Skip to main content Skip to footer

Post-Installation Field Evaluation of a Pressure-Equalized Single-Ply Roofing System to Determine Drying Effects on a Moist, Cementitious, Roof Deck

August 1, 1999

Post-Installation Field Evaluation of a Pressure-Equalized Single-Ply Roofing System to Determine Drying Effects on a Moist, Cementitious, Roof Deck

 

A consulting assignment
allowed evaluation of
moisture content within
the lightweight insulating fill on a
high-rise commercial building, both
before and after roof membrane
removal and replacement using a
single-ply thermoset roofing system
installed in a proprietary pressureequalized
configuration. This type of
roof system was selected due to the
anticipated wind loads this building
would be exposed to, as well as the
fact that the manufacturer claims wet
insulation can be dried out using this
type of installation. A nondestructive
nuclear moisture survey was performed
prior to the original roof
removal, the roof system was then
replaced, and the pressureequalization
valves were allowed to
function for approximately a year.
After about twelve months, another
nuclear moisture survey was performed,
and the moisture content of
the lightweight insulating fill was
evaluated for a second time. This
paper presents the results of this
post-installation roof evaluation and
compares the moisture contents of
the lightweight insulating fill material
both before and after any drying
effects that may have occurred due
to removal of the built-up roof and
application of the pressureequalized
membrane. An attempt is
made to analyze and quantify the
changes in moisture contents
observed, and appropriate comments
regarding the effectiveness of
this type of design for the stated purpose
have been derived.
POST-INSTALLATION
FIELD EVALUATION
Of a Pressure-Equalized Single-Ply Roofing
System to Determine Drying Effects on a
Moist, Cementitious, Roof Deck
By Warren R. French, P.E., RRC, CCS
INTRODUCTION
Moisture in Roofing Insulations
The detrimental effect of the presence of moisture on roofing systems is well known.
These effects include physical deterioration of the membrane, reduced service life, and a
significant reduction in thermal performance of the insulation layer. In addition,
entrapped moisture can cause corrosion of metal roof decks, structural steel framing, and
fastening systems, as well as corrosion of steel reinforcing within concrete roof decks
which can result in spalling and scaling. Accordingly, it has been a generally recognized
axiom that roofing materials should not be installed over moist substrates, and if roofing
materials become significantly wet after installation, they should be removed and
replaced. The real issue, however, has always been “how wet is wet?” and whether or not
a wet roofing material (e.g., insulation) could be dried out.
Nondestructive Roof Moisture Surveys
The use of Nondestructive Testing (NDT) methods for determining moisture in
roofing systems has been well established for a number of years. A great deal of research
has been done regarding the use and methodology of such moisture surveys, as well as
the limitations of each method. The three methods historically utilized in the United
States have primarily consisted of infrared thermography, nuclear moisture surveys, and
capacitance. It is beyond the scope of this article to discuss in depth the differences
among these methods, nor is it deemed necessary to describe in detail the procedures
for each type of survey. However, it should be understood that thermography uses an
infrared imaging device to “read” areas on the roof where thermal anomalies exist. The
survey of these thermal anomalies is performed across the roof, and the anomalies are
generally assumed to be areas of wet insulation due to the lower thermal resistance
(greater heat conductivity) of wet insulation as compared to dry materials. By contrast,
nuclear methods and capacitance methods utilize individual meter readings at discreet
locations across the roof area, which is usually laid out in a grid spacing from 5 to 10
feet in both directions. The nuclear meter relies upon well-established principles of
physics pertaining to the behavior of “fast” neutrons, particularly in an environment with
abundant hydrogen, while the capacitance meter works by measuring the relative
strength of an electric field as it passes through the roofing materials, with the assumption
that there will be greater electrical conductivity in a wet insulation as compared to
dry materials.
Nuclear Radioisotope Method
This study utilized nuclear radioisotope methods exclusively for both moisture surveys.
Confirming cores of the lightweight insulating fill materials were extracted, subjected
to gravimetric testing, and used to correlate the direct meter readings to actual
August 1999 Interface • 3

60 66 58 64 51 56 46 41 39 36 41 58 59 61 63
MAX = 78 MIN = 9 MEAN = 46 STD. DEV. = 15
Figure 1
moisture contents. Correlation results were
extrapolated for meter readings occurring
between the survey points. For each survey, an
appropriate statistical analysis of the survey data
was performed in accordance with the manufacturers
recommended procedure, as well as in
keeping with recognized industry standards
(RCI, 1986). The moisture survey data, correlations,
statistical analysis, and graphic representation
of these results are generally provided by
the use of graphs and a map of the roof surface,
which typically depicts contours of the measured
moisture content. See Figures 2, 5, 7 and 10.
This article presents the results from both surveys
conducted in 1997 and 1998, and refers to
both in this manner.
