Skip to main content Skip to footer

Unintended Consequences: Keeping Alert to Protec Single-Ply Roofs

May 15, 2012

The current generation of TPO
(thermoplastic polyolefin) and
PVC (polyvinyl chloride) singleply
systems has achieved an
outstanding performance rec –
ord in the low-slope market.
These single-ply membranes have been
available and successfully performing in
applications for quite some time – in some
cases, well over 20 years.
However, like any other system,
single plies are vulnerable to the
unintended consequences of poorly
thought-out design decisions and
other incidental issues that have little
or nothing to do with the TPO or
PVC membranes themselves.
The fact is that the industry has
wrestled with some of these concerns
since the first single-ply membrane
was installed back in the late
1960s. Also, problems such as moisture
migration and condensation
beneath the membrane can be an
issue regardless of membrane type
and are not singularly an issue for
single plies.
Let’s start out with an example of
an unintended problem that many
roof consultants have seen firsthand.
Please raise your hand (we’re
not looking, really) if you have seen a
long run of cast iron pipe sitting on
wood blocking over a single-ply or
bituminous membrane. Due to the expansion
and contraction of dissimilar materials,
these wooden supports will move over time
and take the cast iron pipe with them.
The same thing can happen when long
runs of ballasted solar racking are installed
together on a membrane. Despite the overburden,
these heavy rack systems may
move over time and take the membrane
along with them.
Roof consultants, manufacturers, and
contractors are not designing these racks
and may have no say in how long the runs
will be. This simple phenomenon is from
“Mechanics of Materials 101,” but it can be
a serious issue for the membrane under the
solar-racking systems. And currently, we
don’t have a solution for it. The effect of
roof-mounted solar arrays on the fire resistance
of systems is another challenging
20 • I N T E R FA C E F E B R U A RY 2012
The current generation of TPO membranes has achieved an outstanding performance record in the
low-slope roofing market. Shown here is Cardinals Stadium in Phoenix, AZ.
issue that SPRI and the
industry at large are currently
sorting out and need
to address for code compliance.
MOISTURE – PUBLIC ENEMY #1
Roofing professionals
have nothing against water –
without it we would all be
looking for new jobs – but
moisture does become a
problem when it enters the
roofing system and condenses
on the insulation or under
the membrane.
We can all benefit from
reading another detailed
treatise on moisture control
as a refresher course, but it
is beyond the scope of this
article. In reality, it is the
responsibility of the architect
or specifier to determine
the need for a vapor retarder
and, when required, to make
sure it is properly placed
within the system. This decision
will depend heavily on
climate and building use.
However, there has been
a lot of discussion lately
about moisture condensing
on the underside of lightcolored
single-ply membranes
in cold climates. Of
course, roof consultants may
also find moisture problems in dry climates
such as Phoenix, AZ, where unusually high
moisture levels inside the conditioned
building move up and into the system and
condense.
Condensation under white or lightcolored
roof membranes can be a problem
with almost any mechanically attached single-
ply membrane where there is a single
layer of insulation. Moisture can travel up
through the joints in the insulation and hit
the cold side of the membrane – or the
membrane adhesive – and condense. This
may result in “picture framing,” depending
on the insulation. The condensed moisture
(water) may also move laterally through the
system, creating even greater problems for
the roof consultant and building owner.
This phenomenon is nothing new for
roofing professionals. Discussions about
moisture condensing under single-ply membranes
have been ongoing since the early
1980s. Vapor moisture will condense on any
cold surface, and lighter-colored membranes
do not dissipate this condensed
moisture as quickly as dark-colored membranes.
Again, it is the responsibility of the
designer to properly design the system to
minimize moisture condensation, either
through the use of a vapor retarder or
through the use of two layers of insulation
and staggering the joints to make it more
difficult for moisture to reach the underside
of the membrane.
The National Roofing Contractors Asso –
ciation (NRCA) addresses this issue in a
variety of areas on its Web site. Here is one
link to get you started: www.nrca.net/rp
/technical/search/librarydetails.aspx?
IDNumber=24829
SPRI also addresses this concern in the
results of a field study called “The Effects of
Roof Membrane Color on Moisture Accu mu –
lation in Low-Slope Commer –
cial Roofing Systems” (see
Figure 1). For more information,
download the paper
directly from SPRI’s home
page (www.spri.org).
STRUCTURAL CONCRETE DECKS
Moisture emanating from
newly poured structural
concrete decks has been a
problem that is finally getting
the attention it de –
serves. There is a perception
in the industry that all concrete
decks are the same.
The fact is that they are not.
