Skip to main content Skip to footer

Construction Administration Tools Address Unusual Building Enclosure Conditions

September 19, 2022

16 • IIBEC Interface March 2022
Successful termination of building
veneers to roofing systems involving
atypical conditions requires
carefully detailed drawings.
However, in the design development
and construction documentation
phase for a new building, architects and
engineers typically have limited time to detail
every condition necessary to properly communicate
design intent, material usage, and the
interaction of materials for the building enclosure’s
exterior walls and roof assemblies.
Two construction administration tools that
can help overcome the challenges of atypical
building enclosure conditions are mock-ups
and preinstallation meetings. The purpose of
this article is to bring attention to building
enclosure roofing conditions that benefit from
application of these tools (and others), thereby
helping building owners avoid unnecessary,
disruptive, and costly building veneer repair
or replacement projects when roofing materials
require maintenance or reach the end of
their useful service life. Case examples from
the field are presented to illustrate the shortand
long-term risks to the building enclosure
associated with insufficient communication
and coordination between design teams, construction
managers, general contractors, and
subcontractors.
BACKGROUND
In the design development and construction
document phase of most projects, much
of the architects’ and engineers’ time is allocated
to the development of “big picture” items
such as floor plans, reflected ceiling plans, roof
plans, building elevations, wall sections, door
and window schedules, plan details, interior
finishes, and editing of specification sections.
In whatever time remains, the design team
usually will focus on finalizing the contractor
bid set on “common” or “typical” door and window
details, enlarged flashing details, termination
details, and transition details between
dissimilar building materials. These common
or typical details will address many conditions
that will be encountered during the project.
However, they do not capture every condition.
Given the complexity of today’s buildings and
compressed schedules, it can be challenging to
sufficiently focus on unusual conditions in the
construction document phase.
Because not all conditions can be fully
addressed and detailed in the construction
document phase, designers may rely on typical
manufacturer installation details to establish
a baseline for a predetermined level of construction
quality intended to address the complexities
of atypical or uncommon building
conditions. Architects and engineers also may
give unusual building conditions additional
attention during the bid phase as an addendum
item, or in the construction administration
phase as architectural supplemental instructions,
a response to a contractor request for
information (RFI), or a request for proposal.
Even when architects and engineers make
such efforts, uncommon or atypical building
enclosure conditions still may remain unresolved
and undetailed after the completion
of the bid phase. This fact underscores the
importance of contractor mock-ups and preinstallation
meetings to address these types of
building enclosure conditions. Both of these
construction administration tools help the
designers, owner, and contractor team interact,
communicate, and develop solutions in the field
for unusual building conditions, thereby establishing
an understanding among all parties
involved as to what installation expectations
will be. Use of these tools also underscores the
importance of establishing a sufficient level
of quality control for material applications,
differing material interactions, future material
maintenance or replacement, and evaluation of
building enclosure testing procedures.
MOCK-UPS
Mock-ups often are used to evaluate and
refine the aesthetic aspects of a building design.
However, when building enclosure mock-ups
are accurate, full-size representations of a proposed
design, they also can be effectively used
to assess the building enclosure’s future performance.
In particular, testing mock-ups that
represent unusual or atypical building enclosure
conditions may reduce the need for costly
rework and eliminate delays during the actual
project.
When using mock-ups of an exterior wall
and roof assembly to evaluate thermal, water, air,
and vapor issues, it is important that construction
techniques associated with the mock-ups
comply with material manufacturer installation
instructions and relevant ASTM International
standards for quality control testing procedures,
including ASTM E7831 or ASTM E11862
for air leakage testing and ASTM E11053 and ASTM E21284 for water
leakage penetration testing. Complying with minimum ASTM testing
standards establishes a baseline of acceptable construction methods
and quality control for the exterior wall mock-up.
At a minimum, building enclosure mock-ups should include a typical
exterior wall; however, it is the opinion of this author that atypical
conditions such as inside and outside building corners, windows, and
the top of wall-to-roof assembly also should be incorporated into the
mock-up. The addition of these components helps the project team
evaluate the perimeter continuity at transitions where exterior walls
turn directions, as well as flashing conditions at window and door
rough openings, and conditions where the exterior wall’s continuous
insulation, air, and vapor barrier system transitions to vapor barrier
components associated with the roof assembly (Fig. 1).