It should be noted that an attempt was made
to utilize the same grid spacing and configuration
for both surveys. In addition, cores were
extracted contemporaneously with each survey
at essentially a common low meter reading, a
high meter reading, and a reading occurring
generally in the middle of the two extremes.
Gravimetric analysis involves determining the
actual moisture content of the sample by weighing
the sample and drying in a laboratory oven
until a
MOISTURE CONTENT EXTRAPOLATION -1997

constant weight is reached. With this
1997 DATA HISTOGRAM
1997 MOISTURE CONTENT CORRELATION
information, the moisture content of the sample
may be derived as a percentage of dry weight,
and used in the correlation to extrapolate
results to the entire roof.
Description of Project
The structure that became the subject of
this study is a 43-story high-rise office building
in Houston, Texas which was originally constructed
in 1961 with a built-up roof system
installed at the main roof level, as well as on a
15,760 s.f. mechanical penthouse above the
main roof. The building footprint is a simple
rectangle, and approximate heights of the main
roof and penthouse roof above the surrounding
grade are 587′ and 602′, respectively. In addition,
the main roof consists of approximately 13,400 s.f. and is
somewhat protected by a four foot high parapet,- however,
perimeters of the penthouse roof terminate into a metal edge condition
on all four sides. The main roof was originally installed
over a 3/4″-thick fiberglass insulation, while the penthouse roof
had been applied over a layer of l”-thick wood fiber insulation,
installed over a vapor retarder applied directly to the cementitious
lightweight insulating fill. The fill ranged in depth from approximately
8″ at roof perimeters to 4″ at interior drains.
As with many high-rise buildings, implementation of the roof
renovation project presented a number of design and construction
logistics challenges. The latter included limited access, negligible
staging locations, constraints imposed by building occupancy and
management, and the physical aspects of mobilizing manpower
and material from the ground to roof level.
Although this building is located in an urban area, it is on the
4 • Interface August 1999
Left: Lotver roof prior to re-roof
Reloiv Lipper roof after renovation.
southern edge of the downtown district and is fully exposed to
the predominant southerly winds common to this locale.
Accordingly, the surrounding buildings provide virtually no
“shielding” of the wind forces to which this building is exposed.
Further, being a coastal environment (approximately 45 miles
from the coast of the Gulf of Mexico), the building has been,
and would continue to be, periodically subjected to hurricaneforce
winds also originating from the Texas Gulf Coast. The roof
systems on this building had experienced over 35 years of exposure
and deterioration, which prompted the owner to initiate
replacement by commissioning the services of a roof consultant.
An abbreviated investigation and analysis consisted of a visual
survey on both levels and a nondestructive roof moisture survey
using nuclear thermalization techniques on the penthouse
roof. The results of the original study revealed that the lightweight
insulating fill on the penthouse level had incurred significant
amounts of moisture throughout most of its surface, which
extended down to the concrete deck. Moisture contents of the
lightweight fill varied considerably over the roof surface but generally
ranged between 8% and 24% of dry weight. The wood
fiber insulation at this level was also significantly wet with moisture
contents ranging up to 600% by dry weight. Since separate
cores and gravimetric analyses were performed for both the
wood fiber and lightweight insulating fill, it was believed that
the survey produced acceptable results in both situations,
although meter readings were undoubtedly skewed by the presence
of the extremely wet organic insulation.
Purpose of Study
The purpose of this study was to conduct an independent,
objective evaluation of the potential drying effect occurring
within the lightweight insulating fill on a pressure-equalized, single-
ply roofing system and to assess observed drying rates (if
possible).
It should be noted that the author entered into this study
slightly dubious that any significant drying would take place
within the cementitious deck of this roof system. For at least 14
years, I have considered the work done by Wayne Tobiasson at
the U.S. Army Corps of Engineers, Cold Regions Engineering
Laboratory, to be the most definitive work conducted in this area
August 1999 Interface • 5
1997 MOISTURE CONTOURS tractors to competitively bid
the work. Upon selection of a
contractor and award of the
re-roofing contract, our firm
also provided contract administration
services, project management,
and periodic on-site
inspections of the work.
As previously stated, a
pressure-equalized (P.E.),
single-ply membrane roof system
was selected primarily for
its proven track record with
respect to the ability of this
system to resist high wind
uplift. This feature was given
high priority due to the expo-
(Tobiasson, 1983). The basic conclusions of Tobiasson’s study
were that very little drying was achievable, whether by one-way
vents, two-way vents, perimeter-edge venting, or mechanical
ventilation. Where drying was observed, the typical drying rates
were so slow as to be negligible when compared to the anticipated
service life of the roofing materials.
In the absence of contradictory data, we had taken this
research to be “gospel” for the purposes of our consulting practice.
