follow the maintenance and renewals recommendations
provided by the design team
and to visit each suite, particularly during
the winter months, to confirm acceptable
condensation performance.
The following is a checklist of operational
items that owners and building managers
will need to address from time to time:
1 0 8 • HU B B S S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • NO V E M B E R 2 0 1 0
• Locate furniture so heating sources
are not blocked.
• Open drapes/blinds daily to allow
warmer air to reach perimeter walls
and windows.
• Clean exhaust grilles on source fans
(kitchen and bathroom) and dryers.
• Use kitchen exhaust fans when
cooking.
• Use bathroom exhaust fans when
using the bathroom – especially during
a shower.
• Notify the manager of problems with
fans, controls, or condensation.
REFERENCES
1. ASTM, (1993), E783-93, Standard
Test Method for Field Measurement
of Air Leakage Through Installed
Exterior Windows and Doors, American
Society for Testing and Materials,
Volume: 04.11.
2. ASHRAE, (2001), ASHRAE Handbook
– Fundamentals, Atlanta:
American Society of Heating, Refrigerating
and Air-Conditioning
Engineers, Inc.
3. “Multi-Unit Residential HVAC
System Guidelines,” 2005, Report
prepared by RDH Building Sciences
S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • NO V E M B E R 2 0 1 0 HU B B S • 1 0 9
Figure 17 — Conceptual HVAC strategy for multiunit residential building that facilitates effective control of interior
environmental conditions as well as temperatures at exterior walls.
Inc. for Walsh Construction Co.
4. Investigative study performed by
RDH Building Science Inc., 2004
5. THERM 5.2, Lawrence Berkeley
National Laboratory (LBNL).
6. ASHRAE Standard 62.2, Ventilation
and Acceptable Indoor Air Quality in
Low-Rise Residential Buildings,
Atlanta: American Society of Heating,
Refrigerating and Air-
Conditioning Engineers, Inc.
7. B. Hubbs and M. Hircock, “Building
Envelope Performance Monitoring,”
Proceedings Ninth Canadian Conference
on Building Science and
Technology, 2003, and Ongoing
monitoring and data analysis for the
5-year monitoring project performed
by RDH Building engineering for the
Homeowner Protection Office, BC
Housing, and the Canadian Mortgage
and Housing Corporation.
8. National Building Code of Canada,
1995.
FOOTNOTES
1. ASTM E783-93, Standard Test
Method for Field Measurement of Air
Leakage Through Installed Exterior
Windows and Doors, American
Society for Testing and Materials,
Volume: 04.11, 1993.
2. National Building Code of Canada,
1995.
3. ASHRAE Handbook Fundamentals,
American Society of Heating,
Refrigerating and Air-Conditioning
Engineers, Inc., Atlanta, GA, 2001.
4. Multi-Unit Residential HVAC System
Guidelines, report prepared by RDH
Building Sciences Inc. for Walsh
Construction Co., 2005.
5. Investigative study performed by
RDH Building Science Inc., 2004.
6. THERM 5.2, Lawrence Berkeley
National Laboratory (LBNL).
7. ASHRAE Standard 62.2, Ventilation
and Acceptable Indoor Air Quality in
Low-Rise Residential Buildings,
Atlanta: American Society of
Heating, Refrigerating and Air-
Conditioning Engineers, Inc.
1 1 0 • HU B B S S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • NO V E M B E R 2 0 1 0