Conventional Roofing Assemblies: Measuring the Thermal Benefits of Light to Dark Roof Membranes and Alternate Insulation Strategies

March 16, 2014

2 9 t h RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 2 0 – 2 5 , 2 0 1 4 F i n c h e t a l . • 1
Conventional Roofing Assemblies: Measuring
the Thermal Benefits of Light to Dark Roof
Membranes and Alternate Insulation Strategies
Graham Finch, PEng.;
Marcus Dell, PEng.; Brittany Hanam, PEng, BEMP;
and Lorne Ricketts
RDH Building Engineering Ltd.
224 West 8th Ave., Vancouver, BC V5Y 1N5 Canada
Phone: 604-873-1181 • Fax: 604-873-0933 • E-mail: gfinch@rdhbe.com
Abstract
This is the latest publication concerning a large, multiyear conventional roofing study
being performed by the authors. This paper builds off of the 2013 RCI Building Envelope
Technology Symposium (Minneapolis 2013) publication, “Monitored Field Performance of
Conventional Roofing Assemblies – Measuring the Benefits of Insulation Strategy” and
applies the newer findings from this study to the wider North American audience. The
2013 publication focused on the differences in insulation performance, whereas this 2014
publication looks at both insulation and roof membrane color and utilizes calibrated energy
modeling to look at the impact in different climate zones.
Speaker
Graham Finch – RDH Building Engineering Ltd.
Gra ham Finc h is a principal and research engineer with RDH Building Engineering
Ltd. in Vancouver, BC. He has a passion for technology and for making better buildings.
He leads RDH’s building science research group and is actively involved in a wide range
of projects from building research studies to forensic investigations, building monitoring,
hygrothermal modeling, and new construction. Finch has helped develop numerous industry
guideline documents related to durable building enclosures and roofing and energy use
in buildings. In addition, he is a part-time instructor at the British Columbia Institute of
Technology, where he teaches building science courses at the undergraduate and masters’
levels.
2 • F i n c h e t a l . 2 9 t h RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 2 0 – 2 5 , 2 0 1 4
ABSTRACT
A field monitoring study was implemented
to measure the impacts and benefits of
membrane color (white, gray, and black) and
insulation strategy on the performance of
conventional roofing assemblies. The same
roof membrane cap sheet type with three different
surface granule colors was placed over
three different conventional insulation strategies,
creating a total of nine unique roofing
assemblies (each 16 squares, 1,600 sq. ft.
[150 m2] in size) on the same building. The
thicknesses of the different insulation products
were varied to achieve approximately the
same R-value for each of the nine roof assemblies.
Sensors were installed to measure temperature,
relative humidity, moisture content,
and heat flux at various points within each
of the roof assemblies. Displacement sensors
were also installed within the insulation
boards to measure the dimensional stability
of the different insulation products, and solar
radiation sensors were installed above the
cap sheet to document the long-term reflectivity
and soiling of the roofing membranes.
In conjunction with the sensors, webcam
photos were captured to study the impact of
night sky cooling, wetting/frost, and other
differences among the assemblies. To complement
the field study, supplemental laboratory
testing of the insulation products was
performed to measure the installed insulation
R-values, and whole-building energy simulations
were performed to apply the calibrated
results from the study to other building types
and climate zones across North America.
Presented in this paper are findings
from the study that highlight the impact of
both roof membrane color and insulation
strategy on the thermal behavior and energy
gains/losses through conventional roofing
assemblies. Whole-building energy modeling
is used to synthesize the study findings
and demonstrate how whole-building
heating and cooling energy consumption
is affected by different roof membrane colors
and insulation types/strategies within
North American climate zones.
Bac kgr ound
Exposed membrane roofs (i.e., roofs with
exposed roofing membrane on top of the
roof insulation and structure—also called
conventional roofs) make up the majority
of low-slope roofing assemblies in North
America. Membrane colors from dark to
light are chosen based on product availability,
aesthetics, building type/use, energy
efficiency, and standard practices, which
vary from southern to northern latitudes.
Lighter, more-reflective membrane colors or
finishes (high solar reflectivity index [SRI])
are common in the southern U.S. where
required by energy code (ASHRAE 90.1);
though with Leadership in Energy and
Environmental Design® (LEED®) projects
and some other energy-rating programs,
light- or white-colored roofs are often used
regardless of geography. In northern climates,
the benefit of using white membrane
roofs to achieve cooling savings is
often small and can be offset by higher
wintertime heating loads (DOE Cool Roof
Calculator, 2013; Roof Savings Calculator,
2013; Smith, 2001).
