The Case for Aerial Infrared

April 15, 2000

April 2000 Interface • 25
The school of frozen toes
Our company began looking at roofs by walking them with
infrared cameras early in 1990. A couple of facts became clear
rather quickly:
a) Since there are so many types of roof systems in use, one
standard testing plan for performing all roof moisture surveys
was not going to work. Each roof system has different
thermal properties: that is, it may absorb and emit
heat at different rates.
b) Sometimes a roof cannot be successfully surveyed under
any circumstances.
c) We did not know enough about the roofs we were surveying.
The thermal patterns were sometimes fantastic.
Clear outlines of subsurface moisture in one roof would
be followed by very mottled and almost unreadable
imagery on another. Conditions could and would change
radically over the course of the night, sometimes before
our very eyes when a cloud came over or dew formed on
the roof.
d) The infrared camera’s wavelength, filters, windows, and
lenses could dramatically affect the quality of the
imagery.
e) Even with a strong infrared signal, factors on the roof
could affect the analysis and interpretation of the data.
Some of these factors: water between multiple layers, old
patches, heavy flood coats, reflective coatings, heatproducing
equipment under the roof (or heat blowing
down onto the roof), stains on the roof, ponding, heavy
build-up of ballast at parapet walls and along edges, etc.
f) Surveying roofs was a labor-intensive, time-consuming,
and at times, dangerous undertaking, requiring a great
deal of planning and preparation.
g) Information on the target roofs was, at best, sparse; and at
worst, non-existent, especially the drawings. Often, information
on the roof types, repair history, and as-built
drawings was simply not available. Many times the drawings
were not to scale and were incomplete, lacking many
of the objects that we saw when we climbed up on the
roof.
These revelations did not discourage us from performing roof
moisture surveys. We knew that it worked well on most roofs.
We just had to figure out a better way to perform the inspections.
In the case of roofs, infrared thermographers should see
their role as providers of infrared imagery—nothing more, nothing
less: the mappers of heat. We do not profess to know everything
about roofs or how to fix them. Our role is to obtain and
provide information that will help experts at roof construction,
installation, and repair.
Once Upon a Roof
Many consultants have been on a roof when an infrared roof
moisture survey was being performed.Those who have can relate
to the following:
When we started conducting walk-on infrared inspections of
roofs, we had no idea what nightmares these surveys could be.
BY
GREGORY R.
STOCKTON
FORWARD
Infrared thermography has become a very popular
means of testing electrical and mechanical systems over the
past fifteen years. As it relates to predictive/preventive
maintenance (P/PM), infrared thermographers look at the
thermal energy that is emitted from an object or group of
objects, explain what is normal, see abnormalities, and
report them. In turn, someone can act to fix whatever is
wrong as long as they get the information in a usable,
graphic and easy-to-understand fashion. This method works
well on heat emissions from most objects, including building
roofs. A well-prepared, graphic, accurate map of the
infrared signatures of a roof can be of significant benefit to
the roof consultant at all stages of that roof’s service life.
This type of testing is commonly referred to as an infrared
roof moisture survey. Infrared thermography is not leak
management, it is predictive maintenance. No matter how
the water got into the substrate, the purpose of this type of
survey is simply to find and document where the water is.
Performing infrared roof moisture surveys while standing on
the roof is not the best method because imagery from a
walk-on survey is not as useful as aerial imagery.
THE CASE
FOR
AERIAL
INFRARED
26 • Interface April 2000
First, nighttime conditions have to be right. Having low
winds, clear skies, and some sunshine during the preceding daylight
hours is usually not too much of a problem. However,
mobilizing a certified infrared thermographer, a helper, a building
owner’s representative, and a roof consultant to meet at a site
on a specific scheduled date when the weather is just right takes
much more flexibility and some luck. Also, some roofs do not
exhibit a good infrared signal, primarily for two reasons: 1) The
surface is too reflective, and 2) the roof’s ballast is so thick (or
dense), that daylight radiation is not absorbed into the substrate
(insulation), therefore it cannot be emitted back into the atmosphere
at night. There are other reasons why infrared thermography
is of little value on certain other roof types.