When concrete is poured
over a nonremovable, nonventing
substrate, the wet
concrete will often not dry
out. And the use of a surface
dryness test is often insufficient
to measure the large
amounts of moisture trapped
inside these poured concrete
decks. In fact, one may very
well get a “false positive”
indicating that the deck is
ready for roofing.
Because these decks are
not vented from above or
below, once the building is
conditioned and cooler wea –
ther occurs, vapor drive
upward into the roof system
can cause large amounts of
water to enter into the roofing system, often
with catastrophic effects.
This problem has become a greater concern
as more general contractors realize
how much less expensive it is to leave a
metal pan in place below the poured structural
concrete deck. In the past, these metal
forms were typically removed before roofing
installation.
This problem has been slow to be
addressed because structural concrete
decks are used less frequently than the
steel decks the industry is so accustomed to
seeing in new construction applications.
In warm, humid climates, most knowledgeable
general contractors will ensure
that the HVAC system is working even
before the drywall is put up. This way, when
the building is conditioned, the HVAC system
handles the moisture generated during
construction and dries the building out. But
this will only work if the structural concrete
F E B R U A RY 2012 I N T E R FA C E • 2 1
Figure 1 – Dew point analysis of a metal deck used by SPRI as part of its
field study, “The Effects of Roof Membrane Color on Moisture Accumula –
tion in Low-Slope Commercial Roofing Systems.” (Figure courtesy of SPRI.)
deck can vent from the bottom side (i.e., the
metal pans are removed).
One individual attempted to solve this
problem by drilling holes into the metal pans
every six inches. Unfortunately, this still did
not allow adequate venting of the structural
concrete deck, and it began to “rain” inside
the building due to water coming through
the holes drilled into the metal pans.
Fortunately, this problem has come to
the attention of the Midwest Roofing Con –
tractors Association (MRCA). The group’s
Technical & Research (T&R) Bulletin 1/2011,
“Structural Lightweight Concrete Roof
Decks,” covers this issue in detail and
includes a “course of action” for roofing professionals
who encounter these decks. The
document is available for direct download
from MRCA’s home page at www.mrca.org.
One month after releasing this document,
MRCA came out with another T&R
advisory bulletin on the “Noteworthy
Limitations of Water-Based Bonding Adhe –
sives.” This document is also available on
MRCA’s Web site and should help roof consultants
and other roofing professionals
avoid blisters in fully adhered TPO and PVC
single-ply systems.
A SPRI task force headed by Tom
Cleverdon is also preparing a paper on
water-based adhesives. It should be available
by the time this article is published.
Water-based adhesives are environmentally
friendly and versatile when used with
single-ply membranes; but, as with any
adhesive, there are limitations to their use.
HEAT AGING OF SINGLE-PLY MEMBRANES
Another important discussion within
the industry is the incidental high-heat
loading on white single-ply membranes.
This is a particular problem at roof/wall
junctures, especially beneath high, westfacing
walls in warm, sunny climates.
If a white membrane is installed vertically
up a wall or high curb, it may reflect
down onto the horizontal portion of the roof
membrane and create conditions that will
accelerate the heat aging of the sheet.
Typically, the in-surface temperature of
a white TPO or PVC membrane is around
125°F to 130°F. However, the temperature
of the membrane below a highly reflective
wall surface can reach 170°F or higher.
Obviously, this is an unintended consequence
of the designer’s not thinking about
the ramifications of a high wall, curb, or
other highly reflective vertical surface.
The same principle holds true of membranes
beneath reflective glass surfaces,
curtain walls, painted white walls, metal, or
any other type of highly reflective surface.
Of course, premature heat aging of TPO and
PVC membranes is a function of time, temperature,
and UV exposure, all intertwined.
So a white wall in Chicago, IL, will be much
less of a problem than a similar configuration
in Phoenix, AZ.
One solution to this potential issue is to
specify a high-performance TPO roof membrane
around perimeters or other areas
exposed to high heat-aging conditions.
22 • I N T E R FA C E F E B R U A RY 2012
Kiowa County Commons in Greensburg, Kansas, includes high-performance lighting and controls, an enhanced mechanical system, a
stormwater runoff collection system, a pair of wind turbines, and water-efficient landscaping, in addition to solar and vegetative roofs.
Some of these technologies may also have unintended consequences that must be addressed by the building designer.
These new TPO membranes are formulated
with proprietary stabilizers and UV
absorbers specifically for solar roof installations,
but they have other uses, as well.
Laboratory results show that they have
achieved weathering performance far
beyond current standards.
