Skip to main content Skip to footer

Reducing the Risk of Moisture Problems From Concrete Roof Decks

May 15, 2014

ABST RACT
In recent years, the roofing industry
has become increasingly aware of the problems
caused by moisture in concrete roof
decks that migrates into the roofing system.
Installing a vapor retarder over the concrete
deck is the primary method of addressing
this problem. This paper summarizes some
of the challenges associated with incorporating
a vapor retarder into the roofing system.
For example, selecting a vapor retarder
of the appropriate vapor resistance is challenging
due to the shortage of published
data on the acceptable moisture limits of
roofing materials. We explore the question
of acceptable moisture limits through an
extensive review of published literature,
product-specific recommendations from
manufacturers, and some preliminary laboratory
testing of some common roof cover
boards. This paper is based on the authors’
experience as designers and investigators
of roofing systems, literature review, and
laboratory testing.
1. BACKG ROUND
1.1 Consequences of Moisture
While the primary function of a roofing
system is to prevent water from passing
through it into the building or structure
below, water or moisture vapor that collects
within the roofing system can also be
detrimental, both to the roofing system’s
immediate performance and its long-term
durability. Besides leakage to the interior,
moisture in roofing systems can have
numerous negative consequences, including
the following:
• Reduced thermal resistance of insulation
• Loss of strength of the insulation,
coverboard (Photos 1 and 2), adhesive,
or fasteners (Photo 3), leaving
the roofing system vulnerable to
uplift damage from wind or crushing
from foot traffic or hail
• Deterioration of the structural deck
• Dimensional changes in the substrate,
which can in turn damage
the roof membrane
• Blistering or weakening of the roof
membrane itself, especially with
built-up roofing (BUR)
• Mold growth
1.2 Sources of Moisture
Moisture in the roofing system can come
from a variety of sources, such as:
• Installation of wet materials (i.e.,
2 6 • I n t e r f a c e A p r i l 2 0 1 4
Photo 1 – Moisture-damaged gypsum cover board.
insulation that was not properly
protected from weather while stored
on site).
• Water leakage through the roof
membrane, flashing, or adjacent
construction
• Moisture vapor from interior humidity
— Moisture vapor from interior
humidity may migrate into the
roofing system by diffusion if
no vapor retarder is installed.
The need for a vapor retarder
to limit the migration of interior
moisture into the roofing system
is generally acknowledged
to depend on the local climate
and the interior conditions of the
building. Later sections of this
paper include additional information
about determining when
a vapor retarder is needed.
— Moisture vapor from interior
humidity may be carried into
the roofing system by air leakage
if there is no air barrier in the
roofing system, particularly if the
building is positively pressurized
due to stack effect or the operation
of the HVAC system. This is
generally addressed by including
an air barrier in the roofing
system and connecting it to the
air barrier in the wall system to
provide a continuous barrier.
• When a new concrete deck is poured,
some of the mix water is used up in
chemical reactions as the concrete
cures, and some evaporates; but the
rate of evaporation is slow, so large
quantities of water remain stored
within the pore structure of the concrete
for extended periods of time.
While the concrete itself is generally
not damaged by this moisture, the
moisture may migrate into the roofing
system, where it is absorbed by
materials that are more sensitive to
moisture. Historically, roofing systems
were adhered to concrete decks
in hot asphalt; the hot asphalt (often
with reinforcing felts) provided the
additional benefit of limiting the
rate of moisture migration from the
concrete into the roofing system.
However, modern single-ply roofing
systems are often installed today
without any vapor retarder on the
concrete deck.
Comparison can be made to the
A p r i l 2 0 1 4 I n t e r f a c e • 2 7
Photo 2 – Moisture-damaged
fiberboard cover board.
Photo 3 – Corrosion of roofing fastener.
flooring industry, which has also
suffered detrimental effects from
moisture diffusing out of concrete
and, as a result, has developed consensus
test methods for measuring
the internal relative humidity (RH) of
concrete or moisture evaporating out
of concrete. Flooring manufacturers
typically specify acceptable RH or
moisture vapor emission limits for
the concrete as a condition of their
warranties. By contrast, the roofing
industry, while it has begun to focus
more attention on this issue,1 had
not, as of 2011, “established any
benchmarks or acceptance levels”
for moisture in concrete.2
A 2012 research update3 proposes that
“Until we have more data, 75% relative
humidity appears appropriate for normalweight
concrete” and recommends monitoring
the RH of concrete according to
ASTM F21704 to determine when it is “dry”
enough to roof over.
However, one limitation of F2170 testing
is that the standard requires conditioning
both the concrete slab and the air above
it to a constant “service temperature” and
relative humidity for at least 48 hours
before making measurements. But constant
temperature and RH do not exist
for an in-service roof; the conditions vary
constantly with the weather. Furthermore,
the effect that concrete moisture has on the
roofing system will depend on the specifics
of the roofing system and the local climate,
so it may be difficult to establish an industry-
wide “acceptable” level of moisture for
all concrete roof decks.