PREINSTALLATION MEETINGS
As noted previously, another critical component to evaluate
uncommon building enclosure conditions is the preinstallation meeting.
Its primary purpose is to address a specific issue or an array of
topics. However, an added benefit of a preinstallation meeting is that
it is an opportunity to discuss those atypical and complex building
enclosure transitions and geometry that are not reflected in a typical
mock-up assembly or in the construction documents. It is at this point
in the construction administration process that project team members
can review together the uncommon building enclosure conditions and
coordinate the sequencing of construction to address issues such as
aesthetics; compliance with manufacturer-recommended installation
details; thermal, air, and water infiltration; vapor drive performance;
and long-term maintenance (see “Keys to Successful Preinstallation
Meetings” sidebar).
If the construction documents do not provide a plan for efficient
future material removal and replacement when building materials
approach the end of their expected life expectancy, creating such a plan
is another key objective for this meeting, as this plan will be important
to minimize disruption to other building veneers and systems when
Figure 1. Mock-up panel illustrating several key attributes of a
comprehensive evaluation of an exterior wall and roof assembly.
Figure courtesy of Walsh Construction Co.
March 2022 IIBEC Interface • 17
Keys to Successful
Preinstallation Meetings
• Early in the construction administration phase, identify
building enclosure–related areas of concern that warrant
special attention.
• Have the construction manager (CM) or general contractor
(GC) incorporate mock-up reviews and preinstallation
meetings for unique building enclosure conditions into
the construction schedule as milestones. This helps ensure
that these conditions can be discussed in advance and in a
timely manner.
• Include all relevant stakeholders in the meetings. The
recommended attendees are:
— The owner or their representative
— The architect
— Engineering consultants
— The CM or GC
— Building enclosure consultants (RBEC, RRC, RRO,
RWC, REWC, REWO)
— Roofing and sheet metal contractors
— The roofing membrane manufacturer’s field service
technical representative
— Product representatives or technical support staff for
the manufacturers of exterior wall components (for
example, representatives for the sheathing, air barrier,
continuous insulation, and veneer material companies)
— Representatives for other trades affected by the tie-ins
to roofing termination conditions
• If possible, meet where the project mock-up is located or at
the in-situ location site.
• Ensure that the meeting agenda includes the “nuts and
bolts” of how all the building components interact; exterior
wall air and vapor barrier to roof vapor barrier
continuity tie-ins; the sequence of construction; flashing
conditions; flashing elevations to maintain proper clearances
above the tops of parapet wall elevations; aesthetics;
and how to maintain access to roofing terminations and
accommodate future maintenance and replacement of
building material without disruption to adjacent building
veneer systems.
• Allow time to discuss additional topics such as procurement
of materials; coordination of trades; recommended
material installation instructions and procedures;
requests for proposals; and how the top of the parapet wall
interacts with other building elements such as face brick,
stone, precast concrete, aluminum composite material
panels, exterior insulation and finish systems, and aluminum
windows and curtainwalls.
• Focus the meeting on maintaining access to roofing termination
details and establishing proper flashing heights
above top-of-parapet wall elevations where a parapet wall
terminates into a building element that extends higher
than the top of the parapet.
18 • IIBEC Interface March 2022
Figure 3. A thermoplastic
polyolefin–clad parapet
wall transition to exterior
insulation and finish
system condition.
adjacent building materials require repair or replacement. When the
time for replacement arrives, clear communication will be necessary
among the various trades playing an interactive part in completing
the termination, and the foundation for that communication can be
built during the preinstallation meeting by setting a shared understanding
of expectations about the performance and success of future
maintenance and replacement work.
ALTERNATIVE INFORMATION SOURCES AND
CONSTRUCTION ADMINISTRATION STRATEGIES
On some projects, construction managers, general contractors,
and their subcontractors may not find sufficient detailing in the construction
document set, and the project may not include mock-ups or
preinstallation meetings to address uncommon building enclosure
conditions. In these situations, the contractors may be put in a position
to figure out among themselves how they will proceed. Ideally,
contractors will have additional tools at their disposal in the form
of progress meetings or RFI processes. The RFI process engages the
design team to interact with contractors to discuss and develop solutions.
However, in the absence of the RFI process or any other meaningful
form of communication with the design team, contractors
Figure 2. A thermoplastic polyolefin–clad parapet wall transition to a
field-trimmed aluminum composite material condition.
