Abstract
Rooftop amenity spaces can offer building owners significant value. Successfully incorporating
these spaces into the design of a rooftop requires thorough coordination, given the
convergence of cross-disciplinary design requirements, complexity of amenity overburden
materials (e.g., pavers, pools, vegetative roofing, etc.), and dimensional constraints associated
with the roof plan and roof assembly depth. This presentation explores key roof amenity
design decisions that warrant scrutiny early in the design phase, including waterproofing
selection, drainage coordination, energy conservation, fire resistance, wind resistance, maintenance
and fall protection, and associated building code requirements in both new and
retrofit applications.
Speakers
John Karras — Simpson Gumpertz & Heger, Waltham, MA
John Karras is a professional civil engineer with more than 14
years of combined design and construction management experience
with commercial projects. His expertise encompasses building enclosure
design, consulting, construction phase services, and investigation
services—in particular, creatively collaborating with design and
construction teams to navigate roofing and waterproofing challenges.
Sarah B. Rentfro — Simpson Gumpertz & Heger, Washington, DC
Sarah Rentfro received her BS from the University of Maryland
and her MS from Stanford University. She has contributed to a variety
of building enclosure projects in the Mid-Atlantic and Southeastern
United States, including several vegetative roofing, plaza, and amenity
roofing assignments. Rentfro’s work includes design consultation, field
investigation work, and construction administration.
Nonpresenting Coauthor
Joshua B. Kivela, PE — Simpson Gumpertz & Heger Inc.
8 2 • K a r r a s et . a l . B u i l d i n g E n v e l o p e T e c h n o l o g y S y m p o s i u m • No v e m be r 1 3 – 1 4 , 2 0 1 7
ABSTRACT
Rooftop amenity spaces can offer
building occupants comfort, pleasure, and
convenience of features that would otherwise
require offsite travel and public
environments. Often placed on otherwise
underutilized real estate, these spaces can
offer significant benefit for relatively limited
expense. Common amenities include
hardscape, vegetation, water features,
swimming pools, sun decks, fire pits, and
excellent views.
Successfully incorporating these spaces
into the design of a rooftop (including
avoidance of water leakage problems,
problematic design conflicts, and risk of
other moisture-related damage) requires
thorough design coordination, given the
convergence of:
• Multiple cross-disciplinary design
requirements, including architecture,
structure, landscape, plumbing,
and drainage, among others
• Complexity associated with multiple
deck elevations
• Dimensional constraints of the roof
plan area and roof assembly depth
In this article, the authors examine
key amenity rooftop design fundamentals
relating to waterproofing and drainage,
wind and fire resistance, energy conservation,
building science, and programming.
This article does not address seismic
design requirements.
WATERPROOFING SYSTEM
SELECTION
Selecting a waterproofing system for
an amenity roof is a process that combines
fundamentals from vegetative waterproofing,
plaza and below-grade waterproofing,
pool waterproofing, and cladding systems.
These subjects, individually, have been
well documented, including by the authors
referenced at the end of this article. The
specific context of an amenity roof, however,
requires some unique considerations.
Rooftop amenity spaces constructed with
pools and hot tubs are often designed so
that the coping is level with the finished
walking surface, like an in-ground pool.
These heavy and often fully welded stainless
steel or gunnite water features are not
easily removed for waterproofing repairs.
Depending on the location of the pool
mechanical room, the plumbing and electrical
lines may run through openings in a
series of concrete walls below the finished
walking surface (Figure 1). Other rooftop
features, such as glass screen walls
(Figure 2), folding glass walls, and transitions
to coping and cladding systems,
require the use of flexible flashing materials
that can conform to unique shapes and
be applied to various substrates, including
building expansion joints.
Therefore, a durable waterproofing
membrane with good flashing accessories
is desirable. From a material perspective,
several characteristics that impart
durability are low water absorption, high
puncture resistance, and strength. From
a system perspective, monolithic (i.e., no
or few seams) membranes that are sloped
to drain with membrane-level drainage
are important considerations to maximize
membrane durability.
