Top 10 Questions And Answers On Static Vs. Dynamic Wind Testing For Commercial Roofs

May 15, 2006

S E P T E M B E R 2006 I N T E R FA C E • 5
1WHAT ARE THE ATTRIBUTES
OF WIND ON A ROOF?
Wind is a random process.
When it separates from
the roof edges, it creates
zones of suction (negative)
pressure. This suction effect
has two characteristics: (a) it
varies from one zone of the
roof to the other – spatial variations;
(b) it varies from one
period of time to another –
fluctuations with respect to
time. One can distinguish the
spatial variations from zones
of higher to lower suction as
“corner,” “edge,” and “field,”
while the time fluctuations
are simplified through statistical
approach by calculating
the mean, peak, and standard
deviation.
Figure 2: Pressure fluctuations at a location on a roof.
Figure 1: Spatial wind pressure variation over a roof.
2WHAT ARE THE
ATTRIBUTES OF ROOFING
RESPONSE TO WIND?
If one views wind-induced pressure on a roof as
“action,” then the “reaction” is the response of the roof.
Not all roofs respond to wind in a similar manner. The
response can be static or dynamic, and it depends on the
assembly’s components, attachment methods, and application
technologies.
The response of the new generation of mechanically
attached systems is different than a conventional, fully
bonded system. In mechanically attached systems,1
membranes are attached
at discrete points or
rows. Moderate-to-strong
winds will cause the
membrane to lift and billow
between attachment
points or rows. The billow
height is primarily a
function of the wind load,
the fastener row spacing,
the load-strain modulus
of the membrane, and
the presence of an air or
vapor barrier (retarder) in
the roof system. Wind
fluctuations cause the
membrane to flutter, or rapidly flap up and down. The
dynamic (or cyclical) loading induced by the fluttering
can cause fatigue to the membrane, the membrane fasteners,
the substrate onto which the membrane is fastened,
or the fastener-to-deck engagement locations.
Figure 3: Static (fully bonded system)
and dynamic (mechanically attached
system) responses.
3WHAT IS A
STATIC TEST?
In a static test, roofs are subjected to constant pressure
difference across the deck and waterproof membrane.
Normally, in the North American roofing community,
FM Global (FMG) 44702 test method is considered
a static test. In that test, all roofs are subjected to static
pressure differences as shown in Figure 4.
Figure 4: Static load cycle.
6 • IN T E R FA C E S E P T E M B E R 2006
4WHAT IS A DYNAMIC TEST?
In a dynamic test, wind pressures vary across the system. The intensities
and magnitudes are dependent on the building’s aerodynamics and
wind exposure. Normally, in the North American roofing community, the
CSA A123.21-043 test method is considered a dynamic test. In an attempt
to mimic Mother Nature, wind dynamics of varying intensities are induced
over a roofing system. Each wind gust has a frequency of 0.5 Hz or two
seconds.
Figure 5: Dynamic load cycle.
with
www.chemlinkinc.com
CONTRACTOR HOT LINE
800-826-1681
SNOWSHOESTM
STOP
snowslides
Installation is quick and
easy with clear DURASIL
adhesive provided in
every kit!
•Withstands heavy
loads
• Available
in Clear
and
Smoke
• Low
visibility
• Paintable
• Kynar compatible
S E P T E M B E R 2006 I N T E R FA C E • 7
8 • IN T E R FA C E S E P T E M B E R 2006
The development of a full-scale test procedure requires
several levels of generalization on the true wind-induced
effect over a roof assembly. Often, these generalizations warrant
compromise from a technically sound approach to the
practically acceptable procedure. The author is unaware of
the level and extent of generalization of the wind-induced
effects used in the development of the static test.
Nevertheless, the development dynamic of the test involved
input from all parties concerned with roofing, including
researchers, manufacturers, roofing associations representing
contractors, and building owners. (Refer to the acknowledgment
section for the SIGDERS consortium participants.)
Six attributes for the development of a dynamic load cycle
were selected from the concerns raised by the members and
listed, based on priority, as follows:
1. Mimic as much as possible the true wind effects.
2. Simulate failure modes similar to those under field
conditions.
3. Account for the variation in roofing components and
materials.
4. Be easier to apply in a common laboratory environment.
5. Have a reasonable test-processing time of not more
than a day, including setup and testing.
6. Be compatible with local building codes and wind
standards.
SIGDERS consortia and CSA standardization process
scrutinized the generalization conducted in the development
of the dynamic wind load test procedure. Based on this
vision, the CSAA123.21.04 dynamic test was published. Data
from extensive wind tunnel studies of full-scale roof assemblies
were used, and finite element models were developed to
extrapolate the data base.