However, it came to my attention that the manufacturer of
the proprietary, pressure-equalized roof design had recently
made claims that its roofing assembly was exhibiting a certain
amount of success in drying out wet insulation. Due to the special
requirements of this roof system with respect to wind, as
well as the complications provided by the wet lightweight, we
believed it would be worthwhile to take advantage of the potential
benefits arising from this possibility. With the well established
principles of the pressure-equalized design to resist roof
membrane blow-off without fasteners, it was felt that any drying
that might be accomplished would essentially be an unanticipated
“bonus” for this roof system.
PROCEDURES AND CHRONOLOGY
Initial Evaluation
The initial study of this roof system and the associated
nuclear moisture survey conducted in early 1997 were performed
as part of the normal consulting services provided by our firm for
a large international oil and gas company. The subject building
represents a significant regional office for this company and has
been a Houston landmark for over 30 years, since it was, when
constructed, the tallest building in Houston. The roof moisture
survey was conducted in accordance with generally recognized
industry standards and the analysis was presented to the building
owner in order to assist in the re-roof decision. The information
obtained from the original survey was also utilized during the
design and detailing of the proposed replacement roof system.
Construction Documents and Bidding
Subsequent to the initial evaluation, French Engineering was
authorized to develop construction documents for the proposed
replacement roof system, and to coordinate with qualified consure
of this roof (with no parapet)
and in consideration of the hurricane-force winds to which
this location could periodically be subjected. Furthermore, an
additional design imposed was the ability to resist the anticipated
wind uplift using minimal fasteners, which the P.E. system
also accommodates since it is essentially “loose-laid” and depends
upon the pressure-equalization vents to create a negative pressure
(suction) between the roof deck and the underside of the
membrane. The desire to eliminate fasteners, or at least minimize
them, was due to our recommendation to the owner to retain the
lightweight fill, and recognition of the fact that fasteners
installed through chronically wet materials would be subject to
accelerated corrosion.
As might be expected, the building owner had expressed
great aversion to removing the damp, lightweight, insulating fill
during design review
meetings. In addition,
the sheer logistical
problems of removing
an estimated 2,775
cubic feet (42 tons
damp weight) of lightweight
fill from a fairly
inaccessible roof area
located 600 feet in the
air were daunting. Also,
unless an exteriormounted
construction
elevator was erected,
all of the debris would
have to be transported
by hand through a
mechanical enclosure,
down a stairwell for
two floors, then down
the service elevator to
the loading dock of
this fully-operational
building. This, in fact,
was the route taken for
MOISTURE GAGE DIRECT READINGS -1998
ABODE
9 14 12 17 19
15 12 16 14 14
18 18 16 15 11
22 23 13 22 16
20 25 20 18 18
25 23 18 14 17
24 19 17 13 14
20 17 16 9 12
17 14 13 12 11
17 14 17 10 11
14 9 14 12 11
16 10 11 11 18
12 9 11 12 9
15 14 13 9 8
15 12 16 16 12
17 14 12 17 17
19 14 16 14 15
17 14 14 16 13
19 12 14 14 14
25 13 14 11 ‘ 12
17 12 14 13 12
16 11 11 11 11
16 9 10 10 10
16 11 10 10 12
16 11 12 11 12
16 12 12 13 14
16 11 9 11 12
18 10 10 9 11
14 10 10 11 10
16 13 10 14 11
17 10 17 20 13
16 13 15 21 21
15 10 13 17 13
15 11 18 26 27
16 12 27 27 26
12 9 23 25
15 12 18 22 22
16 12 12 17 27
15 12 10 14 22
17 12 12 16 19
16 18 18 15 16
F O H I J
19 17 19 17 14
19 12 13 11 10
18 14 14 10 10
20 13 12 11 12
19 12 12 10 10
20 12 11 8 10
16 12 11 8 8
11 11 12 9 10
14 11 12 9 9
13 11 10 10 11
9 11 9 7 7
9 11 11 13 11
8 14 14 15 12
12 12 17 17 11
14 17 20 18 14
7 12 18 10 10
12 10 10 10 11
16 13 14 9 10
15 11 12 11 9
12 11 14 11 12
10 12 13 14 12
11 11 11 10 12
12 11 12 10 12
10 12 12 13 12
11 12 14 11 14
12 11 13 9 12
11 10 11 11 10
8 10 12 14 11
11 11 11 10 10
11 14 14 11 15
13 15 17 14 15
15 14 14 14 13
17 19 12 13 13
27 19 16 14 10
21 19 13 13
21 18 12 12
21 18 14 14
22 18 15 17
22 15 19 17
18 21 17 18 12
21 22 22 20 21
K L M N O
14 16 15 15 12
12 12 11 15 14
10 8 11 9 13
10 12 11 11 16
11 11 11 10 12
11 8 8 8 12
10 10 10 12 15
10 9 10 16 15
9 11 12 13 15
12 13 14 12 17
10 11 10 10 17
13 12 11 9 15
13 15 13 11 12
10 11 9 11 18
8 12 12 11 20
10 10 10 12 16
8 11 11 16 20
11 13 12 13 20
10 12 12 12 15
12 13 15 12 19
14 16 12 12 21
13 17 12 11 18
11 14 14 12 18
12 13 13 15 19
13 14 14 15 18
12 14 14 14 19
14 12 15 16 19
13 11 12 16 17
13 9 11 12 18
13 13 11 16 18
15 11 12 13 19
14 10 11 14 17
15 15 14 12 15
12 17 15 14 18
16 16 11 16 19
16 14 14 10 17
15 15 16 12 17
19 22 17 14 19
17 20 13 12 19
15 13 11 13 20
21 20 17 19 15
MAX = 27 MIN = 7 MEAN = 14 STD. DEV. = 3.7
6 • Interface
removal of the original
built-up membrane and Figure 6
August 1999
insulation, but removal of the lightweight insulating fill would
have increased the volume of the demolition debris by at least
sixfold. Further, the demolition, which would have unavoidably
required the use of jackhammers, would have taken place over,
and in close proximity to, an exclusive restaurant and club that
serves executives in the oil industry. Both of these prospects
were unacceptable to the building owner, and they were not
completely amenable to the long-term aesthetic problem of having
a construction elevator attached to the outside of the building.
