Metal Roofing from Aluminum to Zinc Part VII: Penetrations and Rooftop Equipment Mounting for Low-Slope Standing-Seam Metal Roofs

August 28, 2012

Standing-seam metal roofing
offers a durable, sustainable
alternative to other roof
types, with its ability to provide
maintenance-free service for
three or four decades. Sadly,
this long life span is often sabotaged with
the mounting of essential rooftop equipment
and ancillary mechanicals.
Regardless of the roof type involved,
consultants (this one included) generally
agree that the best way to prevent roofrelated
problems is to clear the rooftop of
everything possible and just let it function
as a roof—not a mechanical equipment
platform! Often, however, such a perfect
roof eludes us; and it becomes necessary
or convenient to mount HVAC equipment,
along with the screens to hide it, piping to
fuel it, scuttles to access it, and walkways
to service it. And then the list of rooftop
mountings goes on to include satellite dishes,
lightning protection, solar panels, advertising
signage, and fall protection systems
to maintain all of the above.
To help achieve relatively trouble-free
roofs, this segment endeavors to provide
some basic understanding of the dos and
don’ts in situations where rooftop equipment
mounting is unavoidable.
Penetration -Fr ee Attachm ent
A good first rule about any rooftop
mounting is to avoid penetrating the membrane
whenever possible. While this may
seem obvious, this tenet is often violated
with standing-seam metal. The norm for
attaching things seems to involve anchoring
the item to the structure through the roof.
When this happens, it not only threatens
weather integrity, but it also violates the
membrane’s thermal cycling behavior by
inadvertently “pinning” the panel to the
structure. Such a point of attachment
will fatigue and fail from forces of thermal
expansion within a short time. Fortunately,
scores of items and equipment can be
securely mounted to metal rooftops without
any penetration whatsoever, actually making
metal roofing more user-friendly than
other roof types.
In terms of mounting ancillaries,
metal roofing can make use of special
seam-clamping hardware that
grips the standing seam without
puncturing the membrane
(Figure 1). Unlike many other
types of roofing, metal is a rigid,
high-tensile material. The seam
area creates a beam-like structure
that can provide convenient
anchorage for walkways, solar
arrays, condensing units, gas piping,
and the like without harming
the roof’s weathering characteristics.
Mechanicals can be safely
and cost-effectively secured to
these seam clamps, leaving the
roof membrane penetration-free
(Figures 2 and 3). They provide
incredible holding strength (up
to several thousand pounds on
some profiles and gauges), last
the life of the roof, and preserve
thermal cycling characteristics. Using seam
clamps whenever possible will eliminate a
multitude of unwanted holes and unnecessary
problems.
Clamps should be made only of noncorrosive
metals—typically, aluminum with
stainless steel mounting hardware. These
metals are compatible with virtually anything
found on a metal roof, except copper.
In cases where a copper roof has been
specified, brass clamps should be used with
stainless steel hardware.
The clamps should be attached to seams
with round-point setscrews to prevent galling
or other damage that can lead to corrosion.
It is also important to remember any
1 4 • I n t e rf a c e A u g u s t 2 0 1 2
Editor’s Note: This is the seventh and final article in a series about metal roofing in today’s market. The series provides an in-depth look at
materials and their uses, coatings, system designs, and installation techniques. It is reprinted with the permission of metalmag.
Figure 1 – This illustration shows a profile of clamping
hardware affixed to standing-seam metal.
loads introduced into the clamp
will be transferred to the panels
and their anchorage to the structure.
Consequently, anchorage
must be capable of withstanding
the added load.
Mountin g
HVAC With
Structura l
Curbs
In the case
of HVAC and
plumbing vents,
the roof membrane
must
often be penetrated,
so the
aforementioned
“good first rule”
simply does
not apply. The
soil stack must
carry gases from
the interior to
the exterior,
and the HVAC
unit must either
transfer inside
air out, outside air in, or both.
In these situations, holes in the roof
are unavoidable, and the challenge is to
waterproof the penetration area while maintaining
thermal cycling integrity. There are
a few rules about handling these kinds of
rooftop penetrations in low-slope standingseam
metal that can help ensure a troublefree
installation.
Most small, bottom-ducted HVAC units
are curb-mounted, using a preformed
structural equipment curb specially manufactured
to integrate with the specific
roof profile (Figure 4). This curb carries the
unit’s weight, seals to the roof, and maintains
the system’s thermal cycling integrity.
It is important to engage a company specializing
in manufacturing curbs for the metal
roofing industry. (These companies can
usually be identified by the metal roofing
manufacturer.)
