Skip to main content Skip to footer

Parapets: The Critical Juncture Between Roofs and Walls

August 11, 2020

The parapet is so much more than the intersection of roof and wall. It is also the junction where building aesthetics meet structural performance, air and moisture management, energy efficiency, construction trade sequencing, and operational maintenance.
Each of these perspectives is critical for the long-term performance of the building, but they are often at odds with one another. At such a critical interface, proper parapet detailing, installation coordination, and execution are paramount. Continuity of water, air, thermal, and vapor control layers are necessary for long-term performance.
TYPES OF PARAPETS
Parapets can be assembled in many configurations, and each requires project-
specific detailing. The 2018 International Building Code (IBC) defines a parapet as “the part of any wall entirely above the roofline.”1
To simplify the discussion a bit, this article will look at a baseline flush edge condition and two primary parapet types—platform-
framed and balloon-framed—defined by how the roof and wall structure are connected.
Parapets can generally be composed of structural materials, such as wood framing, light-gauge metal framing, pre-
engineered steel, concrete, or masonry. In this context, the terms “platform-framed” and “balloon-framed” are referring to the configuration of the wall and roof structure to form a parapet. These terms are applied to parapets throughout this article, based on the parapet configuration and are inclusive of all materials comprising the assembly (see Figure 1).
The flush-edge roof-to-wall connection
is the simplest approach, with the roof structure placed above the wall system.
10 • IIBEC Interface A August 2020
Parapet assemblies include numerous components and accessories. This often results in complicated interfaces—even before reviewing design-specific conditions. (Photo courtesy of GAF.)
Figure 1 – Flush-edge roof-to-wall connection and two parapet configurations.
Compared with the platform- or balloon-
framed parapets, the flush-edge configuration provides the least wind uplift protection for the system at the roof edge, and the most limited aesthetic options.
Platform-framed parapets are similar to flush-edge construction, with the roof structure sitting directly on the wall system, with a parapet wall assembly on top of the roof structure.
In this configuration, the roof structure acts as a platform for the parapet wall above. Depending on the attachment method, height, and materials of the parapet wall, additional lateral and/or wind-bracing strategies may be needed for this type of parapet.
Balloon-framed parapets are formed when the wall system bypasses the roof system to form a wall that extends above the roofline. In this configuration, the roof structure is commonly hung from the wall structure or supported by a separate superstructure inside the wall system.
CONTROL LAYER CONTINUITY
To better understand common parapet design challenges, it is important to review the continuity (or lack thereof) across the roof and wall systems, specifically the four key control layers: water, air, thermal, and vapor.
These four key control layers should generally be continuous across all six sides of the building enclosure. ASTM E2947, Standard Guide for Building Enclosure Commissioning, defines the term “building enclosure” to “refer collectively to materials, components, systems, and assemblies intended to provide shelter and environmental separation between interior and exterior, or between two or more environmentally distinct interior spaces in a building or structure.”2
It is difficult, but not impossible, to achieve effective control layer continuity across building systems—especially at significant transitions, such as a parapet, where the roof system meets the wall system.
For more complex scenarios, such as parapets, there are simple design tools to connect the control layers as they transition from the wall to the roof. The “pen test,” which traces each of the control layers across the building enclosure (Figure 2), is a helpful tool to design and communicate to the field the intent of the continuity of the critical components and functions of the building enclosure.3
WATER CONTROL
Keeping water out of buildings is a function of both roofs and walls, so it is reasonable to assume parapets should do the same.
Wall systems commonly include a secondary water management layer behind the exterior cladding (see Figure 3). For instance, it is important to protect the top of the wall assembly with a membrane below the parapet cap, sealing fastener penetrations for coping cap cleats, and lapping over the wall’s secondary water management layer in shingle fashion.
Construction-related moisture, installation deficiencies, and damage during ongoing building operations can introduce moisture into the roof and wall systems. Construction acceptance testing, scheduled inspections, and regular maintenance play an important role in ensuring the systems are able to meet their intended performance over time.