For the reasons noted above, the
authors often employ reinforced hotapplied
rubberized asphalt and reinforced
liquid-applied polymeric membranes,
both in protected roof membrane
assembly (PRMA) configurations,
for rooftops rich with amenity features.
Single-ply thermoplastic roof membranes
with heat-welded seams are often used
in situations where the overburden is
relatively easy to remove (e.g., vegetative
roof trays or wood decking). It is prudent
to allow for improved membrane access
with these types of membranes. Leaks
can occur through poorly constructed
seams and travel a significant distance
from the leak source because the roof
membrane is not fully bonded to the
structural deck substrate.
Designing Amenity Rooftops:
Complexity, Coordination,
and Conflict Avoidance
B u i l d i n g E n v e l o p e T e c h n o l o g y S y m p o s i u m • No v e m be r 1 3 – 1 4 , 2 0 1 7 K a r r a s et . a l . • 8 3
Figure 1 – Pool and hot tub installation in progress.
BUILDING CODE REQUIREMENTS
Jurisdiction-specific building code
review is an eclectic exercise for amenity
roofs. In this section, we summarize some
important provisions of model and jurisdictional
codes that warrant attention in a
project-specific, design-phase code review.
Wind Resistance for Gravel
and Paver Ballast
Amenity roofs commonly utilize gravel
and paver ballast as part of the overburden
system above the waterproofing membrane.
The International Building Code
(IBC) includes provisions related to the wind
resistance of these materials. Unless otherwise
noted, the provisions referenced in this
article are from the 2015 IBC.
The authors suggest it is sensible to
begin by reviewing a “gateway” requirement
associated with the use of gravel (also
referred to by the IBC as aggregate, and
by ANSI-SPRI as stone). Section 1504.4
requires that, for ballasted low-slope roof
systems, gravel shall not be used on the
roof of a building located in a hurricaneprone
region or on any other building
with a mean roof height exceeding that
permitted by Table 1504.8 (note: The genesis
of this table was examined by Jay
Crandell and Michael Fischer in a paper
published in the Proceedings of the RCI 25th
International Convention4). The basic/nominal
wind speed, a primary input for Table
1504.8, is determined in accordance with
Section 1609.3.1. A conversion is required
between the ultimate wind speed (shown on
the wind maps in Figures 1609A, 1609B, or
1609C, which differ based on the building’s
risk category) and the basic/nominal wind
speed.
Chapter 15 provides a guide for determining
the design characteristics required
for gravel (if permitted by Table 1504.8) or
pavers on a roof. In this regard, Section
1504.4 requires that ballasted low-slope
roof systems comply with the referenced
standard ANSI/SPRI RP-4, Wind Design
Standard for Ballasted Single-ply Roofing
Systems (RP-4).1 RP-4 provides a method
of designing wind resistance for gravel
or concrete pavers (including traditional
precast concrete or approved interlocking,
beveled, doweled, contoured-fit, or cementitious-
coated lightweight-concrete pavers).
Essentially, RP-4 presents a series of tables
(with each table representing a range of
parapet height) from which a designer can
determine permissible characteristics (e.g.,
weight) of gravel or pavers in the field,
perimeter, and corner zones of the roof.
Similar to the IBC Chapter 15 gateway
requirements regarding gravel, to avoid
problematic design conflicts, the RP-4
analysis should be performed early in the
design phase for reasons that include the
following:
• Many amenity roofs include a relatively
low parapet, provided they
include guardrails to limit pedestrian
access away from the roof edge,
and especially in jurisdictions that
have building height restrictions and
elevation setback requirements (e.g.,
Washington, DC), or when maximizing
views is a primary feature of the
design criteria. For buildings with a
roof height taller than 45 feet, RP-4
does not permit the approach of a
ballasted roof assembly if the parapet
is less than 12 inches tall unless
a project-specific ballast design that
is approved by the Authority Having
Jurisdiction (AHJ) is performed by
a registered design professional.
Alternatively, the design team may
have to consider a conventional lowslope
roofing assembly or concrete
paving slab above waterproofing in
a split-slab configuration, separated
from the main roof by an impermeable
(e.g., glass) guardrail at the roof
perimeter area.
