Onondaga County Re-Roofing Project: Impacts of Reflectance and Thermal Resistance

May 15, 2018

Onondaga County Reroofing Project:
Impacts of Reflectance and Thermal Resistance
Michael D. Fischer
Kellen Company
529 14th Street NW, Suite 750, Washington, DC 20045
Phone: 202-591-2438 • E-mail: mfischer@kellencompany.com
Hugh Henderson, Jr. and Nicholas Genzel
CDH Energy
2695 Bingley Road, Cazenovia, NY 13035
Phone: 315-655-1063
and
Marcin Pazera
PIMA
1220 North Fillmore Street, Suite 400, Arlington, VA 22201
Phone: 703-258-0093 • E-mail: mpazera@pima.org
3 3 r d RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma r c h 2 2 – 2 7 , 2 0 1 8 F isc h e r e t a l . • 9 1
Abstract
The 2009 roof replacement project at the Onondaga County Correctional Facility in
Jamesville, NY, provided a unique opportunity to evaluate the relative performance of roofing
systems with different energy efficiency strategies. Because the project included roofs on four
identical buildings on the same site, the setup allowed comparison of insulation R-value and
roof reflectance values, as well as the thermal performance of vegetative roofing systems in
northern climate zones. By reviewing thermal transmittance data and correlating the results
with local weather conditions, this paper provides insight into various roofing design options
to maximize building energy efficiency and overall roofing performance.
Speaker
Michael D. Fischer — Kellen Company
MICHAEL FISCHER is a 34-year veteran of the building products
industry. He has held management positions in manufacturing, marketing,
and regulatory affairs. Fischer is a member of the International
Code Council (ICC), ASHRAE, IAPMO, and ASTM International, and
represents the Asphalt Roofing Manufacturers Association (ARMA)
and the Roof Coatings Manufacturers Association (RCMA). In addition,
he serves as codes consultant to the Polyisocyanurate Insulation
Manufacturers Association (PIMA) and the Center for the Polyurethanes
Industry (CPI) of the American Chemistry Council (ACC). Fischer has
testified before code, regulatory, and legislative bodies and is a frequent
presenter at building industry events and conferences.
Nonpresenting Coauthors
Hugh Henderson, Jr. — CDH Energy
Nicholas Genzel — CDH Energy
Marcin Pazera — PIMA
9 2 • F isc h e r e t a l . 3 3 r d RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma r c h 2 2 – 2 7 , 2 0 1 8
Energy efficiency requirements for roofing
assemblies in model codes include consideration
of thermal resistance, air leakage,
and roofing reflectance. The introduction of
cool roofing via reflectance requirements in
the International Energy Conservation Code
(IECC) prescriptive path for commercial
buildings in southern climate zones was an
important step forward to advance energy
efficiency. The potential energy use benefits
of cool roof strategies for commercial buildings
in northern climate zones have been
studied (Hosseini, Akbari 2015). The use of
vegetative roof assemblies to manage stormwater
runoff, as well as other environmental
and sustainability benefits, represents
another roofing design parameter.
EXECUTIVE SUMMARY
In 2009, Onondaga County sought to
evaluate and compare the energy performance
of green or vegetative roofing systems
relative to other roofing options. A
major roof replacement project on a multiple
building site at the Jamesville Correctional
Facility n ear S yracuse, N Y, o ffered t he
opportunity for a side-by-side test to evaluate
different roofing systems. This evaluation
was initiated to provide guidance for
future roofing renovations on other countyowned
buildings. A final report was completed
(CDH Energy 2011) comparing four
different roofing assemblies:
1. A conventional absorptive roof with
4 inches of polyisocyanurate insulation
(R-value of 22, or R-22) with
a black ethylene propylene diene
monomer (EPDM) single-ply rubber
roof membrane
2. A reflective or “cool roof” with R-22
polyisocyanurate insulation and a
thermoplastic polyolefin (TPO) single-
ply membrane
3. A vegetative roof with R-22 insulation
4. A highly insulated cool roof (R-45)
with a TPO single-ply membrane
A coalition of roofing industry associations,
including the Asphalt Roofing
Manufacturers Association (ARMA), the
EPDM Roofing Association (ERA), and the
Polyisocyanurate Insulation Manufacturers
Association (PIMA) provided funding to
continue the field testing in order to assess
the long-term performance of the different
roofing membranes. This side-by-side test
arrangement—with different roof assemblies
installed at the same location on
very similar buildings—offered a unique
opportunity to compare the long-term performance
of various roof types. One of
the issues with post-occupancy analysis of
buildings is the variability of internal loads
and other temperature impacts resulting
from building use. The Jamesville facility
buildings are located on the same site,
have almost identical operating hours and
occupancy conditions, and are served by
the same heating plant, thus providing an
excellent basis for building performance
comparison. This report summarizes the
measurements and observations based on
6½ years of data, collected from November
2009 through May 2016.
