Skip to main content Skip to footer

Roof Slopes, Ice Dams and Cold Roofs

January 31, 1999

Roof Slopes, Ice Dams and
Cold Roofs

By Ian Mackinlay, FAIA and Richard S. Flood
IN SNOW COUNTRY IT IS TRADITIONAL TO
design buildings with sloping roofs. Quintessential mountain
architecture embodies various forms of the Swiss
chalet, often without the user’s understanding of its design
principles. In New England, it is difficult to find a residential
building without a steeply sloping roof. The conceptual
underpinning of this almost universal design response to the
snow and cold is that it is desirable to shed the snow off the
roof onto the ground as quickly as possible, both to lower the
load on the building and to reduce the chance of leaks. In the
public’s mind, good snow country design has become synonymous
with the sloped roof. That sloping roof form has taken
on a life of its own, which many designers and builders consider
to be self-justifying. They believe that their duty to deal
with the snow is satisfied by slope alone and no additional
thought or investigation is required. Those who do choose to
look further generally consider no more than the building
official’s mandated snow load and the character of the roof
surface material. Perhaps the designer elects to apply a standing
seam metal roof or a shingle roof with the eaves faced in
stainless steel sheet metal, as is very common in New
England. Unfortunately, these techniques do not always
work. A prudent roof designer must look deeper into what
actually happens when snow falls on a sloping roof.
Unless the fallen snow slips away quickly (and even on slippery
roof surfaces it often does not), building heat causes
melting at the junction of the roof material and the snow
blanket. This moisture remains liquid, protected from the cold
air by the insulating properties of the snow. The water runs
down the roof slope to the eave edge where it refreezes into
an ice dam. These ice dams are the single most serious problem
with pitched roofs in snow country.
Snow-covered, sloping roofs with ice dam formations may
be subject to loads greater than either ground or flat roof
snow loads. These circumstances are created by a combination
of site-specific environmental factors, the building’s
unique architecture, and its internal temperature. When these
design ingredients are ignored or not fully understood, the
result is a project where large, heavy ice dams are formed
(Figure One).
In many instances, the mass of ice and the water reservoir
backed up behind it exert a force on the structure that
exceeds the loads mandated by the building code. Ice dams
also create hydrostatic pressure at the roof surface which can
force water through tiny cracks which otherwise would not
leak. Impermeable underlayment is required from the eave to
at least five feet above the line of the exterior heated wall.
This is especially necessary where buildings have large
unheated eaves and building heat melts snow at the roof surface.
Snow meltwater, held on the roof by eave ice, adds to
Sawtooth Wilderness Information Center near Sun Valley, Idaho, March An interesting example of snow sticking to a metal roof. Camellian Bay
1989 © Ian Mackinlay (Lake Tahoe), CA, February 1985. © Ian Mackinlay
January 1999 Interface • 5
Rick Flood had just come down from the roof of the Hewlett Cabin, in Sugar Bowl, CA (Donner Pass,
at 2040′ elevation) on Nov. <3, 1998 and gotten out his camera to record a 15″ snow-load when the
snow cascaded off the roof as he released the shutter. Cold roofs work/ © Rick Flood
both the weight of the snow and the hydrostatic pressure.
The continuing melt/run down/freeze action can build ice
dams to substantial height and mass. The deeper the snow on
the roof, the larger the potential dam. Ice is heavier than
snow and water is heavier than ice per unit volume. Thus, ice
dams produce roof loads far greater than the same volume of
drifted snow.
Other factors which can significantly increase loading or
leakage problems on sloping roofs include rain-soaked snow
pack, snow retentive roofing surface, snow drifting on roof
slopes in the lee of storm winds, and projections through the
roof surface such as dormers and plumbing vents. Roof geometry
and orientation also play an important role in retaining
snow on the roof. Ice dams can prevent snow shedding even
from steeply sloped roofs with slippery surfaces. When these
design ingredients are ignored or not fully understood, high
roof snow loads and massive leakage can occur. The designer
cannot change nature’s environmental forces, but by understanding
the snow’s capricious characteristics,
a satisfactory design solution can be achieved
for most conditions.
On a typical building in North America
where the ridge runs east and west, the northfacing
sloping roof faces away from the sun,
and often is in the lee of the storm winds.
