Skip to main content Skip to footer

Electronic Leak Detection Methods for Locating Leaks in Waterproofing Membranes

November 16, 2014

Electronic Leak Detection Methods for
Locating Leaks in Waterproofing Membranes
David Vokey, PEng
Detec Systems, LLC
1206 Northwind Circle, Bellingham, WA 98226
Phone: 360-961-9452 • E-mail: david.vokey@detecsystems.com
S y m p o s i u m o n B u i l d i n g E n v e l o p e T e c h n o l o g y • Oc t o be r 2 0 1 4 V o k e y • 1 5
AB STRA CT
This paper presents the new ASTM D7877 standard, which addresses the need for a
systematic procedure to test, verify, and monitor the integrity of waterproof membranes
using electronic conductance measurement methods to locate leaks in exposed or covered
waterproof membranes. The methods described are used on both conventional and protected
roofs and are particularly useful for roof designs that incorporate a waterproofing
membrane under a green roof, wear course, or topping slab, where direct inspection of the
roof membrane is difficult or impossible.
SPEA KER S
David Vokey, PE ng — Detec Systems, LLC
David Vokey, PEng, is a founder, president, and CEO of Detec Systems, LLC. He
graduated from the University of Manitoba with a BS degree in electrical engineering in
1973, and a master of engineering degree from the University of Manitoba in 1984. Prior to
cofounding Detec Systems, he worked for Siecor Corporation (now Corning Cable Systems)
as the manager of research and development, responsible for the design and development
of fiber optic cables. David holds over 35 patents worldwide relating to fiber optic cables
and moisture detection in building envelopes. He is a member of IEEE, RCI, ASTM, and of
the Association of Professional Engineers and Geoscientists in both British Columbia and
Manitoba.
1 6 • V o k e y S y m p o s i u m o n B u i l d i n g E n v e l o p e T e c h n o l o g y • Oc t o be r 2 0 1 4
BACKGROUND
Historically, architects and other
designers have often called for a flood
test to be carried out on horizontal waterproofing
systems when the membrane is
under a green roof, wear course, or topping
slab where direct inspection of the roof
membrane is difficult or impossible. ASTM
D5957, Standard Guide for Flood Testing
Horizontal Waterproofing Installations, is
typically referenced for the test. Flood
testing takes between 24 and 48 hours
and is often considered inconclusive; as a
result, the National Roofing Contractors
Association (NRCA) and the Canadian
Roofing Contractors Association (CRCA) do
not recommend conducting flood tests as
part of a routine qualitycontrol or quality
assurance program for a new roof system.
The first low-voltage electronic conductance
method to test waterproofing membranes
was developed in Europe in the early
1980s and were patented by H. Geesen. The
method, which is a derivation of a technique
used to locate cable sheath faults in buried
telephone cables, was subsequently called
electric field vector mapping. Several new
electronic leak detection (ELD) methods
have been developed in the past 20 years
or so, and they fall into two main categories:
low-voltage (48V or less) and highvoltage
(600V or more) conductance testing.
Although ELD testing has been in use for
several decades, no standard describing the
methods and limitations has been developed
to guide the industry.
INTRODUCTION
The new ASTM D7877 standard serves
as a guide describing current methods for
using electrical conductance testing procedures
to locate leaks in exposed or covered
waterproofing membranes. It addresses the
need for a systematic procedure to test
and verify the integrity of waterproofing
membranes; however, it is not intended to
replace visual, infrared, or other methods of
evaluation. It is to be used in conjunction
with other methods of roof inspection when
specified. The methods described include
testing procedures designed to provide an
important part of the quality control during
membrane installation.
ELD can be used on waterproofing
membranes installed on roofs, plaza decks,
pools, water features, covered reservoirs,
and other waterproofing applications. The
procedures are applicable for membranes
made of materials such as polyethylene,
polypropylene, polyvinyl chloride, bituminous
material, and other electrically insulating
materials.