The thermal insulation used within new
conventional roofing assemblies typically
consists of rigid polyisocyanurate (varying
from <R-5 to R-6/inch), expanded polystyrene
(EPS, R-4 to R-4.5/inch), or rigid stone
wool1 (R-3.7 to R-4.3/inch). (The R-value
of insulation products varies depending
on age, density, moisture content, etc.;
and some variation can even exist among
batches of the same product.) Wood fiberboard,
rigid fiberglass, extruded polystyrene
(XPS), and spray polyurethane foam insulations
are also used in some applications,
but these additional insulation types are
less common in new conventional roofs. It
is also common to use a combination of
insulation layers within conventional roofs,
thus blending the positive attributes of each
insulation type in “hybrid systems.”
An example of a hybrid system would be
using polyisocyanurate over tapered EPS or
the use of rigid stone wool over polyisocyanurate
as investigated in this research. In
this hybrid system, the stone wool is used
on top of the polyisocyanurate, as it is generally
more dimensionally stable than polyisocyanurate
(diurnal movement and longterm
shrinkage), which reduces exposed
membrane stresses and keeps the lower
polyisocyanurate insulation layer within
a tighter temperature range, closer to the
interior temperature (depending on the ratio
of outboard insulation to polyisocyanurate
insulation). This also results in conditions
that optimize the apparent R-value of the
polyisocyanurate insulation as covered later
within this paper.
The research study investigates the
thermal differences and net heat flux
through conventional roof assemblies utilizing
light- to dark-colored (low to high solar
absorptivity) roof membranes in conjunction
with different insulation material combinations,
including polyisocyanurate and
stone wool. It then extends these findings
using whole-building energy modeling to
demonstrate how building energy consumption
is affected by these roof characteristics.
Field Monit ori ng Program
and Study Buildi ng
A large-scale field monitoring study
was implemented in the Lower Mainland
of British Columbia with the intent of
measuring the impacts and benefits of roof
membrane color and insulation strategy on
the long-term thermal and hygrothermal
behavior and performance of conventional
roofing assemblies.
The roofing variables consist of three different
2-ply SBS membrane cap sheet colors
placed over three different conventional insulation
strategies (polyisocyanurate, stone
wool, and a hybrid combination of both),
creating a total of nine unique roofing assemblies
(each 16 squares, 1,600 sq. ft. [150
m2] in size) on the same building. The thicknesses
of the insulation combinations were
varied to achieve approximately the same
total effective R-value in each assembly.
Conventional Roofing Assemblies: Measuring
the Thermal Benefits of Light to Dark Roof
Membranes and Alternate Insulation Strategies
2 9 t h RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 2 0 – 2 5 , 2 0 1 4 F i n c h e t a l . • 3
Sensors were installed
within each of the nine
roof assemblies to measure
material temperatures,
relative humidity, moisture
content, heat flux,
and dimensional stability
of the insulation. Reflected
solar radiation from the
roof cap sheets was measured
using solar radiation
sensors (pyranometers)
pointed downwards toward
the roof surface, and direct
solar radiation was measured
with a solar radiation sensor as part
of the weather station used to measure
exterior conditions. In addition, a camera
was set up to automatically capture photos
of the roof surfaces to study the impact of
night sky cooling, wetting/frost, and soiling
of the white membrane. Finally, the apparent
R-values of the insulation products were
measured in a laboratory to allow for comparison
with the in-situ values calculated
using the embedded heat flux and temperature
sensors. Further information about the
monitoring equipment and sensors can be
found within a previous paper by Dell and
Finch, presented at the 2013 RCI Building
Envelope Technology Symposium and within
the full report (RDH 2013).
The study structure is an industrial
building located in Chilliwack within
the Lower Mainland of British Columbia,
Canada. The climate of Chilliwack is similar
to the larger metropolis of Vancouver;
though, as it is farther inland, it gets hotter
in the summer and colder in the winter.
The average annual temperature at the
Chilliwack airport, located approximately
1 km (0.6 miles) from the site, is 10.5°C
(50.9°F), with the average July temperature
of 18.5°C (65.3°F) and January temperature
of 2.2°C (36.0°F) (Environment Canada
2013).
The building was selected because it
provided a single, large, uninterrupted test
area for the roof monitoring; the construction
schedule coincided with the research
study; and the building owners were willing
to have a number of different roof
assemblies installed on their building. Prior
monitoring of an adjacent building housing
similar industrial equipment ascertained
that the interior conditions in the new
building would be on average between 20°C
(68°F) and 25°C (77°F) year-round. A sketch
4 • F i n c h e t a l . 2 9 t h RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 2 0 – 2 5 , 2 0 1 4
Figure 1 – Study building and layout of roof membrane cap sheet color and insulation strategy.
