Skip to main content Skip to footer

Roofing Wind Speeds: ASCE 7, Uplift Ratings, and Warranties

March 16, 2014

Roofing Wind Speeds:
ASCE 7, Uplift Ratings, and Warranties
Brian P. Chamberlain
Carlisle Construction Materials
1555 Ritner Hwy, Carlisle, PA 17013
Phone: 717-245-7072 • Fax: 717-960-4485 • E-mail: chamber@syntec.carlisle.com
2 9 t h RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 2 0 – 2 5 , 2 0 1 4 C h a mb e r l a i n • 1 4 3
Abstract
• Does 90 lbs./sq. ft. of uplift equal 90 mph?
• Does a Factory Mutual Global-rated assembly of 1-90 equal 90 mph?
• Does the building code require a warranty wind speed of 90 mph?
An ongoing issue that frustrates the industry as a whole is the confusion in how a roofing
assembly will meet the building code, will meet an uplift rating, and be warranted based
on local wind speeds.
Since local wind speed is the common factor is all three, an understanding of how wind
speed is used and associated to each needs to be clarified. This presentation will focus on
the process, from uplift to warranty.
Speaker
Brian P. Chamberlain — Carlisle Construction Materials
Brian Chamberlain has been with Carlisle Construction Materials since 1987. He
graduated from the University of Wisconsin at Milwaukee with a BS in architectural design.
As a member of Carlisle’s Design Services, he is part of a team that is responsible for all
system configurations and details development, including all code-testing operations for
those assemblies. He has been involved in numerous technological presentations throughout
North America and Asia, offering information on unique design issues, such as energy
efficiency of insulation, geographic influence on roof membrane color, roof garden assemblies,
photovoltaic interfacing, moisture vapor movement, and uplift performance of roofing
systems. Chamberlain is a member of RCI and CSI.
1 4 4 • C h a mb e r l a i n 2 9 t h RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 2 0 – 2 5 , 2 0 1 4
INTRODUCTION
The following questions seem simple to
answer, but they are common with building
owners, designers, and contractors:
• Does 90 lbs./sq. ft. of uplift equal 90
mph?
• Does a Factory Mutual Global- (FM
Global-) rated assembly of 1-90
equal 90 mph?
• Does the building code require a
warranty wind speed of 90 mph?
Though these questions are common,
they are all misunderstandings of what the
building code requires, what FM Global’s
criteria are, and what is covered by roofing
material manufacturers’ warranties. One
way to understand this is by reviewing
the minimum requirement in the building
code for roof assembly based on wind uplift
performance, how the roofing assembly can
be verified to meet the building code, and
in what way a roof warranty relates to the
building code and uplift pressures.
As new standards are being developed
and accepted by the roofing industry, such
as the 2012 International Building Code
(IBC), American Society of Civil Engineers
(ASCE) 7-2010, or FM Global Approval
Standard 4470, just to name a few, questions
like the ones above arise because of
assumptions, lack of education, inexperience,
and the various recommendations in
the building code process.
CALCULATION UPLIFT
So where does this all begin?
In Chapter 16 of the IBC, it states that
roof systems must meet uplift pressures
for the specific building conditions based
on calculations using ASCE 7 with the
results in pounds per square foot (lbs./sq.
ft.). Verification of these pressures must
be executed through independent testing
following testing procedures listed in FM
4450, FM 4470, ANSI/FM 4474, UL 580, or
UL 1895, with the testing results reported
in lbs. per sq. ft. so that comparison can be
accomplished between
the calculated results
in lbs./sq. ft. to tested
results in lbs./sq. ft.
The first step is
calculating the uplift
pressure following
the ASCE 7 standard.
Currently, the industry
has two versions—
ASCE 7-2005 or ASCE
7-20101—and depending
on your state or
municipality, the correct
version for calculations
must be used,
because there are slight
differences between the
two that must be taken
into account.
Though this paper
will not go fully into the math, I will limit
the discussion about math to ASCE 7-2010,
because as states adopt the IBC 2012, this
method will be necessary. The purpose of
this overview is to acknowledge that wind
is important to the calculation, but it is
not the sole factor that should be considered.
