CORROSION ASSESSMENT OF AN ALUMINUMFRAMED CURTAIN WALL BY FUSHUANG CUI AND MARK SCHMIDT WISS, JANNEY, ELSTNER ASSOCIATES, INC., NORTHBROOK, IL S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • NO V E M B E R 2 0 0 7 C U I A N D S C H M I D T • 2 1 ABSTRACT The corrosion condition of an aluminumframed curtain wall of a 14story office building was evaluated. The investigation included onsite inspection and testing, as well as laboratory analyses. Techniques employed included screw pullout tests, chloride analyses, Scanning Electron Microscopy/Energy Dispersive Xray Spectroscopy (SEM/EDS) and Fourier Transformed Infrared Spectroscopy (FTIR). The vertical mullions were all painted and little corrosion was observed. For the horizontal mullions, corrosion was concentrated at occluded areas; namely, the connections where the stainless steel screws were in contact with aluminum pressure plates and screw chases. A significant amount of chloride (approximately 1 percent by weight) was detected in the corrosion products and SEM/EDS confirmed the presence of the chlorine element. The chloride was likely from airborne deicing salts. It was speculated that the widespread water leakage, inherent crevices, dissimilar metals, and presence of chloride were responsible for the observed corrosion. The degree of corrosion was found to correlate very well with screw pullout strength: more advanced corrosion corresponded to lower pullout strength values. Despite the corrosion, all the tested screw connections had high remaining strength and it was projected that the screw connections would retain sufficient strength to resist current coderequired wind loads for at least another 20 years of service. SPEAKER MARK SCHMIDT — WISS, JANNEY, ELSTNER ASSOCIATES, INC., NORTHBROOK, IL During his 22 years experience at Wiss, Janney, Elstner Associates, Inc., MARK SCHMIDT has focused on the assessment, preservation, remedial design, contract document preparation, and implementation of restoration programs for a variety of building envelopes. He has led investigations involving glass and aluminum curtain walls, precast concrete panels, thin stone veneers, stone and brick masonry, terra cotta, sliding door and window assemblies, composite panels, exterior insulation and finish systems (EIFS), mosaic tile systems, and stucco systems. These investigations have addressed water infiltration conditions, including systematic sealant failures; surfacerelated distress, such as cracked and spalled concrete or masonry stained or etched glass, corroded aluminum or steel components, and paint or coating failures; glass breakage, failure of insulating glass units, and composite panel distress; and structural failure involving mechanical anchorage and structural silicone glazing. Mr. Schmidt is a member of the ASCE and the ASTM. He has authored papers and presented seminars and short courses on potential problems and preventive maintenance of curtain walls. He has also coauthored a chapter in a book titled Structural Condition Assessment. 2 2 • C U I A N D S C H M I D T S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • NO V E M B E R 2 0 0 7 CORROSION ASSESSMENT OF AN ALUMINUMFRAMED CURTAIN WALL Figure 1 – An overview of the 14story building. INTRODUCTION The curtain wall of a 14story office building (Figure 1) in the Chicago suburbs was manufactured and installed in approximately 1980. It consists primarily of alternating horizontal bands of vision and spandrel glasses that comprise approximately 4,400 distinct glazed openings. Each glass product is supported on four sides by aluminum framing and exteriormounted pressure plates. Rubber setting blocks and gaskets separate the glass from the aluminum framing and pressure plates. A crosssection of the typical pressure plate configuration taken from the curtain wall shop drawings is given in Figure 2. The exterior pressure plates resist wind loads that create suction on the glass. Stainless steel screws are used to fasten the pressure plates to serrated screw chases in both the horizontal and the vertical mullions. Most of the exterior pressure plates are concealed with cosmetic aluminum snapon covers. Figure 3 shows a horizontal pressure plate and a snapon cover, both containing a series of weep holes that allow water, which has penetrated into the glazing pocket, to drain back to the exterior. The authors’ firm was retained by the building owners to develop plans and specifications for