It is also important for roof consultants
and contractors to understand that colored
TPO and PVC membranes may exhibit welding
characteristics different from those of
white membranes. Also, dark-colored membranes
sometimes used for rooftop logos or
other applications may be formulated for
increased heat aging, while the light-colored
membranes they are coupled with may not
be. That’s why it’s important to understand
the differences in thermoplastic membrane
characteristics when using different-colored
sheets on the same roof.
Roof consultants should also think twice
before allowing the use of dark-colored
materials (walkways, etc.) directly over white
TPO and PVC membranes. A more logical
choice may be a light gray walkway roll.
Also, areas of poor drainage can create
dark stains that can absorb heat and speed
up the heat-aging pro –
cess of a membrane.
Dark-colored, thin-film
photovoltaic (PV) systems
may also contribute
to accelerated
heat aging of TPO and
PVC. In this situation,
the roof consultant’s
safest choice may be a
h i g h – p e r f o r mance
mem brane de signed for
solar applications.
HIGH-SPEED WELDERS
Another installationrelated
concern centers
on the use of the industry’s
newer high-speed,
hot-air automatic welding
machines. These
stand-up welders are
capable of welding TPO and PVC seams at
up to 35 ft. per minute under ideal conditions.
But as consultants are well aware, in
the real world, roof conditions are rarely
ideal.
Just imagine an operator walking backward
and attempting to weld a seam at 35
ft. per minute while keeping the welder online.
If the machine is off by just ¼ in. at the
start of the weld, it will be off center by up
F E B R U A RY 2012 I N T E R FA C E • 2 3
Dark-colored, thin-film PV systems may also contribute to
accelerated heat aging of TPO and PVC. In this situation, the
roof consultant’s safest choice may be a high-performance TPO
membrane designed for solar applications.
to 6 in. after 100 ft. of welding is complete.
This situation will be even worse if the
operator is welding TPO or PVC membrane
over fanfold insulation or gypsum board on
a re-cover job. The installer will have to cope
with an uneven surface that may be “rocking
and rolling” his welder. In the case of
uneven roof surfaces, there’s a good chance
the compression wheel on the high-speed
welder will unload, and voids will be created
in the newly created seam.
“It’s a simple matter of looking at what
a high-tech tool can deliver under perfect
conditions, versus a real-world roof,” says a
technician with almost 30 years of experience
in TPO and PVC installations. “The
expectations of this high-speed, laborsaving,
hot-air welding device are not going
to be achieved under some jobsite conditions.
But a good roofing contractor will
make the required adjustments.”
Also, if a roof consultant has to probe
the seams to verify a proper weld on a TPO
or PVC seam, the job may already be in
deep trouble.
“Hand-probing does not tell you
whether you have a 1-in. weld or a 3-in.
weld, and probing will only get you nine or
ten pounds per lineal inch (pli) at the seam,”
says this expert. “You start to get a good
weld at about 22 pli, and the
seam shouldn’t come apart
until around 30 pli or greater.
You cannot determine that by
hand-probing a seam.”
If the roof consultant suspects
voids or weak welds in a
seam, he or she should perform
a test cut to verify the
quality of the weld.
“And forget about using a
hand welder to fix a nonspec
seam from the outside,”
according to this specialist.
“We require that you strip-in a
new membrane.”
Specifically, if the roof
consultant finds a welding
problem that is systemic
throughout the installation,
the questionable welds should
be stripped-in on both sides.
Some manufacturers allow
seam tape, but some require a
45-mil flashing strip with a
weld on both sides of the
membrane – even if that weld
is 100 ft. or longer.
Some – but not all – of the
roofing situations described
above may have unintended
consequences that ultimately
affect the long-term performance
of the system. They
can usually be avoided if common
sense and good roofing
practices are used.
On the other hand, there
are issues – particularly with some solar
roof installations – where the industry does
not yet have all the answers. The good news
is that organizations like RCI, NRCA,
MRCA, SPRI, Oak Ridge National
Laboratory, and others are hard at work to
provide the roof consultant community with
the definitive answers they seek.
24 • I N T E R FA C E F E B R U A RY 2012
Helene Hardy Pierce, FRCI, is vice president of technical services,
codes, and industry relations for GAF in Wayne, New
Jersey. She is secretary of the RCI Foundation U.S. Board of
Directors.
Helen Hardy Pierce, FRCI
The in-service temperature of a white TPO or PVC membrane is around 125°F to 130°F. However, highperformance
TPO roof membranes are now available with proprietary stabilizers and UV absorbers
specifically for solar roof installations, but they have other uses, as well. GAF’s EverGuard Extreme™
TPO is shown here. (Photos courtesy of GAF, Wayne, NJ.)