The ASCE 7 standard is an engineer’s
document, so its focus is on the building’s
structural members and the nonstructural
cladding components of a
building. The result is that
all building components
must be installed to meet
specific pressures.
In determining uplift
pressures for a roof area,
there are five basic factors
that must be considered for
a roofing installation:
1. Building Height.
Higher roof areas will
have stronger wind
velocity.
2. Building Location.
Wind maps (Figure 1)
are included within
ASCE 7 so that the local basic wind
speed can be determined. The maps
are based on a 3-second peak gust
measured at 33 ft. (10 m) above
grade in an exposure condition (“C”)
that is referenced as “basic wind
speed.”
3. Surrounding Terrain. The more
obstructions there are around a
building, the more they will break
Roofing Wind Speeds:
ASCE 7, Uplift Ratings, and Warranties
2 9 t h RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 2 0 – 2 5 , 2 0 1 4 C h a mb e r l a i n • 1 4 5
Figure 1 — Basic wind speed map, risk Category II, ASCE
7-10, Chapter 26.
Figure 2 – Example of Exposure D: buildings near a
large body of water.
up the wind and assist in
reducing the wind effect.
Knowing if the building is
located in an urban/suburban
area, an open-terrain
area, or near a large body
of water becomes important
(Figure 2). For the specific
three exposure definitions
(B, C, and D), refer to ASCE
7-10, Chapter 26.
4. Building Openings. The
more openings in a building,
the greater the chance
of internal pressures increasing
in a wind event. It
is important to know if the
building is enclosed, partially
enclosed, or open (Figure 3).
For a complete definition of building
openings, refer to ASCE 7-10,
Chapter 26.
5. Building Use. This factor is based
on how important the building is to
the surrounding infrastructure in
terms of people’s safety. An example
would be a school or a hospital
compared to a warehouse. Though a
warehouse owner might not want his
building harmed during a natural
disaster, the other two buildings are
very important for the protection of
children and for assistance to those
harmed during a natural disaster.
Refer to ASCE 7-10 for a complete
definition of Risk Categories I, II, or
III/IV.
All the data listed above are plugged
into the following formulas, and the result
is uplift pressure in lbs./sq. ft.:
qz = 0.00256 x KZ x KZt x Kd x V2 x .06
• 0.00256 = numerical coefficient to
be used except where sufficient climatic
data are available
• KZ = velocity pressure exposure coefficient
evaluated at height z = h
• KZt = topographic factor as defined in
ASCE 7-10, Section 26.8
• Kd = wind directionality factor in
ASCE 7-10, Table 26.6-1
• V2 = basic wind speed obtained
from ASCE 7-10, Figures 26.5-1A
through 26.5-1C.
• .06 = load factor to convert to allowable
stress design2
P (pressure) = qz [(GCp) – (GCpi)] • GCp = external pressure coefficient
and gust-effect factor
• GCpi = internal pressure coefficient
and gust-effect factor
For a complete understanding of the
calculation method, refer to Wind Pressures
on Low-Slope Roofs, RCIF Publication No.
01.01.3
SAFETY FACTOR
After the results have been completed,
there are a number of organizations, such
as FM Global, ASTM D6630, NRCA, and
ANSI/SPRI that recommend a safety factor.
Though a safety factor is important for the
design professional to consider, it is not
required by the IBC or ASCE 7-10.
In addition, material manufacturers
submit their results from the testing assemblies
(described later in this paper) to the
ICC Evaluation Service (ICC-ES), Miami-
Dade Building Code Compliance Office’s
Product Control Division, and Trinity ERD
(Exterior Research & Design, LLC) for
review and incorporation into the published
reports. These organizations do not publish
the tested results but use “factored tested
load capacity” of the assemblies. The way to
determine factored tested load capacity is
by taking the tested uplift load capacity (Lt)
and dividing by a safety factor, usually 2, as
shown in the following formula:
Factored Tested Load Capacity =
Tested Uplift Load Capacity
(Lt)/2 lbs./sq. ft.
Both methods are acceptable,
but if desired, one or the other
should be specified in the architectural
roofing specification. This
is important, because at the time
of bid, those associated with the
bid process will know that additional
uplift criteria are being specified
beyond the building code.
Otherwise, the minimum requirements
of the building code will be
followed.