Another recent study5 found that concrete
retains significant amounts of water after
months of drying; therefore, high moisture
levels are likely to still be present when the
roofing system is installed. In most roofing
installations, it is impractical to wait for the
concrete deck to “dry” fully; it is often faster
and more reliable to install a vapor retarder
over the concrete deck to inhibit the migration
of moisture from the concrete into the
roofing system. Specifying the vapor retarder
presents several challenges as discussed
in the next section.
2. VAPOR RETARDER CHALL ENG ES
2.1 Wind Uplift Rating
In many roofing systems installed
over concrete decks, the roof insulation is
adhered to the concrete (often with ribbons
of low-rise foam adhesive). Incorporating a
vapor retarder into the system means adding
another layer that needs to be adhered
to the concrete and to which the insulation
needs to be adhered. In this situation, the
vapor retarder can affect the wind uplift
resistance, so it is crucial that the vapor
retarder be part of the tested assembly.
Most roofing system manufacturers now
offer tested assemblies that include adhered
vapor retarders, but the relative number
of options for this system is more limited
than those without a vapor retarder. Recent
searches of FM Global’s RoofNav online
database6 found that there are 2.5 to 3
times fewer tested systems with a vapor
retarder than the number of systems without
a vapor retarder. These searches included
both adhered and mechanically attached
insulation systems. In the authors’ experience,
roofing system designs with adhered
insulation and a vapor retarder have even
fewer options.
If the vapor retarder is going to be
adhered, moisture in the concrete deck
can affect the adhesion, so the question of
acceptable moisture content in the concrete
deck still must be addressed. Similar to
adhering a plaza waterproofing membrane
or deck coating to concrete, it is advisable to
contact the manufacturer for recommendations
and use a mock-up as the final criteria
for evaluating whether good adhesion can
be achieved.
Fortunately, designers have other
options besides adhesive for securing roof
insulation. Roof insulation (or membranes)
can be mechanically attached through the
vapor retarder into the concrete deck, which
avoids the difficulty in finding a tested
system that relies on adhesion of (and to)
the vapor retarder. Alternatively, roofing
systems in some regions can be ballasted;
however, building codes prohibit stone ballast
in some high-wind regions.
2.2. Product Selection
Another challenge is determining the
appropriate vapor permeance for the vapor
retarder. Some designers rely on past experience
and rules of thumb or the minimum
requirements of the building code, while
others use moisture vapor transmission calculations
to predict the in-service moisture
contents of any moisture-sensitive materials
in the roofing system. Rules of thumb and
calculations are discussed in more detail
below.
2.2.1 Rules of Thumb
One rule of thumb7 that is sometimes
used is that every layer in the system
should be ten times more permeable than
the vapor retarder to avoid creating a vapor
trap. Table 1 lists the typical range of permeance
of some common roof membranes
and vapor retarders. Because of the low
permeance of most roof membranes, using
a vapor retarder often violates the rule
of thumb for avoiding a vapor trap. This
means many roofing systems have very
limited ability to self-dry any water that
leaks through the membrane. Even a small
membrane defect that may not produce a
large enough volume of leakage to appear on
the inside of the building can cause water to
accumulate in the roofing system over time
and result in concealed damage. Desjarlais
explains the disadvantages of compact roofs
in several of his publications8,9,10 and recommends
avoiding vapor retarders where they
can be shown to be unnecessary. However,
in many cases—including new construction
with concrete decks—vapor retarders have
been shown to be necessary.11
2.2.2 Moisture Vapor Transmission
Calculations
Calculations provide a more sophisticated
analysis than simple rules of thumb, but
they also have their own challenges.
Moisture moves between components of
the roofing system by diffusion over time.
The moisture content of a particular layer
may vary with daily or seasonal weather
variations, and there may be a net wetting
or drying over the long term (multiple years).
The construction industry has been
developing and publishing methods for evaluating
moisture vapor flow for many years.
Hand calculation methods developed specifically
for the roofing industry include two
published in 198015 and another in 198916;
other criteria exist in ASHRAE and NRCA
publications. In the past two decades, exponential
increases in available computing
power have made state-of-the-art computer
programs for predicting moisture vapor flow
(e.g., MOIST and WUFI) readily available.
These programs have made moisture vapor
transport easier to quantify and are more
accurate than previous hand calculations.
These state-of-the-art computer programs
are now in widespread use by building envelope
consultants.
WUFI,17 a computer program by the
Fraunhofer Institute for Building Physics
(Germany), calculates transient one-
2 8 • I n t e r f a c e A p r i l 2 0 1 4
dimensional heat and moisture transport
and can be used to quantitatively predict
how moisture levels within a building
envelope assembly vary over time. WUFI
uses historical, hourly weather data for
user-selected project locations to simulate
time-varying exterior conditions (temperature,
RH, solar exposure, etc.) during the
course of the simulation. An example output
screenshot is shown in Figure 1.
WUFI can also simulate several years of
moisture migration to analyze seasonal variations
and year-to-year cumulative wetting
and drying trends. The output data can be
easily reviewed to determine, for each layer
in the roofing system, moisture-related data
such as (1) maximum annual moisture content,
(2) quantities of condensate (if any),
(3) number of occurrences of moisture content
exceeding established thresholds, and
(4) number of freeze-thaw cycles.