While this guide provides a general
description of the equipment and methods
for locating membrane breaches using
electric conductance, it is important that
an operator refer to the manufacturer’s
instructions for the proper operation and
use of the equipment. It is also recommended
that the leak location equipment,
procedures, and survey parameters used
be calibrated to meet established minimum
leak detection sensitivity. The leak detection
sensitivity calibration should be verified on
a regular basis according to the manufacturer’s
recommendations.
The electric conductance methods
described in this guide require a conductive
substrate under the membrane to serve as
a ground return path for the test currents.
In roof assemblies where the membrane is
installed over an electric insulating material
such as insulating foam and/or a protection
board, the electric path to any conductive
deck is interrupted. This situation can be
remedied by placing a conductive surface
directly under the membrane. The conductive
surface provides
the return path for
the test currents.
SUMMARY OF
CONDUCTANCE
LEAK LOCATION
The leak location
methods in this guide
describe the electrical
conductance techniques
used to detect
and locate membrane
breaches. These methods—while accurate
and effective—are subject to certain noted
limitations. Electric conductance leak location
requires that the deck material directly
below the membrane be sufficiently conductive
for the test method employed. In
most instances, a concrete substrate is
sufficiently conductive to allow this method.
In certain membrane assemblies where the
substrate is nonconductive, it may be possible
to install a wire mesh or other conductive
layer directly under the membrane to
facilitate testing.
Application of the leak detection and
location methods in this guide, in conjunction
with construction quality control and
quality assurance programs, can provide
a higher level of confidence that the membrane
is leak-free. This quality control
process can minimize the risk of membrane
breaches during construction and leaks
during the service life of the membrane.
The principle of the conductance leak
location method is the establishment of an
electrical potential between the electrically
insulating waterproof membrane and the
underlying substrate.
For test methods employing a lowvoltage
electrical potential (48V or less),
a controlled covering of water on the surface
forms the conductive path horizontally
across the membrane to any membrane
breach (Figure 1). At a breach location, an
electrical path to the deck is formed through
the water leaking to the deck below. A sensitive
receiver detects the leakage current
and alerts the operator.
Electronic Leak Detection Methods for
Locating Leaks in Waterproofing Membranes
S y m p o s i u m o n B u i l d i n g E n v e l o p e T e c h n o l o g y • Oc t o be r 2 0 1 4 V o k e y • 1 7
Figure 1 – Basis circuit for low-voltage leak location method.
For test methods using a high voltage
potential (600V or more), an electrode is
swept across the surface of the membrane.
The electrode is charged to a high potential
relative to the deck below. At a breach location,
an electrical arc occurs from the electrode
to the deck below. The arc discharge
is electronically detected and the operator
alerted.
LOW-VOLTAGE HORIZONTAL
MEMBRANE SCANNING PLATFORM
The principle of the scanning platform
method is to establish a voltage potential
between the platform and the roof deck
and to track any leakage current passing
through the membrane. This is accomplished
by wetting the surface of the membrane,
applying a voltage with respect to the
deck, and then locating areas where electrical
current flows from the platform through
membrane breaches to the deck.
The basic circuit and application of a
dual sweep-scanning platform is shown
in Figure 2. The platform is constructed
with two sets of metal sweeps, which make
continuous electrical contact with the membrane
surface. The outer sweep forms a continuous
perimeter around the platform with
the inner sweep contained within the perimeter
of the outer sweep. The positive terminal
of the generator is attached to the building
electrical ground or the roof (concrete
or metal) deck/substrate, and the negative
terminal connects to the conductive sweep
of the platform through the measuring and
indicator unit. Since the majority of roofing/
waterproofing membranes are nonconductive
(excluding high-carbon, black-loaded
materials such as certain types of EPDM),
the electrical potential applied to the platform
sweeps provides a path through the
water over the wetted area of the membrane
to any breach, thus completing the circuit
to the substrate and back
to the generator.
