Reviving a Historic Landmark: Restoration and Monitoring of “Detroit’s Largest Art Object,”, the Iconic Fisher Building

July 11, 2024

THE FISHER BUILDING, an iconic example
of Art Deco architecture, stands as a National
Historic Landmark and a symbol of Detroit’s
rich architectural heritage from the golden
age of the automobile. Although it is often
called Detroit’s “largest art object,” neglect
and deferred repairs have taken a toll on
its magnificent facade in recent years. In
response, a new owner group has stepped
forward, dedicated to the restoration of this
architectural landmark. This article presents a
summary of the findings and recommendations
derived from a comprehensive facade
assessment program performed by my firm,
ZS, highlighting the utilization of LiDAR
(light detection and ranging) technology in
conjunction with high-resolution photography
to monitor facade movement.
Feature
Reviving a Historic Landmark:
Restoration and Monitoring of
“Detroit’s Largest Art Object,”
the Iconic Fisher Building
By Ziad Salameh, PhD, PE
This paper was presented at the 2023 IIBEC
Building Enclosure Symposium.
Interface articles may cite trade, brand,
or product names to specify or describe
adequately materials, experimental
procedures, and/or equipment. In no
case does such identification imply
recommendation or endorsement by the
International Institute of Building Enclosure
Consultants (IIBEC).
OVERVIEW OF THE FISHER
BUILDING COMPLEX
The Fisher Building complex encompasses a
30-story tower, two 11-story wing structures, the
Fisher Theatre, and an attached parking structure
(Fig. 1). The complex, as a whole, encompasses
an entire city block along Grand Avenue in the
city’s New Center district.
Each component within the complex
possesses distinct structural framing and exterior
wall construction. The tower and wings feature
steel-framed and transition masonry walls.
Steel-framed/transition masonry walls consist of
structural steel-framed columns and spandrel
beams that are fully encased with masonry
construction or poured concrete. The inner
wythes (backup) of the walls typically consist of
brick masonry or extruded clay tile blocks that
infill the plane of the main building structural
system. The inner wythes are header bonded to
each other (via bonded masonry construction).
The exterior wythe of the walls is supported
by rolled steel shapes attached with lateral tie
anchors into the inner wythes’ construction.
The parking garage and theater are composed
of transition mass masonry walls. The parking
garage exterior wall cladding varies along the
elevations and consist mainly of either granite,
ashlar-stone decorative cut units, or clay brick.
The granite cladding is present at partial height
of the first floor on the north elevation of the
Figure 1. The Fisher Building in Detroit, Michigan.
©2024 International Institute of Building Enclosure C 24 • IIBEC Interface onsultants (IIBEC) July/August 2024
garage. The remaining garage elevations are
clad with limestone, which turns the corner for
a partial bay width on the west elevation. The
remaining portion of the garage west elevation
is primarily a solid brick wall. The Fisher Theatre’s
walls consist of granite-face brick for a partial
height of the first floor of the west wall. The
remainder of the west facade as well as the south
and east facades are stone ashlar units with
glazed brick features. The north facade is brick
with the limestone from the west facade turning
the corner for a small width.
EXTERIOR WALL COMPOSITION
AND CLADDING MATERIALS
At the tower and wings, the walls’ cladding (the
exterior wythe) type varies along the elevations
and consists mainly of either marble, granite,
or decorative cut units made of ashlar stone.
The granite cladding is mainly present on the
first three floors. The remaining floors above
are either clad with marble or limestone. All the
walls are articulated with numerous changes in
plane with the main feature being alternating
mullions and piers of various depth, width, and
articulation. Other main features include bronze
statues, dentils, carved ornaments, various types
of granite and marble insets, stone soffits, carved
brackets, carved figures, and metal spandrels.
The size and thickness of the ashlar decorative
cladding units varies significantly and include
units that are as large as 5 ft x 5 ft x 24 in.
(1.5 m x 1.5 m x 0.6m) thick to units as small
as 16 in. x 16 in. x 3 in. (406 mm x 406 mm x
76 mm) thick. The exterior walls’ backup
construction consists of bonded clay brick/clay
tile block construction or concrete-encased
framing (Fig. 2). The marble, granite, and stone
cladding is gravity supported using embedded
steel plates and shelf angels that are connected
mechanically to the backup wall construction.
In addition, the cladding is laterally tied to the
backup wall construction using brass Z-shaped
dowels at the marble and granite elevations
and mild steel anchors/dowels at the stone
elevations. Adorned with intricate marble cut
details such as mullions, piers, statues, dentils,
and carved ornaments, the facade exemplifies
the meticulous craftsmanship of its era.
ASSESSMENT PROCESS
To evaluate the condition of the exterior walls,
a combination of three-dimensional (3-D)
laser scanning, high-resolution photography,
and hands-on examinations were employed.
A 3-D laser scanning approach was utilized
with a high-speed, infrared laser (coupled
with high-resolution photography) to quickly
obtain millions of 3-D measurements (Fig. 3).