Suppose we have a roof that lends itself to infrared (other
than metal, most roofs do). We have scheduled the job, everyone
is in attendance, and the weather is favorable. The biggest
problems then become logistical in nature.
Again, the infrared thermographer’s job is to make a graphic,
accurate, and easy-to-understand report. For legitimate results,
you need excellent imagery. To get excellent imagery, a high
angle of view and high resolution are needed. When standing on
the roof, eye-level is at best six feet over the surface. If you are
looking out over a roof with large areas of moisture contamination
(even if you have a good infrared camera), there is virtually
no way, without taking multiple shots, that you can get a 900-
square foot amoeba-shaped blob, or an 80-foot long striation of
subsurface moisture resolved on the screen in one infrared shot.
If you take multiple shots, the report starts to become confusing,
and the visual images that you have to take the next day are
going to be hard to reconcile with the infrared images. J.P.
“Sonny” Ledoux, an infrared thermographer with over twenty
years experience, describes the problem best, saying, “When performing
walk-on roof surveys, many times you can’t see the forest
for the trees.”
Marking the roof is not difficult if you are able to yell out the
commands well, and your helper with the marking paint is adept
at his task. But then there are the drawings. Many times I was
faxed a photocopied fire plan of the building (without any
rooftop equipment indicated) for use as my roof drawing. We
really struggled with the drawings, especially on the night of the
survey.
Consider the costs, scheduling woes, logistical problems, and
danger (from tripping, poking yourself in the eye, falling off the
roof or dropping $80,000 worth of your livelihood), together
with how much trouble the report is going to be to produce, and
it’s no wonder that infrared thermographers survey comparatively
few roofs… It is a lot easier to make a living checking electrical
switchgear!
Aerial infrared thermograph showing a roof with extensive rooftop equipment. It would take 20 infrared images to completely document all the areas of suspect
roof moisture on this one roof section.
Imagery vs. paint
Those who have infrared cameras or a
favorite infrared thermographer to perform
on-roof inspections do not need me to
explain how a survey should be done.
Some may be thinking at this moment
that:
1. Good imagery is not all that important.
What is important is finding
and marking the water under the
roof.
2. Printed infrared and/or visual images
of the roof are not necessary if you
mark the outline of the water directly
on the roof with marking paint.
3. Two people can do the job just as
good as four. The owner leaves the
keys to the roof hatch and a helper
who can spray the paint.
4. We can go back on the roof during
the day and measure the paintmarked
blobs with a tape measure. I
have AutoCAD 2000™ and know
how to use it!
No matter which method or style you currently use to perform
these surveys, the end product will benefit from high quality
imagery and drawings. The end product is not only a printed
document but also the knowledge of where the moisture is in the
roof so that precise, cost-effective repairs can be accomplished.
As stated earlier, excellent imagery demands a high angle of
view and high resolution. In order to get excellent infrared and
visual imagery of that 900-square foot blob onto a printed page,
a lot of costly work has to be done with an infrared and visual
camera on the roof and then with a computer in the office to
create the report. To avoid reflections and to image a large area
at the same time, we used to climb rickety ladders with very
expensive infrared cameras so we could get as high above and as
close as possible to a 90-degree angle over a particular area. This
was done by looking down from a higher roof to a lower one or
climbing on air washes and other rooftop equipment. All this
takes time and can be dangerous. Some roofs have only package
air conditioning units, allowing for maybe 12 feet over the surface
at best. So, we decided to try a helicopter.
Why aerial infrared?
The problem with the helicopter was that even as close as
500 feet above the building, we could not resolve (to our satisfaction)
the infrared images of the blobs. We had to deal with
the vibrations. Also, the slow ferrying speeds and $575/hour for
the aircraft and the pilot dissuaded us. By the time we got high
enough to get a large area in the image, we lost our resolution.
