Skip to main content Skip to footer

Class 1 and Class A Roof Assemblies are Not the Same

February 20, 2006

PIMA issued this technical bulletin to assist
architects, specifiers, and consultants in
their decision making regarding fire
performance in the roof systems they may
design or install.
When selecting roof
assemblies containing
foam plastic insulation
such as polyiso or polystyrene,
specifiers, contractors,
and consultants
should confirm that all applicable
specifications, building codes, and insurance
requirements of the job are met. It is
important to note that substitution of other
types of foam plastic for polyiso insulation
in tested roof assemblies may result in violation
of building codes and/or required
insurance ratings.
Below are some key points to understanding
the differences between a Class 1
and a Class A roof assembly containing
foam plastic:
• A Class A rating is only for external
fire performance and is governed by
compliance to either the UL 790
standard or ASTM E-108 standard.
A Class A rating does not ensure
building code compliance.
• FM Class 1 requires that a roof deck
assembly is subjected to a series of
tests – internal fire, external fire,
wind uplift resistance, foot traffic,
corrosion resistance, impact resistance,
and susceptibility to heat
damage – as described in FM 4470
Approval Standard for Class 1 Roof
Covers. A roof assembly must pass
all these tests in order to gain a
Class 1 designation. For insulated
steel roof deck assemblies, FM Class
1 includes FM 4470 and FM 4450
Approval Standard for Class 1
Insulated Steel Deck Roofs.
• Because the testing requirements
are more stringent for a Class 1
assembly, it can be substituted for a
Class A, B, or C roof assembly.
However, a Class A, B, or C assembly
cannot be substituted for a Class
1 roof assembly.
• Remember that in all cases the roof
assembly must be installed as tested.
Substitution of any component
(such as insulation type or thickness)
in tested roof assemblies can
only be granted by FM or UL and
may require additional testing.
Failure to gain approval for the component
substitution from FM or UL
may impact insurance coverage and
could result in violation of the
applicable local building codes.
• Polyiso roof insulation is the only
foam plastic roof insulation board
product that meets the strict standards
of both FM Approvals
(Standard 4450) and UL (UL 1256)
without the use of an additional
thermal barrier layer between the
insulation and the supporting steel
roof deck.
FIRE TESTING AND ROOF ASSEMBLIES
There are two important fire assessments
regarding steel deck roof assemblies:
external spread of flame on the roof covering
surface and below-roof deck spread of
flame.
FM’s Calorimeter in use. (Photo, courtesy
Factory Mutual.)
F E B R U A RY 2006 I N T E R FA C E • 3 7
*All tests conducted at 12 mph wind
Table 1: ASTM E-108 and UL 790
Fire Exposure* Allowable Flame Spread
Class A 1400 F/10 minutes 6 feet maximum
Class B 1400 F/10 minutes 8 feet maximum
Class C 1300 F/4 minutes 13 feet maximum
External Spread of Flame
The exterior spread of flame fire test on
a complete roof assembly is determined
using either ASTM E-108 or UL 790. The
result of this fire test is expressed as Class
A, B, or C, with Class A described as “effective
against severe fire exposure.” 1
ASTM E-108 and UL 790 include three
test procedures: Spread of Flame,
Intermittent Flame, and the Burning
Brand. During all fire tests, there can be no
flaming or glowing wood particles falling off
the underside of the test deck, the roof deck
cannot become exposed, and portions of the
deck must not fall or break away in the
form of glowing particles.
The spread of flame portion of the test is
only conducted on roof assemblies with
noncombustible (concrete, steel, or gypsum)
decks. Test conditions and pass criteria are
shown in Table 1.
For roof assemblies with combustible
decks (wood, plank, tongue and groove),
ASTM E-108 and UL 790 require two additional
fire tests: 1) an intermittent flame
test, in which the flame is turned on and off
during the duration of the test, and 2) the
“burning brand test,” which measures the
ability of the roof assembly to resist fire
from flaming embers.
Below Roof Deck Spread of Flame
FM 4450 and UL 1256 are used to judge
the contribution of the roof assembly components
to the spread of fire within a building.
An examination of the scope of each
test method shows that FM 4450 is a much
more stringent and extensive test than UL
1256. See Table 2 for a summary of the test
parameters.
Elimination of Thermal Barrier
According to building codes, roof assemblies
incorporating foam plastic insulation
installed on a steel deck must include a
thermal barrier – typically 1/2-inch gypsum
board or equivalent – between the deck and
the foam plastic insulation. The thermal
barrier may be eliminated if the complete
roof assembly passes either FM 4450 or UL
1256.
Note that although both FM 4450 and
UL 1256 are conducted on a specific roof
assembly, passing either test without a
thermal barrier in one tested roof assembly
does not mean the thermal barrier may be
eliminated in all roof assemblies. Specific
roof assemblies that have passed FM 4450
may be found in the FM Approval Guide or
the web-based FM RoofNav roof assembly
search tool. Those that have passed UL
1256 may be found in the UL Roofing
Materials & Systems Directory.
For More Information
Class 1 and Class A roof assemblies are
not the same. For additional details, please
see the PIMA Web site (www.pima.org) or
contact a polyiso insulation manufacturer.
1 Sloan, D. E. (2005, May). “The UL
Story: Part 1.” Professional Roofing.
Retrieved on July 25, 2005, from the
Internet: (www.professionalroofing.
net/article.aspx?A_ID=641)
GLOSSARY
ASTM E-108, Standard Test Methods for Fire Tests of Roof Coverings
FM – Factory Mutual Global; www.fmglobal.com
FM 4450 Approval Standard for Class 1 Insulated Steel Deck Roofs
FM 4470 Approval Standard for Class 1 Roof Covers
UL – Underwriters Laboratories Inc.; www.ul.com
UL 1256 Fire Test of Roof Deck Constructions
UL 790 Standard for Standard Test Methods for Fire Tests of Roof Covering
Jared O. Blum is the president of the Polyisocyanurate
Insulation Manufacturers Association (PIMA), the
Washington-based national trade association representing
manufacturers of polyiso foam insulation. The association is
committed to working independently and with public and private
organizations to educate Americans about the critical
importance of national energy conservation. To learn more
about polyiso and PIMA, visit their Web site at www.pima.org.
Jared O. Blum
38 • I N T E R FA C E F E B R U A RY 2006
Table 2: Comparison of FM 4450 and UL 1256 Thermal Barrier
FM 4450 Approval Standard for Class 1 UL 1256 Fire Test of Roof
Insulated Steel Decks Deck Constructions
Roof Assembly Test Yes Yes
Tested Properties Under-deck fire;Wind uplift; Live load Under-deck fire only
resistances; Corrosion of metal parts;
Fatigue of plastic parts
Decks Steel Metallic & Non-metallic
Ratings Class 1 if all tested properties meet test “Pass” or “Fail”
criteria
Component Only if approved by FM Only if classified as such by UL