The objective of the extended testing
effort was to compare the thermal performance
of conventional (EPDM) and cool
(TPO) roof assemblies. Cool or reflective
roofs, such as TPO, lower summertime
heat gains and, therefore, reduce cooling
loads. However, the lower roof temperatures
may increase heating loads in the heating
season. Therefore, it is unclear if cool roofs
provide net annual benefits in heatingdominated
climates such as Syracuse, NY.
It is also possible that over the long term,
the benefits of a cool roof diminish as the
membrane properties change with time as
surfaces become soiled or degrade. While
the buildings are not air-conditioned, heatflux
measurements can provide a basis
for comparing the relative thermal performance
of the various roof assemblies.
Note that comparisons of various roofcovering
types are made only on the basis of
their reflective and thermal properties. No
conclusions regarding other features and
benefits for TPO, EPDM, or vegetative roof
coverings should be drawn from this paper.
The specific goals of this follow-up study
were to:
• Track and evaluate any long-term
changes in heat flux or surface temperature
that might occur due to
aging or soiling of the EPDM or TPO
membranes.
• Compare the long-term thermal performance
between roof assemblies.
• Evaluate the energy use and cost
differences between the roofs for the
heating and cooling seasons.
• Evaluate the impact that snow cover
has on roof heat loss, and compare
ground snow cover to the inferred
snow cover on each roof assembly.
The extended field-testing of the different
roof systems tracked the thermal performance
over the 6½-year monitoring period.
Data were collected at 15-minute intervals.
Some of the initial findings (CDH Energy
2011) continued over the long term:
• The EPDM membrane had roof temperatures
that were as much as
60°F higher than the TPO surfaces,
and had higher heat gains in the
summer and more modest heat losses
in the winter.
• The TPO membrane significantly
reduced the surface temperatures
in the summer but also resulted in
greater heat losses in the heating
season (since beneficial solar gains
are reduced).
• The vegetative roof adds thermal
mass to the roof assembly that
dampens temperature swings.
Evaporation at the surface also provides
cooling in the summer and
swing seasons. The vegetative roof
also retained more snow cover more
often and had lower heat losses in
the winter.
MONITORING APPROACH
CDH initially considered several
approaches to quantifying the energy
impact of the different roof systems, including
measuring the heating energy use of
the HVAC system before and after retrofit.
Ultimately, we determined that measuring
the temperature differences within the roof
Onondaga County Reroofing Project:
Impacts of Reflectance and Thermal Resistance
3 3 r d RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma r c h 2 2 – 2 7 , 2 0 1 8 F isc h e r e t a l . • 9 3
assembly was the most compatible with the
project schedule, building configuration,
and limited access in the facility. A mix
of hardwired and wireless networking was
used to connect the loggers. Transmission
of the data back to CDH was achieved via
a modem link.
Each monitoring station was based
around a Campbell Scientific CR800 or
CR1000 datalogger (Station 2A uses a
CR1000 to accommodate extra data points).
Communication between the loggers was
provided by wired serial communications
(RS-485) or wireless connections (915 MHz
spread spectrum radio). The dataloggers
were programmed to sample all sensors
once per second. Calculated averages and
totals were recorded for each 15-minute
interval. After all records were created at
each station, the datalogger located at 3A
collected each record from all the other
dataloggers. That master datalogger was
called, and data was downloaded each night
by phone modem. The data was loaded into
a database at CDH Energy for automatic
verification and analysis.
INSTRUMENTATION
A monitoring system
was installed to measure
the performance
of each roofing system.
The overall experimental
approach was to measure
and compare the temperatures
in the different
roofing systems in a
side-by-side test in both
seasonal and annual
comparisons. The heat
transfer through the roof
surface is proportional
to the temperature difference
through each
layer. Since all of the roof
systems are exposed to
the same ambient conditions,
as well as similar
indoor temperatures, the performance of
the different systems can be directly compared
at each time step. The measurements
listed in Table 1 were taken at two separate
locations (A and B) on each building (Units
1, 2, 3, and 4), resulting in a total of eight
monitoring locations.
DESCRIPTION OF ROOF
ASSEMBLIES
The four buildings included in this test
program are shown in Figure 1. Each unit
had a different roofing system installed, as
described in Table 2. The TPO membrane
is rated by the Cool Roofing Rating Council
(CRRC) to ASTM D1519 with an initial
reflectance of 0.79 and three-year reflectance
of 0.70, per Carlisle TPO-2007-18
(July 2007) and Carlisle Spec Sheet from
December 2015.
DATA ANALYSIS AND RESULTS
The data collection system at the site
was fully commissioned starting on October
22, 2009. This section analyzes the data
collected from November 1, 2009, through
May 31, 2016.
ROOF THERMAL ANALYSIS
Our experimental analysis of heat transfer
through the Jamesville, NY, roof assembly
in the original report (October 2011)
made several key assumptions. The analysis
in the original report ignored heat storage in
the concrete layer and assumed the insulation
layer had insignificant thermal mass.