sealant repairs to address widespread water leakage problems in the curtain wall. During a related site visit, two horizontal pressure plates and one vertical pressure plate were removed from the west elevation. In the screw chase of one horizontal mullion at the sill of had been engaged. In addition, a thin foam a floor spandrel opening, a white powdery tape was present at the interface between substance (see Figure 4) was observed at the pressure plate and the mullion (see locations where the stainless steel screws Figure 5). No significant amount of white Figure 2 – Cross section of typical pressure plate configuration (reproduced from the curtain wall shop drawings). S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • NO V E M B E R 2 0 0 7 C U I A N D S C H M I D T • 2 3 substance was observed at the screw chase of the other horizontal mullion, which was located at the sill of a vision opening where no foam tape was present. The adjacent vertical mullion also had no signs of the white substance within its screw chase. Preliminary analyses by Scanning Electron Microscopy/Energy Dispersive Xray Spectroscopy (SEM/EDS) of the sampled white substance and the foam tape suggested that the substance was aluminum corrosion product with some chlorine and calcium content. The foam tape was also found to contain chlorine and calcium. It was therefore suspected that the observed aluminum corrosion was the result of an otherwise benign galvanic corrosion cell between the stainless steel screw and the aluminum mullion that had been energized by the Figure 3 – Horizontal presence of free pressure plate (top) and chloride. This interior of snapon phenomenon was cover (bottom). unusual in that deleterious galvanic corrosion between alumiFigure 4 – Initial severe num and stainless steel is rarely, if ever, reported in curtainwall construction. Due to the corrosion site. Figure 5 – Foam tape at pressure plate/mullion uncertainty of the interface. longterm effect of the corrosion on the structural integrity of the pressure plate connections, further investigation was warranted. The building owners retained the authors’ firm to perform further investigation of this condition to determine the extent, cause, and ramifications of the aluminum corrosion and to determine the scope of corrosionrelated repairs, should they be deemed necessary. The investigation included onsite observation, sampling, and testing, as well as laboratory analyses. METHODOLOGY ONSITE OBSERVATIONS AND SAMPLING In an attempt to determine the extent and possible pattern of the ongoing aluminum corrosion, the following activities were performed at 41 façade inspection openings distributed on 2 4 • C U I A N D S C H M I D T S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • NO V E M B E R 2 0 0 7 Location Type Inspected openings Total openings on building Percent inspected Regular VOs 1 16 1560 1.0 Corner VOs 2 2 288 0.7 Regular SOs 3 14 1690 0.8 Corner SOs 4 2 312 0.6 Ground level VOs 5 4 296 1.4 Ground level SOs 6 3 296 1.0 VO – vision opening; SO – spandrel opening Table 1 – Opening type and percent inspected. 11 swing stage drops and at various floors of the building: • Documentation and rating of the corrosion condition of the screw sites on the pressure plates and screw chases using a relative rating system developed for this project • Visual comparison of cleaned, corroded aluminum surfaces at screw engagement with adjacent corrosionfree aluminum surfaces • Sampling of powdery materials and foam tapes for laboratory analyses TESTING To identify possible cause of corrosion and assess corrosioninduced system capacity loss, the following tests were performed: • Onsite testing — Chloride conc e n t r a t i o n tests on exterior surfaces of selected p r e s s u r e plates using commercial chloride testing kits — Mechanical pullout tests on selected s t a i n l e s s steel screws engaged in a l umi n um screw chases using custom test apparatus • Laboratory testing of powder samples — SEM/EDS — Fourier Transformed Infrared Spectroscopy (FTIR) — XRay Diffraction (XRD) — Chloride analyses • Laboratory testing of foam tapes — SEM/EDS — FTIR The three laboratory test techniques (SEM/EDS, FTIR, and XRD) are complimentary to one another and allow possible characterization (i.e., identification of elements and chemicals) of the powdery materials and foam tapes. FINDINGS ONSITE OBSERVATION AND SAMPLING The curtain wall openings were divided into six