5HOW ARE TEST
METHODS DEVELOPED?
6THE STATIC TEST
TAKES LESS TIME.
IS IT BENEFICIAL?
Yes, a static test always takes less time
because it is not simulating wind fluctuations.
Static wind uplift rating data may be an indicator
to compare two systems; however, this test’s benefits
for engineering design are questionable.
7THE DYNAMIC TEST
HAS VARIOUS GUST
LEVELS. WHY?
Roofs, during their lifespan, experience winds
of varying speeds such as periods of calm winds,
moderate winds, and severe winds (hurricane
season). As indicated under question #1, the test
method should account for these wind speed
variations. This is why the dynamic test has varying
intensity gusts and uses wind loads specified
in the national documents, such as NBCC 20054
and ASCE 7-025. Such calculated pressures are
used to convert the test pressure ratios in Figure
5 rather than using an arbitrary selection.
􀀭􀀥􀀴􀀡􀀬 􀀥􀀰􀀤􀀭 􀀵􀀲􀀥􀀴􀀨􀀡􀀮􀀥 􀀦􀀯􀀡􀀭 􀀨􀀹􀀰􀀡􀀬􀀯􀀮􀂧
􀀶􀀡􀀬􀀵􀀥 􀀥􀀮􀀧􀀩􀀮􀀥􀀥􀀲􀀥􀀤
􀀲􀀯􀀯􀀦 􀀣􀀯􀀡􀀴􀀩􀀮􀀧 􀀳􀀯􀀬􀀵􀀴􀀩􀀯􀀮􀀳
􀀤􀀡􀀩􀀲􀀹􀀬􀀡􀀮􀀤 􀀳􀀥􀀥􀀤
􀀣􀀯􀀭􀀰􀀡􀀮􀀹
􀀥􀀴􀀥􀀲􀀮􀀡􀀍􀀳􀀥􀀡􀀬􀂧
􀀯􀀶􀀥􀀲 􀀭􀀥􀀴􀀡􀀬
􀀨􀀯􀀬􀀹 􀀣􀀲􀀯􀀳􀀳
􀀬􀀵􀀴􀀨􀀥􀀲􀀡􀀮 􀀣􀀨􀀵􀀲􀀣􀀨
􀀥􀀴􀀥􀀲􀀮􀀡􀀍􀀳􀀥􀀡􀀬􀂧
􀀯􀀶􀀥􀀲 􀀡􀀳􀀰􀀨􀀡􀀬􀀴
􀀯􀀮 􀀳􀀩􀀧􀀨􀀴 􀀴􀀲􀀡􀀩􀀮􀀩􀀮􀀧 􀀰􀀲􀀯􀀧􀀲􀀡􀀭 􀀡􀀶􀀡􀀩􀀬􀀡􀀢􀀬􀀥
􀀳􀀡􀀲􀀡 􀀬􀀥􀀥
􀀣􀀯􀀦􀀦􀀥􀀥 􀀆 􀀴􀀥􀀡
􀀥􀀴􀀥􀀲􀀮􀀡􀀍􀀳􀀥􀀡􀀬􀂧
􀀯􀀶􀀥􀀲 􀀨􀀹􀀰􀀡􀀬􀀯􀀮􀂧
􀀭􀀥􀀭􀀯􀀲􀀩􀀡􀀬
􀀥􀀬􀀥􀀭􀀥􀀮􀀴􀀡􀀲􀀹 􀀳􀀣􀀨􀀯􀀯􀀬
􀀥􀀴􀀥􀀲􀀮􀀡􀀍􀀳􀀥􀀡􀀬􀂧
􀀯􀀶􀀥􀀲 􀀭􀀥􀀴􀀡􀀬
􀀮􀀡􀀴􀀵􀀲􀀥􀀀􀀩􀀮􀀶􀀥􀀮􀀴􀀥􀀤
􀁨􀀷􀀡􀀴􀀥􀀲􀀴􀀩􀀧􀀨􀀴􀀌􀁶
􀀷􀀥􀀀􀀪􀀵􀀳􀀴
􀀰􀀥􀀲􀀦􀀥􀀣􀀴􀀥􀀤􀀀􀀩􀀴􀀁
􀀴􀀲􀀵􀀣􀀯􀀌􀀀􀀩􀀮􀀣􀀎
􀀔􀀓􀀐􀀑􀀀􀀴􀁒􀁁􀁉􀁎􀀀􀀡􀁖􀁅􀁎􀁕􀁅
􀀣􀁌􀁅􀁖􀁅􀁌􀁁􀁎􀁄􀀌􀀀􀀯􀁈􀁉􀁏􀀀􀀔􀀔􀀑􀀑􀀓
􀀒􀀑􀀖 􀀏 􀀖􀀓􀀑 􀀍􀀑􀀐􀀐􀀐
􀀘􀀐􀀐 􀀏 􀀒􀀒􀀗􀀍 􀀔􀀕􀀖􀀙
􀁗􀁗􀁗􀀎􀁔􀁒􀁕􀁃􀁏􀀍􀁉􀁎􀁃􀀎􀁃􀁏􀁍
S E P T E M B E R 2006 I N T E R FA C E • 9
No. Systems’ responses are different
under static and dynamic loadings.