The best curb is an all-welded design
using sheet aluminum at least 2 mm (0.08
in.) thick (not coated carbon steel). Sheet
steel does not weld well in thin gauges, and
it heat-warps when welded. Additionally,
the protective Galvalume™ coating must be
burned off at welds and cannot be suitably
restored. Aluminum welds exceptionally well
and does not heat-warp because of its low
A u g u s t 2 0 1 2 I n t e rf a c e • 1 5
Figure 2 – Seam clamps have made rooftop
mounting so simple and cost-effective that
metal roofing is now the preferred roof type for
mounting photovoltaic solar arrays. Close-up
of PV panels with shadow (close-up view of
clamp attachment is inset to lower left corner).
Figure 3 – Seam clamps allow
even cumbersome ancillary items
to be attached to metal roofs
without penetrating the rooftop.
melting temperature. It is very compatible
with sheet steels used for roofing and can
provide decades of trouble-free service when
correctly designed, fabricated, and installed.
Common mistakes include dropping roof
equipment curb scope-of-work into HVAC or
sheet metal sections of the specification.
Although this may be prudent practice with
other roof types, it is not so with metal. With
limited exception, HVAC and sheet metal
contractors do not understand principles of
rooftop waterproofing, nor do they understand
thermal movement characteristics
of standing-seam metal roofing. The result
can be design and installation that either
violates thermal cycling issues, weatherproofing
issues, or both. Installation that
“pins” the curb flange through the roof and
into the structure is a common faux pas,
and the use of surface-applied sealants that
are ineffective for long-term performance is
also a frequent malpractice.
Another common mistake is selecting a
curb/flashing design that may be appropriate
for steep-slope metal roofing with underlayment
(water-shedding or hydrokinetic
design), but is not at all appropriate for
low-slope, hydrostatic (watertight design)
metal roofing. A suggested practice is to
insist that the roof manufacturer approve
all rooftop attachments, penetrations, and
appurtenances—curbs included. The manufacturer
should know the type of curb that
is compatible with his system. And when
long-term weathertightness warranties are
specified, they should include all rooftop
attachments and penetrations—especially
curbs.
The curb design should provide that the
curb flange underlays the roof panels at
the upslope end and overlays them at the
downslope end (no “back-water” laps). This
is normally accomplished by terminating the
curb’s side flanges by marrying them into a
panel seam at either side. The curb walls
are built up to a minimum height of 152
mm (6 in.) and flanged at the top to provide
an adequate structural mounting surface
for the equipment. The sides are also beveled
to compensate for the roof slope and to
provide for level
mounting of the
unit. The 6-in.
minimum height
provides that
the mechanical
unit’s interface to
the curb is well
above the drainage
plane of the
roof and, therefore,
more forgiving
of installation
error on the part
of the mechanical
contractor when
waterproofing the
equipment to the
curb.
As this type of
structural curb is “floating” (i.e., moves
thermally with the roof), there are weight
constraints. These curbs can accommodate
units weighing up to about 454 kg (1000 lb.)
placed anywhere on the roof—even heavier
units, if located near the roof’s point of fixity
where movement is minimal. They are
ordered from a manufacturer for a predetermined
roof location, specific roof type,
and by equipment model number (or in lieu
thereof, exact equipment dimensions).
Installation details sealing the panels
to the curb at its upslope end are similar
to the details used to seal the roof panels
at their eave end. They involve tape and/or
tube-grade butyl concealed within the joints
and metal closure components, depending
on the panel’s rib geometry. All details are
hydrostatic in nature. Panel ribs are terminated
well upslope of the curb wall to
allow easy drainage to the sides of the curb.
Upslope curb flange dimensions must provide
for this.
At the downslope joint, the curb flange
mates over the flat plane of the roof panels.
Rib caps furnished loose or welded integrally
into the curb flange serve to terminate the
panel seams. This is again accomplished
with butyl tape and tube seals concealed
within the joints. The downslope joint thus
created is normally reinforced beneath the
assembly with a “backup” plate or channel.
The side flanges are likewise sealed to
the roof panels with butyl inside the mating
components. All joints are completely
hydrostatic with concealed sealants.
Other substructural components may
be employed to facilitate the installation,
and this type of curb is often furnished with
1 6 • I n t e rf a c e A u g u s t 2 0 1 2
Figure 4 – Preformed structural curbs support weight and seal tightly to the roof.
Figure 5 – Frame-mounted HVAC unit using pipe supports extending
down to the building structure and flashed through the roof using
rubber pipe flashings.
board stock insulation mounted to the curb
walls. Installation of all critical seals (especially
those at seam interfaces) is of paramount
importance, and fasteners must be
to the “dry” side of sealant beads or through
them. It is also important that such a curb
and its components are fastened together
without pinning to the building structure.