During the membrane
scan (Figure 3), a light
spray of water is applied to the membrane
in front of the advancing platform. The outer
sweep responds to and displays any leakage
current in the test area.
The inner sweep, which is electrically
shielded by the outer sweep, will detect a
leakage current when the sweep platform is
directly over the membrane defect. This will
result in a noticeable deflection on the inner
sweep meter accompanied by an audible
alert. This is precisely the location where
moisture is penetrating the membrane.
Limitations – The conductance leak
locate method using the scanning platform
cannot be carried out on conductive membranes
such as EPDM. The deck material
directly below the membrane must be sufficiently
conductive for the purposes of this
test method (concrete decks typically meet
this criterion). Drains and other grounding
penetrations can cause a false reading if not
isolated from the applied water spray. See
the equipment manufacturer’s
instructions on avoiding
these unintended grounding
problems.
Note: Certain scanning
equipment designs provide
built-in isolation of the
sweep from drains and other
grounds, thereby minimizing
the potential for false readings.
LOW-VOLTAGE
HORIZONTAL
MEMBRANE ELECTRIC
FIELD VECTOR
MAPPING
The electric field vector
mapping technique employs an electric
potential gradient across the membrane
surface, along with a sensitive voltmeter
and probes to locate membrane leaks. As
illustrated in Figure 4, a conductor cable
loop is installed around the perimeter of
the area to be tested. A signal generator is
connected to the loop cable and the building
ground. The area within the loop is covered
with a spray of water to form a continuous
conductive surface in the test area. Since
most roofing/waterproofing membranes are
nonconductive, the electrical signal from
the perimeter cable loop looks for an electrical
path over the wet area of the roof to
any breach within the wetted area, thus
completing the circuit to the substrate. The
resulting current from the breach location
to the perimeter cable sets up a voltage
gradient in the water within the perimeter.
A sensitive voltmeter and a pair of handheld
electrical probes long enough to reach
1 8 • V o k e y S y m p o s i u m o n B u i l d i n g E n v e l o p e T e c h n o l o g y • Oc t o be r 2 0 1 4
Figure 2 – Basic circuit of the scanning platform.
Figure 4 – Basic circuit for electric field vector mapping.
Figure 3 – Membranescanning
platform.
the membrane surface are used to detect,
measure, and track the leakage current to
its source at the breach.
A signal generator is connected to the
building ground or concrete roof deck and
the perimeter cable that is placed around
the area to be tested. Metal penetrations
and drains must be isolated by looping
a separate cable around them and then
connecting these isolating cables to the
perimeter cable. The meter response is read
at an initial location within the perimeter
area, and the operator carefully moves the
pair of probes left or right while reading the
signal level (Figure 5) to the probe positions
that result in the maximum meter reading.
The probes are then repositioned towards
the indicated direction and the process is
repeated. The location of maximum signal
strength will coincide with the breach location.
Limitations – The proper operation of
the electric field vector mapping system
requires a continuous layer of water on the
membrane within
the test perimeter
and must
always reach
from any breach
to the conductor
cable. Gaps
in the water coverage
can result
in missed areas
and possibly
missed breaches.
This limitation
is particularly
apparent
on new, clean
m e m b r a n e s
where water beading occurs, thereby impeding
the formation of a continuous wet
surface. Protected waterproof membrane
roof systems covered with additional layers—
including insulation, root barriers,
and drainage mats—can interrupt the leaklocating
signal. These layers form an electrical
insulating layer that can interrupt the
locating signal or cause offset errors in the
leak’s identified position. Operator skill and
knowledge are important factors in obtaining
the accurate results.
LOW-VOLTAGE VERTICAL
MEMBRANE SURFACE SCANNING
Vertical surface leak location is a leak
testing and locating system that picks up
where horizontal scanning methods leave
off. The vertical test method provides leak
testing on vertical surfaces, corners, foundation
and parapet walls, seams, etc.,
ensuring that difficult-to-inspect details are
watertight.