Since a safety factor is only a
recommendation at this time, it
is the intent of this paper to focus
on what is required by the building
code. It should be understood
that the building code represents
a minimum requirement, and designers
should always consider going beyond the
building code.
RESPON SIBILITY
The person responsible for doing the
uplift calculation is the design professional,
who should list the results in the architectural
specification. In some cases, they are
included correctly; but unfortunately, most
Division 7 specifications for roofing assemblies
attempt to place the responsibility on
the roofing contractor or installer, who is
typically not an engineer.
At a panel discussion held at the
2013 Carolinas Roofing & Sheet Metal
Contractors Association, Inc. (CRSMCA) in
Raleigh, NC, the responsibility for doing the
calculations was discussed, and the panel’s
engineer and specifier agreed that a roofing
contractor should not bid on the project
unless he or she had the calculation results
from the design professional who specified
the roofing assembly.
Though this is a nice idea, the industry
does not allow enough time during the
bidding process for this communication.
With the push for the bid and the architectural
roofing specification making the calculations
the contractor’s responsibility, the
contractor is forced to request assistance
from the roofing materials manufacturer or
some other source.
Please understand that the above is in
reference to new construction. In reroofing
or re-covering of an existing roof area,
which might be negotiated between the
contractor and the building owner without
a licensed design professional involved, the
building owner or the contractor should
1 4 6 • C h a mb e r l a i n 2 9 t h RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 2 0 – 2 5 , 2 0 1 4
Figure 3 – Example of an open warehouse.
hire a licensed design professional to verify
the uplift pressures.
Material manufacturers want to be as
service oriented as possible, so they will act
upon these requests, do the calculations,
and present the pressures for a given building
roof area, but they clarify that such
results should be verified by a local licensed
engineer or design professional. The demand
for this assistance has increased steadily
over the years, which in turn has generated
a number of published
documents and online calculators.
One such document
is the American National
Standards Institute/Single
Ply Roofing Industry (ANSI/
SPRI) “WD-1: Wind Design
Guide Standard Practice
for Roofing Assemblies,”
approved July 10, 2012,4
which is based on ASCE
7-10 and is focused on
roofing installation. This
document offers guidance
on how this general
process works, including
charts of calculated results
(Figure 4) without using
a wind directionality factor
for a standard building
and assists the designer
in determining the uplift
pressures.
In addition to this document,
there are web-based
calculators; but each has
its own limitations, and at
best, they offer good guidance
for the designer. Even
so, the overall responsibility for confirming
these results lies with the specifier through
an engineer, architect, or other qualified
design professional (Figure 5).
The results determine the uplift pressures
for each zone area of the roof: field,
perimeter, and corners. Take note that the
corner will typically have the highest uplift
pressure. As an example, in Figure 5, the
uplift pressure in the corner for a 30-ft.-
high building is -50.5 lbs./sq. ft.
TESTING
So what should the designer do with
this number?
The designer should review roof assemblies
and their associated reports in uplift
resistance to confirm which assembly meets
or exceeds the calculated uplift pressures.
The process by which a material manufacturer
tests an assembly is by following
the testing procedure described in FM 4450,
FM 4470, ANSI/FM 4474, UL 580, or UL
1895. The most common testing manufacturers
request of independent laboratories
(such as American Testing, Inc.; Atlantic &
Caribbean Roof Consulting, LLC; and PRI
Asphalt Technologies, Inc., to name a few),
is ANSI/FM 44745, which is just the uplift
testing portion of FM 4470.
TESTING PROCEDURE
The standard procedure for the uplift
test starts with the roofing material manufacturer
building a mock-up of the proposed
roof assembly on either a 5- x 9-ft. or 12- x
24-ft. table. The 5- x 9-ft. table is limited to a
rated system up to 90 lbs./sq. ft., with limitations
to mechanically secured membranes
and base sheets; while the 12- x 24-ft. table
2 9 t h RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 2 0 – 2 5 , 2 0 1 4 C h a mb e r l a i n • 1 4 7
Figure 5 – Results from Carlisle Construction Materials’ ASCE 7 calculator.
