Skip to main content Skip to footer

Uplift Resistance of Existing Roof Decks: Recommendations for Enhanced Attachment During Reroofing Work

January 9, 2003

Photo 1: This aggregate-surfaced, built-up membrane blew off as a result of lifting and peeling of the metal edge flashing. Historically, lifting
and peeling of edge flashings and copings (and subsequent membrane lifting and peeling) have been the most common wind failure modes for
membrane roofs.
14 • Interface January 2003
Introduction
Although deck failure has not been a common failure mode
in the past, for a roof assembly to achieve good high-wind performance,
the roof deck must be sufficiently strong and adequately
attached to resist the design wind loads. The good
historical performance of decks is primarily attributable to failure
of the roof coverings (which is typically caused by lifting and
peeling of the metal edge flashing or coping1), rather than good
uplift resistance of decks (see Photo 1).
With loss of the roof covering, the uplift load on an air permeable
deck (such as steel and wood) is substantially reduced.
With greater attention being given to the wind design of roof
systems and metal edge flashings and copings, it is reasonable to
expect that for many roofs, the weak link in the uplift load path
will be the deck attachment. Therefore, an increased incidence
of failure of older decks will likely occur unless greater attention
is given to their attachment.
Designers and contractors involved in reroofing projects currently
have insufficient design guidance concerning upgrading
the wind uplift resistance of roof decks. In some cases, the existing
deck and attachment features are adequate to resist current
design loads. However, more commonly, the deck attachment
does not have adequate resistance. In some of the cases where
the deck is inadequately attached, it is appropriate to strengthen
the deck attachment as part of the reroofing work, while in others,
it is appropriate to accept the existing connections as they
are.
The decision to strengthen or not to strengthen the deck’s
uplift resistance depends on a variety of factors, including building
code requirements, the magnitude of the current design wind
loads compared to the uplift resistance of the existing deck
attachment, the importance of the building (e.g., a hospital or an
office building), whether or not the building is located in a highwind
region, and the type of deck and deck connection.
This article will explore these issues and provide guidance to
assist designers and contractors involved in reroofing work.
Code Compliance
It is incumbent upon the reroofing designer to determine the
building code requirements pertaining to the reroofing project. If
there are ambiguities in the code requirement, the designer
should seek clarification from the building official. As an example,
the following are from the 2000 edition of the International
Building Code (IBC).
Abstract
The uplift resistance of roof decks on many buildings in the U.S. is quite limited, particularly at the perimeter and corners of buildings
constructed prior to the mid-to-late 1980s. As greater attention is given to the wind design of roof coverings, an increasing number of
deck failures will be experienced during high winds unless the uplift resistance of weak decks is increased. This article provides
guidance for assessing the need to upgrade the uplift resistance of roof decks as part of the reroofing work.
UPLIFT RESISTANCE OF EXISTING ROOF DECKS:
RECOMMENDATIONS FOR ENHANCED ATTACHMENT DURING REROOFING WORK
— By Thomas L. Smith, AIA, RRC —
January 2003 Interface • 15
Section 1510.1 requires reroofing
(either tear-off and replacement, or
re-covering) to comply with Chapter
15 (which specifies requirements for
roofs on new buildings). If up to 25%
of the roof is reroofed in any 12-
month period, the new work is to
comply with Chapter 15, but the portion
of the roof that is not reroofed
can be left as is. If over 25% is
reroofed, the entire roof needs to
comply with the new roofing requirements.
However, the provisions in
1510.1 apply to the roof covering
(i.e., everything above the deck), not
the roof deck.
Provisions in Chapter 34 pertain
to the deck itself. Section 3401.2 states that buildings and parts
thereof are to be maintained in conformance with the code edition
under which they were installed. Hence, the intent of the
existing structures chapter is to permit existing decks to remain
as originally constructed. However, if the deck has deteriorated
over time, Section 3402.2 is applicable. It states that if “unsound
or otherwise structurally deficient” structural elements (including
decks) are found, the elements shall be made to conform to the
requirements for new structures. Therefore, if severely corroded
decking is found, the decking must be repaired or replaced. The
repaired or replaced decking must have sufficient strength to
meet current load requirements.