9 4 • F isc h e r e t a l . 3 3 r d RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma r c h 2 2 – 2 7 , 2 0 1 8
Point Description Instrument Units
TRO Roof temperature Type-T ºF
(on top of insulation, under roof board) Thermocouple
TRI Roof temperature Type-T ºF
(under roof insulation, above deck) Thermocouple
TAI Indoor temperature Type-T ºF
(just below the ceiling) Thermocouple
Table 1 – Instrumentation for each measurement location or station.
Table 2 – Construction details for the roofs on each unit.
Location Insulation Surface
Unit 1 4 inches Polyiso1 (R-22) EPDM rubber2
Unit 2 4 inches Polyiso1 (R-22) TPO white3
Unit 3 4 inches Polyiso1 (R-22 + vegetative laver) EPDM w/ vegetative
assembly on top
Unit 4 8 inches Polyiso1 (R-45) TPO white3
1- Polyisocyanurate foam board applied in 2-in. layers
2- Black EPDM single-ply rubber roof membrane
3- White TPO roof membrane
Figure 1 – Aerial view of the four units at the Jamesville facility.
A simplified one-dimensional, steady-state
heat flux through the insulation layer was
assumed to represent the heat flux through
the entire roof assembly.
An EnergyPlus model was developed and
compared to the simple model (Equation 1)
to test the validity of this assumption. The
EnergyPlus analysis, using the finite difference
method, showed that the simple
model (Equation 1) accurately represented
the heat flux at the top of the roof assembly
(i.e., into the top of the concrete layer).
However, the heat flux into the space (i.e.,
from the bottom of the concrete layer) was
much different. We found that the heat flux
into the space predicted by EnergyPlus
was reasonably represented by applying
Equation 2 to the 15-minute interval data
from EnergyPlus. Therefore, this equation
provides an approximate correction for the
field test data for the thermal mass (assuming
the concrete layer is highly conductive
relative to the insulation layer and is essentially
at a uniform temperature represented
by TRI).
The variable q is defined as positive
heat loss from the space through the roof to
ambient. On each roof, a different amount
of insulation board (with an R-value of
5.7 ft2-h-°F/Btu per inch) was installed on
each unit (see Table 2). The variable m is
defined as the mass per area at 46.6 lb/ft2.
The variable cp represents specific heat at
0.1996 Btu/lb-°F. In these tables, the overall,
long-term heat transfer is calculated
using both methods (Equations 1 and 2),
which are shown to yield similar results.
Figures 2 and 3 show the temperatures
for the four different roofs during a fall day
in 2009 and 2015. The top of the insulation
beneath the EPDM membrane on Unit 1 is
at a warmer temperature during the day
3 3 r d RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma r c h 2 2 – 2 7 , 2 0 1 8 F isc h e r e t a l . • 9 5
Equation 1
Equation 2
Figure 2 – Daily temperature profiles for each roof type (November 2, 2009).
Figure 3 – Daily temperature profiles for each roof type (November 2, 2015).
since more heat is absorbed from the sun.
The TPO roofing surface on Unit 2 is significantly
cooler since its higher reflectivity
reduces solar gains. The vegetative roof provides
additional thermal mass that smooths
out the fluctuations across the daily cycle.
The difference in peak temperatures
between the EPDM and TPO roofs in
November 2009 (six months after installation)
was 37°F. For the similar November
day in 2015, the temperature difference had
dropped to 23°F.
Figure 4 and Figure 5 show the heat
transfer performance at the roof surface
(using Equation 1) for each roof type. A
positive number represents net heat loss
through the roof. The assemblies all experience
heat loss in the early morning hours.
The heat flow reverses direction for the
EPDM roof as the roof surface heats up and
drives heat into the roof assembly.
COMPARISON OF DAILY,
SEASONAL, AND ANNUAL
PERFORMANCE
Daily Trend With Outdoor Temperature
Figure 6 plots the heat loss (at the roof
surface, Equation 1) for each day versus
the daily ambient temperature. Each data
point plotted corresponds to one day in the
6½-year period; the roof system on each
unit is shown as a different color. Each
daily value is the average of the A and B
locations on each roof. All the roof systems
show the general trend of more heat loss
at lower outdoor temperatures, though the
trend is not perfectly linear.
The EPDM roof (black) shows the strongest
linear trend, while the vegetative roof
(green) shows an especially nonlinear trend,
with a “knee” corresponding to the freezing
point (32°F). The knee for the vegetative roof
occurs because the formation of ice in the
vegetative layer keeps the roof surface temperature
(TRO) near freezing and flattens
the trend of heat transfer with lower outdoor
temperatures. In contrast, the EPDM roof
is less affected by formation of melting ice
and snow at the roof surface since the black
EPDM material heats up and causes more
melting (so that less snow can accumulate
on the roof). The two TPO roofs fall in
between these two extremes. The TPO roof
with 4 inches of insulation (red) has a slight
knee in the trend since more snow can build
up on the roof and create a freezing liquidsolid
layer at the roof surface. The TPO roof
with 8 inches of insulation (blue) has less
of a knee in the trend, mainly because the
lower rate of heat transfer means that the
9 6 • F isc h e r e t a l . 3 3 r d RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma r c h 2 2 – 2 7 , 2 0 1 8
Figure 4 – Heat transfer rates for each unit on November 2,
2009.