• RP-4 notes that the standard should
be used in conjunction with the
requirements of the manufacturer
of specific products used in the ballasted
roof system. One example of
potential conflict here is that some
manufacturers and some insurance
requirements (e.g., FM Global Data
Sheet 1-35) require a “vegetativefree
zone” at the roof perimeter. If
only RP-4 (and its sister document,
a design guideline that is commonly
utilized though not required by code,
ANSI/SPRI RP-14, Wind Design
Standard for Vegetative Roofing
Systems)2 is utilized, and the roof
has a jurisdiction-specific green roof
area (see “What’s Next?” below), the
vegetative-free zone requirements
should be considered prior to submitting
the green roof area calculations,
since they often compete with
those requirements.
• When the building height exceeds
150 feet, the ballast design shall be
determined by a registered design
professional and approved by the
AHJ. This process requires project
resources (e.g., a component-and-
8 4 • K a r r a s et . a l . B u i l d i n g E n v e l o p e T e c h n o l o g y S y m p o s i u m • No v e m be r 1 3 – 1 4 , 2 0 1 7
Figure 2 – The glass and aluminum curtainwall projects past the roof, forming a screen
wall. Hot rubberized asphalt waterproofing is applied on a sloped concrete deck.
cladding wind tunnel study for irregularly
shaped buildings) and time
to complete. Similarly, any building
not fitting one of the design tables
provided shall be treated as a “special
design consideration” requiring
review by a licensed design professional
and approval by the AHJ.
Waterproofing Slope and Drainage
Slope and drainage are two of the more
important system-level features of a durable
waterproofing system. The 2015 IBC Section
1507 requires a minimum 2% slope (¼ in.
per foot) on new roof projects for all roof
types except for coal-tar built-up roofs,
which may have a 1% slope. The aforementioned
reinforced hot-applied rubberized
asphalt and reinforced liquid-applied polymeric
membranes are typically classified
as built-up roofs and liquid-applied roofs,
respectively. Therefore, the 2% minimum
slope requirement applies to these types
of membranes. In some local jurisdictions
(e.g., Washington, DC), hot-rubberized
asphalt roofs are not required to meet the
2% minimum slope requirement for new
roofs, but should still achieve positive slope
to drain. Drain placement (with consideration
to service and creep deflections) is
critical on roofs that utilize this approach.
Although many of these lower-slope projects
have been successful, the limited slope may
impact membrane durability over the long
term and result in other unintended consequences
associated with long-term ponding
on the roof membrane (e.g., odors and/or
mosquitoes at the amenity area). A tapered
concrete substrate that is monolithically
placed with the slab offers the most architectural
design flexibility because the number
of available slopes and configurations
is infinite.
The 2015 IBC Section 1503.4 includes
requirements related to primary and secondary
(emergency overflow) roof drainage
and references to the International
Plumbing Code. Overflow drainage can be
achieved via independently plumbed internal
overflow drains or by allowing water
to drain over the roof edge. Section 1504
implies that drainage over the roof edge
(provided the load from ponding water on
the roof deck, if all primary internal drains
clog, does not exceed the design capacity
of the structure) can serve as a secondary
drainage path in lieu of secondary internal
drains or scuppers. If the design team
pursues this approach, coordination is also
required with RP-4 parapet height requirements
described above.
Adequate drainage is also important to
limit ponding conditions that may lead to
floating insulation. Contemporary energy
codes continue to require greater amounts
of insulation and, in some localities, use
of blue roofs and roof drain flow restrictors
are encouraged to dampen peak stormwater
flows. Providing adequately sized roof
drainpipes and continuous membrane-level
drainage will typically negate the likelihood
of floating insulation in most situations,
but if a blue roof or flow-restricted roof
is designed, a hydrologic analysis is warranted.
Fire Resistance
The International Fire Code (IFC), which
is adopted by certain U.S. jurisdictions,
includes provisions related to a common
amenity roof feature—the vegetative roof—
that IFC refers to as a roof garden or
landscaped roof. Section 317.2 requires
that vegetative roof areas do not exceed
15,625 square feet without a 6-ft.-wide
Class A-rated roof system providing abovedeck
fire-resistive separation from the adjacent
roof area.
