Curtain Wall Laboratory: Mock-up Testing: The Who, What, When, Why, and How

May 15, 2016

3 1 s t RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 1 0 – 1 5 , 2 0 1 6 P e e v e y • 1 5
Curtain Wall Laboratory Mock-Up Testing:
The Who, What, When, Why, and How
Amy M. Peevey, REWC, RRO, PE
Building Exterior Solutions, LLC
6975 Portwest Dr., Ste. 100, Houston, TX 77024
Phone: 713-467-9840 • Fax: 713-467-9845 • E-mail: apeevey@besgrp.com
Abstract
Curtain wall preconstruction laboratory mock-up testing is often omitted or inappropriately
utilized for many new construction projects. This intermediate presentation/paper will
assist designers, owners/developers, and contractors with understanding preconstruction
curtain wall laboratory mock-up testing. Specifically, case studies will be presented illustrating
how to 1) determine when laboratory testing should be incorporated into a project, 2)
evaluate the qualifications and requirements for the testing facility, 3) develop an appropriate
testing scope, and 4) incorporate requirements determined from the laboratory mock-up
test into the project construction. To supplement the topics presented, case studies will be
utilized from the author’s experience.
Speaker
Amy M. Peevey, REWC, RRO, PE — Building Exterior Solutions, LLC
Amy Peevey is principal and partner of Building Exterior Solutions, LLC (BES). She
holds an architectural engineering bachelor’s degree from the University of Texas at Austin
and is a licensed professional engineer, REWC, and RRO. Peevey specializes in forensic
investigation and repair design, new construction design, litigation support, and testing of
building envelopes. She is a member of several professional associations, for which she has
published and presented for over a decade.
1 6 • P e e v e y 3 1 s t RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 1 0 – 1 5 , 2 0 1 6
3 1 s t RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 1 0 – 1 5 , 2 0 1 6 P e e v e y • 1 7
INTRODUCTION
Curtain wall systems remain one of
the more prevalent exterior wall systems of
modern building construction. When used,
these systems typically comprise a large
portion of the building envelope cost. As
such, there are many curtain wall decisions
made early during project conception without
the specialized expertise of a consultant
or the subcontractor performing the
work. These decisions, such as the use of
“custom” systems, often inadvertently lead
to the use of unproven systems with undesirable
performance. Even if the design
team includes procedures to confirm system
performance, such as delegated design
submittals and preconstruction testing,
these procedures are often not properly
specified, performed, or incorporated into
the project.
This paper discusses curtain wall preconstruction
laboratory testing to assist
designers, owners/developers, and contractors
with the proper specification and
performance of preconstruction laboratory
testing. Specifically, identification of when
to perform preconstruction testing, qualifications
and requirements for the testing
facility, mock-up specimen, testing scope,
and mock-up installation requirements will
be discussed. Additionally, case studies of
laboratory mock-up testing will be utilized
to illustrate the topics discussed, as well as
lessons learned from the author’s experience
over the past 15 years.
THE WHEN AND WHY OF
PERFORMING TESTING
Laboratory mock-up testing provides an
opportunity to determine the efficacy of the
exterior wall design, fabrication, sequencing,
constructability, aesthetics, and performance
of individual exterior wall systems
and integration between systems. It affords
the opportunity to address construction
problems prior to assembly on the building
where remediation can be extremely difficult,
costly, and lead to significant impacts
on the project aesthetics, schedule, and
budget.
For many projects where the design
can accommodate standard manufactured
curtain wall systems, preconstruction laboratory
testing is often not required. For
these projects, manufacturers’ third-party
laboratory testing of their standard system
indicates that it has been tested to meet or
exceed the specified performance requirements
for the project. However, careful consideration
of the test specimen(s) should be
performed to ensure that it is representative
of the project-specific system.
Specifically, when evaluating the system’s
structural performance, the test specimen
must have framing profiles, joinery
and framing connections, system depth, etc.
that are equal to that for the project; and
the mullion spans, insulated glazing sizes,
etc. must be equal to or larger than that for
the project.
When evaluating the system’s air infiltration
and water-penetration performance,
the means of glazing such as structural silicone,
mechanically captured, inside glazed
vs. outside glazing, etc. must be equivalent
to that specified for the project. Another
example where a manufacturer’s standard
laboratory test report may be used in lieu
of preconstruction laboratory testing is for
thermal requirements. When evaluating the
thermal performance, the test specimen
frame type and profile must be equal, the
framed openings must be equal or smaller,
and the glazing must be equal to or inferior
in thermal performance to that for the project
in order to certify that the system meets
the specified requirements.