Figure 2 – Polyisocyanurate roof assembly (3.5 in., R-21.5); weight: 4.6 kg/m2, heat
capacity: 6.75 kJ/K/m2.
Figure 4 – Hybrid roof assembly (2.5 in. stone wool over 2-in. polyisocyanurate,
R-21.3); weight: 14.3 kg/m2, heat capacity: 13.7 kJ/K/m2.
Figure 3 – Stone wool roof assembly (5.75 in. stone wool, R-21.4); weight: 26.7 kg/
m2, heat capacity: 22.7 kJ/K/m2.
of the building
showing the three
different membrane
colors and
three insulation
combinations, as
discussed in the
following section,
is presented in
Figure 1.
As shown,
a total of nine
unique roof assemblies,
each 40
x 40 ft. in area (16 squares, 1,600 sq. ft.
[150 m2]) were constructed and monitored
at the west part of the building. The adjacent
section of the roof along the east side is
insulated with stone wool but is not monitored
or included within the study.
Roof Assemblies and
Insulati on R-val ues
Each roof assembly consists of a 2-ply,
torch-on SBS cap (white, gray, or black) and
base sheet over asphalt protection board
(only over polyisocyanurate), insulation layers
(as indicated), reinforced air/vapor barrier
membrane, and metal Q-deck over
open-web steel joists. The air/vapor barrier
membrane spans between the metal deck
flutes and has been designed and tested by
the manufacturer to do so without sagging
in this application. The use of a continuous
rigid gypsum board over the deck flutes
with standard self-adhered membrane is
generally more common in this application.
The asphalt protection board (where
used) and insulation layers are structurally
adhered together and to the air/vapor barrier
membrane using a low-rise, two-part urethane
adhesive, negating the need
for mechanical fasteners in the
assembly and associated perforations
in the air barrier membrane.
The top surface of the stone wool
insulation contains an integral
asphalt-impregnated surface and
does not require an additional
overlay protection board.
The three SBS cap sheet colors
include standard black, gray, and
white (LEED®-compliant SRI cap).
The thickness of each insulation
combination was varied to achieve
approximately the same design
R-value of R-21.5 (at standard
test conditions of 23.9°C [75°F]).
Samples of insulation were taken from the
site for laboratory testing (covered later in
this paper). These three insulation combinations
are shown in Figures 2 through
4, along with the apparent R-value of the
insulation, insulation weight, and total insulation
heat capacity. Figure 5 shows the
membrane cap sheet colors. The solar reflective
index (SRI), reflectance, and emittance
as specified by the manufacturer are also
listed for each cap sheet type. The insulation
thickness transitions (3.5 in., 5.75 in., and
4.5 in.) between the three different insulation
strategies were made using a few feet of
tapered insulation, well away from sensors
and monitoring equipment.
In conjunction with the field-monitoring
program, ASTM C518 laboratory material
testing of the thermal resistance of polyisocyanurate
and stone wool insulation
was undertaken on representative batch
samples of the products installed within
the test roofs and some additional polyisocyanurate
products that were aged for four
years. These data are used to support the
field monitoring data and demonstrate that
while the total effective R-value for each
assembly is between R-21.3 and R-21.5, the
apparent2 R-value for each case will vary
depending on the in-service conditions.
As previously published from this study
(Dell and Finch, 2013), Figure 6 presents the
apparent R-value per inch as determined by
ASTM C518 testing from six polyisocyanurate
and three rigid stone wool samples
used in this study. These samples were
removed from the site and were two months
old at time of testing. The results for the
minimum, maximum, and average of the six
polyisocyanurate samples are provided to
indicate the range of performance. In addition,
results from a four-year-old sample
of the same brand of polyisocyanurate are
shown for comparison. The results agree
well with published data for stone wool and
polyisocyanurate data from the National
Roofing Contractors Association (Graham
2010, NRCA 2011) and Building Science
Corporation (BSC 2013a), which have also
found a strong relationship between polyisocyanurate
insulation temperature, age,
and its apparent R-value.
These laboratory measurements of the
apparent R-value/inch for each insulation
2 9 t h RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 2 0 – 2 5 , 2 0 1 4 F i n c h e t a l . • 5
Figure 5 – Membrane cap sheet colors (white, gray, and black) shown on left in lab (unsoiled and new) and
shown on right in field shortly after installation.