Figure 5 – Heat transfer rates for each unit on November 2,
2015.
Figure 6 – Daily heat loss vs. outside temperature (November 2009 through May
2016).
melting/freezing does not occur at roof surface.
Therefore, there is no change of phase
to create the nonlinear trend.
Figures 7 through 10 show the heat loss
versus outdoor temperature separately for
each roof type. Different symbols and colors
are used on each plot for the different years
over the 6½-year period.
The dotted line represents the difference
between heat loss (above the line) and heat
gain (below the line). The linear and nonlinear
trends described above for each roof
assembly are more obvious in these plots.
While outdoor temperatures and the impact
of snow might change from year to year,
there is little to no discernable change in
the trends from year to year.
The EPDM roof with 4 inches of insulation
has the most heat gain during the
summer and the lowest amount of heat loss
in the winter (as also shown by Table 3).
Figure 7 indicates for the EPDM roof that
heat gain begins to occur at an ambient
temperature around 50°F to 60°F (10 to
15.5°C). The TPO roofs with 4 and 8 inches
of insulation (Figure 8 and Figure 10) do
not experience heat gain until ambient temperatures
reach 70°F to 80°F (21 to 27°C). It
is not until temperatures reach above 80°F
that the vegetative roof (Figure 9) may have
some heat gain.
The ability of the TPO and vegetative
roofs to reduce solar gains becomes a disadvantage
in the winter. The figures show
a heat loss of 35 to 40 Btu/ft2-day at 30°F
(-1°C) for the TPO roof with 4 inches of insulation
and the vegetative roof, respectively.
The EPDM roof has a slightly lower heat
loss of 30 Btu/ft2-day at the same ambient
temperature. Higher heat loss in the winter
is observed at all temperatures for the 4-in.
TPO roof, especially when the roof is clear of
snow (i.e., days at the top of the trend). The
TPO roof with 8 inches of insulation shows
a commensurate reduction in heat transfer.
Table 3 shows the seasonal heat loss
(and heat gain) for each roof type calculated
two different ways:
• Without the thermal mass correction
(Equation 1) to calculate heat
flux at the top of the roof
• With the thermal mass correction
applied (Equation 2) to calculate
heat flux into the space
3 3 r d RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma r c h 2 2 – 2 7 , 2 0 1 8 F isc h e r e t a l . • 9 7
Figure 7 – Daily heat loss vs. outdoor temperature, EPDM
roof.
Figure 9 – Daily heat loss vs. outdoor temperature, vegetative
roof.
Figure 8 – Daily heat loss vs. outdoor temperature, TPO roof
(4 in.).
Figure 10 – Daily heat loss vs. outdoor temperature, TPO roof
(8 in.).
The heating season includes January
through April, and then October through
December in each calendar year. The cooling
season extends from May through
September. The overall seasonal heat loss
(and gain) calculated by the two methods
are very similar when integrated over the
long term (more than a few days).
The seasonal winter heat losses and
summer heat gains are shown for several
different years in Table 3. The heat loss in
the winter for the TPO roof was 30-45%
greater than the EPDM roof, depending on
the year. The heat loss from the vegetative
roof was 10-33% greater than the EPDM
roof for different years. The heat loss for the
better-insulated TPO roof was 7-14% lower
than the baseline EPDM roof.
For the heating season, the roof with
the EPDM membrane has lower overall heat
loss in the winter (October to April) because
the solar gain reduces the heating load. In
the summer, the TPO and vegetative roofs
reduce the heat gain from the roof since the
surface absorbs less solar energy
and is cooler.
In the summer, the TPO and
vegetative roofs had significantly
lower heat gains than the EPDM
roof.
Annual Energy and Operating
Cost Differences for Each
Roof Type
Table 4 compares the overall
heating and cooling loads, energy
use, and costs for the different
roofs. The EPDM roof is used as
the reference or baseline; fuel
use and cost savings are compared
relative to that roof system,
assuming an 80% efficient
heating system and a gas cost of
$1.00 per therm. The boxes on
the left side of the table show the
results without thermal correction
(same method as in original
report), while the right side of the
table shows results with the thermal
correction. The results are
similar regardless of whether the
thermal correction was applied.
The similarly-insulated TPO
and vegetative roofs result in
slightly higher annual fuel costs
in the winter, at $23 per 1000 sq.
ft. per year and $15 per 1000 sq.
ft. per year, respectively. When
comparing the results for the
TPO roofs on Unit 2 and Unit 4,
the extra 4 inches of insulation
saves about $28 per 1000 sq. ft.
per year.