In summary, for reroofing projects under the jurisdiction of
the 2000 IBC, the roof covering must comply with the requirements
for reroofing. However, upgrading, repairing, or replacing
the deck is not required by the code unless the deck has deteriorated.
Compare Original and Current Wind Loads
Although the IBC does not require uplift resistance of the
existing deck to be strengthened, it is prudent for the reroofing
designer to compare the uplift loads derived from the building
code under which the building was originally designed, to the
uplift loads derived from the current building code. This is especially
important if the building was designed to the 1979 (or earlier
editions) of the Uniform Building Code (UBC) or the Standard
Building Code (SBC), or the 1984 (or earlier editions) of the BOCA
Basic/National Building Code (B/NBC). In these editions, a uniform
uplift pressure was used throughout the entire roof area.
However, in subsequent editions, substantially higher loads were
applied to roof perimeters and corners. Therefore, decks and the
deck support structure on buildings designed to these earlier
code editions are often substantially under-designed in perimeter
and corner areas when compared to current design uplift loads.
To illustrate the magnitude of the difference between current
design practice and that of a few years ago, the following tables
give the design uplift loads derived from the 1979 UBC, the
1979 SBC, the 1984 B/NBC, and from ASCE 7-982 (which is referenced
in the IBC). The example building is 9.1 m (30’) high, with
a low-slope mechanically attached roof membrane in a suburban
exposure (Exposure B). The building for Table 1 is located in
southern Arizona. The building for Table 2 is located at the
southeastern tip of Florida. The glazing for this building is not
protected against breakage from wind-borne debris.
Check Uplift Resistance
In addition to comparing the original and current wind
design loads, it is prudent for the reroofing designer to evaluate
the uplift resistance of the deck. (If the designer is not a licensed
architect or engineer, the designer or building owner should
retain a licensed architect or engineer to perform this evaluation.)
If drawings for the original construction are available, the
design uplift resistance of the deck can be approximated.
Information derived from the drawings (such as deck span, deck
fastener type, and spacing) should be field verified. If drawings
are not available, information for this evaluation will need to be
obtained from a field investigation.
Evaluation of the deck’s resistance may reveal that the deck
has greater or less uplift resistance than would be expected by
calculating the uplift loads derived from the code under which
the building was originally constructed.
As part of this evaluation, spot checking the condition of the
deck and deck attachment should be conducted during the
reroofing design process to determine if the structural integrity
of the deck and deck connections have been degraded by water
leakage or condensation. Where possible, the underside of the
deck should also be evaluated. The evaluation should be conducted
by an investigator experienced with the type of deck
used on the building.
If a tear-off is contemplated, the entire deck surface can be
evaluated during the reroofing work. If a re-cover is contemplated,
a more extensive evaluation should occur during the design
process:
• Several large test cuts (600 mm x 600 mm [2 feet x 2 feet] minimum) should be taken. The number of cuts will
depend on several factors, including the deck type, roof
size, leakage history, and extent of wet insulation.
• Nondestructive evaluation (NDE) for moisture within the
roof system should always be performed (except for those
systems where NDE is not applicable). If wet areas are
found, large test cuts should be taken in the wet areas to
assess deck condition.
Table 1: Design Uplift Loads in Southern Arizona
Field of Roof Roof Perimeter Roof Corners
79 UBC 0.718 kPa (15 psf) 0.718 kPa (15 psf) 0.718 kPa (15 psf)
79 SBC 0.479 kPa (10 psf) 0.479 kPa (10 psf) 0.479 kPa (10 psf)
84 B/NBC 0.790 kPa (16.5 psf) 0.790 kPa (16.5 psf) 0.790 kPa (16.5 psf)
ASCE 7-98 0.718 kPa (15 psf) 1.149 kPa (24 psf) 1.77 kPa (37 psf)
Field of Roof Roof Perimeter Roof Corners
79 UBC 1.796 kPa (37.5 psf) 1.796 kPa (37.5 psf) 1.796 kPa (37.5 psf)
79 SBC 1.628 kPa (34 psf) 1.628 kPa (34 psf) 1.628 kPa (34 psf)
84 B/NBC 1.939 kPa (40.5 psf) 1.939 kPa (40.5 psf) 1.939 kPa (40.5 psf)
ASCE 7-98 2.538 kPa (53 psf) 3.878 kPa (81 psf) 5.506 kPa (115 psf)
Table 2: Design Uplift Loads at the Southeastern Tip of Florida
16 • Interface January 2003
Building Importance
The building’s importance should also
be evaluated when considering whether or
not to upgrade the deck’s uplift resistance.