Figure 6 – Apparent R-value per inch vs. mean temperature for polyisocyanurate and stone
wool insulation (Dell and Finch, 2013)
product were then applied to the three roofing
assemblies from this study to determine
the apparent R-value of the roof assemblies:
• Stone wool (5.75 in. [146 mm] stone
wool, R-21.4)
• H ybrid (2.5 in. (64 mm) stone wool
over 2 in. [51 mm] polyisocyanurate,
R-21.5)
• Polyisocyanurate (3.5 in. [89 mm] polyisocyanurate, R-21.3)
Figure 7 provides apparent R-values for
each assembly based only on the roof membrane
surface temperature and a typical
indoor condition of 21°C (70°F) as originally
published by Dell and Finch (2013). The
impact of long-term polyisocyanurate aging
is predicted with the matching color dashed
lines for both the hybrid and polyisocyanurate
assemblies. This plot demonstrates
the sensitivity of the apparent R-value of
the different roof assemblies when exposed
to either extreme cold or hot outdoor temperatures.
The roof assembly constructed polyisocyanurate
may have a calculated effective
R-value of R-21.3, but when exposed to cold
(-10°C [14°F]) would drop to R-20 or potentially
as low as R-16.5, depending on aging
effects; and when exposed to hot temperatures
(75°C [167°F] membrane surface temperature)
would drop to R-16.5 or potentially
as low as R-14.0, depending on aging
effects. In the hybrid assembly, the use of a
layer of stone wool insulation (in this case,
equivalent to approximately 45% of the
assembly R-value) over top of the polyisocyanurate
significantly improves the effective
R-value of the polyisocyanurate as it keeps
it near optimum temperatures (which are
similar to typical interior temperatures)
and, therefore, results in a better assembly
R-value in cold and hot conditions. The
roof assembly insulated with entirely stone
wool insulation will have a more stable
R-value (increasing at colder temperatures
but decreasing at hot temperatures from
calculated R-value) but is not susceptible to
a loss of R-value with age.
Field -Monit ori ng Res ults
of Heat Flow and Thermal
Beha vior
This paper presents selected results
for the first year of the field-monitoring
program with a focus on the differences
in thermal behavior among the different
insulation strategies and membrane colors.
To compare the insulation assemblies,
the measured heat flux data, along with
cap surface temperature and interior surface
temperatures, are compared for each
assembly. Of interest are key behavioral differences
between the polyisocyanurate and
stone wool due to varying apparent R-value
and different heat capacities in conjunction
with roof membrane color.
Measured heat flux data compare the
hourly transfer of heat energy across each
assembly from interior to exterior. A positive
value indicates that heat flow is upwards
(i.e., when the interior is warmer than the
exterior membrane surface temperature),
and a negative value indicates that heat
flow is inwards (i.e., membrane heated
above interior temperature by solar radiation).
Based on the monitoring to date, we
have found large differences in
heat flux and the interior and
exterior surface temperatures
due to light to dark membrane
color, as would be expected.
Significant differences in the
heat flux and interior and
exterior surface temperatures
were found, depending on the
insulation strategy. This finding
is unique to this study.
An apparent thermal lag is
observed within the stone wool
insulation and hybrid insulation
assemblies compared
to the polyisocyanurate insulation.
This finding presents
as dampened heat flux measurements,
reduced cap sheet
surface temperatures, and lower interior
surface temperatures, primarily when the
roof is heated by the sun. At night, the
differences among the assemblies are very
small. This lag in temperatures can be beneficial
from a thermal comfort and energyefficiency
standpoint, because it moderates
peak temperatures well as energy losses
and gains. The reduction in peak membrane
temperature and in rate of membrane
temperature change also likely reduces the
rate of deterioration of the membrane. It is
theorized that this thermal lag effect is primarily
due to the difference in heat capacity
between the two types of insulation (6.75
kJ/K/m2 for polyisocyanurate, 13.7 kJ/K/
m2 for hybrid, and 22.7 kJ/K/m2 for stone
wool) and thus the difference in heat capacity
of the three insulation arrangements.
The temperature dependence of the polyisocyanurate
thermal resistance (R-value)
and latent energy transfer from moisture
movement through the stone wool insulation
may also be relevant factors.
Figures 8 and 93 present the hourly
heat flux measurements for four representative
two-day seasonal periods during
winter (average winter design condition),
spring (cool), spring (warm), and summer
(peak summer design condition). Average
outdoor temperature and solar radiation for
each period are provided in Figure 10. As
expected, there is a large difference in the
heat flux between the black and white cap
membranes at peak conditions, but there
are also significant differences between the
polyisocyanurate and stone wool insulation
arrangements. The heat flow through
the stone wool compared to the polyisocy-
6 • F i n c h e t a l . 2 9 t h RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 2 0 – 2 5 , 2 0 1 4
Figure 7 – Apparent R-values of study building roof assemblies based on roof membrane
surface temperature over a range of -10°C to 75°C (14°F to 167°F) (Dell and Finch, 2013).
anurate in these cases is
typically less and is offset
by a few hours. (For reference,
Figure 10 presents
the average outdoor temperature
and solar intensity
during each of the periods
presented in Figure 8 and
Figure 9.)
