Infrared Thermography in Today’s Roofing World

May 15, 2012

Infrared thermographic technology has
been used effectively for many years
for performing moisture surveys to
detect entrapped moisture within roof
substrate materials. Infrared cameras
can be used for detecting moisture
within most types of roof construction consisting
of various membranes/coverings and
insulation types that are in place and currently
being constructed. The purpose of this
paper is to outline various thermal images
or signatures of a wide variety of roof compositions,
particularly with newer materials
or systems that have been utilized in recent
years. The various roof membranes, coverings,
insulation, and substrate materials
combined have their own thermal signature
and offer unique challenges.
ANOMA LY TYPES
As presented by others in the past, the
effectiveness of the infrared moisture survey
relies significantly on the experience of the
thermographer. As others have outlined, the
common anomalies related to moisture within
roofing systems include three basic types:
1) “board-shaped” or “board-stock” anomalies,
2) “amorphous” or “free-forming” anomalies,
and 3) “board joint” anomalous areas.
Board-Shaped Anomalies
The board-shaped type of anomaly is
the archetypical anomaly that is geometric
in nature and typically shaped similarly to
the actual insulation board (i.e., 2×4, 4×4,
4×8, etc.). These types of anomalies can
also be triangular-shaped when the wetting
occurs in tapered edge strips or crickets and
saddles. This anomaly is characteristic with
the wetting of organic fibrous insulation
boards, including perlite and fiberboard.
When this type of anomaly is of significant
size due to continued moisture infiltration
and migration, the area affected by the wetting,
when viewed through
an infrared camera, will commonly
exhibit a stair-stepped
or joint-staggered configuration
that is used during the
original installation of the
subject materials (Photo 1).
Amorphous-Shaped
Anomalies
The amorphous or
free-forming anomaly is typically
characteristic of the
N o v e m b e r 2 0 1 2 I n t e r f a c e • 2 3
Photograph 2: Typical
amorphous anomaly:
wet ISO.
Photograph 1: Board stock
anomaly of wet insulation
in stair-stepped fashion.
wetting of cellular foam plastic insulation boards such as polyisocyanurate
(iso), expanded polystyrene (EPS), extruded polystyrene (XPS),
or homogenous materials such as lightweight insulating concrete fill
(LWIC) and spray-applied polyurethane foam (SPUF) (Photo 2). Due to
the relatively low propensity of moisture migration within these types of
materials, the anomaly is often localized around the actual defect/breach
in the membrane. As moisture intrusion continues, the wetting of these
materials occurs outward in an irregular manner, resulting in the amorphous
shape. The wetting direction could also be affected by the slope
of the substrate. These anomalies are commonly contained within an
individual unit when affecting board-stock insulation, as it is much more
difficult for the moisture to migrate through a board and travel past joints
of adjacent boards due to their relatively low absorption rate. However, if
moisture intrusion is significant so that the boards are “sitting in water,”
these materials can eventually absorb significant
amounts of moisture and exhibit thermal evidence
as such.
Board Joint Anomalies
The board joint thermal anomaly can also
occur within cellular insulation material such as
cellular glass and foamed plastics. This anomaly
is observed and typically occurs during the initial
wetting as the moisture becomes absorbed along
the cut or formed edges of these boards. This type of
anomaly, when viewed through an infrared
camera,
typically appears
as irregular-shaped brightened
borders around the perimeter
edges of the insulation
board or joints between adjacent boards
(Photos
3 and 4).
2 4 • I n t e r f a c e N o v e m b e r 2 0 1 2
Photograph 3: View
of wet insulation
occurring along joint
between ISO boards
(color contrast).
Photograph 5:
Thermogram of
wet ISO below
modifiedbitumen
membrane.
Photograph 6: View of anomaly of wet ISO under
modified-bitumen membrane.
Photograph 4: View
of wet insulation
occurring along joint
between ISO boards
(gray contrast).
• Free access to technical articles from RCI’s Interface technical journal
• Download Adobe Acrobat (.pdf) files to your computer
• Keyword-searchable with Google
2 6 • I n t e r f a c e N o v e m b e r 2 0 1 2
Construction Material Issues
In today’s roofing market, applications can be
composed of a roof membrane—either single-ply or
modified-bitumen—installed directly on top of ISO
without the use of a cover board (Photographs 5 and
6). Single-ply membranes, as well as bituminous membranes,
have also been installed directly over LWIC
without incorporating any type of rigid board insulation
above the surface of the LWIC. Modified-bitumen and
single-ply membranes with white-colored surfacing are
currently installed in more widespread applications
and over various substrates that provide additional
challenges for thermographers. If the roof system is
applied directly over cellular insulation or LWIC, and
moisture intrusion has occurred, entrapped moisture
can be detected with infrared thermography (Photos 7,
8, and 9). On white-colored membranes, the images may not be
as discernible compared to other darker-colored membranes.