However, if the third-party laboratory
test specimens, test procedures, test
parameters, etc. are not representative of
the project-specific conditions and performance
requirements, if systems are combined
to create a new hybrid system; if new
elements such as sunshades or vertical fins
are incorporated; if a system is customdesigned
for the project; or if there are project
requirements for which a system has not
been tested (e.g., blast resistance, hurricane
impact, sound transmission, seismic resistance,
etc.) then the standard manufacturer
third-party preconstruction laboratory testing
is not representative of the actual project
conditions and requirements. For these
conditions, preconstruction laboratory testing
is required to ensure that the proposed
system can meet the specified performance
requirements.
Many times, it is justified to extrapolate
the structural performance of a system
through engineering analysis and modeling.
However, while a modified system
can be modeled and the modifications
validated structurally by means of a delegated
design, the assumptions that serve
the basis of the design require verification.
Further, a delegated design cannot assure
air infiltration, water penetration, thermal
performance, etc. of significantly modified
systems. Therefore, the extrapolation
with engineering analysis should only be
performed for a small percentage of the
curtain wall where an existing system has
been certified to meet the majority of the
higher load requirements and will only
require reinforcement to meet higher wind
loads at “hot spots” or at longer spans.
Otherwise, project-specific preconstruction
laboratory testing is warranted to certify
the system performance and confirm that
the modeling and associated assumptions
are accurate.
Additionally, the prefabrication process
can play a significant impact on the system
performance. Many systems originally
intended for field-assembly are modified by
installers, so that portions or entire components
are prefabricated to expedite installation
and reduce construction schedules.
However, these modifications are often not
part of the manufacturer’s standard installation
instructions and have typically not
been incorporated into the manufacturer’s
third-party laboratory testing for a standard
system. As a result, the performance of
these modifications has not been confirmed,
nor is the impact on the performance and
maintenance of the system understood.
Therefore, depending on the extent of modification,
a preconstruction laboratory test
may be warranted or, at a minimum, performance
of a preconstruction field test should
be performed prior to wholesale installation
of these modified systems.
Curtain Wall Laboratory Mock-Up Testing:
The Who, What, When, Why, and How
While the main purpose of performing
the preconstruction laboratory testing
is to evaluate the performance of the
system(s), aesthetic considerations can
also be addressed within the mock-up
test specimen. It is common practice to
have different glazing types or architectural
finishes provided within the test
specimen for the designer’s consideration.
Also, repaired conditions may
be incorporated so that the designer
can develop acceptance thresholds for
various exterior wall cladding system
repairs anticipated during the construction
process.
Who Should Perform and
Be Involved With Testing
Laboratory mock-up testing is a
large project investment. Gleaning
the benefits of this endeavor is only
as valuable as the data generated.
Therefore, it is critical to utilize a qualified
and independent laboratory testing
agency. The laboratory selected should
be qualified according to ASTM E329,
Standard Specification for Agencies
Engaged in Construction Inspection,
Testing, or Special Inspection, for testing
indicated, as documented
according to ASTM E548,
Standard Guide for General
Criteria Used for Evaluating
Laboratory Competence.
ASTM E329 defines the
minimum requirements and
qualifications of the laboratory
personnel, as well as the
technical requirements for
the testing equipment. ASTM
E548 provides guidance on
evaluating the expertise of
testing laboratories.
In addition to utilizing
a qualified laboratory, the
laboratory should be independent,
with no affiliations
with the manufacturer,
installer, or other project
team members. One means
of ensuring a laboratory meets the qualifications
(as well as independent, third-party
requirements) is to utilize an AAMA-certified
laboratory. Utilizing an AAMA-certified laboratory
ensures that the laboratory has the
means and resources to perform the AAMA
and ASTM testing and is an independent
party (no affiliation with manufacturers) so
that the project team is assured they can
properly perform the testing in an unbiased
manner.
During construction of the mock-up
test specimen, a test laboratory representative,
the installer’s foreman and installation
crew, general contractor, consultant, and
designer should be present. Observations
of the mock-up installation by these representatives
should be conducted to ensure
that the systems are being installed in
accordance with the manufacturer’s installation
instructions, as well as the design
intent. The owner’s representative, general
contractor, installer’s foreman, consultant,
designer, and test laboratory representative
should all be present during all testing
of the mock-up, including pre-testing
and retesting, if any. These project team
members should be those designated for
the project construction phase. Typically,
Figure 1A – Mock-up
elevation for a Class-A
office building in The
Woodlands, Texas.