A p r i l 2 0 1 4 I n t e r f a c e • 2 9
American Hydrotech, Inc. 303 East Ohio | Chicago, IL 60611 | 800.877.6125 | www.hydrotechusa.com
© 2013 Monolithic Membrane 6125 is a registered trademark of American Hydrotech, Inc.
Monolithic Membrane 6125, the original rubberized
asphalt membrane, has been entrusted with keeping
high profile structures across the country and around
the globe watertight for 50 years. More than 2
billion square feet of membrane is still performing
today as it did the day it was installed.
50 YEARS OF PROVEN PERFORMANCE – MONOLITHIC MEMBRANE 6125®
RCI-50-Half-Horiztonal.indd 1 12/11/2012 5:15:41 PM
Material T hickness Permeance (U.S. perms) – S ources13
(mils = 0.001 in.) ASTM E96 Procedure B12
Roof Membranes
BUR Not reported 0.000 ASHRAE14
EPDM 60 mils 0.030 – 0.040 2 manufacturers
PVC 60 mils 0.050 – 0.220 4 manufacturers
TPO 60 mils 0.010 – 0.050 3 manufacturers
Vapor Retarders – Loose-Laid
Polyethylene or 6 mils 0.059 – 0.130 2 manufacturers
“polyolefin” sheet – 7-8 mils 0.038 1 manufacturer
various grades 10 mils 0.019 – 0.039 3 manufacturers
15 mils 0.009 – 0.021 2 manufacturers
Polyolefin – 14-15 mils total 0.000 1 manufacturer
aluminum composite
Vapor Retarders – Self-Adhered
Polyolefin – 32 mils total .017 2 manufacturers
bituminous composite
Table 1 – Permeance of selected roof membranes and vapor retarders.
A recent study18 used WUFI to analyze
a variety of roofing systems in a variety of
U.S. climates and found that in new construction,
all roofing systems constructed
over cast-in-place concrete decks accumulated
problematic levels of moisture within
the roofing system unless a vapor retarder
was included. The study further found
that selection of an effective vapor retarder
depends on the roof membrane; on typical
buildings, the vapor retarder should have a
lower permeance than the roof membrane.
The selection of an effective vapor retarder
also depends on the local climate; the study
“did not find systems that perform equally
in all climates[, and]…each geographical
location required some fine-tuning of the
roof system to make it work.”
One limitation of WUFI analysis is that
it focuses on vapor diffusion and generally
does not account for bulk air or water leakage;
therefore, the accuracy of the results
depends on proper functioning of the roof
membrane and air barrier. Also, interpretation
of WUFI results requires knowledge or
assumptions regarding the acceptable moisture
limits of the materials being considered.
The study recommends more research
“to determine the maximum amount of
moisture that roofing materials can safely
tolerate.” Quantitative knowledge of moisture
content and acceptable moisture limits
would also be valuable when one is asked to
evaluate existing roofs to determine whether
problematic levels of moisture are present.
3. ACCEPTABL E MO ISTU RE CONT ENT
OF ROO FING MATERIALS
Several industry sources have recognized
the need for more research to determine
acceptable moisture limits for roofing
materials. The recommendation in the concrete
moisture study discussed in the previous
section echoes an earlier recommendation
by Kyle and Desjarlais19 that “researchers
must establish a set of moisture limits
with a reasonable safety factor by means of
well-controlled experiments.” This need was
discussed even earlier by Tobiasson,20 who
stated, “For most roofs in most locations,
the objective is to limit seasonal wetting to
an acceptable level. This level will vary with
the moisture sensitivity of the materials
present. …However, developing moisture
limit states for each of the myriad roofing
systems on the market is a sizable task that
has not yet been accomplished.” Kirby21
similarly concluded that “the roofing industry
does not have a consensus evaluation
method for determining whether insulation
is wet.”
This section discusses information on
acceptable moisture limits for roofing materials
based on three sources: (1) limits proposed
in industry publications, (2) manufacturers’
recommendations, and (3) recent
laboratory testing conducted in support of
this paper.
3.1 Industry Publications
A wide variety of information and opinions
on acceptable moisture content is
available, illustrating the lack of consensus.
We reviewed technical literature spanning
the past 35 years and found several conflicting
theories regarding acceptable moisture
limits in roofing materials. The theories for
acceptable moisture limits discussed below
are generally listed in order of least stringent
to most stringent, although there is
ambiguity in some of the criteria.
• Thermal resistance ratio (TRR)
80% maximum. The thermal
resistivity (R-value) of insulation
is reduced when it becomes wet.
In 1991, researchers at the U.S.
Army Corps of Engineers’ Cold
Regions Research and Engineering
Laboratory (CRREL)22 proposed the
following criterion: “The ratio of a
material’s wet thermal resistivity to
its dry thermal resistivity is termed
its TRR. …Insulation with a TRR of
80 percent or less is, by our definition,
‘wet’ and unacceptable.” The
paper acknowledges that, “For some
insulations, less moisture than that
required to reduce the TRR below
80 percent can be detrimental for
other reasons (e.g., delamination,
rot, and corrosion of fasteners). It is
not yet known what those moisture
‘limit states’ should be. …As additional
information on other moisture
‘limit states’ becomes available, it is
expected that maximum acceptable
moisture contents for some materials
will decrease below the 80-
percent TRR values.” The paper further
acknowledges that equilibrium
moisture content (EMC), discussed
below, is a more appropriate pass/
fail criterion for new materials to be
installed; TRR is proposed primarily
for deciding when to replace existing
insulation. Table 2 summarizes
some the EMC and TRR data for
some other insulation products still
in use today.