Figure 10 presents the
average daily energy transfer
for the same four selected
two-day periods from
late winter, early spring,
late spring, and summer.
These periods were selected
as data was complete and
representative of typical
conditions for this climate.
Average exterior temperature
and solar radiation
intensity during those periods
are summarized within
the figure. This figure
clearly illustrates the different
performance of the
roof assemblies. Differences
are more dramatic during
the warmer months when
exposed to more solar radiation
and indicate less heat
flow through the stone wool
assemblies than through
the polyisocyanurate assemblies.
In summary,
the lowest amount
of inward heat flux
occurs with the stone
wool assemblies followed
by the polyisocyanurate
and then
the hybrid insulation
assemblies. The
assemblies with a
white cap sheet also
typically had less
inward heat flux than
the black and gray
roofs.
Roof membrane
surface temperatures
and interior metal
deck surface temperatures
are presented
for selected days
for the winter (Feb.
22), spring (May 9),
2 9 t h RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 2 0 – 2 5 , 2 0 1 4 F i n c h e t a l . • 7
Figure 8 – Heat flux measurements through each roof assembly – February 21-23, 2013 (winter)
and April 22-24, 2013 (spring cool). Note: G-ISO-SW data unavailable during April 22-24 period.
Figure 9 – Heat flux measurements through each roof assembly – May 9-11, 2013 (spring warm)
and June 30 – July 2, 2013 (summer peak design). Note: Potential error offset with G-ISO-SW and
G-SW heat flux data during time period.
Figure 10 – Heat flux measurements through each roof assembly – May 9-11, 2013 (spring warm) and
June 30 – July 2, 2013 (summer peak design). Note: Data missing for G-ISO-SW for April 22-24 period and
potentially inaccurate G-ISO and G-ISO-SW data for May 9-11 and June 30-July 2. White and black data
for all three insulation materials are, however, accurate and representative of monitored conditions.
and summer (June 30) within Figures 11
through 16, respectively. These plots show
the seasonal differences in membrane and
interior surface temperatures from dark
to light roofing and demonstrate the thermal
lag among the stone wool, hybrid,
and polyisocyanurate insulation strategies.
These findings support the differences in
measured heat flux as shown above. Note
that variations in the deck temperature
are partially influenced by the interior temperature;
however, the deck temperature
is also not the same as the indoor ambient
temperature.
As shown by the summertime data, the
use of stone wool insulation compared to
polyisocyanurate reduces peak membrane
surface temperatures, reduces the peak
interior surface temperature, and shifts
the peak temperatures by one to two hours
later. This can be a potential benefit for
both thermal comfort and cooling energy
consumption. Data for spring conditions
are similar to the summer but not as pronounced.
As demonstrated by the first set of
wintertime data, the exterior surface of the
polyisocyanurate insulation roof typically
has the coldest temperatures (all colors),
followed by the stone wool insulation and
hybrid insulation assemblies. This indicates
less heat loss through and higher apparent
R-value of the polyisocyanurate insulation
compared to the hybrid or stone wool under
these conditions. The cause of this effect
appears inconsistent with the determined
apparent R-values, and it will be further
investigated as additional monitoring data
become available, as the polyisocyanurate
ages, and as the roof membranes become
soiled.
Selecti on of Roofi ng
Membra ne Color and
Insulati on Strateg y for
Optim um Energ y Efficie ncy
Whole-building energy modeling was
performed to investigate the optimum roof
membrane color (solar absorptivity) and
insulation strategy for a conventional roof.
Simulation runs were used to compare the
same white, gray, and black roof membranes,
and the polyisocyanurate, stone
wool, and hybrid insulation strategies as
used in the monitoring study. Energy modeling
of these variables was performed
using the U.S. Department of Energy (DOE)
Building Energy Codes Program commercial
8 • F i n c h e t a l . 2 9 t h RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 2 0 – 2 5 , 2 0 1 4
Figure 11 – Roof membrane cap sheet temperature for nine monitored roof
assemblies – Feb. 22, 2013 (winter).
Figure 12 – Interior metal roof deck surface temperature for nine monitored roof
assemblies – Feb. 22, 2013 (winter).