Section 317.2 includes a similar provision
for long/narrow rooftop vegetative roof
areas, limiting their length to 125 feet maximum
without Class A-rated separation, and
for vegetative areas adjacent to combustible
vertical surfaces (e.g., building superstructure,
mechanical penthouses, skylights,
and photovoltaic panels). For amenity roofs
over noncombustible decks, design teams
can consider PRMA roof systems with pavers
(provided they are Class A-rated) to
satisfy both these IFC requirements and the
FM Global (where applicable) roofing manufacturer
vegetative-free-zone requirements
described above, while providing access
paths for maintenance personnel or circulation
paths for building occupants.
Energy Conservation
The 2015 Edition of the International
Energy Conservation Code (IECC) is the
applicable standard for energy code compliance
in many states. The ANSI/ASHRAE/
IESNA Standard 90.1-2013 (ASHRAE 90.1)
may also be used as an alternative means
of energy code compliance. The energy
codes generally allow a prescriptive compliance
approach (insulation R-value or overall
U-value) or a performance-based approach.
Based on our experience, regardless of the
compliance path selected, designers typically
try to achieve prescriptive insulation values
on roofing assemblies. This may range
from R-20 to R-35, depending on climate
B u i l d i n g E n v e l o p e T e c h n o l o g y S y m p o s i u m • No v e m be r 1 3 – 1 4 , 2 0 1 7 K a r r a s et . a l . • 8 5
Figure 3 – Spray-foam insulation installed on underside of prefabricated pool
shell. Photo courtesy of CBT Architects.
zone and building use type. An R-30 PRMA
with extruded polystyrene insulation would
require about 6 in. of insulation. Roofing
membrane, protection, and drainage board
will also add thickness to the assembly.
Special consideration should be given to
water features, screen walls, and other roof
penetrations, and creative solutions for
challenging conditions often are required.
For example, spray foam can be used on
the underside of pool shells (Figure 3) to
achieve thermal continuity and structural
thermal breaks, and/or specialized thermal
analysis may be required at structural
supports for screen walls and glass rails
(Figure 4).
Pool Deck Surfaces
The review of building code requirements
related to walking surfaces surrounding
a pool—commonly referred to as
the pool deck—is typically spearheaded by
the architect of record with support from
a specialty pool contractor. The building
enclosure consultant,
however, should be
aware of some code
provisions that may
require coordination
with the amenity roof
waterproofing or traffic
coating design.
As with any building
code review, the
project team must
review jurisdictionspecific
requirements.
This is especially true
in the context of spaces
surrounding a rooftop
pool, since many
local jurisdictions reference
requirements
of local health departments.
With that said,
the International
Swimming Pool and
Spa Code (ISPSC),
referenced by Chapter
31 of the IBC, and the
Model Aquatic Health
Code (MAHC), published
by the Centers
for Disease Control
and Prevention (CDC),
promulgate some
requirements that
represent the types of
provisions that may be of interest to the
building enclosure consultant:
• The MAHC requires, for certain
walking surfaces adjacent the pool,
a minimum dynamic coefficient
of friction. This is notable in the
sense that if the building enclosure
consultant specifies a traffic coating
or waterproofing membrane
on top of the pool deck, the finished
surface must meet the mandated
slip resistance performance
requirements.
• The ISPSC requires that pool decks
must be sloped such that standing
water will not be deeper than
1/8 inch within 20 minutes of
the addition of water to the deck.
Table 306.4 in the ISPSC also provides
“typical minimum drainage
slope” for various wearing surfaces
except when an alternative
drainage method is provided that
prevents the accumulation of surface
water. As such, open-jointed
overburden systems (e.g., wood tiles
or pavers on pedestals) that drain
freely might not require slope, if
authorized by the AHJ. In contrast,
the MAHC provides more general
requirements based on finish type.
Smooth finishes (e.g., tile or lightly
broomed concrete) shall have a minimum
slope of 1/8 inch per foot).