The resulting assembly is free to move
thermally with roof panels, while sealing
completely into the roof “bathtub style,”
in lay terms, or, in accordance with ASTM
International E2140, Standard Test Method
for Water Penetration of Metal Roof Panel
Systems by Static Water Pressure Head,
in more technical terms. Diverters should
be used on the upslope flange of the curb,
and whenever possible, the unit should be
oriented so the smallest dimension opposes
the flow of water (e.g., if a unit is 1 x 1.5 m
[3 x 5 ft.], the 1.5-m dimension should be
parallel to the slope of the roof).
Fram e-Mount ed HVAC
When it is necessary to mount heavier
equipment, the unit is sometimes kept
above the roof on a galvanized steel frame.
The frame is constructed using round pipe
legs so that they can be flashed with rubber
pipe flashings (Figure 5). These legs extend
through the roof to supporting structural
members below. Such a mounting is stationary—
that is to say, there will be differential
movement between the frame and
the roof.
Depending on the unit’s weight, the support
frame can also be mounted on seam
clamps to avoid pipe penetrations through
the roof (Figure 6). The ribs of structural
metal panels normally support point loads
of at least 68 kg (150 lb.), and ASTM standards
for structural standing-seam roofing
require this. In other words, a unit weighing
680 kg (1500 lb.) and spanning five panel
A u g u s t 2 0 1 2 I n t e rf a c e • 1 7
Figure 6 – Frame-mounted HVAC units using seam clamps that avoid roof penetration.
American Hydrotech’s Garden Roof® Assembly has set the standard by which all other
green roofs are measured. Our Total Assembly Warranty provides owners with single source
responsibility from the deck up. This is peace of mind that only American Hydrotech can offer.
To learn more about the American Hydrotech Garden Roof Assembly, please call 800.877.6125
or visit us online at www.hydrotechusa.com.
The key to our
Garden Roof® is our
Monolithic Membrane
6125®, a seamless
rubberized asphalt
membrane with a 45+
year track record for
critical waterproofing
and roofing applications
world-wide.
From concept to completion
American Hydrotech, Inc. | 303 East Ohio | Chicago, IL 60611 | 800.877.6125 | www.hydrotechusa.com
© 2012 Garden Roof is a registered trademark of American Hydrotech, Inc.
The Soliare – New York, NY
RCI-Solaire-VPL-halfpage.indd 1 2/10/12 12:34 PM
seams can be mounted this way, resulting
in ten bearing points on the five seams.
When ducting a frame-mounted unit
through the roof, it is always advisable to
use the smallest hole possible. That is to
say, a very large unit may only require a
very small duct penetration. A small curb
of the same type described earlier is used
to waterproof the ducted hole(s) in the roof.
In this case, the curb need not be structural,
as it supports no weight, but acts
as a flashing only around the duct passing
through the roof. The curb style is the same
in all other respects.
If the unit is mounted on a stationary
frame, the curb must be slightly larger than
the actual duct size to allow differential
thermal movement between the two. If the
unit is mounted to seam clamps, then this
is unnecessary as the unit and curb move
together in tandem.
Doub le curbs
When larger HVAC equipment size and
weight are involved, the unit is frequently
mounted on a structural curb, which is
integral to the building’s structural framing
system. When such a design is employed,
a second “flashing curb” is used for waterproofing
reasons. The concept here is that
the first curb (or frame) supports the weight
of the unit, and the second does the waterproofing
and integrates into the roof system.
In this case, there is differential movement
between the two, so the outer “flashing
curb” is oversized to the first, and a
counterflashing of either metal or flexible
membrane is married to the unit to shed
water over the outer curb. The outer curb
is of the same design and material as previously
described. Again, it need not be
as heavy-gauge, as it supports no weight.
Installation details of the outer (flashing)
curb connection to the roof are also the
same as previously described with hydrostatic
seals. Because there is differential
movement, the joining of the counterflashing
is sometimes done with hydrokinetic
(water-shedding) details. This is acceptable
because the joint is sufficiently above the
drainage plane of the roof. Alternatively,
hydrostatic detailing can also be performed
when flexible membrane flashings are used.
The following advice applies to all the
curbs described above:
• All-welded, aluminum curb construction
should be used.
• Curbs must be equipped with diverters
on the upslope flange.
• Upslope curb flanges should underlay
roof panels.
• Lower curb flanges should overlay
roof panels.
• Curb walls should be a minimum of
152 mm (6 in.) in height.
• Curb and installation should be
“floating” (i.e., not pinned to the
building structure).
• All seals should be accomplished
with butyl tape/tube grade within
the joints (not exposed sealants),
with careful attention to marry seals
at panel seams.