So, based upon the limited maintenance traffic occurring on
the upper roof level, the overall height of this building, and its
exposure to anticipated wind forces, as well as the roof renovation
logistical problems, the roof system selected for the
mechanical penthouse was a 60-mil, ethylene propylene diene
monomer (EPDM) membrane installed in a proprietary, pressureequalized
design configuration.
This type of assembly avoided installation of fasteners into
the lightweight fill, where concerns related to corrosion and adequacy
of uplift resistance would be a problem. In addition, this
particular membrane vendor had claimed success in drying out
wet insulation using the pressure equalized design and was one
of the few suppliers willing to warrant its roof installation over a
damp substrate. As a design choice, it was decided not to install
the roof in a recover assembly, so the original built-up roof
membrane and all wood fiber insulation were removed down to
the lightweight insulating fill in order to promote drying of the
roof deck material.
Although the mopped vapor retarder was not fully removed,
no efforts were made during the tear-off to protect this membrane.
The contractor, in fact, was instructed to deliberately disturb
the felt plies comprising this membrane before installing the
loose-laid, siliconized gypsum sheathing board with fiberglass
facers over which the P.E. single-ply membrane was ultimately
installed. In keeping with the manufacturer’s requirements, the
sheathing and insulation were mechanically fastened for about
four feet around the roof perimeter, and the EPDM membrane
was fully adhered in this area (approximately 14% of the total),
while being loose-laid in the field of the roof.
1998 DATA HISTOGRAM
Figure 7
Figure 8
August 1999 Interface • 7
MOISTURE CONTENT EXTRAPOLATION – 1998
A B C D E
7 16 12 20 23
18 12 19 16 16
21 21 19 18 11
26 28 14 26 19
24 30 24 21 21
30 28 21 16 20
29 23 20 14 16
24 20 19 7 12
20 16 14 12 11
20 16 20 9 11
16 7 16 12 11
19 9 11 11 21
12 7 11 12 7
18 16 14 7 5
18 12 19 19 12
20 16 12 20 20
23 16 19 16 18
20 16 16 19 14
23 12 16 16 16
30 14 16 11 12
20 12 16 14 12
19 11 11 11 11
19 7 9 9 9
19 11 9 9 12
19 11 12 11 12
19 12 12 14 16
19 11 7 11 12
21 9 9 7 11
16 9 9 11 9
19 14 9 16 11
20 9 20 24 14
19 14 18 25 25
18 9 14 14
18 11 21 33
19 12 33 31 31
12 7 28 33 30
18 12 21 26 26
19 12 12 20 33
18 12 9 16 26
20 12 12 19 23
19 21 21 18 19
F G H I J
23 20 23 20 16
23 12 14 11 9
21 16 16 9 9
24 14 12 11 12
23 12 12 9 9
24 12 11 5 9
19 12 11 5 5
11 11 12 7 9
16 11 12 7 7
14 11 9 9 11
7 11 7 5 5
7 11 11 14 11
5 16 16 18 12
12 12 20 20 11
16 20 24 21 16
5 12 21 9 9
12 9 9 9 11
19 14 16 7 9
18 11 12 11 7
12 11 16 11 12
9 12 14 16 12
11 11 11 9 12
12 11 12 9 12
9 12 12 14 12
11 12 16 11 16
12 11 14 7 12
11 9 11 11 9
5 9 12 16 11
11 11 11 9 9
11 16 16 11 18
14 18 20 16 18
18 16 16 16 14
20 23 12 14 14
33 23 19 16 9
25 23 14 14
25 21 12 12
25 21 16 16
26 21 18 20
26 18 23 20
21 25 20 21 12
25 26 26 24 25
MAX = 33 MIN 4.7 MEAN = 15
K L M N O
16 19 18 18 12
12 12 11 18 16
9 5 11 7 14
9 12 11 11 19
11 11 11 9 12
11 5 5 5 12
9 9 9 12 18
9 7 9 19 18
7 11 12 14 18
12 14 16 12 20
9 11 9 9 20
14 12 11 7 18
14 18 14 11 12
9 11 7 11 21
5 12 12 11 24
9 9 9 12 19
5 11 11 19 24
11 14 12 14 24
9 12 12 12 18
12 14 18 12 23
16 19 12 12 25
14 20 12 11 21
11 16 16 12 21
12 14 14 18 23
14 16 16 18 21
12 16 16 16 23
16 12 18 19 23
14 11 12 19 20
14 7 11 12 21
14 14 11 19 21
18 11 12 14 23
16 9 11 16 20
18 18 16 12 18
12 20 18 16 21
19 19 11 19 23
19 16 16 9 20
18 18 19 12 20
23 26 20 16 23
20 24 14 12 23
18 14 11 14 24
25 24 20 23 18
STD. DEV. = 5.6
Figure 9
Tear-off and
Installation
The roof tear-off
and installation of the
new roof began in
September 1997 and
continued through
March 1998. The
upper penthouse roof
was replaced first,
with substantial completion
of the pressure-
equalized EPDM
membrane by the end
of October 1997. The
remainder of the construction
schedule was
utilized to replace the
main roof (which is
subject to heavy maintenance
traffic and
window washing
equipment) using a
hybrid built-up/modified
bitumen roofing
system. In addition,