• The MAHC requires that all water
that touches the pool deck shall
drain effectively to either perimeter
areas or to deck drains, and not
towards the aquatic vessel (e.g., pool
or spa).
• Both the ISPSC and the MAHC
require watertight isolation joints
between the pool coping and surrounding
deck.
INTERSTITIAL SPACE DESIGN
Rooftop pool structures and deep planters
(when the design intent is for the adjacent
walking surface to be flush with the
top of the pool/planter wall) are commonly
designed as overbuilt structures above the
structural deck, resulting in an interstitial
space adjacent to the planter/pool structure.
The presence of multiple deck elevations
creates design and construction complexities
that can, without close attention,
result in performance pitfalls. We address
the waterproofing location and building
science considerations in this section, and
drainage in the following section.
The building enclosure consultant
should, in the schematic phase and with
the architect, plumbing engineer, structural
engineer, and landscape architect
present, map out the path of the waterproofing
membrane on a building section
drawing that includes representations
of the various deck levels. Figures 5, 6,
and 7 show three common configurations
of the waterproofing path as it relates
to the interstitial space. Note that in all
three cases, the waterproofing membrane
extends up and over the stem walls (i.e.,
structural basin) immediately adjacent
to the pool. This isolates the pool waterproofing
system from the field of the
roof, which is necessary to help contain
leaks through the pool shell. The pool
waterproofing should tie into the adjacent
waterproofing system in a continuous
manner.
8 6 • K a r r a s et . a l . B u i l d i n g E n v e l o p e T e c h n o l o g y S y m p o s i u m • No v e m be r 1 3 – 1 4 , 2 0 1 7
Figure 4 – Structural penetrations for screen walls and
glass rails must be considered as part of the project’s
energy conservation goals. A consultant takes in the great
views from the soon-to-be-completed private cabanas.
Redundant Waterproofing
Redundancy in waterproofing above and
below the interstitial space is prudent when
the project budget allows and when the
design team desires the lowest risk profile.
Figure 5 takes this approach. The waterproofing
system in this configuration would
include a membrane on the overbuilt deck
that is contiguous with the pool waterproofing
membrane. The membrane on the
structural deck should share the primary
characteristics of the upper waterproofing
membrane, but it is not unreasonable to
reduce the durability of the lower membrane
because of its reduced exposure.
The pool deck, if it is comprised of a paving
slab, is sometimes covered with a decorative
overlay, primarily for cosmetic and slipresistance
purposes. From a thermal barrier
standpoint, locating the insulation above
the lower waterproofing layer, particularly
when the waterproofing membrane is a
vapor retarder and the lower membrane is
on the winter-warm side of the insulation,
simplifies the hygrothermal analysis associated
with this configuration.
Structural Deck Waterproofing
The waterproofing membrane is below
the interstitial space only. This approach
requires detailing the waterproofing membrane
so that it can, after it passes over the
walls immediately adjacent to the pool, pass
under adjacent stem walls that support the
elevated deck and other walls (e.g., planter
walls; see Figure 10) that are constructed
above the structural deck. From a constructability
standpoint, this option (as does the
lower waterproofing level of the redundant
waterproofing option in Figure 5) has the
benefit of facilitating rapid “drying-in” of the
building interior, since the structural deck
can be waterproofed in its entirety immediately
following installation of pool waterproofing.
If the interstitial space will be used
to route pool plumbing lines, placing waterproofing
on the structural deck also helps
avoid building leakage from plumbing leaks.
Since the overbuilt deck is not waterproofed
and is subject to deterioration, it must be
designed so that the metal deck is a sacrificial
form and not part of composite deck.
Overbuilt Deck Waterproofing
The waterproofing membrane is above
the interstitial space only. It is often difficult
for the construction team to prevent water
entry into the interstitial space during con-
B u i l d i n g E n v e l o p e T e c h n o l o g y S y m p o s i u m • No v e m be r 1 3 – 1 4 , 2 0 1 7 K a r r a s et . a l . • 8 7
Figure 5 – Redundant waterproofing (above and below interstitial space).