Building heat produces snowmelt. With a typical
shingle roof surface, there is a great tendency
for retention of the snowpack on the
roof. The south facing roof slope often faces
into the storm winds. The north facing roof
slope, with a typical slope of 5:12, receives
the least solar exposure (almost none at midwinter).
Any gap in the roof insulation will
lead to excessive melting of the snow blanket
on the roof. Meltwater freezes at the
eaves which are unheated. These conditions
can lead to ice dams several
feet high at the roof edge, massive
roof loads and impressive icicle formation.
Such conditions can lead to much
more roof load than that calculated by
applying the factors given in the building
codes. Due to drifts and ice
damming, the lee-side, north-facing
roof could readily be subjected to 1 –
1/2 to 3 times the ground snow load.
This can be 200% to 500% greater
than the original sloped roof design
load as required by current regulations.
At the same time, due to wind stripping
and solar radiation, the portion of
the roof that is south-facing (on the
windward side of the ridge) could have
very little snow cover. This uneven
roof loading is often overlooked by
roof designers.
Projects with these characteristics
suffer from significant north roof ice damming and unbalanced
loading conditions, even in light snow years. North
side dormers, down slope chimney projections and vent pipes
in the roof field contribute to the north side snow/ice
buildup. Some relief through snow shedding might be
obtained if the roof is designed with standing seam metal roof
rather than shingles. Ice dam build-up is magnified by roof
surfaces that retain the snow blanket on the roof.
Unfortunately, even standing seam metal roofs can retain ice
dams at sloping roof eaves, as the ribs freeze into the snow
pack and prevent the snow from sliding. W’hen the snow pack
does cascade from such metal roofs, it comes without warning
and with great force (see photo this page). Without manual
roof snow/ice dam removal several times per winter season,
the north side roof would be overstressed structurally most of
the time, even in moderate snow years. Hand snow removal
can cause great damage to the roof. If the cold weather strate-
SNOW DRIFT———
WATER SATURATED SNOW
MELTWATER
DAMMED WATER
ICE DAM
ICICLES
UNHEATED EAVE
5 ft. 15 ft.
COMPOSITION
SHINGLES
FIGURE ONE
INCREASE IN SNOW LOAD DUE TO DRIFTING AND ICE DAM FORMATION
36° N. LATITUDE ; 2499m ( 8200 FT. ) 250 PSF GROUND SNOW LOAD
6 • Interface January 1999
gy is to periodically remove the
snow, then suitably durable roof surface
materials must be selected.
One strategy for ice dam mitigation
is through the use of a snow
arrester/heated gutter combination.
The snow arresters are placed at the
edge of the eave and the heated gutter
is placed immediately upslope of
the arrester. The arresters retain the
snow blanket on the roof. The snow
blanket insulates the meltwater,
keeping it from freezing. The heated
gutter intercepts the meltwater prior
to its exiting the snow blanket and
keeps the intercepted water from
freezing as it is drained away, thus
reducing ice damming and roof loading.
This technique is especially
effective where outdoor pedestrian-
/vehicular circulation space occurs
below the eave. Proper design will
often result in snow loads not exceeding
ground snow load on roofs
where no load reductions due to
slope are taken. It is important to design
the snow arrester for the full
weight of the snow blanket all the
way from roof edge to ridge. This
must be done regardless of the frictional
resistance of the roofing material.
Where unprotected parking or
decks are below sloping roofs, no
cascading of snow and ice is permissible.