The scans were then registered, so that each
individual scan is aligned within a group of
scans to form a “point cloud.” For this project,
we generated a composite point cloud model
that accurately depicted the as-built/as-existing
conditions of all elevations. We then utilized
the point cloud model to generate as-built
elevation plans that depicted and quantified
all observed exterior walls’ distress conditions.
These same elevation plans will then be used
in the future to prepare the repair construction
documents. Additionally, through the use of
the state-of-the-art scanner and supporting
software, subsequent laser scan point clouds
can be generated and utilized to perform facade
monitoring via future plane deviation analysis
for each exterior wall elevation. This analysis
technique can detect out-of-plane movement as
small as 1 in. (25 mm) and will enable remote
monitoring and movement/displacement
detection at areas of localized distress. The
results of this analysis will then enable the
owner to strategically prioritize and phase
locations that require repairs.
We also performed a hands-on/close-up
examination and condition documentation of
a 60 ft (18 m) wide by full building height area
that is clad with marble and granite at the lower
Figure 2. Composition of exterior walls at the Fisher Building.
1/2″ STEEL PLATE
(4) L4 x 4 x 3/8 FOR CONNECTION
STEEL MULLION COLUMN
BOND STONE
SILL, SOFFIT, AND SPANDREL
STONES, BEAR ON MARBLE
BELOW
BOND STONE
SEALANT AT MARBLE JOINTS
1/2″ STEEL PLATE SUPPORT AT
EVERY OTHER FLOOR
1/2″ STEEL PLATE
SUPPORT AT EVERY
OTHER FLOOR
July/August 2024 IIBEC Interface • 25
floors and located at the north end of the east
wing. A swing stage was utilized for access
at this location. The hands-on examination
included sounding (using a hammer) testing to
determine loose/delaminated material, sample
measurements of level/plumb, and inspection of
joints and connections at each level at different
areas of the building elevation. A rappelling
subcontractor was utilized for performing a
hands-on/close-up examination and condition
documentation of two 15 ft (4.6 m) wide by full
building height areas that are clad with marble
and located at the southeast corner of the tower.
Originally, the rappelling access was planned
at six additional tower locations; however, the
activities of a pair of peregrine falcons that have
a nest with fledglings—located behind a bronze
sculpture at the fifth level above the south
elevation main entrance door—endangered the
rappelling personnel and resulted in ending the
hands-on examination of the tower structure.
It is important to note that the presence of
the falcons and their endangered status must
be considered in planning and scheduling
all exterior wall restoration efforts. We also
performed three invasive wall examination
openings to examine and document the
condition of the exterior wall backup
construction.
ASSESSMENT FINDINGS
The comprehensive assessment uncovered
various types of distress and classifications
for each cladding material. These distresses
included damaged/spalled units, failed
repaired units, unsafe/ready-to-fall units,
displaced units, cracked units, deteriorated
coping units, failed mortar joints, failed
sealant joints, unsafe cladding and supports at
bronze sculptures, and deteriorated brick-clad
areas (Fig. 4). The extent and severity of these
issues were meticulously documented on
as-built facade elevations, created from laser
scans and converted into digital twins using
Scan-to-BIM (building information modeling)
technology.
The distresses observed and documented
included, but were not limited to, the
following:
• Previously replaced marble ashlar units with
matching marble units.
• Temporary stabilized/anchored marble and
limestone units. Five temporary repair details
were observed as follows:
❍ A strapping technique using steel wires,
wood blocking, turn buckles, and round-eye
anchor rods.
❍ Steel anchor rods that are drilled into the face of
a displaced unit and grouted in place.
❍ Bent steel plates or shelf angles placed at the
sides of a displaced unit and anchored with bolts
to adjacent units.
❍ Plywood sheets anchored into the wall backup
construction at the north elevation at a location
where two stone units have been removed.
❍ Netting anchored into adjacent units.
The previous repair records did not reveal
when these measures were installed; however,
most of the measures appear to be more
than 10 years old. Additionally, there are no
engineering design or detailing records available
to review the load capacity or predict the useful
life of the installed temporary repairs.
• Damaged/spalled marble/limestone/granite
units.
• Previously repaired damaged/spalled marble/
limestone/granite units.
• Unsafe/ready-to-fall damaged/spalled
marble/limestone/granite/brick units. The
observed unsafe damaged/spalled units
and areas are occurring at locations that are
in direct contact with (or near) embedded
steel elements which indicate that the
damage was primarily caused by corrosion
of embedded steel. To protect the public,
building users, and pedestrian traffic
from the falling hazard of these units and
Figure 3. Laser Scanning utilized during assessment.
26 • IIBEC Interface July/August 2024
areas, the owner has erected a pedestrian
protection canopy along the building’s
street- facing elevations.
• Displaced/out-of-plane movement at marble/
limestone/granite/brick units. The majority
of the displaced units are located near
embedded steel units and exhibited signs of
active movement (that is, split open vertical
sealant joints, visible out-of-plane movement,
and plane deviation).
• Low-severity cracked marble and limestone
units.
• Unsafe/ready-to-fall cracked marble and
limestone units.