Figure 1B – Mock-up sections for a Class-A
office building in The Woodlands, Texas.
1 8 • P e e v e y 3 1 s t RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 1 0 – 1 5 , 2 0 1 6
a large amount of information is collected
regarding the required prefabrication process,
installation procedures, and integration
of the exterior wall components during
the mock-up test specimen installation and
testing. The presence of project-designated
team members will help ensure that this
knowledge is properly incorporated into the
project submittals and field installation so
that the system(s) perform properly in the
field.
What Is the Scope of the
Test Specimen and Testing?
Laboratory mock-ups are to be full-sized
and representative of the actual project
conditions including the exterior wall systems
that comprise the building cladding.
The mock-up elements are to be of accurate
size, orientation, and configuration, including
their means of cladding attachment and
integration between systems. ASTM E2099,
Standard Practice for the Specification and
Evaluation of Preconstruction Laboratory
Mock-ups of Exterior Wall Systems, and
AAMA 501, Methods of Tests for Exterior
Walls, provide insight into the scope, size,
and testing for exterior wall mock-ups.
These standards should be utilized and
referenced in the specification of preconstruction
laboratory mock-up testing. ASTM
E2099 provides minimum parameters that
include interior and exterior corners, at
least one floor in height or one repetition
of the cladding design that bypasses
a floor line (whichever is greater), and at
least three bays in width. Figures 1A and
1B illustrate a mock-up size, configuration,
and components that meet the ASTM E2099
parameters.
Another consideration that may be
included is to simulate the transport and
erection process of prefabricated units
as a part of the mock-up test specimen.
Specifically, if a fabrication facility requires
long transport, shipping transport, or other
transport of prefabricated components that
may impact the prefabricated work and
related performance, then the units fabricated
for the mock-up should undergo
the same transport procedures so that the
process (storage, crating, lifting, vibration,
transport loads, etc.) can be vetted as a part
of the preconstruction laboratory mock-up
testing. Or if the erection process may result
in loading of the units that is outside the
typical performance requirements, such as
the potential torqueing of twin-span units
(units that are two stories in height) during
erection, then the project-specific erection
process should be incorporated as a part
of the mock-up installation. Ultimately,
the actual extent of the preconstruction
laboratory mock-up test specimen and testing
scope is left to the specifier, installer,
testing laboratory, and other project team
members.
As a general rule, the author recommends
following the parameters outlined in
ASTM E2099 for the specimen size and that
the configuration of the mock-up be representative
of a majority of the actual project
conditions. However, specific features that
may be performance concerns (such as
bump-outs, overhangs, large projecting
shading elements, cantilevered parapets,
or soffit conditions, etc.) may also be incorporated
so that they can be studied and
their performance verified. Incorporation
of these elements and their impact on the
overall mock-up performance should be
heavily considered. Finally, it should be
noted that the laboratory chamber size
might restrict the size of the mock-up, as
well as the mock-up components. Some
test laboratories may have head clearance,
load capacity, or accessibility issues for
crane access for heavier cladding components
such as precast panels. Therefore,
the proposed testing laboratory should be
consulted prior to finalizing the mock-up
size and scope.
The purpose of testing the laboratory
mock-up is to confirm the performance
of the exterior wall system’s air infiltration,
water penetration, and structural performance,
as well as other requirements.
Therefore, at a minimum, testing for the
air, water, and structural requirements
should be incorporated into the testing
sequence. AAMA 501, Methods of Test for
Exterior Walls, provides a testing sequence
that includes associated performance tests,
as well as optional testing for other performance
characteristics. Optional additional
testing can be performed to evaluate the
thermal performance, condensation resistance,
seismic performance, acoustical performance,
etc. The specifier should review
the performance requirements and corresponding
testing to develop an appropriate
testing scope and test parameters for the
project.
To define the system parameters, the
specified performance requirements are utilized.
For the mock-up air infiltration and
water penetration resistance pressures, the
specified pressures are used. However, it
isn’t always so straightforward when establishing
the structural test pressures. For
structural testing, the positive and negative
test pressures should be representative of
the higher wind pressures for the building
cladding, yet not necessarily the “hot spots”
where the design can be extrapolated in
the delegated design. As a general rule, the
author recommends that the structural test
pressures be the highest pressure representative
of 95% of the cladding area.