Even for a particular installation category
(say, a mechanically attached system),
resistance data from a static test
can be different from that of a dynamic
one. Significant efforts were made under
the SIGDERS consortia to develop an
experimental factor to convert the static
wind uplift rating into an equivalent
dynamic wind uplift rating. It has been
concluded (considering the material
advancements and application technologies),
that use of a single conversion
8
Figure 6: Weakest resistance link chain diagram for mechanically attached system.
IS THERE AN EXPERIMENTAL FACTOR TO CONVERT
STATIC WIND UPLIFT RATINGS TO DYNAMIC WIND
UPLIFT RATINGS?
10 • I N T E R FA C E S E P T E M B E R 2006
Figure 7.1: Failure modes of PVC systems.
Figure 7.2: Failure modes of EPDM systems.
COMPARISON OF STATIC VS. DYNAMIC RATING AND FAILURE MODES OF VARIOUS MECHANICALLY ATTACHED SYSTEMS.
factor is scientifically invalid. This can further be explained
by means of a “weakest resistance link” chain (Figire 6).
Components of a mechanically attached system are:
deck, fasteners, plates, air/vapor barriers (retarders),
insulation, and membrane. Each component offers a certain
resistance to wind uplift. All resistance links should
remain connected for the system to be durable and to keep
the roof properly in place.
Failure occurs when the wind uplift force is greater
than the resistance of any one or more of these links. For
example, the assembly is considered to have failed when a
fastener pulls out from the deck even if the membrane and
its seams are in good condition. Similarly, a system is considered
failed when a seam tears under gusting wind while
other components remain intact. Due to variations in
resistance, the failure mode can also vary.
Figures 7.1-7.4 show typical examples of the difference
in failure mode and wind uplift rating data between static
and dynamic tests for various systems. Note that all these
test were completed at the SIGDERS table setup. As
shown, some systems perform similarly, irrespective of the
test methods; while for others, there are significant variations.
It is worth mentioning that one cannot use similar
observations for other systems using the same membrane,
as it may have a different application technology.
Static test – Wind uplift rating 150 psf. Dynamic test – Wind uplift rating 60 psf.
Static test – Wind uplift rating 90 psf. Dynamic test – Wind uplift rating 45 psf.
S E P T E M B E R 2006 I N T E R FA C E • 1 1
9IS THERE A FORMULA TO CONVERT THE
WIND UPLIFT RATING TO WIND SPEED?
The wind uplift rating and wind speed are different parameters; therefore, one cannot
use a conversion factor. Wind uplift ratings obtained from testing can be used in the design
process, as shown below.
Figure 7.3 Failure modes of modified bitumen systems.
Static test – Wind uplift rating 60 psf. Dynamic test – Wind uplift rating 75 psf.
Figure 7.4 Failure modes of TPO systems.
Static test – Wind uplift rating 135 psf. Dynamic test – Wind uplift rating 100 psf.
10WHAT IS THE USE OF A
WIND UPLIFT RATING IN
THE DESIGN PROCESS?
First, the rating data should be converted to resistance.
Using a safety factor, divide the rating to obtain the resistance.
The designer then correlates the resistance with the
required design load to validate that the resistance is
always higher than the load requirement. A simplified case
study is presented below.
12 • I N T E R FA C E S E P T E M B E R 2006
Figure 8 – Wind load diagram.
Step 1: Calculate the Design Load
Calculate the wind load for various zones (i.e., field,
edge, corner) of the roof assembly in accordance with the
local building code.
Step 2: Select the Roof Assembly
Use a minimum safety factor of 1.5 if the wind uplift rating
of the roof assembly and components is obtained from
dynamic testing. Use a safety factor of 2.0 if the uplift rating
is obtained from static testing. This provides the resistance
data.