(Figure Two). A steel tube arrester
bar is often required, due to high
structural load. The snow arrester
tube must be firmly tied to the basic
structure and allowance must be
made for uneven loading. When support
metal tubes are carried into
warm, heated, interior space, they
SNOW BLANKET
SHINGLES
INSULATION
HEATED
GUTTER
SNOW
ARRESTER
SUN
SNOW REMOVED
BUILDING
HEAT
-S.S. CABLES
INSULATION SUPPORT TUBES
PARKING AREA
SNOW REMOVED
FIGURE TWO
DECK
2m
SNOW ARRESTORS PROTECT PEOPLE ON DECKS AND IN PARKING AREAS
38 30’ N. LATITUDE; 1400m (6300 FT.) 150 PSF GROUND SNOW LOAD
SNOW ARRESTER BAR
GUTTER LIP—————– –
BELOW ROOF/GUTTER FLASHI
TO ALLOW WATER OVERFLOW
SNOW ARRESTER
SUPPORT TUBE
SHINGLE ROOFING
ALIGNMENT———————–
UPSLOPE FACE OF SNOW
ARRESTER 4 DOWNSLOPE (FRONT)
OF CUTTER. TO ALLOW SNOW
TO INSULATE GUTTER
SNOW ARRESTER WITH HEATED GUTTER
MINIMUM INSULATING
SNOW BLANKET HEIGHT
( 0.3 m, 1 FT. )
MELTWATER
BARRIER
INSULATED
SUPPORT TUBE
FOR CONDENSATION
PREVENTION
INSULATED
DRAIN PIPE
50cm
GUTTER LIP
ABOVE ROOF LEVEL TO PROVIDE A
BASE RESTRAINT FOR SNOW BLANKET
HEATED GUTTER
FIGURE THREE
must be insulated within the soffit
and rafter space to prevent condensation.
The upslope face of the arrester bar must be positioned
to restrain a minimum 12-inch thick snow blanket. This
thickness of snow blanket is usually sufficient to insulate
and protect the roof meltwater from freezing. The heated
gutter is positioned to align the front (downslope) face
nominally in the same plane as the upslope face of the
arrester bar. This is done to allow the snow blanket to completely
cover the gutter and leave only a minimal roof surface
downslope (Figure Three).
The front lip of the gutter deviates from standard rain
gutters in that it extends above the plane of the roofing
approximately two inches. This high front lip will stop
small amounts of snow that slide under the arrester bar and
January 1999
ft. 10 ft.
A heated gutter up-roof of a snow arrester. Incline, NV. © Ian Mackinlay
Interface • 7
The danger of ice dams on sloping roofs. An accident waiting to happen.
King’s Beach (Lake Tahoe), CA, January 1993. © Roh Mackinlay
will restrain the bottom of the snow blanket as it tends to
migrate downslope. The lip further helps to keep the gutter
snow covered and insulated, even when only a relatively small
amount of snow is on the roof. The front lip is still below the
high point of the gutter back to allow a normal rain water
overflow condition.
The gutter is heated with two rows of snowmelt cable.
The cable is electrical, self-regulating, with a conductive core.
In this manner the roof meltwater is kept from freezing in the
gutter. The heat cable is also installed in the piped/downspout
drainage to ensure a free-flowing
path to on-site drywells or storm
drains. The heat trace must be carried
down into the drywell below the frost
line. Heat cables burn out from time
to time and must be replaced. The
design should allow for this contingency.
With snow arresters and heated
gutters, ice dam formation is greatly
reduced as the gutter intercepts
almost all of the roof meltwater without
permitting it to refreeze while the
arrester retains the snowpack. This
limits ice dam/icicle formation and
protects people and property below.
In heavy snow years, or under certain
drifting conditions, the snow
blanket may be of such depth that
snow cornices will occur over the top
of the arrester bar. If the snow cornice
becomes a hazard, it can be
8 • Interface
manually removed relatively easily and safely by using the
arrester bar as a guide for the removal tool. Removal of the
hazardous snow cornice does not jeopardize retention of the
insulating snow blanket, nor does it damage the roof surface.
A cover of snow should be left on the roof at all times during
winter months.
Provided there is an unoccupied area below the lower
edge of the sloping roof for snow slippage, the best method
of mitigating ice dams is to incorporate a “cold roof” into the
design. The cold roof is an “umbrella” over the heated portions
of the building. Cold, outside ambient air is allowed to
freely circulate in a roof cavity directly below the roofing surface
and its supporting substrate. This ventilation cavity is
above the primary insulated roof. The ventilation cavity must
have sufficient depth to promote an unrestricted flow of outside
air. Air volume must be great enough to absorb building
heat and vent it away without contributing significantly to an
increase of roof surface temperature. Use of a slippery roofing
material will promote shedding of the snow blanket. As a
word of caution, the falling roof snow needs a dump area that
will not fall back against the wall of the building. The design
must consider the effects of the snow berm that will be created
on the ground below the roof slope. An alternate design
might use snow arresters to hold the snow blanket on the roof
as described above.