The reduction in cooling energy
use and costs were determined
assuming a seasonal average
cooling efficiency of 0.9 kW per
ton and an electric cost of $0.12
per kWh. The TPO roof with R-22
reduced annual costs by $16 per
1000 sq. ft. compared to EPDM with R-22.
The vegetative roof with R-22 reduced cooling
costs by $20 per 1000 sq. ft.
Overall, the cost savings for cooling
were slightly smaller than the added costs
for heating with the TPO roof. The net
annual impact for the TPO roof was to
increase costs by about $8 per 1000 sq. ft.
This analysis assumes that the facility
was in the cooling mode from May through
September and in the heating mode for
the rest of the year. This approximately
9 8 • F isc h e r e t a l . 3 3 r d RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma r c h 2 2 – 2 7 , 2 0 1 8
Table 3
corresponds to a building
balance point that is around
the indoor setpoint (around
65-70°F). In many types of
buildings, internal gains
from lighting, plug loads,
and occupants can reduce
the balance point so that
space heating is not required
in the building until the outdoor
temperature drops to
50-60°F. Correspondingly,
greater internal gains mean
that cooling can be required
at lower ambient temperatures.
Buildings with differing
levels of internal gains
can require more cooling and
less heating, thus changing
the impact of the cool roof
on energy costs. If cooling is
needed under moderate conditions
(around 55 to 65°F),
this cooling load could be
satisfied by economizer operation
at little to no energy
use.
One way to approximate
the impact of a lower balance
point combined with economizer
operation is to exclude
months from the heating and cooling seasons.
If we assume the heating season
now only includes five months (November
through March) and the cooling season only
includes three months (June to August), the
analysis can be repeated as shown in Table
5. This change reduces the heating penalty
of the TPO roof with R-22 but also decreases
the cooling benefit. As a result, the net or
combined cost impact changes very little
for this case.
Comparing Energy and Cost Results
to Other Studies
A series of studies at Concordia
University (Hosseini and Akbari 2014,
Hosseini 2014, and Hosseini and Akbari
2015) used the DOE-2.1E simulation tool to
evaluate the annual energy and cost performance
of cool roofs in cold climates. They
compared the annual energy performance
of dark and white roofs and also considered
the impact of snow accumulation on
the thermal performance of the roof. They
looked at various different building and
HVAC types with various efficiency levels.
Generally, they found that snow buildup on
the roof had only a modest impact on overall
heating loads and fuel use.
One of the cities they considered was
Toronto, which has a comparable climate
to the Jamesville test site. They simulated
a new small office building that had a new
building envelope (the roof had an R-value
of 31.5). The heating and cooling system
was supplied by a package cooling unit
with gas furnace section. The HVAC system
used an economizer to provide free cooling
when outdoor temperatures were low
enough. Several key parameters used in
the Hosseini study are compared to our
assumptions in Table 6.
The cool roof savings from Hosseini
(2014) without snow impacts are compared
to the savings from this study in Table
7. The Hosseini results are based on the
DOE-2.1E fuel and electricity reduction
differences. Starting with those values, we
used the efficiencies from Table 6 to infer
the cooling and heating load impacts. For
our results, we determined the load impacts
and calculated the change in fuel and electricity
using the efficiencies from Table 6.
The results that were directly determined in
each study are shown as bold and shaded
in the table.
The results from this study are shown
for both Case 1 in Table 4 and Case 2 in
Table 5. The Case 2 results are expected to
better reflect Hosseini’s results for the office
building with internal gains and an economizer.
The heating penalty we determined
is slightly larger than the value Hosseini
found for Toronto (1.2 compared to 0.7
MMBtu per 1000 sq. ft.). This could, in part,
3 3 r d RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma r c h 2 2 – 2 7 , 2 0 1 8 F isc h e r e t a l . • 9 9
Table 4
Table 5
Hosseini (2014) CDH Analysis
Roof R-Value (ft2-F-h/Btu) 31.5 25
Heating Efficiency 0.8 0.8
Cooling Efficiency (kW/ton) 1.33 nominal 0.9 avg.
Table 6 – Comparing key parameters and assumptions.
be explained by the 20% higher R-value
used in Hosseini’s simulation model. The
cooling energy use values are very similar
between CASE 2 and the Hosseini results
(75 and 74 kWh per 1000 sq. ft., respectively).
Where our study found a slight cost
penalty for the TPO roof, the Hosseini data
with cost assumptions are cost-neutral.
Hosseini (2014) used different utility cost
assumptions and found slightly larger net
cost savings (approximately
$1 to $2 per
1000 sq. ft.).