• Seasonal wetting of 1-2% by volume.
23 For foam insulation with
2-pcf density, this equates to 31-62%
moisture content when calculated as
a percent of dry weight.
• No visible liquid water. Kirby24
states, “One factor can never be
ignored: If liquid moisture is present
in existing insulation, the insulation
is too wet to be left in place or
re-covered.”
3 0 • I n t e r f a c e A p r i l 2 0 1 4
Figure 1 – Example WUFI simulation screenshot for a roofing system, showing the results
for a typical year in International Falls, MN. The physical layers of the roofing system from
top (exterior) to bottom (interior) are listed from left to right. The shading in the top panel
indicates the range of service temperatures. The lower shaded areas indicate the ranges of
relative humidity and water content.
• Only small amounts of condensation.
Tobiasson25 stated, “A small
amount of moisture may condense,
then, without doing any real harm.”
He also stated, “A little condensation
on the coldest day of the
winter will do no harm, but when
condensation occurs for many days,
weeks, or months, the amount of
moisture deposited can create major
problems.”26 Condren took a similar
approach but quantified his
acceptable “small amount” of condensation,
proposing a limit of no
condensation deeper than 1/16 in.
or 1/32 in. below the membrane,
depending on the substrate material.
27 Desjarlais and Karagiozis28
base their analysis on the criterion
that the insulation should not have
an RH of 100% (i.e., condensation
occurring) for more than 24 hours,
which is consistent with one of the
three criteria in ASHRAE 160 (discussed
below).
• No condensation. Desjarlais and
Byars29 contend that “moisture accumulation
in a roof system must not
be large enough to cause condensation
within the roof, since this can
damage the insulation and reduce
its effectiveness.” They also state
that “moisture accumulation should
not be great enough to cause degradation
of the insulation material
or membrane. To pass this requirement,
there must be no condensation
under the roof membrane.”
• EMC 40%, 45%,
or 90% maximum.
The concept
of EMC as a
metric for determining
acceptable
moisture levels
in roofing materials
was first proposed
in a 1977
paper30 regarding
roofing felts, but
later expanded to
include insulation
and other materials.
The 1977
paper proposed
40% EMC as the
limit for roofing
felts that were
sufficiently dry to
avoid the appearance of blisters
when hot asphalt is applied to the
felts in construction of a built-up
roofing membrane. In addition to the
blistering concerns, the 1977 paper
found that conditioning organic and
coated organic roofing felts in a
moist environment reduced their
tensile strength (compared to ovendried
samples) by 6-18% when conditioned
at 40% RH for six weeks,
and by 11-38% when conditioned
at 90% RH for nine weeks. The
effects of moisture on roofing felts
were also studied by several other
researchers around the same time.31
The 1977 paper also examined the
EMC of insulation materials, and
notes, “The test results do not allow
definite conclusions as to the ‘tolerable’
moisture level of the insulations.
However, we expect any
‘excess’ moisture in the insulation
to be available to influence the roofing
membrane. …In view of our
field experience and pending further
research results, it seems prudent to
assume that insulation moisture will
not damage the system if the moisture
does not exceed the equilibrium
moisture content attained by 40%
RH storage.”
A 1985 article32 provides EMC
for various roofing materials conditioned
at 20°C (68°F) and both
45% and 90% RH. The article notes,
“When the material contains more
water than its EMC, it is wet and
may donate water to surrounding
air or materials.” The EMCs for
unfaced polyisocyanurate insulation
were updated in 2003.33 EMCs for
selected products that are still in
use today are summarized in Table
2, along with TRR data.
A material that contains less than
45% EMC is considered dry; between
45% EMC and 90% EMC is considered
moist; and over 90% EMC is
considered wet.
• Avoid three conditions favorable
to mold growth. There is broad consensus
that mold growth should be
avoided in buildings due to potential
health impacts and because mold
growth implies at least some level
of decay. The International Energy
Agency (IEA)36 states that susceptible
surfaces are in danger of developing
mold growth if the relative
humidity at the surface rises above
80% RH for a sustained period of
several days.
Temperature also plays a role.
Below 32°F, fungal cells may survive
but rarely grow; and above 104°F,
most cells stop growing and soon
die. ASHRAE 16037 is generally consistent
with IEA but provides more
specific recommendations. ASHRAE
recommends avoiding the following
humidity conditions in order to minimize
problems associated with mold
growth on surfaces of components of
building envelope assemblies; these
criteria apply when the running
A p r i l 2 0 1 4 I n t e r f a c e • 3 1
Table 2 – EMC and TRR of selected roofing materials.