On smooth-surfaced, white, single-ply membranes, thermal
anomalies may appear as ghost-like images, depending on the
weather conditions during the day and survey time.
Photo 7 – Thermogram of wet LWIC under TPO membrane.
Photo 8 – View of demarcated anomaly.
Photo 10 – View of thermal anomalies caused by soiled areas of
white-surfaced modified-bitumen cap sheet.
Photo 11 – View of soiled areas of
white-surfaced modified-bitumen cap sheet.
Photo 9 – Small hole in membrane that
was source of water entry.
With the reflectivity and physical characteristics
of white roofs, the surface temperature
of the roof can remain close to
the ambient air temperature on the day
of the inspection and not become elevated
such as typically occurs with bituminous
or dark-colored coverings. Therefore, the
thermal loading and thermal differential
between wet substrate and outside and
interior air temperatures may not be as
great during the warmer months. The optimum
weather conditions for performing
an infrared survey would be a relatively
warm, sunny day followed by a rapid
cool-down after sundown, resulting in a
thermal difference of 20º to 30º or greater.
Although most commonly
used equipment is capable
of detecting temperature differentials
of less than 1º,
the greater the difference in
temperatures from daytime
to survey time, the better
the opportunity for finding
thermal anomalies. Whitecolored
surfacings could also
have false thermal anomalies
associated with isolated
areas where the surface has
become darkened or stained,
such as is associated with
ponding water (Photographs
10 and 11). Stained or darkened
areas on white-colored
surfaces that are commonly associated with
small “bird baths” of ponding water can
have a thermal appearance (amorphous)
that is very similar to wetted areas of
underlying cellular insulation, LWIC, or
SPUF. The staining that commonly occurs
on white-colored coated SPUF within undulations
of the SPUF also can appear as
thermal anomalies. Care must be taken in
these areas as well, as the ponding that
causes the staining can also be causing the
coating to break down or develop pinholes,
thereby exposing the SPUF to water intrusion
(Photograph 12). The utilization of other
nondestructive instrumentation would be
beneficial in confirming suspect areas of
Photo 12 – Small thermal anomalies in SPUF at holes in coating.
Photograph 13: Reflection of chimney and penetrations in
surface of TPO single-ply.
800.255.4255 • www.prosoco.com
Fluid-applied flashing
Use independently or as part of a
building-wide air & water barrier system
Seals rough openings
fast, effectively, and forever
• Window retrofits for existing and historic buildings.
• New construction window installation.
• Can be applied to wet or dry surfaces.
• Repels rain from the instant it goes on.
Air & Waterproof Barrier Systems
FastFlash Air & Waterproof barrier systems
for new construction and window retrofits.
RCI Feb. Ad.indd 1 10/11/12 11:03 AM
N o v e m b e r 2 0 1 2 I n t e r f a c e • 2 7
thermal anomalies identified under these conditions.
Reflections of equipment, building walls, parapet
walls, penetrations, or other items in the background
can appear, at first glance, as thermal anomalies on whitecolored
membranes that have a slick surface finish such as
typified by new TPO single-ply or modified-bitumen sheets with
film surfacing (Photo 13). The author has found that black EPDM
membranes installed over fiberboard or perlite insulation (that
has become wetted) on a concrete deck can offer the optimum
thermal imagery conditions almost any time of the year.
With the advent of new and different inorganic cover boards
with higher density and low water-absorption rates (i.e., gypsum
roof board, high-density iso, etc.), detecting moisture intrusion
in these materials can be challenging. These types of cover
boards are relatively thin (5/8 in. or less), and by their nature
will not readily “absorb” a significant amount of moisture.
Consequently, suspect wet areas (thermal anomalies) can be
difficult to discern, most likely will be generally lower in bright-
2 8 • I n t e r f a c e N o v e m b e r 2 0 1 2
Photograph 14 – Thermogram of wet area of gypsum roof board
under modified-bitumen membrane.
Photograph 15 – Thermogram of water entrapped in TPO
base flashing along parapet wall.
Photograph 17 – Thermogram of entrapped water
pockets in fiberglass insulation located below
metal roof (interior view).
Photograph 18
– Thermogram
of entrapped
water pockets
in fiberglass
insulation
located below
metal roof
(interior view).
Photograph 16 – View of anomaly location
of water in TPO base flashing.
ness (faint image), and will be amorphous in
shape (Photo 14). In addition, the roof membranes
are typically fully adhered to these
types of cover boards, which also limits and
minimizes the lateral migration of moisture
within the material.