HOW GROUND SNOW
COVER RELATES TO
ROOF SNOW COVER
Obtaining NCDC Ground Snow
Cover Data for Syracuse
The National Operational
Hydrologic Remote Sensing
Center (NOHRSC) in Chanhassen,
MN, is a division of
the National Weather Service
and National Oceanic and
Atmospheric Association (NOAA)
(http://www.nohrsc.noaa.gov/).
NOHRSC has developed tools
to estimate snow cover at various
locations throughout the United States.
Snow cover data are available from station
NY-OG-20, which is located 1.9 miles
southeast of Syracuse at an elevation of
587 ft. This station is about three miles
from the facility in Jamesville, which is at
a slightly higher elevation (about 740 ft.).
The “Modeled Snow Depth” for the NY-OG-
20 station is shown in Figure 11 and Figure
12 for the seven winter seasons from 2009
through 2016.
1 0 0 • F isc h e r e t a l . 3 3 r d RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma r c h 2 2 – 2 7 , 2 0 1 8
J amesville Results
Hosseini
(2014) CASE 1 CASE 2
Toronto Table 8 Table 9
Annual Heating Load Reduction (MMBtu per 1000 sq. ft.) -0.71 -1.9 -1.2
Annual Heating Fuel Savings (therms per 1000 sq. ft.) -8.8 -23.2 -16.1
Annual Cooling Load Reduction (ton-h per 1000 sq. ft.) 561 144 84
Annual Cooling Energy Savings (kWh per 1000 sq. ft.) 74 129 75
Net Cost Savings ($ per 1000 sq. ft.) ~0 –8 –7
Note: Cost savings are based on $0.12/kWh and $1.00/therm.
Figure 11 – Snow cover data from NOHRSC showing winters
from 2009 through 2013.
Figure 12 – Snow cover data from NOHRSC showing winters
from 2013 through 2016.
Table 7 – Comparing cost savings from this and other studies.
3 3 r d RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma r c h 2 2 – 2 7 , 2 0 1 8 F isc h e r e t a l . • 1 0 1
Comparing Ground Snow Coverage
From Roof Temperatures
The plots in Figures 13 through 19 compare
the ground snow cover data (top graph)
from NOHRSC to the temperatures measured
at the top of the roof insulation (TRO)
for the EPDM roof (second, black graph), the
TPO roof with 4 inches of insulation (green),
and the TPO roof with 8 inches of insulation
(blue). Station A on each roof is shown with
a solid line, while Station B is shown with
a dotted line. Figure 13 through Figure 19
compare snow cover and temperature data
for the first three months of each year from
2010 through 2016.
From the graphs, it is apparent that
the periods with snow cover correspond to
periods when the roof temperatures do not
exceed the freezing point. The EPDM roof
appears to “clear” its snow more quickly
than the other roof types as indicated by a
greater number of temperature excursions
above freezing when there is a small amount
of snow. For the EPDM roof, temperature
excursions above freezing start when the
ground snow level drops to approximately
5 inches. The TPO roof with 8 inches of
insulation holds snow longer, and the temperature
excursions above freezing more
closely correspond to the periods with any
snow cover on the ground. The roof surface
temperature data generally all imply that
the snow cover on each roof clears sooner
than snow cover on the ground.
If we identify days when the modeled
snow cover is greater than 1 inch for more
than 18 hours, we can determine the number
of hours and days per year that there
was snow cover on the ground. The number
of snow-covered days for each year is shown
as the row labeled “Ground” in Table 8. We
assume that roofs have snow cover on days
that have ground snow cover and the peak
daily roof surface temperature is lower than
35°F. The number of days that meet these
criteria is shown in the subsequent rows
in the table. Figure 20 uses this data from
Table 8 to show the portion of time that
each roof has snow cover compared to the
ground snow cover.
Generally, the time with snow accumulation
on each roof is about 60-80%
of the time that snow is on ground. That
percentage is lowest for the EPDM roof and
is highest for the TPO roof with 8 inches of
insulation.
Heat Loss on Snow-Free Days
The daily heat transfer plot in Figure
6 includes all days—both with and with-
Figure 13 – Comparing snow cover and roof temperatures
(TRO) for three roof types, winter 2010.
Figure 14 – Comparing snow cover and roof temperatures
(TRO) for three roof types, winter 2011.
out snow cover. If days with ground snow cover are
excluded, then the trends become much more linear,
as shown by Figure 21. The knee in the trends at the
freezing point is eliminated for all the roofing assemblies,
except for the vegetative roof, which still appears
to retain moisture after the snow cover is gone.
Table 9 summarizes the regression statistics for the
best fit lines shown on the plot. The EPDM roof shows
the highest degree of scatter, since variations in the
daily solar flux have a larger impact on the heat loss
for this roof. The TPO roofs absorb much less solar
energy, so the degree of scatter is significantly lower
than for the EPDM roof. The greater insulation level
further reduces the scatter (or reduces the impact of
solar gains).