March 2022 IIBEC Interface • 19
may take it upon themselves to resolve unique building
conditions. In some circumstances, this strategy may be
acceptable; however, in other cases, it may lead to building
enclosure problems, either during construction or
in the future, because there is a lack of clarity about who
is doing what and why.
The following section presents examples of situations
when a lack of mock-ups, preinstallation meetings,
or RFI process resulted in constructed conditions
that will be a long-term hindrance to roof maintenance
and increase the difficulty of roofing material removal
and replacement at these conditions.
FIELD OBSERVATIONS
The following illustrate actual field conditions
encountered as part of building enclosure observations.
In some instances, the descriptions for a particular condition
are applicable to multiple figures. These conditions
are curious and raise questions as to how and why
they arose. In particular, the following should be noted:
• In Fig. 2 and 3, the roofing terminations
are concealed from view behind exterior
wall veneers, are inaccessible, and cannot be
inspected without removing the veneer materials.
These conditions also lack fixed sheet metal
receiver trim and removable counterflashings
necessary to maintain access to roofing terminations.
It is the opinion of this author that
building veneer materials should be held at a
minimum 8 in. (200 mm) above and away from
the backside of the parapet wall, per National
Roofing Contractors Association (NRCA)
minimum flashing height recommendations.5
• In Fig. 4 and 5, the close proximity of the
vertical leg of the sheet metal receiver trim or
raw edge of the sheet metal counterflashing
Figure 4. A thermoplastic polyolefin–clad
parapet wall transition to an aluminum
composite material condition.
Figure 5. A thermoplastic polyolefin–
clad parapet wall transition to exterior
insulation and finish system condition.
20 • IIBEC Interface March 2022
piece to the thermoplastic polyolefin (TPO) roof
membrane flashing sheet is problematic. If any portion
of these sheet metal fabrications comes into
contact with the parapet wall, this would increase
the potential for the roof flashing sheet to be compromised
or, in a worst-case scenario, cut, providing
a direct path for water leakage into the exterior wall,
the roof assembly, or both.
• In Fig. 6 and 7, the exterior insulation and finish
system (EIFS) sill-height elevations at roof-to-wall
transitions are at a lower elevation than the top of
the parapet wall. This results in a unique flashing
condition of the inside corner where the parapet
wall terminates perpendicular into the higher wall.
It is this author’s opinion that the sheet metal fabrication
elevation should be established at a minimum
NRCA-recommended flashing height of 8 in. (200
mm) above the top of the parapet wall, with that elevation
held at a constant around the perimeter of that
roof area.5
• In Fig. 8 and 9, brick was laid across the top of the
parapet wall and rests directly onto the white TPO
flashing membrane without a steel lintel to support
the brick. In addition to the roofing terminations
being concealed from view or inspection, the brick
will impose a load on the TPO flashing sheet, which
Figure 6. A
thermoplastic
polyolefin–clad
parapet wall
transition
to exterior
insulation and
finish system
condition.
Figure 7. A thermoplastic polyolefin–clad parapet
wall transition to exterior insulation and finish system
condition.
March 2022 IIBEC Interface • 21
ultimately may result in
failure of that flashing
sheet.
• In Fig. 10 and 11, the top
of the parapet wall is at
a slightly higher elevation
than the sill height
of the aluminum curtainwall
frame. To address
this condition, the construction
manager and
subcontractors held a
field coordination meeting
and implemented an
alternative solution that
introduced an overflow
scupper or stepdown in
the parapet wall to simplify
and accommodate the
transition to the aluminum
curtainwall frame.
• In Fig. 12, the stone cap
profile at the inside exterior
wall corner condition
was carried through to
the backside of the parapet
wall, resulting in an
unusual condition where
the stone cap and sheet
Figure 8. A thermoplastic polyolefin–clad parapet wall
transition to exterior face brick veneer condition.
Figure 9. A thermoplastic polyolefin–clad
parapet wall transition to exterior face brick
veneer condition.
Figure 10. A thermoplastic polyolefin–clad parapet wall
transition to aluminum curtainwall sill condition.
Figure 11. A thermoplastic polyolefin–
clad parapet wall transition to
aluminum curtainwall sill condition.