On roofs with a single layer of insulation
installed over the roof deck, wide joints
between adjoining insulation boards and
broken and missing corners on boards can
have an enhanced thermal image very similar
to that associated with “wet” insulation.
However, the thermographer should be able
to “feel” a void under the subject membrane
to determine the true source of the thermal
difference.
Water entrapped in base flashings (most
likely occurring when the flashing was
installed during construction and an adequate
tie-in/night seal was not provided)
can often be readily detected with infrared
imaging.
Water that has migrated through a metal
roof that has exposed fiberglass blanket
insulation with a facer and
taped seams can also accumulate
moisture. The water
may not be contained within
an insulation material or the
substrate, but it can be of
significant quantity to form
a blister or a balloon shape
within the flashing material
and, therefore, become
detectable with infrared technology
(Photos 15 and 16).
After a good daytime
thermal loading of the roof
surface, with the lights off
in the building interior after
sundown and an exposed
underside of the insulation,
water pockets that have formed within
the fiberglass insulation become thermal
anomalies that can be readily detected with
an infrared camera (Photos 17 and 18).
Although demarcating the suspect areas
via infrared methods is much more difficult
than when walking on a roof surface, the
use of lifts, scaffolding, or other types of
mapping or recording methods of the findings
can be achieved. These “bulges” can
form in vinyl-face fiberglass insulation and
create a permanent deformation that may
N o v e m b e r 2 0 1 2 I n t e r f a c e • 2 9
Photo 20 –Thermal anomaly of wet perlite insulation under gravelsurfaced
BUR (note “grainy” appearance).
Photo 22 – Core showing wet upper layer of perlite in BUR.
Photo 21 – View of anomaly of wet perlite under BUR.
Photograph 19: Thermogram depicting stained fiberglass
(darker image) with concentrated pocket of water.
3 0 • I n t e r f a c e N o v e m b e r 2 0 1 2
be visible during the daytime hours, though
the actual presence or extent of moisture
cannot be confirmed without manually
checking each location (Photos 17,18, and
19). Therefore, infrared thermography can
be very efficient in assisting with this task.
Gravel-surfaced built-up roof coverings
typically can offer the most challenging conditions
for gathering accurate results from
thermal imaging (Photos 20, 21, and 22). The
irregular surfacing from the differing accumulations
of bituminous materials or gravel
typically creates numerous variations in the
thermal appearance of the roof and will most
likely involve significantly more time for the
thermographer to differentiate between false
and actual anomalies associated with wet
substrate materials. Asphalt bleed-out at side
and end laps or other overlapped sections
of sheets, together with embedded metal
flashings, provide obstacles such as “false”
readings during the survey for detecting
thermal anomalies in a roof with a granulesurfaced
cap sheet (Photo 23). It is prudent
to take additional time when viewing these
areas, as they are considered to be more
vulnerable to moisture intrusion or are most
likely sources of moisture penetration if a
breach is present.
SUMMA RY
With the advent of new materials and
roof system combinations, new challenges
arise for the individual who is tasked with
the detection of moisture within the roof—
either during or at the end of the original
installation or during its service life. The
use of infrared technology still has its
merit and is an effective tool when used
accurately, but supplemental techniques
or equipment may be necessary to properly
diagnose the actual conditions.
Karl A. Schaack is president of Price Consulting, Inc., a
professional engineering consulting firm in Houston, TX.
Schaack received a BS in civil engineering from Clemson
University in 1983 and is a registered professional engineer
in Texas and North Carolina. He has been an active
Professional member of RCI since 1996 and an RRC since
1997. Mr. Schaack is a member of the panel that authored
the RCI Registered Waterproofing Consultant examination,
participated in the 2008 RCI 10-Year-Plan Task Force, is a
current member of the RCI Technical Advisory Committee,
current member of RCI Document Competition Committee, and has authored several
articles for Interface and other industry publications. In 2007, Schaack was awarded
the Richard Horowitz Award for excellence in writing for Interface. He is an AWCI
Certified Inspector for Exterior Insulation & Finish System (EIFS) and has successfully
completed the Tile Roof Institute Certified Tile Installation program.
Karl A. Schaack, RRC, PE
Photo 23 – Thermal anomalies from asphalt bleed-out along side and end laps of a cap
sheet.
RCI is looking for photography of consultants in action:
• On ladders and roofs
• Using technology: IR tools, wind-uplift chambers, computers, etc.
• Performing inspections: roofs, walls, and waterproofing
Selected photos will be used in publication, in advertising, on Web sites,
and in e-mails. Photo credit will be given to the photographer or company.
Please submit high-resolution digital photos as well as photographer
information and a short caption to wmyers@rci-online.org.
Once submitted, copyright is owned by RCI, Inc. Contact William Myers, director of marketing
communications, at 919-389-1088 or wmyers@rci-online.org for more information.