Quick Reference Table
Building Risk Category II, Exposure C
115 MPH Peak Gust Wind Zone
Building Field Design Perimeter Design Corner Design
Height, ft. Load, psf Load, psf Load, psf
0-15 -20.4 -34.2 -51.5
20 -21.6 -36.2 -54.5
25 -22.5 -37.8 -56.9
30 -23.5 -39.4 -59.3
40 -24.9 -41.8 -63.0
50 -26.1 -43.8 -66.0
60 -27.1 -45.4 -38.4
Figure 4 – Partial ANSI/SPRI WD-1, Page 13.
allows for a rated system greater than 90
lbs./sq. ft. and wider spacing of membrane
securement. Refer to ANSI/FM 4474, paragraph
5.1.2, for complete limitations.
Once installed, the perimeter of the table
is sealed airtight, and positive pressure—
measured in lbs. per sq. ft.—is pumped
from underneath the roofing assembly.
The test is meant to simulate the negative
pressure of wind trying to pull off the roof
assembly as the wind blows across.
At the start of the test, the assembly is
subjected to 30 lbs./sq. ft. of positive pressure.
This pressure is held for one minute,
and then an additional 15 lbs./sq. ft. is
added, for a total of 45 lbs./sq. ft., which is
also held for one minute. This process continues
until a failure mode occurs, at which
time the system is rated at the last pressure
the assembly held for one minute (Figure 6).
The minimum rating any assembly can
earn is 60 lb./sq. ft. Please note that the
laboratory test for a 90-lb./sq.-ft. assembly
only lasts for five minutes.
Failure Mode for Adhered Membrane
Assemblies
• If the membrane separates from
insulation
• If the insulation facer delaminates
• If the insulation boards break
Failure Mode for Mechanically Fastened
Membrane Assemblies
• If the fasteners pull out of the deck
• If the membrane ruptures (Figure 7)
COMPARISON
Once the roof assembly’s strength is
determined through this test and reported,
we can compare its uplift rating to the ASCE
7 calculations. For example,
if the corner pressure were
-50.5 lbs./sq. ft., the minimum
acceptable rated assembly
would be 60 lbs./sq. ft.
If it happens that the calculated
perimeter and corner
pressures are greater than the
reported uplift performance of
the assembly, the IBC and
ASCE 7 do not offer any guidance
other than the assembly
must have been tested to
meet or exceed those pressures.
There are a number
of documents published that
offer recommendations on how
to enhance the rated assembly to compensate
for those additional pressures, such
as ANSI/SPRI WD-1 and FM Global Loss
Prevention Data Sheet 1-29, but they are not
required by the building code. The design
professional will have to decide which if any
of these recommendations to include in his
or her specification.
SPECIFICATION S
Architectural specifiers incorporate the
above process in their architectural roof
specifications; but unfortunately, depending
on how they are written, this create its
own confusion. Where this process should
be listed in the quality assurance or performance
articles, the wording can be misleading.
The best way this can be handled is by
actually inserting the results of the ASCE 7
testing in the referenced articles and requiring
certification that the specified roofing
assembly meets or exceeds those results.
Since, based on my personal review, most
specification writers do not seem to include
this information, I offer the following statement
that could be modified:
The specified roofing assembly must
have been successfully tested by
a qualified testing agency following
ANSI/FM 4474 to resist the
design uplift pressures calculated
according to American Society of
Civil Engineers (ASCE) 7 and after
multiplying the results with a safety
factor (determined and provided by
a design professional), but assembly
uplift pressures shall be not less
than 60 lbs./sq. ft.
Another very common listing in architectural
roof specification is FM Global.
Specifiers feel that inclusion of FM Global
will guarantee that the roof installation will
be of high quality. Though FM Global follows
a very similar process as the IBC, there are
some subtle differences. Keep in mind that
all FM Global documents are for buildings
insured by them, so their documents are
not building code but rather their insurance
standards. In addition, their documents
have no public review and comments associated
with them. FM Global can modify or
change its documents and publish them
without notifying the industry.
1 4 8 • C h a mb e r l a i n 2 9 t h RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 2 0 – 2 5 , 2 0 1 4
Figure 6 – Mechanically fastened membrane system
tested on a 12- x 24-ft. table.
Figure 7 – Seam plates bent and cut through the single-ply roof membrane.