Figure 13 – Roof membrane cap sheet temperature for nine monitored roof
assemblies – May 9, 2013 (spring).
Figure 14 – Interior metal roof deck surface temperature for nine monitored roof
assemblies – May 9, 2013 (spring).
building prototype model for a stand-alone
retail building designed to meet ASHRAE
90.1-2010. These files are available online
and use the hourly energy modeling program
EnergyPlus (DOE, 2012). Models were
run for one representative city in each of
the eight ASHRAE North American climate
zones.
One goal of the energy modeling was
to investigate the impact of temperaturedependent
insulation R-values on wholebuilding
energy consumption. While the
material testing discussed earlier in the
paper identified that thermal conductivity
variations with temperature are different for
polyisocyanurate and stone wool insulation,
this effect is typically not modeled in most
whole-building simulation programs but
can be modeled in EnergyPlus.
Figure 17 shows the energy simulation
results with constant insulation conductivity
and with temperature-dependent insulation
conductivity per the values reported
earlier within this paper. Though the overall
difference in heating energy consumption
between the two cases is low (generally
within 1 kWh/m2 [320 Btu/ft2] per year),
the results show that polyisocyanurate has
the lowest heating energy consumption
when constant conductivities are used,
but stone wool has the lowest heating
energy when the more accurate temperature-
dependent conductivities are included.
The differences in the first case can be
attributed to the differences in heat capacity
of the three insulation strategies, where
polyisocyanurate has a lower heat capacity
and responds faster than the stone wool
(also seen from the monitoring results). This
is an important finding for energy modelers
and needs to be addressed by the default
insulation material properties within energy
modeling programs.
Energy modeling was also completed
to investigate the impact of using aged
temperature-dependent conductivity values
for polyisocyanurate insulation, since the
conductivity has been shown to degrade
over time. In all cases, the four-year aged
conductivity of the polyisocyanurate insulation
was used and was varied in relation
to temperature based on the relationships
presented previously in this paper. Figure
2 9 t h RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 2 0 – 2 5 , 2 0 1 4 F i n c h e t a l . • 9
Figure 15 – Roof membrane cap sheet temperature for nine monitored roof
assemblies – June 30, 2013 (summer).
Figure 16 – Interior metal roof deck surface temperature for nine monitored roof
assemblies – June 30, 2013 (summer).
Figure 17 – Impact of modeling constant roof insulation conductivity (left) and temperature-dependent conductivity (right) for
retail building in Vancouver.
18 shows the total energy consumption (heating and cooling)
simulation results for Vancouver, including new and aged polyisocyanurate
insulation. The results show a clear increase in energy
consumption for aged polyisocyanurate as expected from the lower
R-value, making it the highest energy consumption case.
Whole-building energy simulations were run for one representative
city in each of the eight ASHRAE/DOE climate zones.
Figures 19 through 21 show the annual heating, cooling, and total
heating and cooling energy, respectively, for the eight ASHRAE
climate zones with the same black and white roof membranes (SRI
-4 and +70 respectively) as used in the study, and aged polyisocyanurate,
stone wool, or hybrid insulation. Note that this modeling
1 0 • F i n c h e t a l . 2 9 t h RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 2 0 – 2 5 , 2 0 1 4
Figure 18 – Impact of modeling aged conductivity of
polyisocyanurate insulation on total building energy
consumption in Vancouver.
Figure 19 – Commercial retail building annual heating energy use intensity in eight climate zones.
Figure 20 – Commercial retail building annual cooling energy use intensity in eight climate zones.
Figure 21 – Commercial retail building annual combined heating and cooling energy use intensity in eight climate zones.
does not account for the effect of snow on
the reflectivity of the roofs.
Comparing roof membrane color across
each climate zone, the black membrane
uses less heating energy but more cooling
energy, while the white roof uses less
cooling energy but more heating energy.
The overall space conditioning consumption
depends on the balance of heating and cooling
energy within that climate zone.
The total heating and cooling plot
(Figure 21) shows that overall energy use is
lower for white roofs in cooling-dominated
climate zones (zones 1 and 2), and lower for
black roofs in heating-dominated climate
zones (zones 5 through 8). In mixed heating
and cooling climate zones (zone 3 and 4),
the differences are very small between lightand
dark-colored roof membranes. The use
of a more reflective white roof membrane
(higher than SRI 70 modeled here) would
exacerbate these results. With membrane
aging and dirt soiling, the cooling savings
of white membranes will be reduced as the
SRI decreases. Other factors such as comfort
and urban heat island effects are not
considered here.