Material EMC, Mass % @ 20°C34 Moisture content,
45% RH 90% RH M ass % @ 80% TRR35
Faced Polyisocyanurate 1.1 2.9
Unfaced Polyisocyanurate 1.7 5 262
Expanded Polystyrene (1 pcf) 1.9 2 383
Extruded Polystyrene 0.5 0.8 185
Perlite Board 1.7 5 17
Wood Fiberboard 5.4 15 15
Gypsum 0.4 0.6 8
D226 Asphalt – Organic Felt 4.1 – 4.3 7.9 – 8.2
D2178 Glass Felt 0.5 – 0.9 0.6 – 1.1
average surface temperature (for the
duration of interest) is between 41°F
and 104°F:
— 30-day running average surface
RH ≥ 80%
— 7-day running average surface
RH ≥ 98%
— 24-hr running average surface
RH = 100%
In summary, a wide range of theories
has been proposed regarding acceptable
moisture limits in roofing materials. Most
past physical testing on the effects of moisture
on roofing materials has focused on
two issues: (1) loss of thermal resistance of
insulation, and (2) weakening, decay, and
dimensional instability of built-up roofing.
In our experience, loss of strength of the
insulation (or its facers) and cover board
are also significant concerns, because they
affect the ability of the roofing system to
resist common loads such as foot traffic,
hail, or wind uplift. Moisture-induced degradation
of water-based membrane bonding
adhesive has also been reported.38
However, we are not aware of any industry
publications containing data on how
moisture affects the strength of insulation,
cover boards, or bonding adhesive, with the
exception of some limited data on gypsum
cover boards discussed in the next section.
3.2 Product-Specific Manufacturer
Recommendations
We contacted manufacturers of polyisocyanurate
insulation and gypsum cover
boards to ask for recommendations on
acceptable in-service moisture limits for
their products. This section summarizes
the information provided by manufacturers.
3.2.1 Polyisocyanurate Insulation
We contacted four manufacturers
of polyisocyanurate roof insulation and
inquired about acceptable in-service moisture
limits. One manufacturer was unresponsive,
and two said they do not have
any data or recommendations. The fourth
manufacturer cited 3% moisture content
as a rule of thumb but did not provide any
supporting data.39
3.2.2 Gypsum Cover Boards
A 2001 article40 provides data on the
water absorption of a gypsum cover board
product after 24 hours of conditioning at
95% RH, two hours of exposure to surface
moisture, two hours of immersion, and 24
hours of immersion. The article also provides
peel adhesion data for hot asphalt
application to boards at ambient conditions
and after seven days at 95% RH. The article
does not provide any recommendations for
acceptable moisture limits; its main focus
is on avoiding heat damage to the gypsum
during installation of roofing membranes
set in hot asphalt or torch application.
In addition, we contacted two manufacturers
of gypsum cover boards and inquired
about acceptable in-service moisture limits.
One manufacturer stated that it manufactures
its gypsum board to less than 2% free
water and recommends that its product
does not become “wet” but could not define
what moisture content it considers to be
“wet” or provide any recommendations for
in-service moisture limits.41 The other manufacturer
stated that its product often has
less than 1% free water as delivered from
the factory, and cited a variety of thresholds
of concern for moisture content in service,
including 2%, 4%, and 5% but did not provide
clear recommendations for an acceptable
level for long-term performance.42 Also,
the manufacturer did not provide any supporting
data on the strength of its material
at those moisture levels.
In summary, very little information is
available from manufacturers of roofing
materials regarding their products’ resistance
to moisture degradation.
3.3 Laboratory Testing
To collect some initial data on the
moisture resistance of roofing materials,
we selected three insulation cover board
products for testing. Two of the products
are gypsum-based, the third is high-density
polyisocyanurate, and all are nominally ½
in. thick. Insulation and bonding adhesive
are also of interest, but are excluded from
this initial testing.
3.3.1 Description of Testing Program
We exposed the samples to a variety of
moisture conditions and tested their flexural
strength. Flexural strength is relevant to
3 2 • I n t e r f a c e A p r i l 2 0 1 4
Issue S ubjec t S ubmission Dea dline
July 2014 Entrapped moisture April 15, 2014
August 2014 Insulation May 15, 2014
September 2014 Building envelope issues June 13, 2014
October 2014 Roofing failures July 15, 2014
November 2014 Traditional materials August 15, 2014
December 2014 Codes and standards September 15, 2014
Publish in Interface
Interface journal is seeking submissions for the following issues. Optimum article size is 1,500
to 2,500 words, containing five to ten graphics. Articles may serve commercial interests but
should not promote specific products. Articles on subjects that do not fit any given theme may be
submitted at any time.
Submit articles or questions to Executive Editor Kristen Ammerman at 800-828-1902
or kammerman@rci-online.org.
the wind uplift resistance of intermittently
attached cover boards. Tensile strength and
compressive strength perpendicular to the
plane of the board are also of interest; these
properties are excluded from this initial
testing but should be considered in future
testing.