Figure 6 – Structural deck waterproofing (below interstitial space).
struction (i.e., prior to waterproofing membrane
installation on top of the elevated
deck). Moisture entry into the interstitial
space can result in a lengthy drying process
that limits the construction team’s ability to
install waterproofing on the elevated deck
and install interior finishes below the structural
deck.
General Interstitial Space
Considerations
Regardless of the waterproofing path
or whether water leaks into the interstitial
space during construction, it is very likely
that the interstitial space will always be
damp or may experience water leakage from
some source. The design of the interstitial
space should therefore address the following:
• Mechanical ventilation may be recommended
in certain situations to
reduce the likelihood of condensation
within the space. For the
redundant waterproofing (Figure 5)
and structural deck waterproofing
(Figure 6) options, since the interstitial
space is outside of the air/
water/thermal barrier, ventilation
with outdoor air should be considered.
For the overbuilt deck waterproofing
(Figure 7) option, where the
interstitial space is essentially an
attic space, the mechanical ventilation
would be with conditioned interior
air.
• L acking dehumidification (via ventilation
or other mechanical means),
built-in moisture from construction
(e.g., water from concrete placement
and leakage) will be trapped
in the materials within the interstitial
space (air, concrete, formwork
remnants, etc.), further increasing
this risk of condensation for the first
several winters after initial construction.
Especially with the overbuilt
deck waterproofing approach, the
built-up moisture cannot readily dry
to the exterior.
• Provide a means of access to the
interstitial space in service for the
purpose of maintaining the slab/
pipes/etc. or performing repairs to
the waterproofing membrane. Avoid
designing stem walls that completely
segregate cells of the interstitial
space. If CMU or concrete stem walls
are required to support the field of
the elevated deck, include blockouts
large enough for communication
of ventilation air and access for
maintenance personnel.
• With the anticipated high humidity
and constantly damp conditions predicted
for the interstitial space, there
is an increased risk of corrosion of
mild steel components in the interstitial
space (and material degradation/
biological growth of any organic
material that resides in that area).
Biological growth and material degradation
can result in an offensive
odor that may manifest itself at adjacent
interior and exterior spaces.
Accordingly, avoid insulation materials
that are sensitive to moisture,
and avoid other organic materials
that will remain permanently in the
interstitial space.
• Even if the interstitial space is not
waterproofed, providing floor drains
at low points in the structural deck
is prudent. Additionally, provide
concrete curbs around all openings
in the structural slab (e.g., duct
penetrations and access hatches) to
minimize the chance that the slab
openings serve as paths for water
leakage to the interior, should water
reach the interstitial space.
• Avoid designing a composite elevated
metal deck whose structural performance
is reliant on the integrity of
the metal deck, given the likelihood
of deck corrosion in service.
• All piping within the interstitial
space should be jacketed and insulated
to limit the risk of sweating. All
piping joinery within the interstitial
space should be pressure-tested for
leaks prior to activating.
DRAINAGE COORDINATION
Adequate drainage is vital to the longterm
performance of an amenity roof waterproofing
system, just as it is for vegetative
roofs, plazas, and rooftop pools. Unique
to amenity roofs, however, is the relatively
complex task of coordinating the fundamentals
of primary and secondary/overflow
drainage with drainage off of multiple deck
levels, drainage around rooftop obstructions
(e.g., planter/stem walls and curbs, which
are plentiful on amenity roofs), and drainage
below pools/water features. We expand
on these concepts below.
8 8 • K a r r a s et . a l . B u i l d i n g E n v e l o p e T e c h n o l o g y S y m p o s i u m • No v e m be r 1 3 – 1 4 , 2 0 1 7
Figure 7 – Overbuilt deck waterproofing (above interstitial space).
Slope
We discussed code provisions related to slope
at the waterproofing membrane level(s) earlier in
this article. Additionally, membrane-level slope and drainage layers are
expounded upon by Greg Doelp and Phil Moser in their March 2009 RCI
Interface publication.3 Apply these requirements and guidelines at each
waterproofing level.