For conventional wood frame buildings located in an area
of heavy winter snow, the regulatory ground snow load might
be 400 Ibs/sf. The cold roof structure is comprised of nominal
12-inch deep manufactured wood truss joists at two feet on
center. The joists sit on a vapor retarder covered continuous
plane of wood decking which is structurally supported by
glue-laminated beams 4-1/2 feet on center. Plywood roof
sheathing spans the top of the joists and provides support for
a standing seam metal roofing system. The plywood forms
the top of the deep ventilation cavity. The joists are laterally
strengthened with metal “X” bracing in lieu of solid blocking
January 1999
at the beam lines to ensure an open ventilation
cavity. The bottom half of the joist space
is filled with R-38, 6-inch thick closed cell
polyurethane insulation sealed on its surface.
The upper half is left open, providing a ventilation
cavity (Figure Four).
Structurally, the lateral force transfer of
the snow loaded roof diaphragm into the
shear walls below must be accomplished. In
this example, lateral design snow load uses
one third of the roof design snow load. The
slippery nature of the metal roof predicated
the use of this value. One half of the roof
design would probably be more appropriate
for a nonslippery roof or a roof designed with
snow arresters. Normally, solid wood blocking
would be used between the joists to provide
the force path. In this case, solid blocking
would negate any airflow into the cold roof
cavity. To solve this problem, a series of steel
plates with a hole cut out will be used to transmit the horizontal
forces to the peripheral shear walls and still permit air
circulation.
Pressure equalization between adjacent cavities is achieved
by having the wood joists factory-punched with one inch
diameter holes at 12 inches on center along the upper quarter
point of their plywood web.
The gable roof thus comprises a series of 24-inch-wide by
6-inch ventilation cavities running from eave to ridge on both
the north and south sides of the roof. The eaves are provided
with continuous screened vents with a free area approximately
75% of the cross sectional area of the ventilation cavity. The
ventilation cavities are vented up through the chimney structures
at the ridge, utilizing the metal roof ridge cap as an airflow
duct (Figure Five).
Cold roofs work best when the outside ambient air temperature
remains cold, below freezing, day and night during
the snow season. Where the winter air temperature is often
above freezing at midday, there will be some melting of the
snow blanket, even with a well designed cold roof, and some
ice damming may occur at the eaves and some icicles may
form. This ice damming will be far less than it is where the
building heat significantly contributed to the melting of the
snow blanket.
Ground snow snow loads are generally used as the basis of
determining design snow loads for the roofs of buildings. Flat
roof snow loads are usually assumed to be some fraction of
ground snow loads due to wind stripping. If the roof slopes,
roof snow loads are often further reduced by the “slope factor.”
This reduction is generally greater as the slope becomes
steeper. Our studies have shown that these reductions may
not be justified in many cases. Roof loads may be two or even
three times ground snow loads due to the tendency of ice
dams to hold snow on the roof. These loads may be distributed
highly asymmetrically on the roof structures, producing
unbalanced loads. Snow arresters with heated gutters or cold
roofs may be effectively used to reduce the effect of ice dams
on sloping roofs. A clear understanding of these principles
will make life more pleasant for designers and builders working
in the land of snow and cold.
About the Authors
Ian Mackinlay, FA1A
Ian Mackinlay is president of Ian Mackinlay Architecture Inc., San Francisco,
CA. He is a licensed architect in 14 states and Guam, was named a Fellow of the
American Institute of Architects (AIA) and has been on its Committee on Design.
Mackinlay has earned over 50 awards for Architectural Design Excellence and is a
three-time winner of America’s highest a ward for constructed architecture, the AIA
National Award. He has published widely on snow country design and spent six years
in Europe as Chief Engineer with European Exchange System. Mackinlay’s interest in
architectural problems of the snow and cold has led him to publish and lecture on the
subject and to be appointed to the Loads Subcommittee of the American Society of Civil
Engineers (ASCE).
Richard S. Flood has been a licensed architect for 21 years. He has been assodated
with Ian Mackinlay for the last 28 years and has been involved with the technical
design and failure analysis of more than 25 major projects in the snow and cold. Currently he is consulting with major ski resort developments in
Colorado and Idaho. In 1996, he co-authored a paper, “The Impact of Ice Dams on Buildings in Snow Country, ” which he co-presented with Ian
Mackinlay at the Third International Conference of Snow Engineering in Sendai, Japan.
January 1999 Interface • 9