FM Global Property Loss Prevention
Data Sheet 1-28,6 (which is based on ASCE
7-05), offers very similar information to
that presented in ANSI/SPRI WD-1, where
precalculated charts of uplift pressures
based on building location and height are
included. FM Global’s beginning pressures
are typically higher, because in their calculation,
they classify all of their buildings as
the highest category or importance factor,
even if they are not hospitals or schools.
In addition, they also include a safety
factor, so the end-result pressures are
higher. Note: Though these calculations are
not required by the IBC, they are required
for FM Global-insured buildings. As a recommendation,
FM 1-28 should only be
used in association with FM Global-insured
buildings, and the calculation of the uplift
pressures should be completed by an FM
Global engineer. After all, they are insuring
the building and enforcing their published
enhancements, which are not required by
the IBC, so they should be the responsible
party to assist the design professional.
This author’s recommendation is that
if the building being specified is not FM
Global-insured, that FM Global should not
be listed or referenced in the specification,
for who would be available to confirm that
the installation of the roof assembly will
meet the FM Global installation criteria?
Material manufacturers can assist in certifying
that their assembly has been rated by
FM Global and would meet the uplift pressure
results, but they only inspect for their
warranty criteria, not FM Global installation
criteria.
Along with publishing their own calculations
and installation criteria, FM Global
also does its own testing following standard
FM 4470, which includes ANSI/FM 4474.
FM 4470 is more than just testing for uplift,
it includes tests involving internal and
external fire, hail, foot traffic, seam, and
fastener corrosion testing. FM Global labels
its tested assemblies based on the uplift
rating, such as FM Class 1-90 SH. The “90”
listed in this rating means the assembly is
rated up to 90 lbs./sq. ft. of uplift pressure,
not a 90-mph wind speed.
So the answer to the first two questions:
• Does 90 lbs./sq. ft. of uplift equal 90
mph?
• Does an FM Global-rated assembly
of 1-90 equal 90 mph?
…is, no, they do not.
The basic wind speed is one factor in the
calculation in determining uplift but not the
sole concern. The requirement is to prove
that the specified assembly has been tested
and rated accordingly for the specific building
calculated uplift pressures.
Because uplift pressure is so critical in
determining the correct roofing assembly,
some specifiers have attempted to make
ASCE 7 or calculated uplift results included
in the warranty. What needs to be understood
is that the calculations are static,
and the pressure applied in the laboratory
test ANSI/FM 4474 is perpendicular
to the roof assembly and nondynamic.
The calculations and testing do give guidance
to a designer on proper installation,
but common sense points to the fact that
buildings receive wind pressure from many
directions and locations other than just the
exterior across the roofing assembly. These
additional wind pressures can infiltrate
into the assembly unintentionally, causing
unexpected failures if the building is
not properly designed and installed. Most
people understand that these conditions
are outside of the roofing material manufacturer’s
control, and most membrane
manufacturers have this clarified under the
warranty limitation. Even so, because of
all the uncontrollable variables, it becomes
very difficult for a material manufacturer
to define what the warranty is responsible
for if uplift is included. I have found one
warranty that attempts to warrant uplift,
but it includes the following statement if
wind damage should occur: “At the building
owner’s expense, a report from a licensed
engineer certifying failure was not caused
by wood blocking, decking, or other building
components must be submitted.”
Most of the failures within a roof assembly
after a major wind event will be from
other forces, such as flying debris causing
damage to the roof assembly, breaking
outer surfaces or windows, weak design
of metal edging or coping, etc., which will
allow additional pressure to be introduced
into the assembly (Figure 8). Though ASCE
7 is a good method, it is a standard used
throughout the U.S. and other parts of the
world and does not address every variable
the design professional would need to be
concerned about. This is one of the reasons
that safety factors are promoted, but
these safety factors are applied to the roof
assembly but may not be applied to other
components that might fail and cause the
roof system to fail. Just as the IBC is the
minimum criterion for a building, common
sense and experience need to be applied
to any building design, not a warranty. If
surveyed, one would discover that most
manufacturers will not cover uplift forces,
but most will include wind coverage in some
fashion within their warranties.
2 9 t h RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 2 0 – 2 5 , 2 0 1 4 C h a mb e r l a i n • 1 4 9
Figure 8 – Wind effects on a building (National Weather Service Weather Forecast
Office).