Three samples of each of the three products
were exposed to each of the following
ten different moisture conditions (90 samples
total):
• Oven drying at 100°F (below the 110
to 115°F maximum recommended by
one of the gypsum manufacturers)
• Standard laboratory conditions (50%
RH and 74°F)
• High humidity (95% RH and 74°F)
• High humidity (95% RH and 74°F)
followed by oven drying
• Water immersion for 30 minutes
• Water immersion for 30 minutes followed
by oven drying
• Water immersion for 1 hour
• Water immersion for 1 hour followed
by oven drying
• Water immersion for 24 hours
• Water immersion for 24 hours followed
by oven drying
After conditioning, we tested the flexural
strength of the samples according to
modified ASTM C47343 method B. The test
procedure generally followed C473, but the
sampling procedures and the definition
of breaking load were modified to suit the
goals and scope of our test program. Our
test method is briefly summarized as follows
and is depicted in Photos 4 and 5:
• Samples were cut to 12 x 16 in., with
the 16-in. dimension parallel to the
long dimension of the board. Some
samples included the factory edge of
the board. All samples were tested
face up.
• The flexure fixture was set up with
supports at a 14-in. span and a centerloading
nose.
• Load was applied at a constant
crosshead rate of 1 in./minute until
the load resistance of the sample
decreased; the maximum load was
reported.
The polyisocyanurate board has anomalies
in the foam structure, known as “knit
lines,” where the ribbons of foam came
together during the manufacturing process.
The knit lines are parallel to the long dimension
of the board. By testing only samples
spanning parallel to the knit lines, we avoided
testing the weaker orientation.
3.3.2 Results
The results of our testing are summa-
A p r i l 2 0 1 4 I n t e r f a c e • 3 3
Photo 4 – Flexural test setup.
Photo 5 – Flexural test in progress.
rized as follows. We refer to the two gypsum
products as “GYP #1” and “GYP #2,” and the
polyisocyanurate product as “ISO.” Our test
results are not suitable for design-strength
values; our testing was intended only to
explore the trends of strength loss caused
by exposure to moisture.
Moisture conditioning had the following
effects on the flexural strength:
• 50% RH – None of the three products
was significantly weakened by
conditioning to standard laboratory
conditions (50% RH) compared to
oven-dry conditions.
• 95% RH – The ISO was unaffected
at 95% RH, but the two gypsum
products lost some strength. GYP #1
was reduced to 70% of its standard
laboratory strength, and GYP #2 was
reduced to 80%.
• Water immersion – The three products
showed differing rates of water
absorption when immersed. After 24
hours, GYP #1 had gained 4% weight,
GYP #2 had gained 24% weight, and
ISO had gained 11% weight (Figure
2). All three products rapidly lost
strength when immersed in water
(Figure 3). Most of the strength loss
occurred in the first hour of immersion.
In the first hour, the two
gypsum products were reduced to
approximately 60% of their standard
laboratory strength, and ISO was
reduced to approximately 70% of its
standard laboratory strength. The
rate of loss slowed significantly after
one hour of immersion; at 24 hours,
the two gypsum products retained
approximately 50% of their standard
laboratory strength, and ISO
retained around 70%.
• Moisture content – When we plot
strength versus moisture content
rather than wetting time (Figure
4), we see that the most dramatic
strength loss occurs in the range of
0 to 3% moisture content by weight.
We also see more of a difference
among the three products. At 6%
moisture content, GYP #1 is reduced
to approximately 45% of its standard
laboratory strength, GYP #2 is
reduced to approximately 63%, and
ISO to 73%.
• Oven drying after wetting – All
three products regained all of their
original strength (to within the level
of accuracy of the test method) when
oven dried after one wetting cycle.
3.3.3 Discussion of Test Results
Our testing showed that some common
cover board products lose strength quickly
and at relatively low moisture contents (less
than 5% by mass) when wetted. This result
is consistent with our field observations on
existing roofs with wet cover boards and is
also consistent with statements from one
gypsum board manufacturer that moisture
content over 2-5% is a concern.
The polyisocyanurate product was less
affected by moisture than the two gypsum
products.
Our testing further showed that some
common cover board products exposed to
one relatively short wetting cycle will regain
virtually all of their original strength after
oven drying. While this result supports the
concept that a small amount of short-term
condensation may be acceptable in some
3 4 • I n t e r f a c e A p r i l 2 0 1 4
Figure 2 – Moisture content (% of original mass) vs. duration of water immersion (hours) for
three cover board products. Each data point indicates an average of three or more samples.
Figure 3 – Flexural strength (lbs.) vs. duration of water immersion (hours) for three cover
board products. Each data point indicates an average of three or more samples.
circumstances, it does not provide sufficient
data to define those acceptable circumstances.
On many roofs, the wetting is longer
term, and the drying is less complete than
in our tests. In addition to longer-duration
wetting, other factors that could result in
unacceptable strength loss in cover boards
include: (1) a greater number of wetting and
drying cycles, (2) freeze-thaw cycles, which
are common because the coldest weather
coincides with the peak moisture levels
directly under the roofing membrane, and
(3) loading from wind or foot traffic during
one of the wetting cycles when the materials
are temporarily weakened may result in
permanent strength loss or even immediate
failure. There is no guarantee that loading
will occur only when the materials are dry
and at their maximum strength.