different types based on their locations. Table 1 lists the classification of the openings and the percentage of opening types inspected. The vertical mullions were all painted and exhibited insignificant levels of corrosion (see Figure 6). The investigation focused, therefore, on the unpainted horizontal members. The screw chases of the horizontal mullions, which have a mill finish, were corroded to varying degrees. Corrosion ratings developed for individual screw sites within the screw chases (listed in increasing magnitude of corrosion activity) included trace, moderate, heavy, and severe (see Figure 7). While a few sporadic screw sites (approximately 2 percent of the total sites observed) were rated as severe, the vast majority was rated as trace or moderate, and the average rating was between Figure 6 – Vertical members exhibited trace, if any, corrosion activity: (a) condition of a pressure plate (left); (b) condition of a painted screw chase (above). S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • NO V E M B E R 2 0 0 7 C U I A N D S C H M I D T • 2 5 trace and moderate. Figure 8 shows the condition of a screw Figure 7 – Varying corrosion conditions: A) trace; B) moderate; C) heavy; D) severe. A B C D site rated as “severe” before and after cleaning was performed. The extent of aluminum access difficulty. sion activity also varied significantly. A simsection loss in the screw chase was difficult The exterior surface of the horizontal ilar corrosion rating system (Figure 9) was to measure or otherwise quantify due to pressure plates often exhibited corrosion used to assess the condition of these comlocal deformation from the screw and products at locations immediately adjacent ponents, and most ratings were “trace” or to the stainless steel “moderate.” screw heads. This corroAt the inspected curtain wall openings, foam tapes were found exclusively along spandrel sills at the interface between pressure plates and horizontal mullions. In general, there was no correlation between the presence of foam tape and level of corrosion activity in the screw Figure 8 – Condition of a site with severe corrosion: A) before cleaning(above); B) after cleaning (right). A B 2 6 • C U I A N D S C H M I D T S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • NO V E M B E R 2 0 0 7 chase. Powdery materials and foam tapes were sampled for laboratory characterization. Widespread water infiltration and water retention within the horizontal mullions of the curtain wall system were observed. Pressure plate gasket shrinkage resulted in gaps (see Figure 10A) for water penetration into the glazing pockets. At three inspection openings, water poured out of the glazing pockets during removal of the horizontal pressure plates. Figure 10B shows one of ONSITE TESTING Chloride Test Commercial chloride testing kits were utilized at selected horizontal pressure plate surfaces to determine whether or not chloride was present. As shown in Table 2, Figure 9 – Varying corrosion condition at pressure plate surface around stainless steel screw: A) trace, B) moderate, C) heavy, D) severe. A B C D these openings with a significant quantity of chloride was consistently Screw PullOut Testing free water in the upper and lower glazing detected at sites with visible corrosion prodIn an effort to quantify the probable pockets, as well as in the screw chase. ucts and was not detected at sites that were screw connection strength loss associated largely free of such products. with the localized aluminum corrosion of A B Figure 10 – Evidence of water infiltration: A) avenue for water penetration at shrinkage gap in gasket (above); B) free water in glazing pockets and in screw chase at an inspection opening (right). S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • NO V E M B E R 2 0 0 7 C U I A N D S C H M I D T • 2 7 Test ID Drop Floor Type of opening Surface with powdery materials (ppm) Chloride concentration 1 S2 8 3 No 0 2 E1 12 1 Yes 12 3 E1 10 3 Yes 27 4 E2 2 6 No 0 5 N1 13 2 Yes 47 6 N1 4 3 No 0 7 W2 1 6 Yes 30 8 W3 1 5 Yes 25 9 W4 14 4 No 0 Table 2 – Chloride test results performed on horizontal pressure plates. 