For example, if the deck is overstressed
when current design uplift loads are
applied, it may be appropriate to not
upgrade the structure if it is an office
building. But if it is an essential facility
(i.e., a Category III or IV building as
defined in ASCE 7-98), such as a hospital
or school, it would be prudent to upgrade
the deck’s uplift resistance. Upgrading the
deck’s uplift resistance is also prudent on
buildings that contain expensive equipment
or critical operations (such as computer
centers and research labs), even
though these types of buildings are not
designated as essential facilities.
For essential facilities and buildings
that contain expensive equipment or critical
operations, it is also prudent to consider uplift resistance of
the deck support structure. If the deck is well attached to the
roof framing, the attachment of the beams/joists may be the
weak link in the uplift load path (See Photo 2), or buckling of the
beams/joists may be the weak link. Upgrading the roof framing
can be very difficult and expensive, but if high reliability is
important, framing upgrade is sometimes necessary.
Page 16
Half Page Horizontal
4-Color
CertainTeed
Pick-up from 11/02, Page 18
Photo 2: Because of inadequate joist attachment, the entire roof
assembly (i.e., joists, plywood decking, and asphalt shingles) blew off
as a single unit and landed about 135 m (450′) from the building.
The joists were merely toe nailed to the top plate of the wall.
High Wind Areas
Deck uplift resistance becomes increasingly important as
design uplift loads increase. For buildings located in areas with a
basic wind speed (as defined in ASCE 7-98) greater than 40 m/s
(90 mph) for a 3-second peak gust, upgrading the deck’s resistance
should be considered if its resistance is significantly lower
than that required to meet the
current building code.
Upgrading deck resistance
on buildings in excess of
approximately 30 m (100’)
should also be considered.
Because cast-in-place concrete
decks are common on tall
buildings, and this type of
deck typically possesses great
uplift resistance, the need for
deck upgrade on tall buildings
is infrequent.
The decision to upgrade
the deck resistance is usually
based on economic considerations
pertaining to property
damage and interrupted use of
the property,
or because
the building
provides a
vital service
(such as a
hospital).
However, the
decision to
upgrade the
deck on tall
buildings
may be based
on concerns
pertaining to
injury or
death from
wind-blown
roof debris.
(See Photo 3)
Deck Type and Connection
As noted above, cast-in-place concrete decks typically offer
exceptionally good uplift resistance. However, this is not the
case with precast concrete decks. Although precast decks are
heavy, they can be lifted during high winds (see Photo 4). The performance
of these decks is very dependent upon the connection
of the deck to the support structure (as is the case with most
deck types).
If precast Tee decks are designed for gravity loads only, large
uplift forces can cause failure once the uplift load exceeds the
dead load of the particular element.
The uplift performance of other deck types primarily depends
upon the adequacy of the attachment to the supports.1
(See Photo 5) Many deck types designed in accordance with the
1979 UBC, 1979 SBC, or 1984 B/NBC, or earlier versions thereof,
possess very limited uplift resistance.
Steel decks are commonly attached with puddle welds.
Puddle welds are often poorly made, and are sometimes inadvertently
broken during roofing work because the welds are inadequate
to carry the loads induced
during the work. During the reroofing
design investigation as well as
the reroofing work itself, if the deck
is steel and attached with welds, special
attention should be given to the
adequacy of those welds. If broken
or poorly executed welds are discovered,
new attachments should be
made. Screw attachment is recommended
for greater reliability.3
Recommendations on the magnitude
of safety factors for deck attachments on essential facilities
are given in Reference 4.