A
ugust 2020 IIBEC InterfaceCE • 11
Figure 2 – An example of air control “pen test” continuity across the building enclosure.
Figure 4 – Water control elements are highlighted in blue in this parapet continuity example.
Figure 3 – Water control diagram for flush roof edge (left), platform-framed parapet (center), and balloon-framed parapet (right).
Figure 4 shows an example of a platform-
framed parapet and the individual components to be considered. In a parapet condition, it starts with managing the flow of water on the parapet coping cap, which is sloped back to the roof system; this also helps prevent staining on the exterior wall.
Where the roof membrane meets the parapet wall, the membrane should be installed to allow for the possibility of differential movement and terminated with flashing/counterflashing, under an appropriate transition membrane under the coping cap.
AIR CONTROL
Most buildings require a continuous air barrier. If one thinks of a building as a solid 3-D shape, like a cube, then the air barrier must be continuously detailed across all six sides of the building enclosure to be effective.4
To achieve continuity, the air control layer requires much more than selecting a material or specifying a lab-rated assembly. Across the various roof edge and parapet conditions, there are many common and alternative approaches to continue air barrier design (see Figure 5).
In addition, air control discontinuities in parapets can lead to water ingress, impact occupant comfort, waste energy from loss of conditioned air, and cause damage from significant condensation moisture and movement of airborne contaminants through the building enclosure.
The amount of moisture transported through the building enclosure via an air leakage pathway at normal interior-to-exterior pressure differences is many times greater than the amount of water vapor that can pass through a permeable material due to vapor diffusion alone. When it comes to the air control layer, parapets are among the most challenging areas to get right.
Roof membranes are generally good at blocking airflow. However, unless they are designed to be part of the continuous air barrier system and tied into the other five sides, the building will still leak air.
For low-slope roof systems, it can be beneficial to design the primary air control layer as the roof deck or applied to the topside of the roof deck.
An example of this would be air-sealing the penetrations to a concrete roof deck or installing a dedicated membrane to the roof deck prior to installing insulation. Clearly identifying and communicating the air control layer in the roof system simplifies detailing at penetrations and transitioning at the parapet.
Installing an air barrier after the parapet wall is in place is also difficult to get right. It requires significant coordination among trades to install the air control layer up and around the parapet wall, transition to the coping cap flashing, and terminate to the wall system air control on the other side of the wall.
One alternative is to connect the air control layer from the roof side of the wall to the exterior wall by insulating within the wall cavity with a closed-cell spray foam (see Figure 6).
While this may be the “fussiest” option with regard to blocking, trade coordination, and use of specialty trades, in some cases, such as balloon-framed light-gauge stud walls, it may be the best (or only) option.
The case of a flush-edge design is fairly straightforward: Maintain continuity of the air control layer—either over or under the roof edge blocking—and terminate over the wall air barrier system.
When the parapet wall is built on top of the roof deck, as in a platform-framed parapet, it gets a bit trickier (see Figure 7). The best option for continuity is to “strip-in” the air barrier to the roof deck before framing the parapet wall above the roof deck.
Though the strip-in method is preferred as a way of keeping conditioned air out of the parapet, it requires significant trade coordination and is not often implemented in the field.
To accomplish it successfully, the
12 • IIBEC InterfaceCE A August 2020
Figure 5 – Air control diagram for flush roof edge (left), platform-framed parapet (center), and balloon-framed parapet (right).
Figure 6 – Air control elements highlighted in red across the parapet cavity.
Figure 7 – Air barrier “strip-in” example with platform-framed parapet.
stripped-in portion of the air barrier should be installed with excess material on either side of the roof edge. The parapet wall would then be framed on top of the roof deck and the excess stripped-in membrane connected to the air control materials on the wall and at the roof deck.
THERMAL CONTROL
Maintaining continuity of the insulation layer (especially the continuous exterior insulation) across the parapet is important to achieve the intended energy performance and to prevent moisture condensation on cold surfaces.