• Deteriorated/damaged/displaced marble/
limestone coping units.
• Deteriorated/failed mortar joints repaired
with multiple layers of sealant/caulk
products.
• Unsafe/damaged cladding and supports at
bronze sculptures.
• Unsafe deteriorated brick-cladded areas.
CAUSES OF DAMAGE
AND INSTABILITY
The observed damage and instability of the facade
cladding primarily resulted from the corrosion of
embedded steel elements, such as shelf angles
and tie anchors. Furthermore, previous improper
repair campaigns, including inadequate patching,
incorrect removal of spalls, anchoring unstable
damaged cladding with mild steel supports, and
the improper application of sealant to repair cracks
or mortar joints, contributed significantly to the
ongoing deterioration.
RECOMMENDATIONS
FOR RESTORATION
The assessment report proposed a
comprehensive make-safe campaign, involving
a yearly 100% hands-on inspection to remove
or stabilize damaged cladding areas. This
included hammer sounding and removal of
all ready-to-fall masonry pieces and spalls,
installation of engineered netting systems at
displaced and cracked units, and installation
of engineered shoring systems at projecting
elements. In addition to the locations identified
by examination of the laser scan point cloud,
engineers marked the locations of all new
make-safe measures on building elevation
sheets in real time during hands-on inspections.
These elevation sheets created from the point
cloud served as a record of work for construction
crews with easily verifiable locations and extents.
Final certification inspection was performed
using these sheets for comparison.
Additionally, we recommended semiannual
laser scanning of the cladding to detect
out-of-plane movement using point cloud—to—
point cloud analysis (Fig. 5). The initial laser
scans have been archived as a baseline model
to serve as a point of comparison. Through the
use of state-of-the-art scanner and supporting
software, subsequent laser scan point clouds
can be generated and utilized to perform
cloud-to-cloud deviation analysis for each
Figure 4. Examples of cladding distress observed.
July/August 2024 IIBEC Interface • 27
exterior wall elevation. This analysis technique
uses software that automatically colors the new
point cloud data using the least squares method
based on the distance from the prior cloud
data. Subsequent scans will reveal significant
local movement in the building street facades.
Any new critical repairs can thus be identified
and performed in a timely manner. The
recommended repair schedule and exterior wall
classification can also be continually evaluated
and adjusted during the planning phase for
long- term repairs.
A phased restoration effort was suggested
to address the distresses and ensure
the long-term preservation of the Fisher
Building’s exterior walls. The integration of
advanced scanning technology with hands-on
examinations provided invaluable data for the
formulation of long-term restoration plans.
The primary repair construction elements
recommended for permanent repairs include
the following:
1. At select damaged/spalled/cracked/displaced
cladding locations along all elevations of
the building, and as directed by engineer,
perform the following:
a. Carefully remove and salvage the
cladding units/areas as necessary to
expose the embedded supporting steel
elements (plates and shelf angles).
b. Replace unsalvageable embedded
support elements with corrosionresistant
steel elements and install
waterproofing/through-wall flashing
where required and as directed by
engineer.
c. Clean, repair, prepare, and paint all
salvageable steel elements and install
waterproofing/through-wall flashing
where required and as directed by
engineer.
d. Reinstall salvaged cladding units with
corrosion-resistant lateral ties/anchors.
e. Replace unsalvageable cladding units
with matching units.
2. Remove sealant installed at all marble and
granite mortar joints. Grind and tuckpoint the
joints with new mortar.
3. Grind and tuckpoint deteriorated mortar
joints at select areas at all elevations as
directed by engineer.
4. Remove, salvage, and reinstall select coping
units at all elevations. Reinstall the coping
units with new engineered stainless steel
anchors and copper flashings.
5. Rebuild localized areas of brick wall
construction with new brick units (matching
in color and size) and stainless steel lateral
ties and as directed by engineer. Where
exposed, replace embedded support
steel shelf angles with corrosion-resistant
steel elements and install waterproofing/
through-wall flashing where required and as
directed by engineer.
Completing this phase of repairs should give
the building’s exterior walls up to 50 years of
additional life, excluding the windows, and
assuming proper maintenance.
CONCLUSION
By adhering to the recommendations put forth
by the comprehensive facade assessment
program, the new owner group can embark
on a journey to restore the Fisher Building
to its former grandeur. With a meticulous
approach to addressing the identified issues
and implementing appropriate rehabilitation
measures, this architectural masterpiece can
continue to serve as a cherished symbol of
Detroit’s splendor and a tangible vision of the
Motor City’s storied history.
ABOUT THE AUTHOR
Ziad Salameh, PhD,
PE, is owner and
principal-in-charge of
ZS LLC Architectural
Engineers.
Please address reader comments to
chamaker@iibec.org, including
“Letter to Editor” in the subject line, or
IIBEC, IIBEC Interface,
434 Fayetteville St., Suite 2400,
Raleigh, NC 27601.
ZIAD SALAMEH,
PHD, PE
FIgure 5. Laser scanning monitoring plots.