4. CON CLUS IONS AND
RECOMM END ATIONS
We conclude the following regarding
roofing system design for moisture in concrete
decks:
• Most roofs on new concrete decks
need vapor retarders. This poses
some challenges with wind uplift
rating and product selection, but
these challenges can be addressed
through careful design. As additional
roofing systems that include an
adhered vapor retarder are developed
and tested for wind uplift,
designers will gain more flexibility.
• State-of-the-art analysis tools are
available to predict time-varying
moisture levels due to vapor migration
through the roofing system and
assist selecting an appropriate vapor
retarder. Interpreting the results of
these analyses requires knowledge
of the acceptable in-service moisture
limits of roofing materials.
We conclude the following regarding
acceptable in-service moisture limits:
• Prior publications have proposed
various acceptance criteria for moisture
content of roofing materials. An
industry consensus does not exist,
and product-specific data and recommendations
from manufacturers
are lacking.
• Our test data show that some common
cover board products lose
strength quickly and at relatively
low moisture contents (less than
5% by mass) when wetted. However,
our data are insufficient to establish
acceptable moisture levels.
• We recommend additional research
into the acceptable in-service moisture
limits of roofing materials. In
the interim and until additional data
become available, roofing professionals
will have to continue to rely on
their experience and judgment.
Acknowledgments
The authors would like to thank the
management and shareholders of Simpson
Gumpertz & Heger, Inc. for their financial
support of the laboratory testing described
in this paper.
The authors would also like to acknowledge
the significant contributions made by
Stephen Condren, Joseph Piñon, and Paul
Scheiner in their August 2012 work referenced
in this paper. Their work has lent
much-needed clarity to the issue of moisture
in concrete roof decks, and provided
a clear direction for future research needs.
This article is republished from the
Proceedings of the 28th RCI International
Convention and Trade Show.
Footnotes
1. Mark S. Graham, “Moisture in
Concrete Roof Decks,” Professional
Roofing, February 2010.
2. Structural Lightweight Concrete Roof
Decks, MRCA T&R Advisory Bulletin
A p r i l 2 0 1 4 I n t e r f a c e • 3 5
Figure 4 – Percent of original flexural strength retained vs. moisture content (% of original
mass) for three cover board products. Each data point indicates one sample.
ENVIROSPEC INCORPORATED
The PAVE-EL®
Pedestal System
• Transforms flat roofs into
attractive, maintenancefree,
landscaped paver
stone terraces.
• Elevates paver stones
for perfect drainage.
• Levels paver stones and
ensures their uniform
spacing for an ideal roof
terrace surface.
• Ideal for laying paver
walkways in roof gardens.
Turn your roof tops into
beautiful, useful decks
716-689-8548 • www.envirospecinc.com
1/2011. September 2011.
3. René Dupuis, “Research Continues
on Moisture in SLC Roof Decks,”
Midwest Roofer, June 2012.
4. ASTM F2170-11, Standard Test
Method for Determining Relative
Humidity in Concrete Floor Slabs
Using in-situ Probes, ASTM
International, 2011.
5. S. Condren, J. Piñon, and P.
Scheiner, “What You Can’t See Can
Hurt You – Moisture in Concrete
Roof Decks Can Result in Premature
Roof System Failure,” Professional
Roofing, August 2012.
6. www.roofnav.com, searched September
2012 with the following
search terms: single-ply roof system,
new roof application, adhered cover,
structural concrete deck, board
stock insulation, and wind uplift
ratings ranging from 60 to 300.
7. Like any rule of thumb, this is a generalization,
and there are some conditions
where it may not be suitable.
8. D. Kyle, A. Desjarlais, “Assessment
of Technologies for Constructing Self
Drying Low-Slope Roofs,” CON 380,
Oak Ridge National Lab, p. 82, May
1994.
9. A. Desjarlais, N. Byars, “A New Look
at Moisture Control in Low-Slope
Roofing,” Proceedings of the 4th
International Symposium on Roofing
Technology, pp. 341-346, NRCA,
September 1997.
10. A. Desjarlais, A. Karagiozis, “Review
of Existing Criteria and Proposed
Calculations for Determining
the Need for Vapor Retarders,”
Proceedings of the North American
Conference on Roofing Technology,
pp. 79-83, NRCA, September 1999.
11. Condren et al., 2012.
12. The conditions at which permeance
is measured can significantly affect
the result, but most manufacturers
only report data for standard conditions.
Some manufacturers do not
report the test procedure, but most
do. Those that do report a procedure,
report Procedure B.
13. Manufacturers’ data is from a combination
of published data sheets and
telephone conversations with technical
representatives, September 2012.
14. ASHRAE Fundamentals, American
Society of Heating, Refrigerating and
Air Conditioning Engineers, 2009.
15. S.J. Condren, “Vapor Retarders in
Roofing Systems: When Are They
Necessary?” Moisture Migration in
Buildings, ASTM STP 779, M. Lieff
and H.R. Trenschell, eds., American
Society for Testing and Materials,
1982, pp. 5-27.
16. W. Tobiasson, “Vapor Retarders
for Membrane Roofing Systems,”
Proceedings of the 9th Conference
on Roofing Technology, NRCA, pp.
31-37, May 1989.