In current IECC5 and ASHRAE 90.16 national model commercial energy codes, the basic prescriptive requirements for both walls and roof systems include the use of continuous insulation in many climate zones and construction types.
Continuous insulation is far more effective than cavity insulation, which is tucked into the voids between framing members. In parapets, the framing members are exposed to exterior conditions on both sides of the wall, rendering cavity insulation highly ineffective.
Across the flush roof edge and parapets, maintaining continuity of the “continuous insulation” can be difficult. Even with continuous insulation designed in the roof and wall systems, a common thermal discontinuity emerges where the roof system meets the backside of the parapet wall (see Figure 8). These discontinuities are important because they represent thermal bridges in the thermal control layer.
For the flush-edge condition, the thermal
discontinuity primarily results from the intersection of roof edge blocking for terminating the roof system and wall cladding at the transition. The compactness of this detail makes it difficult to simply add insulation.
Roof edge blocking is commonly a solid wood material, which has a much lower thermal conductivity than steel. Roof framing members over the wall below should be covered by the continuous insulation from the wall system below. That is, don’t stop the continuous insulation short of roof framing edge conditions!
For platform-framed and balloon-framed parapets, the strategies for maintaining the thermal control layer may be specific to the wall-framing material that extends past the roof.
For walls composed of concrete, insulated precast, masonry, or steel framing, the best
Figure 8 – Thermal control diagram for flush roof edge (left), platform-framed parapet (center), and balloon-framed parapet (right).
A
ugust 2020 IIBEC InterfaceCE • 13
Piping on roofs constantly moves, which can result in roof damage. Wood or rubber blocks used as pipe supports don’t allow pipe movement. The solution? MAPA engineered rooftop pipe supports. They help prevent roof abrasion and add years to the life of a roof. www.mapaproducts.comInnovative rooftop supports since 1998Severe damage to roof and pipe due to the use of wood blocks. PIPE PLACED HERE PROTECTS ROOFS.
approach may be to go up and over the wall with continuous insulation (see Figure 9).
In this case, continuous insulation is applied to the roof side of the parapet wall, under the coping blocking at the top of the wall and connected to the continuous insulation on the exterior wall. However, if the parapet walls are of the tall cavity type, this may not be ideal. Although insulated, the two-sided exposure and limited conditioning of the air via the HVAC system in the cavity space within the parapet could still lead to condensation moisture on cold surfaces (see Figure 10).
Another strategy that is better suited for wood-framed and very tall steel-framed walls is to effectively, but not literally, extend the roof thermal control layer through the backside of the parapet cavity wall and connect on the other side to the exterior wall continuous insulation (similar to Figure 6).
This is also similar to the technique described in the air control section, using closed-cell spray foam to connect the control layer from the roof side of the wall to the exterior wall within the wall cavity.
As stated previously, this may still be the “fussiest” option. It is, however, well suited for wood-framed walls where thermal bridging is less pronounced than steel framing, and with tall steel-framed cavities where even continuously insulated, air-
controlled parapets can result in condensation due to their exposure and isolation from the regular interior space conditioning.
It is important to note that when insulating across the parapet wall cavity, air-
permeable insulation like fiber batts is not effective. If interior air can bypass or travel through the insulation, it can still lead to condensation and moisture problems in the parapet above the air-permeable insulation.
VAPOR CONTROL
The primary function of a dedicated vapor control layer is to prevent condensation that results from vapor diffusion. Vapor diffusion occurs when water molecules in the air (vapor) pass through a solid material due to a vapor pressure differential (high to low) on either side of the material.
Vapor diffusion through a solid material—even a vapor-permeable one—is a slow process. There are specific scenarios where enough vapor is able to diffuse through a solid material (not carried along by air leakage) to result in significant moisture accumulation over time. For example, consider all the moisture that can potentially accumulate in a roof system as a concrete roof slab cures.