1/64in oversized chase (1/64in oversize in graph). This suggests that the screw chase section loss induced by corrosion to date is small (i.e., approximately equal to or less than the effect of oversizing the screw chase by 1/64 in). LABORATORY TESTING OF POWDER SAMPLES SEM/EDS Test A total of four corrosion product samples (white powdery substances) were tested using SEM/EDS. Two of the samples were collected from the exterior surfaces of two pressure plates, and the other two were collected from the screw sites of two screw chases. Regardless of sample location, each sample was found to consist of some particles that contained aluminum, oxygen, and chlorine, and of some particles that contained primarily aluminum and oxygen, with only “trace” amounts or no chlorine. In addition, some particles were found to be primarily chloride salts, such as potassium chloride. Figure 13 shows two examples of the SEM micrographs and EDS spectra, suggesting that the powders contain corrosion products of aluminum mixed with some chloride salts. the screw chase, screw pullout tests were performed. After removal of the pressure plate, selected screws were carefully threaded into the serrated screw chase at the originally installed locations and to the original penetration depth. A custom apparatus, shown in Figure 11A, was then attached to the screw head. A slowly increasing tension force was applied (see Figure 11B) until the screw reached its maximum load. Tests were performed on original screws at locations with different corrosion ratings and on new screws installed at new sites with no corrosion. Screw pullout strength loss was generally small. Table 3 shows the average values for all the original screws and new screws. The original screws had an average pullout strength that was 1027 lbs, or 9 percent less than the average value obtained for new screws. Figure 12 graphically presents the average pullout strength values for original screws grouped according to the related corrosion condition of associated screw chase sites. Evidently, average screw pullout strength decreases as the observed corrosion condition worsens (from “trace” to “severe”). The figure also shows the theoretical strength values (calculated using the procedure outlined in AAMA TIRA91991 Metal Curtain Wall Fasteners)1 for screws installed in an optimumsized screw chase (zero oversize in graph) and screws installed in a Screw type Number of tests Average pullout strength (lbs) Original 40 1027 New 11 1134 A B Table 3 – Screw pullout strengths. Figure 11 – Screw pullout test: A) the test apparatus; B) a pullout test in progress. 2 8 • C U I A N D S C H M I D T S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • NO V E M B E R 2 0 0 7 Figure 12 – Average pullout strength data for screws in horizontal mullion. A B FTIR and XRD Tests Two powder samples were also characterized using the FTIR technique. However, no conclusive information was derived from this test. After completing SEM/EDS and FTIR tests, XRD tests were performed on the remaining powders of the two samples. It was found that these powders were mostly amorphous, and no peaks of crystalline structure were positively identified. Chloride Test Six powder samples were weighed and tested for chloride content using commercial chloride testing kits. As shown in Table 4, the detected chloride content (0 to 2.4 percent) varies from sample to sample. This is consistent with the EDS analyses (chloride signal peak amplitude varied from particle to particle). The strong chlorine signal suggests that the polymer is chlorinated. Both tape samples appeared to be in good condition with no sign of degradation. They were flexible and would quickly return to their original shape when compressed. Figure 13 – Selected SEM micrographs and EDS spectra: A) aluminum corrosion products (Al and O) and chlorine detected; B) chlorine and potassium identified as primary content (likely KCl salt). Test ID Drop Floor Type of opening Sample mass (g) Chloride concentration (wt %) 1 S2 1 5 0.0113 0 2 E2 8 3 0.0315 1.8 3 W2 9 3 0.0135 0 4 W2 1 6 0.0289 2.4 5 E1 10 3 0.0231 0.78 6 W4 3 3 0.0194 0.88 LABORATORY TESTING OF FOAM TAPES SEM/EDS Test Two foam tape samples were tested with SEM/EDS to identify their compositions and to determine whether or not the tapes are sources of free chloride. As shown in Figure 14, SEM/EDS analysis of the foam tapes indicated signals from carbon, chlorine, and calcium. The calcium signal is likely from the calcium carbonate filler. A Table 4 – Chloride test results performed on corrosion product samples. Figure 14 – Selected SEM micrographs and point EDS spectra of foam tape: carbon, chlorine, and calcium detected in both A) and B). B S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • NO V