Even though we were using state-of-the-art infrared cameras,
they just did not have the thermal and/or spatial resolution
required for obtaining good imagery from high above. Most
infrared cameras are built to resolve images a short distance away
from the detector. These cameras, including the modern 2000
model focal plane arrays, have only 256×256 pixels–a total of
65,536 pixels. They work fine for looking at switchgear, electric
motors, or boilers (which is what they were designed to do).
They were not designed to image objects a half-mile away.
The breakthrough came in the form of the 5122 focal plane
staring array chip. These cameras can be used for aerial infrared
because they have 512×512 pixels–a total of 262,144 pixels,
which is four times the resolution of the 2562. That’s four times
farther away at the same resolution. Because of the high resolution,
this type of camera can be mounted in a fixed-wing aircraft
allowing the infrared thermographer to quickly fly over buildings,
obtaining great imagery of large areas of roofs. What used
to take a four-man crew six hours can be done better and less
expensively in 60 seconds.
Fixed-wing aerial infrared imaging provides:
 High-angle, straight down infrared images which lessen
reflections.
 High-resolution images that capture large areas at once,
making the report easier and less expensive to produce.
 A more cost-effective platform to obtain infrared imagery
than rotor-wing, while reducing ferry times and vibrations.
More advantages:
 Plan view allows for infrared images, visual images, and
AutoCAD drawings to be reconciled closely. As a result,
the report is clear, concise, and easy to understand.
 Plan view imaging allows accurate marking of areas of
suspect roof moisture contamination. AutoCAD drawings
can be made by drawing “over” the captured visual and
infrared images on the screen. Hatch marked areas indicate
probable and possible wet areas. The infrared, visual,
An aerial infrared thermograph showing clear outlines of subsurface moisture contamination from 2,000
ft. AGL (Above Ground Level).
April 2000 Interface • 27
and AutoCAD components can then be separated. If
dimensional information is available, this creates a quantitative,
scale quality AutoCAD drawing of the suspect roof
moisture contamination on the roof. If dimensional information
is not available, the drawings become scaleable
and easily updated at any time in the future, once quantitative
data are obtained.
 The printed AutoCAD drawings can be used on the roof
to paint areas of moisture contamination directly on the
roof, if desired.
 The aerial infrared thermographer can wait for a good
night for imaging, surveying many roofs under good conditions.
If the image quality is not acceptable on a particular
building roof early in the night, he can return at
different times during the night in order to image the
building under the best possible conditions.
 Instead of inefficiently using four people for a night to
perform a survey, an airplane crew of two can do many
times as much data collection and then process the data
(not in a hurry on a freezing cold night) under comfortable
conditions at a consistent pace in the office.
 Instead of imaging 200,000 square feet in
a night, up to ten million square feet can
be imaged!
 Access to multiple levels of the roof is
never a problem.
Flexible Reporting
The owner of a roof and his roof consultant
should be given as much latitude as possible
with respect to the level of detail in the infrared
roof moisture survey report. Here are the different
levels of reporting, in ascending order of
costs:
Unedited videotape. If scheduled in an
area where the plane will be operating on a particular
night, a building roof can be imaged
(recorded on digital videotape and VHS) and
the unedited VHS videotape can be delivered to
a local airport that night. The owners’ roof consultant
can review the videotape the next morning.
Edited videotape. An edited videotape
can be made from the original digital videotape
and copied onto VHS.
Printed thermographs. Printed infrared thermographs
(infrared pictures) of each roof section can be captured and
printed in high resolution.
Aerial photographs. Printed photographs of the roof
(straight down) and building site photographs (lower angle
“beauty shots” of the building and property) can be developed
and printed. Photographs, of course, must be taken during daylight
hours, requiring a second flight over the building. The
costs increase, but a straight down photograph of a roof section
aids significantly in the infrared analysis, showing stains, equipment,
and roof boundaries.
AutoCAD drawings. AutoCAD drawings, printed and
saved to disk, can be made by analyzing all the infrared, photographic,
and drawing information. Often, the roof’s old drawings
are outdated and inaccurate. The old drawings can be corrected
by using the new photographs as a reference.