When it comes to vapor control, it is also possible to cause moisture problems by adding a vapor-impermeable material to an assembly—intentionally or unintentionally.
All materials, from insulation to membranes, air barriers, sheet metal, sheathing boards, paint, adhesives, and so on, have some level of vapor-retarding properties.
Not all wall, roof, and parapet scenarios
require a vapor control layer. In fact, adding a vapor barrier to a design can lead to unintended moisture problems, such as preventing an assembly from drying from incidental moisture.
14 • IIBEC InterfaceCE A August 2020
Figure 10 – Looking up inside a balloon-framed parapet with condensation at the top of parapet from interior conditions. (Image adapted from the U.S. Environmental Protection Agency – Moisture Control Guidance for Building Design, Construction and Maintenance.)
Figure 11 – Vapor control diagram for flush roof edge (left), platform-framed parapet (center), and balloon-framed parapet (right).
Figure 12 – Example of initial concrete roof deck moisture.
Figure 9 – Example of thermal control continuity within the parapet.
Often when vapor control is discussed,
the conversation quickly slips into “air
control” strategies to manage condensationrelated
issues, as air movement can transport
up to many times more moisture than
vapor diffusion alone.
Vapor-retarding materials (and vaporpermeable
materials) often also act as air
barriers, and they can be incorporated
into the continuous air barrier design. As
designing and installing continuous air barriers
becomes required in most buildings,
the confusion regarding air barriers and
vapor retarders still exists.
For parapets and roof systems in general,
one of the more challenging vapor
control scenarios involves newly placed or
“green” concrete roof decks (see Figure 12).
Significant initial moisture within the concrete
will diffuse into the lower vapor pressure
areas in the rest of the roof system or
interior space over a potentially long time.
If the concrete is placed on a steel
composite deck and cannot dry downward
through the steel, then moisture in
the concrete will drive to the exterior
(upward) through the roof system,
wetting the roof system along the
way.
One common strategy is to install
a Class I or lower vapor retarder on
the top surface of the concrete deck
to prevent the moisture from rising.
However, a self-adhered vaporretarding
material will not always
stick to high-moisture concrete.7
If a vapor barrier is to be installed
above the composite concrete deck,
a vented steel composite deck may
be somewhat helpful as a means to
provide a path for downward drying
of the concrete, but this is not a
definitive solution. Alternatively, an
above-deck vapor retarder that allows
horizontal movement of moisture with
perimeter venting (for example, insulating
lightweight concrete roof design)
may also be beneficial.8
COMPLEXITY IS COMMON
Parapet assemblies include numerous
components and accessories. That
often results in complicated interfaces—
even before reviewing design-specific
conditions (see Figure 13).
Critical detail locations are often
difficult to illustrate on 2-D drawings
alone and can require exploded
diagrams and/or sequence information
to communicate the design intent.
Additional complexity is common for parapets
at the following locations:
• Parapet wall terminating into an
adjacent building wall
• Height or material changes of the
parapet wall
• Parapet with cladding on both sides
of the wall system
• Eave and soffit conditions extending
past the exterior wall face
• Curtainwalls extending beyond the
roofline
• Inside/outside corners of parapet
walls
• Scuppers and other penetrations
Using the skills of a building enclosure
professional and selecting products with
details and field support to assist in maintaining
the four key control layers (water,
air, thermal, and vapor) is critical to achieving
the optimal performance of the building
enclosure.
Figure 13 – Common complexity at parapet-to-wall
interface.
Figure 14 – End wall not assembled by the framing
contractor at parapet termination.
one third page.indd 1 7/10/2020 2:16:26 PM
A u g u s t 2 0 2 0 I I B E C I n t e r f a ce • 1 5
COORDINATION IS KEY
The project design and details should consider construction sequencing, access, and replacement across the expected life of the building. The framing contractor, for example, should be allowed to complete the construction of the primary framing before beginning the installation of the air barrier components (see Figure 14).