CONCLUSIONS
Extended field testing of the four different roof systems
tracked the thermal performance over 6½ years,
from November 2009 through May 2016. Some of the
1 0 2 • F isc h e r e t a l . 3 3 r d RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma r c h 2 2 – 2 7 , 2 0 1 8
Figure 15 – Comparing snow cover and roof temperatures
(TRO) for three roof types, winter 2012.
Figure 16 – Comparing snow cover and roof temperatures
(TRO) for three roof types, winter 2013.
Table 8
initial findings (summarized in the October
2011 report) continued over the long term:
• The EPDM surface did result in roof
temperatures that were as much as
60°F higher than the other surfaces.
This surface had higher temperatures
in the summer, as well as in
the winter.
• The TPO membrane significantly
reduced the surface temperatures in
the summer, but also resulted in a
greater heating penalty in the heating
season (since beneficial solar
gains are reduced).
• The vegetative roof adds thermal
mass to the roof assembly that
dampens the temperature swings.
Evaporation at the surface also provides
cooling in the summer and
swing seasons. The vegetative roof
also retained more snow cover more
often and had lower heat losses in
the winter.
Over the long term, the TPO membrane
with 4 inches of insulation had 30% to 45%
higher thermal losses over the heating season,
as measured at the roof surface.1 This
higher heat loss increases heating costs by
$23 per year per each 1000 sq. ft. of roof
area. However, the reduced summertime
heat gains equate to about $16 per year
per 1000 sq. ft. in cooling energy savings.
Overall, heating losses and cooling savings
resulted in a net annual cost penalty of $8
per 1000 sq. ft. for the 4-inch TPO roof.
Using different assumptions for internal
gains and cooling system arrangement (corresponding
to a small office with a packaged
cooling system that uses economizer
cooling in the swing season) changes the
resulting impact on heating and cooling
3 3 r d RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma r c h 2 2 – 2 7 , 2 0 1 8 F isc h e r e t a l . • 1 0 3
Table 9 – Linear regression statistics for different roof assemblies (in Figure 21).
Roof Assembly R-squared Coefficient of Variation (CV)
EPDM 0.885 1.09
TPO with 4 inches 0.960 0.18
TPO with 8 inches 0.964 0.14
Note: CV indicates the average variation of the data from the linear model.
Figure 17 – Comparing snow cover and roof temperatures
(TRO) for three roof types, winter 2014.
Figure 18 – Comparing snow cover and roof temperatures
(TRO) for three roof types, winter 2015.
loads and energy use. The heating penalty
of the 4-inch TPO over a shorter heating
season (caused by internal gains) drops to
$16 per 1000 sq. ft., and the cooling benefit
becomes $9 per 1000 sq. ft. The net annual
cost penalty of the 4-inch TPO roof compared
to the EPDM roof is still around $7
per 1000 sq. ft.
The results from Hossieni (2014) and
Hosseini and Akbari (2015) showed similar
trends of heating penalties from reflective
roofs and summertime savings, with a
slightly smaller net annual penalty of $1
to $2 per 1000 sq. ft. for nearby Toronto
(using our assumptions). Details of building
application (office, retail, institutional, etc.)
and HVAC arrangement (economizer, cooling
efficiency), as well as utility costs have
a significant impact on whether cooling
roofs provide net cost increases or savings
in each climate.
Hosseini and Akbari (2015) included
roof snow in the analysis whenever ground
snow was present;
however, this
assumption does not
reflect known snowfall
behavior. The
cited analysis thus
overestimates the
effect of roof snow
cover in reducing
heat gain of highly
absorptive roof coverings
during winter
months. Live-load
calculations for roof
snow loads include
reductions for sliding
snow; other variables
permit adjustments
to the structural
requirements
in the model codes. In this research project,
we sought to determine the relationship
between ground snow cover and the presence
of snow on the
roof.
To predict hourly
ground snow cover for
the Jamesville, NY,
site over the monitoring
period, we used
snow cover data from
a monitoring station
three miles from the
Jamesville facility provided
by the NOHRSC
in Chanhassen, MN.
We found that periods
with ground snow
cover generally have
roof surface temperatures
that remain
very close to freezing,
regardless of outdoor
temperatures. By combining the snow cover
and roof temperature data, we were able to
show that the roofs are generally covered
with snow less often than snow is on the
ground; the ratio of roof-to-ground snow
cover ranged between 60 and 80%. The
EPDM roof clears snow faster than the other
roof types (as evidenced by temperature
excursions above freezing). The TPO roof
with extra insulation retained snow longer,
since the lower heat loss results in less
melting at the roof surface.
When we look at the days that are snowfree,
the trend of heat loss with ambient
temperature becomes highly linear for the
EPDM and TPO roofs. The highly-insulated
TPO roof has the lowest degree of scatter
from the linear trend, since the impact of
solar gains is minimal in this case. The vegetative
roof shows a nonlinear trend, even
with snowy days excluded, since it retains
water and ice even if there is no snow on
the ground.