Once the test scope and parameters are
determined, the sequencing of the testing
must be established. AAMA 501 provides
guidance on the testing sequence and ASTM
E2099 outlines a specific testing sequence
for testing, including optional testing that
may be performed.
One element essential to the long-term
performance of curtain wall systems is
the performance of the curtain wall after
reglazing. Curtain wall systems will require
replacement of units from damage or performance
issues throughout the life of the
building. Therefore, the manufacturer’s
reglaze procedure should be tested to confirm
that it is able to meet the air infiltration,
water penetration, and structural
performance requirements. As such, the
author highly recommends incorporation
of a reglazed insulated glass unit into the
mock-up testing scope. It should be noted
that reglazing of units that are structural
silicone-glazed and then weather-sealed at
the face will impact the overall test schedule,
as the weather seal will need to sufficiently
cure prior to performance of the
testing.
How to Incorporate Into the Project
The preconstruction laboratory mockup
process takes a significant amount of
time; therefore, the project schedule should
include sufficient lead time to allow for
preparation, construction, and testing of
the mock-up. Initially, to coordinate the
mock-up construction and confirm it meets
the specifier’s intent, mock-up shop drawings
should be generated. ASTM E2099
provides guidance regarding the information
to be conveyed in the mock-up shop
drawings, which entails dimensioned elevations
and plans with details sufficient to
illustrate the mock-up construction. The
author recommends the following additional
general requirements. First, the shop
3 1 s t RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 1 0 – 1 5 , 2 0 1 6 P e e v e y • 1 9
drawings should be a coordinated set from
each installer representing their scope of
work and how it is integrated with adjacent
systems. Next, testing should be performed
in the presence of the specifier, contractor,
installer, laboratory, and owner’s representative,
and the results of testing should be
documented by the laboratory. Finally, after
testing is completed, any modifications to
the mock-up components should be documented
into as-built shop drawings and
incorporated into the project.
Additionally, there are several other
recommended provisions that can be incorporated
that will assist with maximizing
the benefit of performing a preconstruction
laboratory mock-up testing. These include
the inclusion of mock-up submittals, a preconstruction
mock-up meeting, key personnel
requirements, and provisions for extra
materials. To ensure that the pre-fabrication
and field installation procedures utilized
for the mock-up meet the project requirements,
the author recommends that these
procedures be submitted prior to erection
of the mock-up. If test failures occur, then
these procedures
can be reviewed and
revised accordingly.
The final procedures
generated after successful
mock-up performance
are to be
those utilized for the
project. Additionally,
shop and field quality
control and assurance
procedures
can be submitted so
that their effectiveness
can be reviewed
during mock-up construction.
To ensure
that sequencing,
constructabi l i ty,
compatibility, and
other construction
installation issues
are vetted, the
author recommends
the performance of
a preconstruction
mock-up meeting.
As previously indicated,
to ensure that
the lessons learned
during mock-up construction
and testing
are transferred to project personnel performing
and supervising the actual work, the key
personnel supervising and performing the
mock-up construction are to be the same as
that for the project. Finally, because mockup
failures result in expensive delays due
to repairs and laboratory personnel availability,
the author recommends that extra
materials be on hand at the mock-up site,
should repairs be required after a failure
occurs.
CASE STUDY #1
In 2013, a 20-story, high-rise, concreteframed
Class-A office building located in the
Galleria area of Houston, Texas, was constructed
with the exterior walls consisting
of aluminum-framed glass curtain wall. The
office building included a two-story groundfloor
lobby and eight parking decks at the
lower floors with 12 floors of office space at
the upper floors. The owner/developer negotiated
a contract price with the curtain wall
installer for a “custom” unitized curtain wall
system at a significant savings without the
involvement of a project building envelope
consultant. The custom system was to be
designed by the manufacturer to meet the
project requirements, including the incorporation
of large sunshades and cantilevered
conditions at the entry-level soffit and roof
parapet condition. Additionally, the proposed
custom system’s extrusions were to
be fabricated in China, partially assembled
in South America, and then glazed in the
United States.