Required System Required System
Rating from Rating from
Dynamic Testing Static Testing
Corner 84 x 1.5 = 126 psf 84 x 2 = 168 psf
or higher or higher
Edge 48 x 1.5 = 72 psf 48 x 2 = 96 psf
or higher or higher
Field 39 x 1.5 = 59 psf 39 x 2 = 78 psf
or higher or higher
Step 3: Correlation
Select roof assemblies and related components with
resistance data higher than the load data.
Figure 9 – Correlation of resistance with load. Figure 10 – Correlation of resistance with load – generalization.
Step 4: Generalization
In some cases, it may be economical to use a single set
of components for both the edge and corner zones. In such
cases, the corner zone resistance data should be applied to
the edge zone (not vice versa).
Acknowledgement
The presented research is being carried
out for a consortium – Special Interest
Group for Dynamic Evaluation of Roofing
Systems (SIGDERS). SIGDERS was formed
from a group of partners who were interested
in roofing design. These partners
include:
Manufacturers: Atlas Roofing Corporation,
Canadian General Tower Ltd., Carlisle
Syntec Incorporated, GAF Materials Corporation,
GenFlex Roofing Systems, Firestone
Building Products Co., IKO Industries Ltd.,
ITW Buildex, Johns Manville, Sarnafil, Soprema
Canada and Stevens Roofing Systems,
Tremco Inc. and Trufast Corporation.
Building Owners: Canada Post Corporation,
Department of National Defence,
Public Works and Government Services
Canada.
Industry Associations: Canadian
Roofing Contractors’ Association, Canadian
Sheet Steel Building Institute, National
Roofing Contractors’ Association, and RCI,
the Institute of Roofing, Waterproofing, and
Building Envelope Professionals.
References
1 Baskaran, A. and Smith, T.L, “A
Guide for the Wind Design of
Mechanically Attached Flexible
Membrane Roofs,” www.nrc.gc.ca/
virtualstore, 2005.
2 FM Global, “Approval Standard:
Class I Roof Covers (FMG 4470),”
Norwood, Massachusetts, 2005.
3 CSA A123.21-04, “Standard Test
Method for the Dynamic Wind Uplift
Resistance of Mechanically Attached
Membrane Roofing Systems,”
www.csashop.ca. 2004.
4 NBCC. “National Building Code of
Canada, National Research Council
of Canada, Ottawa, Canada. 2005.
5 ASCE. “Minimum design loads for
buildings and other structures.”
ASCE Standard 7 –02, American
Society of Civil Engineers, Reston,
Va.,USA. 2002.
Dr. Baskaran is a group leader for the Roofing Sub-Program
at the National Research Council of Canada, Institute for
Research in Construction (NRC/IRC). At the NRC, he is
researching the wind effects on building envelopes through
experiments and computer modeling. He also acts as adjunct
professor at the University of Ottawa. He is the vice-chairperson
for the Roofing Industry Committee on Weather Issues
(RICOWI) and a member of ASCE, SPRI, and CIB technical
committees. He has authored and/or co-authored over 150
research articles in the area of wind effects on buildings. Baskaran received his bachelor’s
degree in engineering from Annamalai University, Madras, India. His master’s
degree in engineering and PhD were from Concordia University, Montreal, Canada. Both
research topics focused on the wind effects on buildings and earned best dissertation
awards from the Canadian Society of Civil Engineers.
Bas A. Baskaran, PhD, PEng
We’re proud to be lighter,
leaner and meaner. Without
trying to substitute excess fat
for true quality, we pioneered the
ASTM standard for use of Elvaloy®
KEE in roofing membranes.
That’s why our 36 mil membrane
out-performs the other guys’
45 mil – and sometimes 60 mil
or thicker. And why we never
wavered from our original membrane
formula. Get it together by calling
800-927-8578. Or visit our
web site at www.fibertite.com.
Winning
innovations like
FiberTite never
yield to fads.
S E P T E M B E R 2006 I N T E R FA C E • 1 3
CALL FOR PAPERS: GREEN ROOFS
Green Roofs for Healthy Cities is looking for papers for its Fifth Annual International
Greening Rooftops for Sustainable Cities Conference, Awards, and Trade Show from
April 29 to May 2, 2007, in Minneapolis, Minnesota. The conference will raise awareness
of the many benefits of green roofs; share new research findings; provide information on
the latest designs, implementation techniques, and products; and broaden networks
while working towards building more sustainable cities through green roof implementation.
Conference streams fall under Policy, Design and Case Studies, and Research.
Abstracts are due by September 29, 2006, and final papers by January 5, 2007. A 300-
word abstract and 50-word biography must be submitted by September 29, 2006. For
more details, visit www.greenroofs.org.