WIND S PEED L ISTED ON A
ROO FING SYSTEM WARRANTY
Though IBC requires the specifier to
determine the correct roofing system design
by comparing calculated uplift pressures
with test-rated pressures, the document
does not require that a building owner
obtain a warranty or guarantee from the
manufacturer.7 None of the building
code standards mention a warranty being
required. Seldom, if ever, do building owners
require other components of the building to
carry a wind speed warranty (i.e., roof deck,
walls, windows,
etc.), yet all of
these building
components must
meet the pressures
indicated in
ASCE 7. In
contrast, if, after
a storm event, the
siding of the
building is
damaged, the
building owner
will turn to
his insurance
company, not the siding manufacturer.
So if few other component manufacturers
offer wind speed warranties, why do most
roofing material manufacturers?
When single-ply roofing manufacturers
entered the industry, they had to differentiate
themselves from more traditional and wellknown
built-up roofing (BUR) material. To
do this, they had to offer something as an
incentive that BUR did not offer, which at
that time was simply bonded through the
contractor. So they offered a roof warranty;
and, eventually, wind coverage was included.
Deciding on how they wanted to list
wind speed in the warranty, they first used
terms such as “strong gale-force winds,”
which came from the Beaufort wind speed
scale. Even today, some manufacturers use
“strong gale-force winds” or “windstorms”
to define their wind coverage. The partial
Beaufort wind speed scale chart in Figure
9 shows “strong gale-force” starts at 47
mph, while “windstorm” starts at 64 mph.
Though material manufacturers use these
terms in correspondence to their wind
speed coverage, the scale was originally
based on the nautical term “knots,” which
were converted to wind speeds at 10 meters
above sea level.
As other roofing material manufacturers
included wind speed coverage, some roofing
material manufacturers had to consider
how they could again place themselves
apart, so some started to put the actual
numerical wind coverage on the warranty
in miles per hour. At first they only offered
coverage up to 55 mph, which is a step
above “strong gale.” When this number
became common, it was decided by some
manufacturers to up it to 72 mph—1 mph
less than a hurricane.
As some roofing
material manufacturers
played the warranty
game, ASCE 7 was being
used more and more,
including a revision of
the ASCE 7-05 wind
speed maps from “fastest
mile” (Figure 10), where
most of the U.S. was
shown to be 79 mph or
less, to “3-second peak
gust wind” (Figure 11),
which shows most of the
U.S. is 90 mph.
When this document
changed, specifiers
and building owners
began to notice their
buildings were located
in a 90-mph wind zone,
and the warranty listed
only 55 mph. They
started to question the
material manufacturer to
learn why they were not
getting 90-mph coverage,
even though the system
was installed following
the correct uplift rating.
1 5 0 • C h a mb e r l a i n 2 9 t h RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 2 0 – 2 5 , 2 0 1 4
Figure 9 – Partial Beaufort wind speed scale.
Figure 10 – Basic wind speed map, ASCE 7-88.
In an attempt to minimize this confusion and
again to separate from the competition, some
roofing material manufacturers started offering
90-mph and greater wind coverage. Even today,
with the latest version of ASCE 7-10 and the
new wind speed maps, specifiers are asking
why they cannot get even higher wind speed
coverage (Figure 12).
When a request for a high wind speed is
specified, typically manufacturers attempt to
incorporate stronger, more-durable products,
because though they are membrane roofing
manufacturers and not insurance companies,
they need to limit their liability as much as
possible. These products might incorporate
any or all of the following: a stronger facer
on the polyisocyanurate, a thick cover board,
additional fastening requirements, stronger
adhesives, and thicker and specialty-type
membranes.
Building owners and specifiers hope that by
specifying a higher wind speed warranty, they
will receive a more durable system. Though in
most instances this is true, the assumption
that all manufacturers offer the same warranty
coverage is incorrect. Since manufacturers’
warranties are marketing tools to assist in
selling the materials, the roofing manufacturers
can control their coverage of the wind speed by
how they write the warranty.