As illustrated in Figure 5, the vertical
leak locate system employs a sensitive
receiver, water-moistened sensor, audible
alert, and ground lead. The receiver supplies
the power source referenced to ground
for testing the membrane integrity.
In operation, the moistened sensor,
which is connected through a cable to the
voltage source in the receiver, is pressed
against the surface under test. This action
forces water onto the membrane surface
and into any breaches. A leakage current
will flow from the ground connection
through the breach location, returning to
the receiver through the moistened sensor.
The receiver will register a deflection on
the signal level meter, accompanied by an
audible alert.
The vertical surface leak locator is used
to test the membrane integrity of corners,
parapet walls, and seams.
Limitations – The vertical surface leak
locating method cannot be carried out on
conductive membranes such as EPDM or
heavy carbon-black-loaded material. The
material directly underneath the membrane
must be sufficiently conductive for the purposes
of this test method.
HIGH-VOLTAGE MEMBRANE
TESTING
Unlike the low-voltage method, which
is carried out on a wet membrane, highvoltage
testing is performed on a dry horizontal
or vertical surface using a limited
current at relatively high voltage. One
lead from the portable current generator
is grounded to the roof deck (either metal
or concrete). The other lead is attached to
a special electrode brush made with conductive
metal bristles. The brush electrode
is then swept over the surface of the roof
S y m p o s i u m o n B u i l d i n g E n v e l o p e T e c h n o l o g y • Oc t o be r 2 0 1 4 V o k e y • 1 9
Figure 5 – Basic circuit of vertical surface scanner.
Figure 6 – Vertical scanning of membrane. Figure 7 – High-voltage scanning.
membrane (Figure 7). An electric arc will
jump from the electrode through any breach
in the membrane, thereby completing a circuit
between the brush and the roof deck.
Where there are no breaches, the membrane
acts as an insulator and prevents the flow of
current to the deck.
Using a voltage source of approximately
40 kV, a membrane up to a maximum thickness
of 26 mm can be tested. For the test to
be effective, the membrane must be adhered
to a conductive deck or have a conductive
backing.
Limitations – The test can only be
carried out on nonconductive roof membranes
that have a conductive substrate.
The surface must be dry when the testing
procedure is carried out. The thickness of
the waterproof membrane must be known
so that the test voltage can be calculated.
The operator must be isolated and protected
from the voltage source.
RECORDKEEPING AND REPORTING
Daily field notes should be written with
entries describing the areas scanned; the
number and location of any breach; and
weather conditions, date, and name of scan
operator. It is recommended that the field
notes include a plan view drawing of the
total area to be scanned. At the end of each
day, the scanned area should be marked on
this drawing with crosshatching or shading.
If the entire area to be scanned cannot
be completed in one day, the area scanned
each day should be identified on the membrane.
This identification should be made
with a clearly visible mark drawn on each
corner with a compatible marker.
The operator should copy and submit
daily field notes to the designated receiver.
The information on this document will be
transferred to a periodic field report for submittal
and storage.
A periodic field report should describe
the work performed, persons contacted on
the site, items discussed, and any additional
remarks. The report should include
the project information, weather conditions,
and date of the report and should be submitted
digitally by the end of the following
day.
The operator should maintain a breach
location and repair log that records a running
tally of the breaches located and
repaired. Information on this log should
include the breach identification numbers,
date located, date of repair, notes, and
square footage of area scanned.
CONCLUSIONS
Electronic leak locating methods for
locating breaches in waterproofing membranes
have been in use for several decades.
The new ASTM Standard D7877, Electronic
Leak Detection Methods for Locating Leaks in
Waterproof Membranes, provides a guideline
to the industry on the application and use
of ELD. In particular, it helps specification
writers to better understand the capabilities
and limitation of the various test methods
so that the most accurate results can be
realized in every case.
2 0 • V o k e y S y m p o s i u m o n B u i l d i n g E n v e l o p e T e c h n o l o g y • Oc t o be r 2 0 1 4