Once construction was underway and
the consultant was integrated into the construction
phase, the consultant expressed
concerns regarding the custom system. Of
significant concern was that the system had
not undergone laboratory testing to certify
that its performance could meet the project
requirements and confirm the basis of the
engineering assumptions and modeling of
the curtain wall design. Additionally, the
procurement of the components and prefabrication
process for the unitized system was
of concern. Materials fabricated in China
do not have the same American processes
and standards to confirm they meet the
specified requirements. Prefabrication and
shipping of unglazed units present concerns
regarding potential damage to joinery seals
and components during shipping. In addition,
quality assurance and quality control
concerns were expressed, as the prefabrication
process would be difficult to monitor
at such a long distance. The consultant
recommended that the custom system be
fabricated and glazed locally and undergo
preconstruction laboratory testing to certify
its performance. However, the installer and
general contractor indicated that the initial
project schedule would not allow for the
testing without resulting in delays, as well
as adding significant cost to the project.
During discussions with the project
team regarding incorporation of the recommended
preconstruction testing, the manufacturer
indicated that testing could be
performed in South America. However, it
was quickly determined that the facility
in South America was not an accredited
facility and was only capable of performing
air infiltration and water penetration
testing. Further, partial and/or full fabrication
in South America did not address the
consultant’s shipping or quality assurance
and quality control concerns. Eventually,
the installer agreed to fabricating and
glazing locally and assured the general
contractor and owner/developer that it
would maintain the initial schedule while
2 0 • P e e v e y 3 1 s t RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 1 0 – 1 5 , 2 0 1 6
Figure 2 – Stick-framed curtain wall mock-up.
assuming the risk of proceeding with fabrication, though testing could potentially
require necessary modifications to the system in order to meet the performance
requirements.
It was determined that two mock-ups would be performed: one for the twostory
entry stick-framed curtain wall, and one for the unitized curtain wall of the
tower. An agreement was made to utilize an accredited laboratory in Texas. The
installer proposed the configuration of the two test specimens: a two-story, twounit-
wide mock-up specimen for the stick-framed curtain wall (Figure 2), and a
two-story, three-unit wide with a single-unit outside corner return (Figures 3 and
4) for the unitized curtain wall. Further, the soffit and parapet cantilever conditions
were incorporated into the installer’s proposed unitized mock-up configuration
(Figure 5). Both mock-up configurations were accepted by the project team.
The installer proceeded with final engineering for the mock-up and the building,
as well as the subsequent shipment and fabrication of the curtain wall
components at the installer’s plant in Texas. Initially, the mock-up units were
prefabricated, and then the building units were prefabricated, starting with the
lower floors. The consultant conducted plant
visits to observe the process and confirm that
quality assurance and control provisions were
3 1 s t RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 1 0 – 1 5 , 2 0 1 6 P e e v e y • 2 1
Figure 5 – Section through
unitized mock-up.
Figure 4 – Outside corner of
unitized curtain wall mock-up.
Figure 3 – Unitized curtain wall mock-up.
in place. Once the mock-up units were fabricated, they were sent to the
testing laboratory and were erected onto the test chamber.
The consultant required that one of the insulated glass units (IGUs) be
deglazed and reglazed within the unitized mock-up specimen (Figure 6) to
confirm the performance of the custom system’s reglaze procedure. During
the deglazing and reglazing process, it was determined that the reglaze
procedure was inadequate because it omitted ripping of the pressure plate
to allow clearance for the IGU installation, and also because it required
additional joinery and zone plug sealant repairs as a result of deglazing.
The consultant, installer, and manufacturer worked together to create a
new reglaze procedure that accurately reflected the reglaze requirements to
ensure that replacement of units would still meet the project requirements.
The preconstruction laboratory test scope included air infiltration, water
infiltration (dynamic and static), and structural testing of the stick-framed
and unitized curtain wall specimens, as well as testing of the window
washer tie-back buttons on the unitized curtain wall. Both the stick-framed
and the unitized curtain wall met the air infiltration testing requirements.
Water intrusion was observed at the perimeter joint conditions during initial
water testing of the unitized curtain wall. For the stick-framed curtain wall,
deformation of the stick-framed mullions at the anchors (Figures 7 and 8)
was observed during structural testing. For the unitized system, excessive
structural deflection of the unitized two-piece intermediate mullions
(Figures 9 and 10) was observed. As a result, both systems failed to meet
the structural performance requirements. Subsequently, structural testing
was suspended and the remainder of the testing was canceled.
For the stick-framed curtain wall, it was determined that the singletrunk
“T” mullion anchors resulted in excessive bearing pressure on the
aluminum mullion interior wall, resulting in deformation of the
mullion. The anchors were replaced with standard two-trunk
“T” brackets to distribute the bearing between the anchors and
the mullions so that it did not exceed the allowable aluminumbearing
strength. Once the structural issues were mitigated,
static water testing was performed and water intrusion was
observed. The water intrusion was subsequently repaired, and
the specimen was able to pass the remainder of the testing,
meeting the specified performance requirements.