other work included in the contract scope was installation of the
various sheet metal details, application of a Hypalon® coating on
the EPDM, minor concrete repairs, application of an elastomeric
coating on the plaster surfaces of the main roof parapet, and
application of a urethane deck coating on an exposed concrete
stair and at other locations.
Post-Construction Evaluation
The second roof moisture survey on the upper penthouse
roof of this project was conducted in November 1998, approximately
13 months after installation had been complete. Once
again, the survey was conducted in accordance with generally
recognized industry standards and the appropriate statistical
analysis was performed. Three additional roof cores were taken
at areas of low, medium, and high meter readings obtained from
the nuclear moisture meter during the survey in order to confirm
the survey results.
The lightweight insulating fill on this roof was subjected to
gravimetric testing to determine actual moisture content, and a
similar correlation was derived for the remainder of the data so
the moisture content could be extrapolated over the entire roof
area. There was no attempt to extract samples during this survey
(1998) from the exact locations where gravimetric samples had
been taken during the initial (1997) survey, since it was anticipated
the gravimetric correlation and extrapolation would provide
adequate comparisons for the majority of the roof.
Local Weather Subsequent to Installation
In order to provide a complete evaluation of the P.E. roof
system performance with respect to drying, we believe it is pertinent
to discuss briefly the local weather that occurred in the
Houston area subsequent to installation of the replacement roof.
Obviously, it would be anticipated that a similar roof located in
Phoenix, Arizona would behave differently (or else exhibit different
drying characteristics) than an identical roof located in
Seattle, Washington, simply due to the disparity between these
two climates with respect to ambient temperature, air humidity,
water vapor pressures, etc. Accordingly, it is pertinent to point
out that we believe the conditions in Houston for the twelvemonth
period following installation of the P.E. roof system were
excellent for achieving a good drying rate, if in fact that phenomenon
is achievable.
During the first quarter of 1998, Houston experienced a winter
that was rather mild but otherwise unremarkable with respect
to temperature, humidity, and rainfall. However, it should be
noted that Houston, and indeed all of Texas, suffered a significant
period of drought from about April through August of
1998. In addition, the state recorded a record heat wave, with
the City of Dallas reporting over 25 straight days of daily high
temperatures above 100 degrees. While the temperatures in
Houston were not as dramatic, the city also experienced a long,
very dry, very hot summer. This pattern was finally broken in the
fall, when, once in September and again in October, there was
heavy rainfall and local flooding. Both of these rainfall events
were related to the arrival of tropical storms but were not associated
with hurricane activity. The remainder of the year returned
to a more “normal” weather pattern. The point of this discussion
is that during the prime period for anticipated drying of the P.E.
roof system (i.e., the summer months), conditions in Houston
could not have been better from a weather and environmental
standpoint.
TEST RESULTS AND COMPARISONS
1997 Moisture Survey
As previously stated, the 1997 roof moisture survey indicated
that the original wood fiber insulation was saturated, with a large
majority of the roof area exhibiting moisture contents in excess
of 30% and ranging as high as 600% by weight. Previous studies
indicate that wood fiber insulation can exhibit a moisture content
of up to 580% when subjected to immersion (Anderson,
1985), which correlated well with our results. In contrast, based
upon our study, the moisture content of the lightweight insulating
fill was significantly lower than the wood fiber, with most of
the roof area (86%) exhibiting moisture contents below 25%.