Conclusion
Upgrading the deck’s uplift resistance (particularly at the roof
perimeter and corners) can be a prudent component of many
reroofing projects. After giving due consideration, it may or may
not be appropriate to upgrade. However, upgrading should
always be considered, based on the factors discussed in this
paper.
In most cases, the deck upgrade evaluation typically occurs
during the reroofing design process because upgrading the deck
from below is usually very difficult and expensive. However, for
some buildings, such as essential facilities located in hurricane-
Photo 3:
This 14-
story building
had a
built-up
membrane
attached to
a lightweight insulating concrete (LWIC) deck that was cast over metal form
decking. The LWIC was reinforced with steel mesh, but the mesh was near
the lower portion of the LWIC (where it should have been able to resist gravity
loads). However, during high winds, large windows at the top floor failed
due to over-pressurization. This resulted in an increase in the internal air
pressure in the floor below the roof and increased the uplift load on the deck.
Because the reinforcing in the LWIC was not located in the upper portion of
the deck, the LWIC broke apart and the roof membrane ruptured.
Fortunately, during this particular storm, the 1.8 m (6’) high parapet prevented
most of the debris from blowing off the roof.
January 2003 Interface • 17
prone regions, it is often prudent to evaluate the deck’s resistance
prior to the need for reroofing. If the deck is a prime candidate
for upgrading, it can be prudent to perform upgrading and
reroofing before the existing roof reaches the end of its service
life. 
References
1. Smith, T.L. (1994), “Causes of Roof Covering
Damage and Failure Modes: Insights Provided
by Hurricane Andrew,” Proceedings of the Hurricanes
of 1992, American Society of Civil Engineers,
New York, New York, USA, pp. 303-312.
2. Minimum Design Loads for Buildings and Other
Structures, ASCE 7-98 (2000). American Society
of Civil Engineers, Reston, Virginia, USA.
3. Smith, T.L., “Deck Attachment: Anchoring the
Roof Covering’s Foundation,” Professional Roofing,
National Roofing Contractors Association,
Rosemont, Illinois, USA, December 1995, p. 50.
4. Smith, T.L. and McDonald, J.R., “Preliminary
Design Guidelines for Wind-Resistant Roofs on
Essential Facilities,” Proceedings of the 7th U.S.
National Conference on Wind Engineering, The Wind
Engineering Research Council, Los Angeles,
California, USA, Volume II, 1993, pp. 709-718.
EDITOR’S NOTE: This article was adapted from a paper presented in June
2001 in Ottawa, Canada, at the International Conference on Building Envelope
Systems and Technologies (ICBEST). The conference was organized by
the National Research Council of Canada, Institute for Research in Construction.
18 • Interface January 2003
Thomas L. Smith is president of TLSmith Consulting Inc. He specializes in architectural technology
and research with an emphasis on roof systems. Smith is a licensed architect and a registered roof consultant.
From 1988 to 1998, Tom was the research director for the National Roofing Contractors
Association (NRCA). Prior to that, he was in private practice in California and Alaska. He has designed
roofs from the arctic to the tropics and is an internationally recognized expert on roofing technology. In
particular, he is recognized for his expertise related to wind performance of roof systems. Smith’s wind
expertise is based on a unique combination of extensive experience with wind damage investigation and
analysis, involvement in academic and applied research, involvement in standards development and
preparation of wind design guidelines, experience in designing roof assemblies in high-wind regions, and
teaching. Smith has been a member of ASCE and worked on its roofing committees, including
“Minimum Design Loads for Buildings and Other Structures,” since 1990.
ABOUT THE AUTHOR
THOMAS L. SMITH,
AIA, RRC
Photo 5: This 38 mm (1-1/2″) deep 0.76 mm (22
gauge) steel deck was puddle welded at every other
rib to steel beams, which were spaced at 2.1 (7′) on
center. Large areas of decking blew off at a corner
and along one of the walls.
Photo 4: A precast concrete twin-tee deck panel was
lifted and thrown back toward the center of this roof.
Three large roll-up doors collapsed, which increased
the internal air pressure in the building and
increased the uplift load on the deck. Although precast
deck panels are heavy, they need to be anchored
to resist large uplift loads.