Digital and printed report. A complete quantitative
infrared roof moisture survey report would include all of the
above, printed in high resolution and saved to a CD, put on the
Internet with a password to access, and/or e-mailed to all the
interested parties.
A roof consultant must verify all infrared data and analyses.
The infrared report should be reviewed and the printed data
taken on the roof to aid in visual, destructive, and non-destructive
testing. I cannot overstress this point! Infrared images of the
roof, no matter how spectacular, are only signatures of heat. As
stated earlier, there are many causes of heat (or apparent heat)
on a roof. Professional verification is a required part of the survey,
without which the information is not and should not be
considered reliable. I believe this is one of the reasons that this
type of infrared survey is not performed more frequently.
Example of a scaled AutoCAD drawing of roof moisture.
Slate Roof Bible
B&W
Pickup from 1/00, page 12
Remove this border.
28 • Interface April 2000
Other Considerations
The main use for aerial infrared thermography is predictive
maintenance for existing roofs; however, the prospective owner
of a building could have the roof flown over before he buys it. If
the roof looks good, he would not have spent much money to
find out. If it looks bad, he can ask for a more detailed analysis
and use this information as a “bargaining chip” to negotiate the
price of the building.
After installation, a new roof that can be imaged effectively
should have a survey performed to verify that no wet insulation
boards were installed during construction. Also, aerial infrared
images taken soon after installation become very important documentation
later as the roof ages, since they can be used for
comparison. Subsurface fasteners are also evident (in the
infrared) on certain roof systems.
Designers could have a roof flown over in order to furnish a
quantitative document to all bidders, in the form of verified
AutoCAD drawings, for the localized removal and replacement
of all wet insulation.
Aerial infrared has a big advantage over walk-on infrared in
the ability to trend areas of a certain roof system. A one-year-old
aerial thermograph can easily be superimposed over a new aerial
thermograph, producing a three-part composite: the area of
moisture one year ago, the area of moisture now, and the difference
(growth). Using this information, the rate of growth for
that particular roof system can be reasonably extrapolated.
Permission to fly over any building in the US is not required.
The airspace over a few sensitive federal buildings may be
restricted, but even in this rare case, permission is usually granted
to fly over.
Soon, the insurance industry will discover
the potential benefits of aerial infrared thermography
on their insureds’ roofs. Highly
insured facilities in one area can be surveyed
from the air in a matter of minutes. If problems
are discovered, the insured can be informed
that a more effective roof maintenance program
needs to be started at that facility or, for
instance, their rate and/or deductible will be
increased, or coverage discontinued. Also, if a
particular area is prone to hurricanes, tornadoes,
or severe storms, the insured roofs in
that area can be flown over on an annual basis,
thereby limiting the insurance company’s liability,
in case of roof damage, to the pre-storm
condition, as compared to post-storm. Aerial
infrared and visual imaging can also be used to
quickly assess roof damage after a disaster
when security and/or automobile road conditions
make on-roof surveys impossible for the
purpose of determining which roofs should
receive top priority.
Conclusions
Once a roof consultant has determined that
a particular type of flat- or low-slope insulated
roof lends itself well to infrared inspection, it
should be considered an integral part of the
roof asset management program. Regular infrared surveys will
help the roof consultant to assess the roof’s condition at all
stages of its service life. Whether performed on-roof or aerial,
infrared imaging only provides a picture of the heat. Infrared
analyses must be professionally verified on the roof in order to
be reliable. Infrared heat signatures are most efficiently gathered
from the air. In order to get a graphic, usable report, the infrared
thermographer must obtain high-resolution infrared images of
large areas from high above. Therefore, the infrared camera used
must have a detector with enough pixels to achieve the desired
resolution from the maximum desired altitude. 
Gregory R. Stockton is
President of Stockton Infrared
Thermographic Services, Inc. Based
in Randleman, NC, the corporation
operates six complete infrared systems
in four divisions. Greg has
twenty years experience in the construction
industry, specializing in
energy-related technologies. He is
an Infraspection Institute Certified
Infrared Thermographer (#3583)
and publishes technical papers for
the infrared industry.