However, testing of the unitized system was not as straightforward.
The deflections recorded during structural testing of
the unitized system were not representative of the behavior
modeled by the curtain wall engineer responsible for the del-
2 2 • P e e v e y 3 1 s t RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 1 0 – 1 5 , 2 0 1 6
Figure 6 – Reglazing of unitized mock-up.
Figure 7 – Structural failure at mullion
connection of stick-framed curtain wall.
Figure 8 – Structural failure at mullion
connection of stick-framed curtain wall.
egated design. This was
of particular concern, as
not only was the curtain
wall experiencing excessive
deflection that was
partially deglazing units
and causing rolling of
the intermediate twopiece
mullions, but the
engineer’s assumptions
for structural modeling
of the curtain wall system
did not appear to be
accurate. As a result, the
custom unitized curtain
wall design was in question.
Initially, rotation of
the anchor clips was suspected
as the cause of
the abnormal behavior.
However, adjustments to
the anchors did not mitigate
the excessive deflections
during subsequent
retesting, and displacement at the anchors was observed (Figures 11 and 12).
In addition, the unitized curtain wall was disassembled so that steel reinforcing
could be incorporated. However, additional retesting continued to result in
excessive deflections of the intermediate mullions, which continued even after
the maximum amount of reinforcing was incorporated at the intermediate mullion
conditions.
After multiple rounds of testing, the curtain wall engineer was unable to
reconcile the calculation model with the actual behavior observed during testing.
Therefore, in order to certify the performance of the unitized curtain wall
for the lower floors where the units had already been fabricated,
it was determined that a separate mock-up would be constructed
that was representative of a typical two-story unitized
configuration (Figure 13). This mock-up was tested, and while
it experienced multiple water penetration failures due to poor
stack joint, joinery, and gasket seals, it was able to meet the
3 1 s t RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 1 0 – 1 5 , 2 0 1 6 P e e v e y • 2 3
Figure 9 – Partial deglazing of vision unit
due to excessive deflection of two-piece
mullion for unitized curtain wall.
Figure 10 – Rolling of two-piece
intermediate mullions and partial
deglazing of IGU following negativepressure
structural testing.
Figure 11 – Shim added at unitized
curtain wall anchor bracket assembly.
Figure 12 – Displaced shim following
structural testing at negative pressure.
structural performance requirements. So, despite the ongoing structural
failure of the original unitized curtain wall, installation on the building proceeded
at the lower floors, as the third mock-up was able to confirm that the
system was able to meet the structural requirements for standard floors.
Meanwhile, additional testing of the original unitized mock-up was
performed with modified anchors and maximum reinforcement of the intermediate
mullions. This testing yielded breakage of the glazing when tested
at 150% negative structural load (Figure 14). The failure was attributed to
displacement of the horizontal stack assembly (Figure 15).
Following the mock-up testing, it was determined that the mock-up
configuration with two cantilevered conditions at each end with only an
intermediate twin-span condition was not representative of any condition of
the actual project. While the deflections of the fully reinforced intermediate
mullions at the taller upper floors adjacent to the parapet condition still
exceeded the requirements, it was determined that the mock-up configuration
resulted in significantly higher deflections than representative for
the project and that the fully reinforced mullions at the upper floors was
acceptable.
Another asset gained from preconstruction laboratory testing that was
gained was the requirement to incorporate the unitized system’s reglaze
procedure. During installation of a portion of the unitized curtain wall
that included fritted insulated glass units, it was determined that the
low-E coating was omitted from the fritted units. As a result, a few hundred
preglazed unitized IGUs had to be removed and replaced. The revised
reglaze procedure was utilized for these replacements, and field-pressurized
chamber water testing was performed to confirm successful performance.
CASE STUDY #2
In 2014, a 12-story, high-rise, concrete-framed Class-A office building
located in Houston, Texas, was constructed with the exterior
walls consisting of aluminum-framed glass curtain wall (Figure
16). As with Case Study #1, the owner/developer negotiated a
contract price with a curtain wall installer for a “custom” unitized
curtain wall system at a significant savings without the
involvement of a building envelope consultant on the project.