(Reference Figures 1 through 5.)
The 1997 study consisted of 608 data points. The minimum
moisture content measured for the lightweight insulating fill was
3.4%, with a maximum moisture content of 43% by weight. The
mean moisture content throughout the readings of the entire
roof was 16%, with a standard deviation of 8%. Anderson has
previously reported that lightweight insulating fill can exhibit a
moisture content of up to 110% when subjected to immersion
(1985). In our opinion, the differences in moisture contents
between the wood fiber and lightweight insulating fill during the
1997 survey are due to the relative densities and absorption
properties of these two materials, as well as the fact that the
vapor retarder may have served as a water barrier between the
wood fiber and the lightweight fill, restricting the amount of
water actually getting into the cementitious layer.
8 • Interface August 1999
1998 Moisture Survey
The 1998 roof moisture survey
also consisted of 608 data
points and indicated extremely
consistent conditions within
the gypsum sheathing layer of
the new roof. Although the
moisture content of these materials
was slightly elevated (with
moisture contents ranging
between 17.8% and 18.2% by
weight), the integrity of the
water-resistant sheathing had
not been adversely affected. In
addition, although no isocyanurate
insulation samples were
extracted, moisture probes
using a Delmhorst meter indicated no significant moisture in that
roofing layer either. However, the lightweight insulating fill still
exhibited moisture contents ranging from 4.7% to 33%. The
mean moisture content throughout the readings of the entire
roof was 15%, with a standard deviation of 5.6%. (Reference
Figures 6 through 10.)
Comparisons and Contrasts
After a year of in situ performance, it is significant to point
out that the maximum moisture content measured within the
lightweight insulating fill, by extrapolation of the nuclear moisture
meter readings and correlation with the gravimetric analysis
of confirming cores, had actually been decreased by ten percentage
points by weight (representing an overall reduction of 23%).
However, the mean moisture content was reduced by only 1 %
by weight (a reduction of about 6%). Nevertheless, the standard
deviation had been reduced from 8% to 5.6% (a 30% change).
From this data, it would be possible to conclude, at first blush,
that a respectable amount of drying had taken place during the
study period. However, an attempt was made to evaluate the
drying rate of this roof at individual grid points. This further
analysis yielded some unanticipated and rather surprising results!
Based upon a comparison of our two surveys, it was noted
that 289 data points (48%) had decreased in moisture content
from 1997 to 1998. However, using our field data on this roof, it
was noted that 318 data points (52%) in the 1998 survey exhibited
an increase in moisture content when compared to the 1997
survey. (See Figure 11.) Only one data point exhibited the same
extrapolated moisture content for both surveys, which is statistically
insignificant. A visual comparison of the two histograms
developed for the data from each survey indicates that the 1998
data is very consistent and, in our experience, represents an
extremely good correlation between the actual meter readings
obtained and the standard distribution (bell curve) expected for
this type of survey. See Figures 2 and 7. The histograms are obviously
different, but it is suggested that the 1997 data would be
naturally “skewed” by the saturated wood fiber insulation layer
that previously existed on top of the lightweight fill. In our
experience, the 1997 data are consistent with a roof that exhibits
wet insulation, with numerous data points lying outside the standard
distribution curve.
Further comparison of the data from both surveys indicated
that of the 289 points exhibiting a decreased moisture content,
the average decrease (or change) at individual grid points was
August 1999 Interface • 9
97/98 DIFFERENCES
DRYING WETTING
about 32%. By contrast, for those 318 points exhibiting an
increase in moisture content, the average increase (or overall
change) at each individual grid point was about 61%. So, essentially,
it could be said that individual grid point locations on
about half of the roof area increased in moisture content and did
so by about twice the amount that the other half of the roof
decreased. The cause of this observed anomaly is not known but
it is somewhat instructive to tabulate the data points with respect
to the various ranges, or breakdowns, of moisture contents utilized
to draw the moisture contour maps for each survey.
Although the break-down divisions are completely arbitrary,
using identical breakdowns for both surveys allows a direct
graphical comparison of the moisture contours within the roof as
determined by the two surveys. In addition, tabulating these data
points allows another measure of the changes exhibited by the
lightweight insulating fill material. (Reference Table 1.)
Table 1: Comparison of Data Point Changes
M.C. Range 1997 Survey’ 1998 Survey1 Group Change2
>36% 2% 0% 2% Decrease
26% to 35% 12% 4% 8% Decrease
12% to 25% 40% 66% 26% Increase
0% to 11% 46% 30% 16% Decrease
Note 1: Percentage of total data points with moisture contents in specific ranges
Note 2: Percentage of total data points changing within each specific range
As may be observed in the table above, the number of data
points occurring in the two moisture content ranges that were
most “wet” decreased in both the highest and next-to-highest
range. The number of data points occurring in the lowest, or
most “dry” range also decreased significantly,- however, the number
of data points occurring in the next-to-lowest range overwhelmingly
increased. Of the 608 data points, 158 more points
(401 total) exhibited moisture contents between 12% and 25%
by weight in the second survey as compared to the first survey.