E M B E R 2 0 0 7 C U I A N D S C H M I D T • 2 9 Figure 15 – Correlation between pullout strength and corrosioninduced section loss. Measured pullout strengths for horizontal mullions and 20year projected strength are also plotted. FTIR Test The FTIR results indicated the presence of a phthalate plasticizer and calcium carbonate filler. The sample was then extracted with tetrahydrofuran (a solvent) in an attempt to dissolve and analyze certain chlorinated polymers. After extraction, only the phthalate plasticizer (which was dissolved) was detected. As the most likely chlorinated polymer that is not soluble in tetrahydrofuran is neoprene (polychloroprene), it was speculated that the foam tape material is likely a neoprene rubber with a phthalate plasticizer. While the analyses of the tapes suggest that the polymer contained in the tapes is chlorinated, the lack of degradation of the foam tape, along with the inability to extract chlorinated polymer, indicates that the tape is not likely a source of free chloride. Considering these findings and the fact that there was no observed correlation between the presence of the tape and corrosion activity, it is unlikely that the tape is contributing to the corrosion of the aluminum. DISCUSSION environment. A corrosion process typically requires water and oxygen. It is widely known that the presence of crevices,2 aggressive ions such as chloride,3 and a more noble metal can result in severe localized corrosion of a metal4 that would otherwise remain passive. Unfortunately, the horizontal aluminum mullions in this curtain wall system have the following documented characteristics that promote corrosion: 1. Widespread water infiltration and water retention 2. Crevices at the interface between screws and serrated screw chases 3. Presence of a more noble stainless steel screw material (as compared to the base aluminum) 4. Presence of free chloride (detected in the corrosion products) These factors (possibly also a synergistic effect) are responsible for the observed corrosion. The laboratory analyses suggest that the detected free chloride did not originate from the foam tape. Instead, the detection of potassium chloride in the corrosion product suggests that airborne deicing particles are the most probable source of the chloride. CORROSIONINDUCED SECTION LOSS One of the consequences of corrosion is the section loss of metal components. In the case of screw chases, the impact of section loss on pullout strength can be reasonably approximated by calculating the effects of oversized screw chase. Figure 15 shows the theoretical strength values (red solid circles) corresponding to zero, 1/64in, and 1/32in oversize. These values were calculated following the AAMA TIRA91991 procedure. 1 Assuming linearity between two adjacent points, section loss induced by corrosion can be estimated based on measured pullout strength values. Table 5 lists the estimated section loss values corresponding to each corrosion condition. SERVICELIFE PROJECTION The impetus for this investigation was concern regarding the longterm effect of the corrosion on the structural integrity of the screwed pressure plate connections. A lowerbound (i.e., conservative) estimate of the pullout strength of the screws after another 20 years of service can be predicted by using the most severe current corrosion condition and by assuming corrosion conPullout strength (lbs) Estimated section loss (in) New site pristine 1134 0.0037 Trace 1097 0.0047 Moderate 1037 0.0064 Heavy 996 0.0075 Severe 824 0.0123 Projection1 580 0.0210 CAUSES OF CORROSION 1 Assume severe corrosion condition. Corrosion is the deterioration of a metal due to its reaction with the surrounding Table 5 – Estimated section loss and projected pullout strength after 20 years of additional service. 