17. A free educational version is available
online at http://www.ornl.gov/
sci/btc/apps/moisture/; the professional
version is for purchase.
18. Condren et al., 2012.
19. Kyle and Desjarlais, 1994.
20. W. Tobiasson, “Condensation
Con-trol in Low-Slope Roofs,”
Proceedings of Workshop on Moisture
Control in Buildings, Building
3 6 • I n t e r f a c e A p r i l 2 0 1 4
October 20-21
2014
Tampa Convention
Center
Marriott Waterside
Hotel & Marina
Tampa, Florida
Tampa
2014 Building Envelope Symposium
RCI, Inc. | www.rci-online.org/symposium.html | 800-828-1902
Thermal Envelope Coordinating
Council (BTECC), Washington, DC,
September 1984. Also available as
CRREL miscellaneous paper 2039.
21. J. Kirby, “Determining When Insulation
Is Wet,” Professional Roofing,
February 1999.
22. W. Tobiasson, A. Greatorex, and
D. VanPelt, “New Wetting Curves
for Common Roof Insulations,” Proceedings
of the International Symposium
on Roofing Technology, pp.
383-390, 1991.
23. Tobiasson, 1984, cites the following
source: K. Hoher, Environmental and
Climatic Factors in the Specification of
Roofing Membranes, 1982, Sarnafil,
Canton, MA.
24. Kirby, 1999.
25. Tobiasson, 1989
26. Tobiasson, 1984.
27. Condren, 1982
28. Desjarlais and Karagiozis, 1999
29. Desjarlais and Byars, 1997.
30. Thomas A. Schwartz and Carl G.
Cash, “Equilibrium Moisture Content
of Roofing and Roof Insulation
Materials, and the Effect of Moisture
on the Tensile Strength of Roofing
Felts,” Proceedings of the Symposium
on Roofing Technology, National
Bureau of Standards and National
Roofing Contractors Association, pp.
238-243, September 1977.
31. H. Busching, R. Mathey, W. Rossiter,
W. Cullen, “Effects of Moisture in
BUR: A State-of-the-Art Literature
Survey,” Tech Note 965, National
Bureau of Standards, July 1978.
32. Carl G. Cash, “Moisture and Built-
Up Roofing,” published in A Decade
of Change and Future Trends in
Roofing – Proceedings of the 1985
International Symposium on Roofing
Technology, September 1985.
33. Carl G. Cash, Roofing Failures, Spon,
2003, p. 46.
34. Extracted from Cash, 1985, and
Cash, 2003.
35. Extracted from Tobiasson et al.,
1991.
36. International Energy Agency
(IEA) Condensation and Energy
Sourcebook, Report Annex XIV,
Volume 1, 1991.
37. ASHRAE Standard 160, Criteria for
Moisture-Control Design Analysis in
Buildings, 2009.
38. “Noteworthy Limitations of Water-
Based Bonding Adhesives,” MRCA
T&R Advisory Bulletin, 2/2011.
39. Telephone conversations with manufacturers,
September 2012.
40. Colin Murphy and Robert Wills,
“Dens-Deck Roof Board: Product
Review, Testing, and Application
Recommendations,” Interface, March
2001.
41. Telephone conversation with manufacturer,
September 2012.
42. Private correspondence from manufacturer,
2010 through 2012.
43. ASTM C473-10, Standard Test
Methods for Physical Testing of
Gypsum Panel Products, ASTM
International, 2010.
A p r i l 2 0 1 4 I n t e r f a c e • 3 7
Greg Doelp, RRC,
PE, is a senior principal
with Simpson
Gumpertz & Heger
Inc. (SGH) and has
27 years of experience
as a consulting
engineer.
Doelp specializes
in designing and
investigating roofing,
waterproofing,
and exterior wall systems. He holds a BS
in civil engineering from the University of
Delaware and an MS in civil engineering
from Cornell University. He is an RRC and
member of RCI.
Phil Moser, PE,
LEED AP, is on
the building technology
staff at
SGH and holds a
BS in civil infrastructure
from
Cornell University.
He specializes
in designing and
investigating roofing,
waterproofing,
and exterior
wall systems, and is also actively involved
in ASTM Committee D08 on Roofing and
Waterproofing as a task-group chair.
Phil Moser, PE,
LEED AP
Greg Doelp, RRC, PE
The engineer who declared that a mall was safe two days before its roof
collapsed, killing two, has been charged with three counts of criminal negligence.
Robert Wood, 64, former president of M.R. Wright & Assoc. Inc., Sault Sainte
Marie, Ontario, had inspected the Algo Centre Mall in Elliot Lake, Ontario, just
prior to its collapse in June 2012.
A judicial inquiry heard that the roof of the poorly designed structure leaked
from the time of its construction, and decades of water and salt penetration
caused severe rusting of the steel support structure. In a 2011 conversation
attested to during the hearing, Wood was said to have told a prospective buyer
that it would cost $1.5 million to fix the mall’s roof and reportedly warned that the
structure had to be fixed or the roof would cave in.
Wood was stripped of his professional engineering license in November 2011
after admitting to misconduct related to the mall.
— Canadian Press Enterprise
Engineer
Charged
With
Negligence
in Mall Roof
Collapse