S Weather With product resistive openings drying-was exposure, frustrating NEW
22 • IIBEC Interface March 2022
metal coping awkwardly meet and the
air cavity associated with the exterior
wall assembly was exposed. The vertical
leg of the stone coping profile at the
inside corner condition should have
been eliminated and a detail developed
for contractor use. The contractor
ultimately ended up installing a silicone-
coated, precompressed expansion
joint to seal off the open gaps.
For any of these conditions, what does
the future reroofing scope of work look like?
Will the scope of work require contractors
to access existing roofing terminations by
removing, storing, and reconstructing brickwork
to accommodate access to the roofing
terminations? Will the scope of work require
replacement of aluminum composite material
and EIFS damaged as a result of accessing the
roofing terminations?
In either case, color matching of veneers
after long-term ultraviolet exposure and weathering
may be difficult even if color fade is minimal.
Perhaps an “easier” choice will be made, in
which existing roofing terminations concealed
by building veneers are simply
abandoned in place and
new terminations are created
as close as possible to the face
of the building veneer. Would
a roofing manufacturer provide
a warranty for those terminations?
Time will tell.
From a finish-grade
perspective, some designers
contend that they do not
want to see roof membrane
flashings above the top of
the parapet wall. They prefer
the look where the building
veneer materials “scoot” right
across the top of the parapet
at transitions, which can
be seen in these figures. The
design of these locations may
look appealing from finish
grade, but the conditions
created are impractical for
maintaining access to roofing
terminations for maintenance
purposes or accommodating
proper reroofing in the
future without disruption to
installed veneer systems.
The field examples presented
in this paper underscore
the importance of an
interactive process between
the design team and contractors, the contractor
RFI process, mock-up reviews, and preinstallation
meetings, especially when building enclosure
conditions and terminations are atypical.
In the absence of these processes, there is elevated
risk that individual trades may make
decisions that they believe to be in the best
interest of the building owner without fully
understanding the ramifications of their decisions
for future building material maintenance
and replacement.
CONCLUSION
Effective use of construction administration
tools such as mock-ups and preinstallation
meetings can go a long way toward ensuring
that each trade will properly execute their scope
of work, with the goals being to maintain vertical
flashing heights and maintain access to
roofing termination details to minimize future
disruption to building material veneers when
roofing materials require repair or replacement.
The ultimate objective in this process
is to ensure strong designer–contractor team
communication so that we can all act to the
best of our ability to achieve a well-crafted and
detailed outcome that performs in the owner’s
best interest.
REFERENCES
1. ASTM International. 2018. Standard
Test Method for Field Measurement of
Air Leakage Through Installed Exterior
Windows and Doors. ASTM E783-
02(2018). West Conshohocken, PA:
ASTM International.
2. ASTM International. 2017. Standard
Practices for Air Leakage Site
Detection in Building Envelopes and
Air Barrier Systems. ASTM E1186-
17. West Conshohocken, PA: ASTM
International.
3. ASTM International. 2015. Standard
Test Method for Field Determination of
Water Penetration of Installed Exterior
Windows, Skylights, Doors, and Curtain
Walls, by Uniform or Cyclic Static Air
Pressure Difference. ASTM E1105-
15. West Conshohocken, PA: ASTM
International.
4. ASTM International. 2020. Standard
Guide for Evaluating Water Leakage
of Building Walls. ASTM E2128-20.
West Conshohocken, PA: ASTM
International.
5. National Roofing Contractors
Association (NRCA). 2019. The NRCA
Roofing Manual: Membrane Roof
Systems. Rosemont, IL: NRCA.
Please address reader comments to
chamaker@iibec.org, including “Letter to
Editor” in the subject line, or IIBEC, IIBEC
Interface Journal, 434 Fayetteville St., Suite
2400, Raleigh, NC 27601.
Bob Sanderson,
RRC, REWC, is a
construction engineer
at Design
Collaborative with a
passion for a meticulous
attention to
detail and quality of
construction documentation.
Trained
at Purdue University
Fort Wayne, he has
more than 30 years
of unique experience
in design and construction administration of
multimillion dollar projects in the higher education,
multifamily, mixed-use, and workplace
markets, which leads to high-performance solutions
on every project he touches.
Bob Sanderson,
RRC, REWC
Figure 12. An inside corner of a parapet wall clad with white
ethylene propylene diene terpolymer to stone and sheet metal
coping termination detail condition.