According to this analysis, there appeared to be a “centralizing”
of a great majority of the data points toward a moisture content
range that was on the lower (drier) end of the scale, with the
“most dry” points becoming slightly more damp and the “most
wet” points becoming significantly drier.
A final evaluation of the two studies indicates that the 1998
survey exhibited apparent “drying” of specific areas such that the
one-way pressure-equalization vents tended to be within or on
the edge of the closest drying area. Sixteen of the eighteen P.E.
vents installed on this roof (89%), when located on the contour
map showing change of moisture contents at specific data points,
occur adjacent to or within an area exhibiting drying. In our
opinion, this is a fairly strong correlation between the location
of these vents and the drying observed on this roof.
CONCLUSIONS
Based upon this study, it appeared that the overall moisture
content of the lightweight insulating fill at this project had been
slightly lowered (about 1%) after removal of the old built-up
roof and installation of the pressure-equalized single-ply roofing
membrane.
In addition, the upper extreme range of moisture contents
occurring within these materials appeared to have been reduced
from 43% to 33%. Where the previous study indicated 14% of
the total roof area exhibited moisture contents greater than 25%
by weight, the second study indicated only 4% of the total roof
area exhibited moisture contents greater than 25%. Based upon
the evaluation of this one building, it cannot be stated with confidence
whether the apparent drying was due to the P.E. membrane
installation or simply due to the removal of the saturated
wood fiber layer that had previously overlain the lightweight fill.
However, it cannot be denied that the overall patterns and levels
of moisture content within the lightweight had “changed” and
the apparent change was positive with respect to the amount of
moisture observed.
10 • Interface August 1999
As has been previously noted, about half of the data points
exhibited an increase in moisture content, with the average
increase being about 61% of the original moisture content. In
addition, about half of the data points exhibited a decrease in
moisture content, with the average decrease being about 32% of
the original moisture content. It should be noted, however, that
assuming a dry weight of 26 pounds per cubic foot, a 32%
reduction of moisture for a lightweight sample originally having
40% moisture content by weight represents a greater amount of
total water (about 3.3 Ibsm. H2O) than a 61% increase of a sample
originally having 10% moisture content by weight (about 1.6
Ibsm. H2O).
It was further observed from the differences among our data
for each survey that the wettest areas of the roof became drier
and the driest areas of the roof generally became wetter, such
that the lower middle range of moisture readings significantly
increased in quantity overall. In fact, the number of data points
exhibiting moisture contents between 12% and 25% by weight
increased from less than half the roof area (40%) to virtually
two-thirds (66%) of the total roof area. This fact appears to indicate
a “centralization” or “uniformity” effect for the moisture contents
of this roof system. Accordingly, the patterns of drying and
the amount of moisture actually removed from the roof appears
to be the result of a very complex process that is not easily categorized
by this one example, and does not behave in a linear
fashion at any particular point on the roof.
Based upon this study, we would deem the results for this one
roof to be essentially_”inconclusive” with respect to determining
once and for all: (a) whether significant drying may be induced
from moist lightweight insulating fill using a P.E. membrane configuration,-
and (b) what drying rate might be anticipated by this
type of design. The reasons for the variability of these results
may be due to a number of factors, including one or more of the
following:
1. Perhaps one year is an insufficient length of time to satisfactorily
observe the drying phenomenon desired.
2. Perhaps roofs with lightweight insulating fill installed
over a structural concrete (unvented) roof deck
are not good candidates for the drying efforts
claimed by the manufacturer for the P.E. roof
membranes.
3. Perhaps other types of roof insulations (organic
or plastic foam) would lend themselves better
to the drying effects claimed.
4. The absence of a more consistent drying pattern
on this building may have been due to the
fact that the vapor retarder was not fully or
consistently removed from all roof areas.
RECOMMENDATIONS
In our opinion, the design rationale for using the
P.E. membrane configuration for this roof (in regard to
wind uplift and warranty availability) was a valid
design option that provided significant benefits to the
building owner with respect to renovation costs, job
site logistics, and inconvenience to the building occupants.
In addition, it may be claimed that moisture content of the
lightweight insulating fill on this roof is, based on this study, at
least “trending” in the desired direction of drying out, if not actually
exhibiting acceptable drying overall. However, the results
from the study of one roof are not definitive enough, in our
opinion, to promote selection or design of this roof configuration
based solely on potential drying effects. It should be noted
that the successful performance of the pressure-equalized roof
membrane configuration is highly dependent upon proper design
and installation of an effective air seal at the roof perimeter to
avoid air leakage that would counteract the pressure-equalization
efforts. Accordingly, it is not possible to add perimeter venting
or underside “holes” in the deck to promote additional drying for
these types of roofs without circumventing (destroying) the critical
pressure-equalization characteristics that resist wind uplift.