Drain Layout and Coordination with Walls/Curbs
The layout of drains on an amenity roof should endeavor to locate
at least one primary drain in each zone formed by an obstruction and
should provide an inverted pyramid slope configuration within each zone
for maximum slope in the valleys. Include provisions for secondary drainage,
such as scupper drains through planter walls and parapet walls,
during the drain layout exercise (Figure 8).
Given the cost associated with independently piped internal overflow
drains, many project design teams elect to utilize scuppers at the roof
perimeter to evacuate secondary drainage. Additionally, though one
drain in each primary zone is prudent, some amenity roofs include many
small zones formed by wall/curb obstructions, rendering this approach
impractical. With that said, if either primary drainage or secondary
drainage must pass through wall/curb obstructions, careful attention to
membrane-level drainage at the obstructions is required.
In the context of reinforced HRA and liquid-applied polymeric membranes,
the building enclosure consultant has two primary options to
consider with regard to coordinating drainage with wall/curb obstructions
above the structural deck. With the exception of the structural
basin walls of the pool (where the waterproofing should always extend
up and over the pool structure, high enough to pass above the water
B u i l d i n g E n v e l o p e T e c h n o l o g y S y m p o s i u m • No v e m be r 1 3 – 1 4 , 2 0 1 7 K a r r a s et . a l . • 8 9
Figure 8 – Primary
and secondary drain
layout exercise.
Figure 9 – Waterproofing over planter wall. Figure 10 – Waterproofing below planter wall.
line), fluid-applied waterproofing membranes
can extend up and over (Figure 9)
(when covered, as dictated by membrane
UV resistance or durability, or for aesthetic
reasons), or continuously below, wall/curb
obstructions (Figure 10). The authors often
prefer the Figure 10 approach for similar
reasons, as described above, for the structural
deck waterproofing strategy.
Within the Figure 10 approach, designers
then have two options for draining
water through the obstruction: Provide
continuous drainage composite below the
wall, or provide discrete knock-outs. In
both approaches, since the waterproofing
extends continuously below the wall, the
vertical reinforcing steel bars that engage
the wall to the structural deck must each
be individually flashed. That said, the
authors prefer the knock-out approach,
provided the knock-outs are coordinated
to avoid the rebar penetrations, since the
reliability of a rebar penetration flashing
encased in concrete is likely to outperform
rebar penetration flashings that are in a
drainage path.
Service Access to Drains
Water features and pools on amenity
roofs also warrant attention in the design
phase regarding placement of drains from
the standpoint of maintenance access.
Michael Phifer and Robert Holmer, in their
article published in the October 2016 RCI
Symposium on Building Envelope Technology
Proceedings,8 appropriately describe the
need for what they refer to as a structural
vault drain (also referred to by
specialty pool contractors as a condensation
drain) to evacuate water from the
waterproofing membrane level below the
pool shell. These drains should be located to
allow for access and maintenance, such as
through a cleanout pipe or a maintenance
hatch. Similarly, for rooftop water features
(e.g., water wall with an associated catch
basin), the authors recommend avoiding
locating the drain where it will be inaccessible
to maintenance personnel (e.g., below
an overbuilt cast-in-place concrete structure
for the feature).
CONVERTING EXISTING ROOFS TO
AMENITY PROGRAMMING
For repositioning projects, where designers
convert existing roofs into useable space
(Figures 11 and 12), greater flexibility and
creativity with roofing/waterproofing design
may be required. Designers must meet
the building code provisions for roof deck
strength, slope, and energy conservation
(among other requirements) while developing
a design that is durable and cost-effective.
Many roof deck repositioning projects
do not make it past the feasibility stage due
to these challenges. The projects that do
get implemented often do not incorporate
all of the best practices that are readily
achievable on new construction. Tapered
insulation or concrete build-up at adjacent
walls often limits slope, and new drains
may be required to reduce this build-up.