Across all climate zones, stone wool
insulation results in the lowest heating
and cooling energy consumption, while the
four-year aged polyisocyanurate insulation
has the highest energy consumption due
to the loss of its initial R-value. The hybrid
approach of stone wool over polyisocyanurate
results in a good compromise of performance
and maintains the higher R-value
of the polyisocyanurate insulation by reducing
temperature fluctuations.
Concl usi ons and
Rec omme ndati ons
This large-scale field monitoring study
was implemented with the intent of measuring
the impacts and benefits of roof
membrane color and insulation strategy on
the long-term thermal and hygrothermal
behavior and performance of conventional
roofing assemblies. At the study building
in the Lower Mainland of British Columbia,
Canada, three different 2-ply SBS membrane
cap sheet colors (white, gray, and black)
were placed over three different conventional
insulation strategies (polyisocyanurate,
stone wool, and hybrid combination of both),
creating a total of nine unique conventional
roofing assemblies. Sensors were installed
within each of the roof assemblies to measure
material and surface temperatures, relative
humidity, moisture content, heat flux,
and dimensional stability of the insulation.
As part of the study, thermal resistance
testing of the polyisocyanurate and stone
wool insulation was performed using ASTM
C518 procedures. The insulation products
were tested at a range of in-service temperatures,
and a relationship between R-value
and temperature was developed. The results
were then applied to the three insulated
assemblies monitored within this study
to determine in-service apparent R-values
based on exterior membrane temperature.
The findings show that the stone wool and
hybrid roofs will maintain R-values close
to calculated values, whereas the R-value
in the roof with polyisocyanurate will drop
a fair amount when exposed to either
extreme of cold or hot outdoor (and solar
radiation-induced) temperatures. This is
an important consideration when designing
roof assemblies.
The heat flow and temperature measurements
show a difference in behavior
between the polyisocyanurate, stone wool,
and hybrid insulation strategies. Stone wool
has a heat capacity approximately 3.4 times
higher than polyisocyanurate for the same
design R-value, which likely reduces peak
temperatures of the membrane and interior
and offsets the peak load (thermal lag
effects). This reduction in peak roof membrane
temperatures, as well as in the rate
of temperature change, positively affects
the longevity of the membrane as larger
magnitude and faster dimensional changes
of viscoelastic materials (such as modifiedbitumen
roof membranes) negatively affect
their durability (Dell, 1990). Reduced peak
interior temperatures also typically improve
occupant comfort. In addition, stone wool
has a more stable R-value than polyisocyanurate
for the same installed R-value
(note that installed R-value is different
than thickness); so it insulates better when
exposed to larger temperature differences,
as can frequently be experienced on roofs.
Energy modeling was used as a tool
to better understand the impact of temperature-
dependent insulation R-values on
annual space heating and cooling consumption
and to demonstrate the importance
of accounting for a varying R-value in
energy models. In addition to accounting for
a dynamic R-value, including the long-term
aging effects of polyisocyanurate is particularly
important in predicting long-term
energy use within a building.
Whole-building energy modeling was
performed to investigate the optimum roof
membrane color (solar absorptivity) and
insulation strategy for a conventional roof.
Simulation runs were used to compare the
same white, gray, and black roof membranes
and the polyisocyanurate, stone
wool, and hybrid insulation strategies as
used in the monitoring study. Energy modeling
of these variables was performed using
the DOE Building Energy Codes Program
commercial building prototype model for a
stand-alone retail building designed to meet
ASHRAE 90.1-2010. Models were run for
one representative city in each of the eight
ASHRAE North American climate zones.
Comparing roof membrane color across
each climate zone, the black membrane
uses less heating energy but more cooling
energy, while the white roof uses more
cooling energy but less heating energy.
Overall energy use is lower for white roofs
in cooling-dominated climate zones (zones 1
and 2), and lower for black roofs in heatingdominated
climate zones (zones 5 through
8). In mixed heating and cooling climate
zones (zone 3 and 4), the differences are
very small between light- and dark-colored
roof membranes. With membrane aging
and dirt soiling, the cooling savings of white
membranes will be reduced as the surface
reflectivity decreases. The impact of membrane
soiling and aging is being monitored
as part of this study but is not presented
within this paper.
Across all climate zones, stone wool
insulation results in the lowest heating and
cooling energy consumption, while aged
polyisocyanurate insulation has the highest
energy consumption due to the loss of
its initial R-value. The hybrid approach of
stone wool over polyisocyanurate results
in a good compromise of performance and
maintains the higher R-value of the polyisocyanurate
insulation.