Owners and specifiers both need to be
aware of the many different terms that are
used and what assemblies could be offered that
would be durable. They should not assume
that warranty length and wind speed coverage
dictate sustainability. Upon reading through the
warranties, one will learn that some offer very
good coverage, while others are written so that
very competitive assemblies can be installed
without offering any coverage in the warranty.8
Here are some terms that are actually
used in warranties today. The numbers in
parentheses show the related wind speeds
in mph; but typically, they are not defined
as to where they might be measured or the
measurement of time (fastest mile or 3-second
peak gust wind speed):
• No mention of a wind speed (0 mph)
• “Windstorms” (64-72-mph)
• “Full gale-force” (46 mph)
• The actual wind speed printed from 38
to 120 mph
• “Gale force” (46 mph)
• Beaufort wind scale #8 (46 mph)
• “Gales excluded” (31 mph)
• “Capped at 38 mph”
• Wind speed coverage prorated (loses a
portion of the wind coverage every year)
2 9 t h RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 2 0 – 2 5 , 2 0 1 4 C h a mb e r l a i n • 1 5 1
Figure 11 – Basic wind speed map, ASCE 7-05.
Figure 12 – Basic wind speed map risk category III/IV, ASCE 7-2010.
In combination with these terms, “where
the wind is measured” can be written into
the warranty:
• “Ground wind speed” = 33 ft.
• “Rooftop wind speed” = building
height
• No mention = allowing the manufacturer
to decide at the time of the
wind event
Where the wind speed is measured
can be important when one considers that
the higher the roof area is, the greater the
wind speed will be. Remember that ASCE 7
specifies that building height is one of the
five factors in determining the correct uplift.
Though most warranties are measured at
“ground wind speed,” which is defined as
33 ft. (10 m) from the ground surface (the
same height at which airports and the
ASCE 7 basic wind speed is measured),
some warranties have the phrase “rooftop
wind speed.” As an example, if the building
has a 300-ft.-high roof area and the warranty
lists a 100-mph “rooftop wind speed,”
the “ground wind speed” would be 55 mph.
In reverse, a 100-mph “ground wind speed”
warranty would actually cover winds up to
180-mph at that height (Figure 13). Note
that this is wind speed vs. wind speed and
has nothing to do with uplift in lbs./sq. ft.
For warranty coverage, the higher the
roof area, the greater the wind speed, so if
you are considering wind speed coverage,
“ground wind speed” offers better coverage
on a higher building.
With so many options available from
assemblies to warranty coverage, the building
owner will need to be assisted on what
first would be a durable assembly for his
building and location, and compare this
with good coverage by a warranty (not the
other way around or just a number in
miles per hour). The assembly also should
be assessed outside of warranty considerations,
so when contractors go through the
bidding process, items are not clouded by
different promises.
The request for higher wind speeds
beyond the minimum a material manufacturer
would offer should be incorporated
into the “warranty” section of the Division
7 roofing specification. The “quality assurance”
and the “performance” sections make
sure that the roof system will meet the
building code, so any reference to wind
speed would be related to ASCE 7 calculations,
not warranty criteria. The warranty
section is what is being requested from the
roofing material manufacturer. If the specifier
does not list any additional wind coverage
in the warranty section, material manufacturers
can default to their minimum
offered wind speed coverage. As long as the
desired warranty wind speed is listed in the
warranty section, the specifier will know
that the contractors will bid as instructed,
based on the material manufacturer’s criteria
for that warranty.
Another common question is how much
uplift does a 90-mph warranty offer?
Though we could do the math backwards,
it doesn’t really mean anything,
because there is no test a manufacturer can
do that would actually rate the assembly in
mph. So there is no method to determine a
verification of the roofing assembly in mph
that would be equal to or greater than the
basic wind speed in mph. As stated earlier,
the basic wind speed is one factor out of five
in the uplift calculation in lbs./sq. ft. This is
the reason we use ASCE 7—so that a comparison
and verification can be completed
in lbs./sq. ft.
So what is the relationship between
basic wind speeds based on ASCE 7 and
warranties?
Since most manufacturers do not or
will not include code compliance or uplift
performance within the coverage of the warranty,
the answer is none. If a manufacturer
is willing to include this type of coverage,
the owner should read the warranty very
closely and understand everything that is
being offered.