Furthermore, restrictions on the use of hotapplied
or odorous membranes can drive
selection of less durable systems. From
our experience, diligent coordination among
owners, prime designers, and subconsultants
(structural engineers, code consultants,
building envelope consultants, landscape
architects, and HVAC consultants) is
required to optimize the amenity features
on these types of conversions. For example,
9 0 • K a r r a s et . a l . B u i l d i n g E n v e l o p e T e c h n o l o g y S y m p o s i u m • No v e m be r 1 3 – 1 4 , 2 0 1 7
Figure 11 – Existing roof to be converted to useable space. Note the elevation of
the curtainwall relative to the surface of the pavers.
Figure 12 – Architectural rendering of reprogrammed roof space (the “cantina”
scheme). Image courtesy of CBT Architects.
heavy planters are often placed directly
above columns, or various tapered substrate
layouts must be considered alongside
overburden selection.
For these reroofing projects, where meeting
the minimum slope requirements for
new roofs would be overly burdensome for
the owner (e.g., replacing the roof with ¼ in.
per ft. slope would also require raising the
elevation of adjacent windows and throughwall
flashing), roofs may be designed and
built with “positive drainage.” The National
Roofing Contractors Association (NRCA)
defines positive drainage as the drainage
condition in which consideration has been
made during design for all loading deflections
of a deck, and additional roof slope
has been provided to ensure drainage of a
roof area within 48 hours following a rainfall
under conditions conducive to drying. Since
PRMAs used in amenity roof design are not
conducive to drying, the positive drainage
exception should not be used according
to the NRCA’s definition. However, in concept,
the positive drainage exception “holds
water.” Codes require minimum slopes to
compensate for finish tolerances, ponding
instability, and progressive deflection. If
these items can be evaluated for a particular
project, there is no reason why a roof
cannot drain adequately with a slope less
than ¼ in. per ft.
Designers should proceed with caution
when employing the positive drainage
exception. Missteps during the surveying,
analysis, and design process could easily
lead to ponding conditions that lead
to reduced durability and leakage (and
the other pitfalls associated with ponding
described above). As noted by the NRCA,
“providing for adequate roof drainage is the
most important consideration in designing
and installing quality, long-lasting, lowslope
membrane roof assemblies.”
WHAT’S NEXT?
As it stands today, amenity roofing/
waterproofing design is already a relatively
complex endeavor requiring specific expertise
in, and early/intricate collaboration
among, the design team. Still, the number
of relevant considerations continues to
increase as some jurisdictions roll out new
regulations related to stormwater retention,
green roof area, and other parameters that
affect amenity roof design. These relatively
progressive initiatives are currently limited
to select locations, but may expand to other
regions, especially cities with combined
storm/sewer systems. In parallel, building
codes (e.g., energy conservation, plumbing
drainage) continue to develop across the
country, with generally increasing stringency.
The well-informed designer can remain
at the forefront of these developments and
continue to play a central role in successful
implementation of amenity roofs.
REFERENCES
1. ANSI/SPRI RP4 2013, Wind Design
Standard for Ballasted Single-ply
Roofing Systems. Single Ply Roofing
Industry. 2013.
2. ANSI/SPRI RP14, Wind Design
Standard for Vegetative Roofing
Systems. Single Ply Roofing Industry.
2010.
3. G. Doelp and P. Moser. “Paving
Systems Over Plaza Waterproofing
Membranes: The Importance of
Membrane-Level Drainage.” RCI
Interface. RCI, Inc. March 2009. pp.
18-24.
4. J. Crandell and M. Fischer. “Winds
of Change: Resolving Roof Aggregate
Blow-Off.” Proceedings of the RCI
25th International Convention. RCI,
Inc. pp. 21-31.
5. J. Henshell. “Waterproofing Under
Green (Garden) Roofs Part 1 of 2.”
RCI Interface. RCI, Inc. January
2005. pp. 27-36.
6. Graham, M.S. “The Importance of
Proper Roof Slope.” Professional
Roofing. National Roofing Contractors
Association. March, 2005. p. 64.
7. M. Phifer and R. Holmer. “Everyone
Loves a Pool, but What’s Lurking
Beneath the Surface?” Proceedings
of the RCI Symposium on Building
Envelope Technology. RCI, Inc.
October 2016. pp. 45-54.