Therefore, we would recommend that anyone considering this
type of roof system be sure to obtain input and advice from the
manufacturer for the intended design and that steps be taken to
properly install the roofing system in general and the perimeter
air seals in particular.
Based upon the current study, it may be prudent and informative
to conduct an additional test on this building after more
time has elapsed (i.e., perhaps the fall of 2000). This would
allow a total of three years since installation, with the cumulative
drying potential of three summers to promote the desired effects.
In addition, we recommend that additional projects be selected
for a similar type of study where the test procedures may be
accurately applied and the results carefully analyzed. Once additional
data are obtained, further justification of the P.E. membrane
configuration for promoting drying of wet insulation may
be forthcoming.
REFERENCES
1) “Standard Practice for the Detection and Location of
Latent Moisture in Building Roofing Systems by Nuclear
Radioisotopic Thermalization,” Roof Consultants Institute,
Raleigh, North Carolina, 1986.
Upper roof after renovation.
August 1999 Interface • 11
2) Tobiasson, W., C. Korhonen, B. Countermarsh and
A. Greatorex, “Can Wet Roof Insulation Be Dried Out?” in
ASTM Special Technical Publication (STP) 789, Thermal
Insulation^ Materials and Systems for Energy Conservation in the
’80s, American Society for Testing and Materials,
Philadelphia, PA, 1983.
3) Anderson, Richard G., “Dry Range and Wet Range
Moisture Content of Roofing Materials as Found in
Existing Roofs,” Second International Symposium on Roofing
Technology, A Decade of Change and Future Trends in Roofing,
National Roofing Contractors Association, Chicago,
Illinois, 1985.
BIBLIOGRAPHY
1) Tobiasson, W. and J. Richard, “Moisture Gain and Its
Thermal Consequence for Common Roof Insulations,” in
Proceedings of the 5th Conference on Roofing Technology, National
Roofing Contractors Association, Oak Park, Illinois,
April 1979.
2) Tobiasson, W. and C. Cohornen, “Roof Moisture Surveys:
Yesterday, Today, and Tomorrow,” Second International
Symposium on Roofing Technology, A Decade of Change and
Future Trends in Roofing, National Roofing Contractors
Association, Chicago, Illinois, September 1985.
3) Tobiasson, W., “Roof Moisture Surveys: Current State of
the Technology,” Proceedings of SPIE-The International Society
for Optical Engineering, Volume 371, Society of Photo-
Optical Instrumentation Engineers, Bellingham,
Washington, October 1982.
ACKNOWLEDGMENTS
The author would like to acknowledge the professionalism
and generosity of RCI colleague Richard Cook, Jr. of the firm of
Austin, Dillon, Cook, Engineers, Hanahan, SC, who referred this
project to French Engineering, Inc.
The author would also like to acknowledge the assistance
and contribution of Tom Kelly and the roof membrane manufacturer,
2001 Roofing Systems, as well as the assistance and contribution
of Jim Dorsey, Project Manager for the roofing
contractor, Texas Coatings Applications & Waterproofing, Inc.
Finally, the author would like to acknowledge the assistance
and contribution of Jerry D. Thomas of French Engineering,
Inc., in conducting certain portions of the field testing and performing
analysis on some of the data. B
About the Author
Warren R. French is president
and founder of French
Engineering Inc., Houston,
TX. French Engineering specializes
in investigation and
renovation of building
envelopes experiencing moisture
problems, including roofing,
waterproofing, curtain
wall, and condensation issues.
He is currently Second Vice
President of RCI. Warren R. French, RRC
Correction
In the June issue of Interface, a table in the article by Derek Hodgin, “Wind Failures,- Avoiding A Roof Failure Requires an
Understanding of Many Factors Other Than Wind Speed,” was misplaced. Table 1 (on page 3) should have been inserted on page 5
after the first paragraph in the second column. The second paragraph should have been deleted, as it is actually part of the table. We
regret any confusion this may have caused to the reader.
Momentum Technologies, inc.
Bringing Technology to the Roof Consulting Industry with
Laboratory Services that make the consultants job easier.
Roof Core Forensics – Asbestos Analysis – Expert Witness Services
Chemical & Mechanical Analysis of Materials – ASTM & ICBO Testing
For more information contact us at
1-800-720-0261
Visit our web site at
www.momentumtech.net
Momentum Technologies, inc.
1507 Boettler Road, Uniontown, OH 44685
An ICBO Accredited and ISO Guide 25 Certified Laboratory
12 • Interface August 1999