This study provides insight into the
behavior of polyisocyanurate-and-stonewool-
insulated conventional roof assemblies
with light- to dark-roofing membranes. The
study is ongoing and will continue for the
next few years.
Acknowledgme nts
The authors wish to thank the product
manufacturers and building owner for providing
a roof to test, the building materials,
funding, and technical peer review on this
project. Special recognition is also extended
2 9 t h RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 2 0 – 2 5 , 2 0 1 4 F i n c h e t a l . • 1 1
to SMT Research for installing and troubleshooting
the sensors and data-logging
equipment, and to Building Science Labs
for the ASTM C518 material testing.
Refere nces
ASTM Standard C518, 2010, Standard
Test Method for Steady-State
Thermal Transmission Properties
by Means of the Heat Flow Meter
Apparatus, ASTM International,
West Conshohocken, PA. Available at
http://www.astm.org/Standards/
C518.htm.
ASHRAE Standard 90.1, “Energy
Standard for Buildings Except Low-
Rise Residential Buildings,” I-P
and S-I Editions. 2007 and 2010,
ANSI/ASHRAE/IESNA. American
Society of Heating, Refrigerating and
Air-Conditioning Engineers, Inc.
Available at http://www.ashrae.org.
Building Science Corporation (BSC).
2013a. BSC Information Sheet 502:
Understanding the Temperature
Dependence of R-values for
Polyisocyanurate Roof Insulation.
Available at www.buildingscience.
com.
Building Science Corporation (BSC).
2013b. The Thermal Metric Project.
Available at http://www.buildingscience.
com/documents/special/
thermal-metric/
M. Dell, Behavioral Characteristics of
Fully Adhered Modified-Bitumen
Roof Membranes When Subjected
to In-Plane Loads. University of
Waterloo, 1990. Waterloo, Ontario.
M. Dell and G. Finch, “Monitored Field
Performance of Conventional Roofing
Assemblies – Measuring the Benefits
of Insulation Strategy,” Proceedings
From the 2013 RCI Symposium
on Building Envelope Technology,
November 13-14, 2013, RCI, Inc.,
Minneapolis, Minnesota.
DOE. 2012. Building Energy Codes
Program – Commercial Prototype
Building Models. Available at http://
www.energycodes.gov/development/
commercial/90.1_models
DOE Cool Roof Calculator. 2013, Oak
Ridge National Laboratory, Software
Version 1.2. Available at http://
web.ornl.gov/sci/roofs+walls/facts/
CoolCalcEnergy.htm.
Environment Canada. 2013. “Canadian
Climate Normals, Chilliwack
Airport,” Available at http://climate.
weather.gc.ca/climate_normals/
M. Graham, “Revised R-Values,”
Professional Roofing, May 2010.
Available at http://www.professionalroofing.
net/.
C.P. Hedlin, “Seasonal Variations in the
Modes of Heat Transfer in Moisture
Porous Thermal Insulation in a Flat
Roof,” Journal of Thermal Insulation,
Vol. 11, pp. 54-66, July 1987, (IRC
Paper No. 1496).
RDH Building Engineering. 2013,
Conventional Roofing Monitoring
Study – Year 1 Summary Report.
Roof Savings Calculator (RSC), 2013,
Oak Ridge National Laboratory
and Lawrence Berkeley National
Laboratory. Software Version v0.92.
Available at http://www.roofcalc.
com/index.shtml.
T.L. Smith, “Benefits of Reflective
Roofs in Northern Areas of the
U.S.,” Proceedings of the 16th RCI
International Convention & Trade
Show, RCI, Inc., April 20-24, 2001,
Baltimore, Maryland.
Footnotes
1. Stone wool is within the class of
mineral wool/fiber insulation products.
Within this paper, it is used
to describe a stone fiber insulation
material with a higher fiber density
(typically above 10 pcf) and is
intended for roofing rather than wall
applications.
2. Apparent R-value is the actual thermal
resistance of the insulation at
a given point in time. It varies with
temperature and due to other factors
such as age.
3. In all of the subsequent plots within
the legend code, “W” refers to the
white roof membrane, “G” for gray,
and “B” for black. ISO refers to the
polyiso insulation, ISO-SW refers to
the hybrid (stone wool over polyiso),
and SW refers to the stone wool. The
nine different test areas are defined
in short form using a combination
of these letters. Within the heat flux
plots, negative values indicate gain
of energy through the roof insulation
(e.g., due to solar loading), and positive
values indicate a loss of energy
(e.g., due to colder outdoor conditions).
1 2 • F i n c h e t a l . 2 9 t h RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 2 0 – 2 5 , 2 0 1 4