1 0 4 • F isc h e r e t a l . 3 3 r d RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma r c h 2 2 – 2 7 , 2 0 1 8
Figure 19 – Comparing snow cover and roof temperatures
(TRO) for three roof types, winter 2016.
Figure 20 – Percentage of days with snow cover on each
rooftop relative to ground cover.
Figure 21 – Daily heat loss vs. outdoor temperature on
snow-free days.
We found that the temperature difference
between the similarly-insulated EPDM
and TPO roofs was as high as 60°F on
summer days when the roofs were first
installed. Over the first two or three years,
the temperature difference dropped by 10°F
to 15°F. Generally, the peak temperature
of the EPDM roof stayed about the same
over the long term, while the peak surface
temperature of the TPO roof increased by
10°F to 15°F—perhaps due to soiling or
aging. This long-term temperature increase
of the white reflective roof is less than what
was observed in earlier studies using the
first cool roof membrane products (Miller et
al. 2004), but seems to be consistent with
the published rating numbers for this TPO
membrane (initial and three-year reflectance
ratings per Energy Star CRRC are
0.79 and 0.70, respectively).
These findings support a whole-building
approach to roof system selection and
design, with appropriate consideration
given to occupancy, internal loads, site, and
orientation. Design for insulation levels and
roofing reflectance and absorptance values
should be optimized on a project-specific
basis using energy modeling. Future
research might look at refining the assumptions
and variables in energy modeling for
roof snow cover. Note that there were no
measurements of relative humidity or moisture
content within the roof assemblies;
additional consideration for condensation
management of the various roof assemblies
is another possible research topic.
FOOTNOTE
1. We applied a correction for thermal
mass of the roof deck, developed from
an analysis using EnergyPlus that
resulted in a similar heat loss rate at
the ceiling over the long term.
ACKNOWLEDGEMENTS
The authors wish to thank Scott Perry
and his team at Ashley McGraw Architects
for providing the detailed specifications for
this roofing project, as well as their insights
on its design and construction. Thanks
also to Lee Klosowski, Director of Energy at
Onondaga County, and to Daniel Loguidice
and George Manolis in Onondaga County
Correctional Department, who graciously
arranged for access to this secure facility.
Technical Oversight Committee: Michael
Fischer, Kellen Company, Coalition Chair,
ARMA; Marcin Pazera, PIMA; Jerry Phelan,
Covestro, PIMA; Ellen Thorp, ERA; Rick
Gustin, Johns-Manville, ERA.
REFERENCES
CDH Energy. Comparative Roof Testing
at Onondaga County Correctional
Facility. Final Report. Submitted
to Onondaga County with Ashley
McGraw Architects. October 2011.
CDH Energy. “Long-term Performance
Monitoring of Various Roof Assemblies
– A Side-by-Side Comparison.” Final
Report. Submitted to the Asphalt
Roofing Manufacturers Association.
February 2017.
M. Hosseini and H. Akbari. “Heating
Energy Penalties of Cool Roofs:
the Effect of Snow Accumulation
on Roofs.” Advances in
Building Energy Research. DOI:
10.1080/17512549.2014.890541.
2014.
M. Hosseini. “Cool Roofs Savings and
Penalties in Cold Climates: the
Effect of Snow Accumulation on
Roofs.” Master’s thesis. Concordia
University, Montreal, Quebec,
Canada. 2014.
M. Hosseini and H. Akbari. “Effect of
Cool Roofs on Commercial Buildings’
Energy Use in Cold Climates.”
Energy and Buildings. DOI:10.1016/j.
enbuild.2015.05.050. 2015.
W. Miller, A. Desjarlais, and D.
Roodvoets. “Long Term Reflective
Performance of Roof Membranes.”
Oak Ridge National Laboratory and
DLR Consultants. 237680034. www.
researchgate.net. January 2004.
3 3 r d RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma r c h 2 2 – 2 7 , 2 0 1 8 F isc h e r e t a l . • 1 0 5
GLOSSARY OF TERMS
ARMA Asphalt Roofing Manufacturers Association
CRRC Cool Roof Rating Council. Part of Energy Star cool roofs program.
Economizer An optional HVAC arrangement where outdoor air is used to
provide “free cooling” when outdoor conditions are favorable.
EnergyPlus A building simulation software tool from the U.S. Department of
Energy. Used to determine theoretical heat transfer through the
roof assembly to verify calculations in this study.
EPDM Ethylene propylene diene monomer single-ply rubber roof
membrane. Also a conventional or dark roof membrane.
ERA EPDM Roofing Association
HVAC Heating ventilation and air conditioning. System that provides
heating and cooling for a building.
PIMA Polyisocyanurate Insulation Manufacturers Association
TPO Thermoplastic polyolefin roof membrane. Also a white, reflective,
or cool roofing membrane.
TRI Temperature roof inside. Temperature under the insulation layer.
TRO Temperature roof outside. Temperature at the roof surface (but
under the deck board).