Uplift Pressures ≠ Wind Speed on a
Warranty
The warranty wind speed offered by
roofing material manufacturers is not based
on uplift ratings. Ratings are results from
static laboratory tests that could last only
5 to 10 minutes—possibly more, depending
on the strength of the assembly. A 20-year
warranty has approximately 1,051,200 tenminute
increments, which, if one thinks
about it, is a lot of responsibility for a
10-minute test. When deciding on wind
speed coverage, a roofing materials manufacturer
considers basically two factors:
1. H ow can more durable products be
incorporated into the assembly and
still be competitive?
2. More importantly, has the material
manufacturer installed a similar
project and did it perform historically
well?
SUMMARY
In conclusion and to show how simple
the process is for determining the correct
roofing assembly for a specific building:
1. Determine the building “uplift pressure”
using ASCE 7 calculations,
which should be completed by a
locally licensed or qualified design
professional.
2. Review the roofing assembly’s
“reported pressure” collected from
the manufacturer results and rat-
1 5 2 • C h a mb e r l a i n 2 9 t h RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 2 0 – 2 5 , 2 0 1 4
Figure 13 – Rooftop wind speeds, Uniform Building Code.
ings from ANSI/FM 4474 or other
test methods listed in the IBC.
3. Compare and verify the “correct
assembly.” Reported pressures must
be equal to or greater than the
calculated pressures. If the design
professional wishes to consider a
safety factor of his choosing, this is
where it would be considered—be it
to multiply the factor by the ASCE
7 results or by dividing the reported
assembly pressures.
After these three basic steps are completed,
the designer can look at the products
and assembly details to see what could
be enhanced beyond the building code for
the building owner’s needs.
Once the assembly has been decided,
warranties should be considered and read
thoroughly to confirm that the wind coverage
meets the building owner’s needs and
is easily understood. Keep in mind: When
higher wind speed coverage is requested
from the material manufacturer, additional
enhancements may be necessary to
qualify for the warranty. When required,
these additional enhancements will likely
increase the cost of the total assembly and
may increase the cost of the warranty being
purchased.
One way to mitigate the cost to a building
owner, after determining the uplift pressures
and the preferred roofing assembly,
is to specify the higher-performing products
and details associated for higher wind speed
warranty assemblies, but only request from
the manufacturer a lower wind warranty to
avoid the additional cost of the warranty for
that higher wind speed.
Bear in mind, if we related this process
to baking cupcakes, the ASCE 7 would be
a recipe, while the roofing assembly would
be the batter. Mixed together and baked
(roof assembly installed), we have a nice
tasty cupcake, but a cupcake is also covered
with icing (the warranty). The choice
of a type of wind speed warranty coverage
can be made with the realization the icing
on the cupcake isn’t necessary to hold the
cupcake structure or the roof together. This
should assist in turning the focus away
from warranties and looking more directly
for quality and durable roofing assemblies
and installation.
Refere nces
1. ASCE/SEI 7-10, Minimum Design
Loads for Buildings and other
Structures, 2010
2. William L. Coulbourne, “Review of
ANSI/SPRI WD-1,” update for compliance
with ASCE 7-10, August
2011
3. Stephen Patterson and Madan
Mehta, Wind Pressures on Low-Slope
Roofs, RCIF Publication No. 01.01,
(Revised 2013)
4. ANSI/SPRI “WD-1: Wind Design
Guide Standard Practice for Roofing
Assemblies,” July 2012
5. ANSI/FM 4474, American National
Standard for Evaluating the
Simulated Wind Uplift Resistance
of Roof Assemblies Using Static
Positive and/or Negative Differential
Pressures, March 2004
6. Factory Mutual Global, “Property
Loss Prevention Data Sheet 1-28,”
January 2012
7. Marty Gilson and Brian Chamberlain,
“Roofing Warranty Wind
Speed Coverage Versus Local Building
Codes, Local Wind Speeds, and
FM Global: Solving the Mystery,”
Northern Illinois CSI Link, May 2007
8. Brian P. Chamberlain, “Roof Warranties
– Reading Beyond the Duration
to Comprehend the Coverage,” RCI
27th International Convention &
Trade Show, 2012
2 9 t h RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 2 0 – 2 5 , 2 0 1 4 C h a mb e r l a i n • 1 5 3