The custom system was to be designed by the installer to meet
the project requirements, including the incorporation of glazed
granite panels within the unitized system. This time, consideration
for a preconstruction laboratory mock-up was included
within the installer’s scope and the project schedule.
2 4 • P e e v e y 3 1 s t RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 1 0 – 1 5 , 2 0 1 6
Figure 13 – Two-story unitized mock-up of typical floor
spans.
Figure 14 – Glazing breakage during
150% negative structural load testing.
Figure 15 – Displaced unitized curtain
wall horizontal stack assembly.
It was determined that the mock-up configuration would be two
stories in height and three units wide, with a single-unit outside
corner return (Figure 17). The preconstruction laboratory test scope
included air infiltration, water infiltration (dynamic and static), and
structural testing of the unitized curtain wall specimen, as well as
testing of the window washer stabilization anchorage. Specifically, the
testing sequence was as follows: static water testing, dynamic water
testing, structural testing at +100%, static water testing, structural
testing at +150%, and window-washer stabilization anchor testing.
During initial testing, excessive air infiltration was observed, and
testing was suspended. No water testing was performed, as failed air
testing would typically yield water penetration during water testing.
However, to confirm that there were not structural performance issues
with the mock-up, preliminary testing of 50 and 100% structural at
3 1 s t RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 1 0 – 1 5 , 2 0 1 6 P e e v e y • 2 5
Figure 16 – Case Study #2—a 12-story
commercial office building.
Figure 17 – Unitized mock-up of Case Study #2.
Figure 18 – Air exfiltration observed with smoke bomb
and pressurized chamber.
Figure 19 – Air exfiltration observed with
smoke bomb and pressurized chamber.
positive and negative pressures was conducted. No excessive
deflections or structural performance issues were identified.
Additionally, the source of the air leakage was investigated
with a smoke pen and a smoke bomb while negatively pressurizing
the chamber (Figures 18 and 19). Air infiltration was
observed at each mullion head, stack joint, and sill condition.
Specifically, it was determined that air was passing up and over
the stack joint vertical receiver (aka “chicken head”) inside the
overlying hollow two-piece mullions. Additionally, the mullion
end caps were not of sufficient depth to encapsulate the back
of the glazing pocket, allowing air infiltration at each end of the
unit mullions.
Repairs were made to the test specimen, which included the
installation of deeper mullion end caps (Figures 20 and 21) at
the head and sill of each mullion, as well as the installation of
sealant at the interior pocket at the stack joint condition within
each mullion (Figures 22A and 22B). Testing was repeated, and
the system met the air infiltration and water penetration performance
requirements, as well as the structural requirements.
2 6 • P e e v e y 3 1 s t RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 1 0 – 1 5 , 2 0 1 6
Figure 20 – Extended mullion end cap.
Figure 21 – Section at extended
mullion end cap.
Figure 22A – Additional seal at hollow two-piece
mullion stack joint condition.
Figure 22B – Close-up of additional seal at
hollow two-piece mullion stack joint condition.
CASE STUDY #3
During 2007 and 2008, a 14-story, highrise,
concrete-framed Class-A office building
located in Houston, Texas, was constructed
with the exterior walls consisting of aluminum-
framed glass curtain wall. As with
Case Studies #1 and #2, a “custom” curtain
wall system was selected for the project;
however, the system was stick-framed and
not unitized. The custom system was to be
designed by the installer to meet the project
requirements, including the incorporation
of sunshades. Consideration for a preconstruction
laboratory mock-up was included
within the installer’s scope
and the project schedule.
It was determined that
the mock-up configuration
would be two stories in height
and three units wide (Figure
23). The preconstruction laboratory
test scope included
air infiltration, water infiltration
(dynamic and static),
and structural testing of the
curtain wall specimen, as
well as testing of the windowwasher
stabilization anchors.
Specifically, the testing sequence was as
follows: static water testing, dynamic water
testing, structural testing at +100%, static
water testing, structural testing at +150%,
and window-washer stabilization anchor
testing.
During initial static water-penetration
testing, water intrusion was
observed at several locations.
Through field-nozzle testing
(used to isolate the location
of the water penetration) with
the pressurized chamber
and visual observation of the
curtain wall installation, three installation
issues were identified as contributing to
water infiltration. These sources were modified
glazing stops, modified weep holes, and
installation sequencing.
A large source of water intrusion was
the premature termination of the interior
glazing stops (Figure 24) or discontinuity
of the glazing stops at curtain wall mullion
anchor locations (Figure 25). The glazing
stops were replaced with continuous glazing
stops that terminated within ¼ inch of the
glazing corner conditions.