Sequencing the work of different trades makes it easier to coordinate air barrier installation. Sometimes it is necessary for one trade to pause one phase of work in order to pre-treat a critical interface before proceeding (e.g., “pre-stripping” the roof joint at a platform-framed parapet wall).9
Early, clear, and frequent communication helps to keep everyone on the same page. The following are best practices for enabling communication among the owner, general contractor, trade contractor, architect, building enclosure professional, and performance testing agency.
Prior to Construction
•Meet with the design team, contractor, and affected sub-trades to discuss control layer continuity strategy and details.
•Affirm the expected service life of thebuilding and systems installed inconjunction with the control layers.
•Make final material selections andconfirm compatibility of substratesand accessories across roof and wallsystems.
•Confirm requirements for manufacturer warranties and/or guaranteesacross wall and roof systems.
•Confirm sequencing and mobilization expectations across trades. Whogoes first? Who has to come back?
•Discuss the quality control andquality assurance procedures duringinstallation.
•Prepare mock-up(s) demonstratingthe parapet details.
During Construction
•Ensure weather and overnight protection during onsite parapet assembly.
•Consult product literature prior to useof all roof and wall products to ensureinstructions are followed at parapets.
•Install control layer pre-stripping,blocking, and accessories, as required, at penetrations, details, and interfaces to maintain continuity.
•Minimize “blind” attachment throughexterior finishes into the structureand sheathing.
•Involve manufacturer or certifiedprofessionals, as required, to establish warranty and/or guaranteerequirements.
•Notify enclosure professionals whenair barrier details are ready for review.
•Perform qualitative and/or quantitative testing to verify water andair control performance and identifyair leakage locations; document anyresulting design changes.
After Occupancy
•Document and communicate criticalcontinuity details for maintenanceand replacement in the future.
— This includes methods for maintaining air barrier continuity upon replacement when the roof membrane is designed as part of the continuous air barrier, and/or conditions where “hidden” elements such as closed-cell spray foam in the parapet assembly are integral to the performance of future replacements.
•Perform, schedule, and documentregular inspections, maintenance,and repairs of the parapet conditions.
In closing, the continuity of water, air, thermal, and vapor control layers is necessary for long-term performance, and the oft-neglected parapet wall plays a central role in air and moisture management.
ENDNOTES
1.International Code Council. 2018International Energy ConservationCode. ICC, November, 2017.
2.ASTM International. E2947-16a Standard Guide for BuildingEnclosure Commissioning. WestConshohocken, PA; ASTMInternational, 2016. doi: https://doi.org/10.1520/E2947-16A
3.U.S. Environmental ProtectionAgency. Moisture Control Guidancefor Building Design, Constructionand Maintenance. EPA 402-F-13053,December 2013. www.epa.gov/iaq/moisture
4.ANSI/ASHRAE/IES. ANSI/ASHRAE/IES, Energy Standard for Buildings Except Low-Rise Residential Buildings. ANSI/ASHRAE/IES, 2019.
5.ICC. op. cit.
6.ANSI/ASHRAE. op. cit.
7.H.H. Pierce and J.P. Crowe.“Structural Concrete Decks,Vapor Retarders, and Moisture –Rethinking What We know.” IIBECInterface. February 2020. pp. 26–30.
8.Ibid.
9.BC Housing. Illustrated Guide–Achieving Airtight Buildings.September 2017.
16 • IIBEC InterfaceCE A August 2020
Benjamin Meyer is a roofing and building science architect with GAF, Parsippany, NJ. Meyer serves as a member of the LEED Technical Committee, a member of the ASHRAE 90.1 Envelope and Project Committees,and a director of the Air Barrier Association of America (ABAA).
Benjamin Meyer
BNP Media has announced that it will hereafter focus exclusively on digital delivery of its content for Roofing Contractor magazine. The June 2020 issue of the magazine, first published in 1981, was its last print edition. The company noted its decision was accelerated due to the COVID-19 pandemic.
Roofing Contractor Goes All Digital