• Curb sidewalls should occur a minimum
of 6 in. from the nearest adjacent
seam location to allow sufficient
drainage to the sides of curbs.
• Roof and structural manufacturers
should be kept “in the loop” for
weather integrity and structuralsupport
adequacy issues.
A u g u s t 2 0 1 2 I n t e rf a c e • 1 9
Roxul® is committed to providing the most sustainable
commercial roofing insulation in North America and is pleased
to have third-party certification of our products recycled content for
our Milton facility, completed by ICC-ES SAVE™. As part of that commitment,
our stone wool insulation is made from a high percentage of recycled materials which
helps contribute to LEED® points. All Roxul products produced in the Milton facility contain a
minimum of 75% and are available with up to 93% recycled content.
In addition to its environmental advantages, Roxul stone wool insulation has a long term stable
R-value, is dimensionally stable, fire resistant, water repellent, non-corrosive, sound absorbent
and will not promote mold and fungi growth.
ROXUL® on
the Roof
The Next Generation in Roofing Insulation
ICC-ES SAVE ™ C ERT IF IED
REC YCLED C O N TE NT*
75%
* M i lton F a c il it y
Roun d Penetrations
Round shapes, such as plumbing vents,
should be flashed through the roof using
ethylene propylene diene monomer (EPDM)
rubber pipe flashings (Figure 7). Although
these parts are widely available in various
colors, black has the greatest ultraviolet
(UV) resistance and, hence, the longest life.
Standard installation is to cut an undersized
hole and stretch-fit the rubber to the
pipe. Using a stainless steel draw band at
the top of the flashing to further secure it
will ensure the flashing never inverts itself
and will typically add about five years of life
to the assembly. The part has an integral
aluminum compression ring laminated to
the rubber base, which should be sealed to
the roof panel using butyl copolymer tape. It
should then be secured using #14 x 22-mm
(7/8-in.) “lap-tek” screws with #1 drill point
at 51-mm (2-in.) centers through the compression
ring, rubber, and butyl and into
the metal panel.
Ideally, excess
butyl tape should
be trimmed away
and a bead of
one-part polyurethane
sealant filleted
around the
joint thus created
(base to roof). This
bead hides and
protects the butyl
from direct exposure
to sunlight,
ensuring a longer
life. After a service
life of 25 years or
so, this assembly
is easily replaced.
When attaching the pipe flashing, it
must be anchored to the roof panel only and
not to the building structure or deck. To do
so would create an inadvertent “pinning” of
the panel, violating its freedom of thermal
movement. Ideally, these flashings should
be centrally located on the roof panel so
there is free drainage to both sides without
seam interruption.
If the location of the pipe interrupts
a seam and it cannot be relocated, a preformed
adapter plate can be fabricated to
span both panels adjacent to the seam and
the pipe flashed per the above directions to
the adapter plate. Most companies that premanufacture
curbs will make such adapter
plates on request.
When installing pipe flashing, the following
advice is applicable:
• Use unitized black EPDM rubber
pipe flashings.
• When possible, the pipe flashing
should be centrally located in the
roof panel.
• Stainless steel draw bands should
be employed.
• After butyl tape has been used
beneath the base, fillet with one-part
polyurethane.
• The pipe flashing should never be
pinned to the structure or deck.
Conc lusion
Rooftop mountings and penetrations are
a challenge for any roof type or material.
Following these simple guidelines can help
ensure trouble-free and enduring performance
for a state-of-the-art low-slope metal
roof system.
2 0 • I n t e rf a c e A u g u s t 2 0 1 2
Rob Haddock is president of the Metal Roof Advisory Group,
Ltd., and a well-recognized authority on metal roofing.
He is a consultant, technical writer, training curriculum
author, inventor, and educator. Haddock is a member of
NRCA, ASTM, ASCE, ASHRAE, MBCEA, and MCA. He has
been a course author and instructor of RCI classes and a
course instructor for the University of Wisconsin School of
Engineering. He is a past recipient of RCI’s Horowitz Award.
Rob Haddock
Figure 7
Interface’s technical articles are reviewed by a seasoned peer committee of professionals from the membership of RCI. Members
and industry professionals are urged to contribute articles for Interface. Following is a schedule of the journal’s upcoming theme
issues. Articles on any topic, however, are encouraged at any time.
For information on how to submit an article or possible changes in schedule, contact Director of Publications Kristen
Ammerman by phone at 800-828-1902 or via e-mail to kammerman@rci-online.org.
Write for Interface
Issue Theme Peer Review Deadline
November 2012 Forensics August 15, 2012
December 2012 International Roofing September 15, 2012
January 2013 Steep-Sloped Roofing October 15, 2012
February 2013 Hail November 15, 2012