Another source was determined to be
weep holes that
were modified in
size and profile from
that indicated in the
shop drawings along
the sill condition.
Rectangular slotted
weeps, in lieu of circular
weeps, were
observed (Figures
26 and 27). These
weeps allowed more
water into the system
than could be
managed and evac-
3 1 s t RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 1 0 – 1 5 , 2 0 1 6 P e e v e y • 2 7
Figure 23 – Stick-framed mock-up of
Case Study #3.
Figure 26 – Rectangular
weepholes at base sill track.
Figure 27 – Modified weepholes at other
intermediate horizontal mullions.
Figure 24 – Prematurely
terminated interior
glazing stop.
Figure 25 –
Discontinuous
interior glazing stop
at mullion anchor.
uated to the exterior, resulting in overflow
at the back of the glazing pocket along the
sill condition.
Finally, the alignment plate at the mullion
splice along the face of the left mullion
prohibited proper field adhesion of the splice
sealant (Figure 28). Therefore, the field
installation procedure was modified so that
the alignment plates were removed during
installation to permit adequate field-sealant
installation. The alignment plates were then
reinstalled with cap-sealed fasteners.
CLOSING
While preconstruction laboratory testing
adds additional cost and schedule impacts
for new construction projects, it is often
necessary to ensure that the proposed
system(s) meet the project performance
requirements. If cost and schedule take
precedence, then the designer should incorporate
curtain wall systems that have been
tested by a third-party laboratory as a basis
of design. When specifying these systems,
the designer must carefully review the product
test reports to ensure that the tested
specimen is representative of the project
and meets the desired performance requirements.
However, deviations from the basis of
design system—such as custom or hybrid
systems, incorporation of new components,
or laboratory test reports with specimens
that are not representative of the project—
will require preconstruction laboratory
testing for a project. Also, preconstruction
laboratory testing is often desired to confirm
that the detailing of the transitions between
exterior wall systems meet the specified
structural, air infiltration, and water penetration
requirements. Finally, evaluation of
different glazing types and other aesthetic
considerations is desired in support of
performing project-specific preconstruction
laboratory testing.
When it is determined that preconstruction
laboratory testing is to be performed,
then only a qualified and independent
laboratory should perform the testing.
Certification programs such as those by
AAMA are a means of ensuring that unbiased
parties properly perform the testing.
During construction of the mock-up and
performance of testing, at a minimum,
project-dedicated representatives from the
owner, designer, consultant, general contractor,
and installer should be present to
help ensure that lessons learned during
testing will be properly incorporated into
the project.
Prior to testing, the scope of the test
specimen must be developed. The scope of
the mock-up should indicate what is to be
tested and what testing is to be performed.
The mock-up test specimen should incorporate
full-sized exterior wall elements that
are representative of the project conditions.
At a minimum, the air infiltration, water
penetration, and structural performance
should be tested. The scope of the mock-up
test specimen and the testing performed
should be coordinated with the testing
laboratory and the project team members.
Additionally, the author strongly suggests
that the transport and erection procedures,
as well as incorporation of a reglazed insulated
glass unit, be considered as a part of
the mock-up test specimen to ensure that
these procedures do not negatively impact
the system’s performance requirements.
Sufficient time for the construction and
testing of the mock-up test specimen should
be provided within the project schedule
to ensure completion of testing prior to
prefabrication of exterior wall components
and field installation. The schedule should
include provisions for retesting, if necessary.
Further, to maximize the benefit of
preconstruction laboratory mock-up testing,
mock-up submittals, a preconstruction
mock-up meeting, key personnel participation
requirements, and provisions for extra
materials should be included.
The case studies presented highlight
the need for testing of curtain wall systems.
Had preconstruction laboratory
mock-up testing not been performed for
these projects, the results could have been
catastrophic. These case studies present
considerations for preconstruction laboratory
mock-up testing scope and importance
of incorporating the provisions indicated
within this paper. When properly specified
and performed, preconstruction laboratory
mock-up testing can ensure proper performance
of the system(s), as well as proactively
resolve issues prior to construction,
thereby mitigating the potential for costly
and time-consuming repairs during or after
construction.
2 8 • P e e v e y 3 1 s t RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 1 0 – 1 5 , 2 0 1 6
Figure 28 – Alignment plate at the face
of the splice joint prohibiting proper
field sealant installation.