3 0 • C U I A N D S C H M I D T S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • NO V E M B E R 2 0 0 7 tinuing over the next 20 years at a constant rate equal to the corrosion rate that has occurred over the past 20 years. (This methodology is conservative because very few of the screws presently have a severe corrosion rating and because the scheduled exterior sealant repairs will reduce water infiltration, a response that should decrease the corrosion rate in the future.) With this methodology, after another 20 years of service, the projected section loss was estimated to be about 0.021 in and the projected screw pullout strength would be approximately 560 lb (Table 5). Figure 15 shows the estimated section loss for screw sites with various corrosion conditions and the projected section loss after another 20 years of service. Under design wind loads (calculated per the current governing ASCE 795 standard5), the maximum load per fastener is about 150 lb. Maximum screw loads occur only at select locations, such as near building corners and near the center of each pressure plate. Average wind load per fastener is somewhat less. Table 6 shows the projected screw pullout strength (calculated conservatively as described above), the required maximum strength to resist wind loads, and the resulting projected factor of safety. As shown, the calculations indicate that the pressure plate screw connections will have sufficient strength to resist current code wind loads with an adequate factor of safety (nearly 4.0) for at least the next 20 years. It should be noted that future strength loss of the screws that currently exhibit “trace” to “moderate” corrosion can be estimated with confidence based on the results of this testing. However, future strength loss of the screws that currently exhibit severe corrosion is more difficult to predict (i.e., additional strength loss for these severe corrosion conditions may not be linear). However, since severe corrosion conditions only account for approximately 2 percent of those inspected, the abovedescribed methodology should be conservative. Furthermore, even if the currentlyrated severe corrosion screw sites provided no windload resistance in 20 years (i.e., if these screws were to fail completely), the remaining screw connections at their projected strengths would still be capable of resisting currentcode wind loads with an adequate factor of safety. CONCLUSIONS Based on the findings of the onsite investigation and the laboratory testing, the following conclusions can be drawn regarding corrosion conditions at the screw connections of the aluminum pressure plates in the subject curtain wall system: • Observed corrosion activity at the screws along the millfinished horizontal mullions varied from “trace” to “severe,” with the average condition being in the trace to moderate range. Slight to no corrosion activity was observed along vertical mullions, which were all painted. • Foam tapes containing chlorinated polymers were detected at spandrel sill locations. The tapes are not likely contributors to the aluminum corrosion. • The conditions within glazing pockets – including the presence of water, detected free chloride, inherent crevices, and dissimilar metals – are favorable to corrosion. • The source of the chlorides was not determined in this study, but it is suspected to be airborne particles of deicing materials used on nearby parking lots and roadways. • Corrosion ratings correlate well with screw pullout strength loss. • Based on conservative assumptions, calculations indicate that the screw connections will retain sufficient strength to resist current coderequired wind loads for at least another 20 years. • The observed corrosion conditions and the corresponding screw pullout strength losses did not warrant imminent repair. REFERENCES: 1. AAMA TIRA91991, “Metal Curtain Wall Fasteners,” American Architectural Manufacturers Association, Schaumburg, Illinois, 1991, pp. 1617 and 2000 Addendum. 2. R.G. Kelly, Crevice Corrosion, in: M. Stratmann, G.S. Grankel (Eds.), Encyclopedia of Electrochemistry 2003, vol. 4, WileyVCH Verlag GambH & Co. KGaA, Weinheim, Germany, 2003, pp. 275. 3. F. Cui, F.J. PresuelMoreno, R.G. Kelly, “Experimental and Computational Evaluation of the Protection Provided by an Aluminum Cladding to AA2024T3 Exposed at a Seacoast Environment,” Corrosion 62 (3), 2006, pp. 252631. 4. L.J. Korb and D.L. Olson (Eds.), Corrosion in Metals Handbook, vol. 13, ASM International, Metals Park, Ohio, 1987, p. 83. 5. ASCE 795 Minimum Design Loads for Buildings and Other Structures, American Society of Civil Engineers, Reston, Virginia, 1995, pp. 1234. Table 6 – Projected and maximum required strengths. Estimated/projected screw strengths Horizontal mullions1 and factors of safety Pullout strength – Current (lbs) 824 Projected pullout strength – In 20 years (lbs) 580 Required maximum strength (lbs) 150 Conservative projected factor of safety in 20 years 3.8 1 Severe corrosion condition assumed. S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • NO V E M B E R 2 0 0 7 C U I A N D S C H M I D T • 3 1