Skip to main content Skip to footer

Electronic Leak Detection: A Quality Assurance Tool

May 15, 2010

Water penetration through
roofing and waterproofing
systems is a common
problem to many buildings.
In fact, industry
studies show that over
50% of newly completed buildings are delivered
with water intrusion problems of the
building envelope. Low-slope roofs, commonly
referred to as “flat roofs,” have a disproportionate
share of leaks, due mostly to
the fact that they also act as a staging area
for other trades during new construction.
We also see them used as a traffic surface
and work platform for performing maintenance
on rooftop equipment and adjacent
surfaces. These circumstances are further
supported by a study completed by the
National Roofing Contractors Association
(NRCA) in which poor workmanship, bad
design, and accidental damage during construction
were blamed for over 60% of leaks
and premature roofing failures.
Given these statistics and the fact that it
is considerably less expensive to make a
repair at an identified breach while on site
than to come back to the site after the project
is complete, it’s no surprise that quality
assurance testing is
becoming more prevalent.
To address these
problems, certain quality
assurance methods have
been in place for a number
of years. To date,
these standard testing
methods have consisted
of the following: construction
observation,
flood testing, and a number
of nondestructive
test methods, including
electronic impedance
testing, infrared thermal imaging, and
nuclear testing. For comparison purposes,
we will mention these methods briefly.
FLOOD TESTING
• This is used most often in waterproofing
and roofing applications
over concrete decks in protected
membrane roof (PMR) assemblies.
• Loads exerted on decks are considerable
and may exceed the structural
capacity of the deck.
• This is not recommended for use on
conventional roof assemblies due to
the potential for water damage to the
insulation or structure.
• This does not identify the leak
source.
ELECTRONIC IMPEDANCE, INFRARED IMAGING, AND
NUCLEAR TESTING
• All are nondestructive tests.
• These are used most often on conventional
roof assemblies, as test
methods are very effective in detecting
moisture content in insulation.
• None identifies the leak source.
WHAT IS ELD?
Electronic leak detection (ELD) is also
known as electronic field vector mapping.
This introduction of ELD will cover
• The principles of ELD,
• A description of the process and the
hardware,
• When ELD is to be used,
• Where ELD can be used,
• Limitations of this growing technology,
and
• Comparisons to existing quality
assurance test methods.
Fundamentally, ELD entails creating a
conductive electronic field over the roofing
and/or waterproofing membranes, grounding
the test equipment to the structure, and
having the nonconductive membrane act as
an insulator. If there is a breach in the
membrane, the electronic field grounds
itself to the structure. Below is a more indepth
description of the methods.
There are two common methods of electronic
leak detection: low voltage and high
voltage. An in-depth description of the pro –
cess and equipment follow.
Figure 1 – The surface of the waterproofing must be wetted to provide an electrically conductive medium.
F E B R U A RY 2010 I N T E R FA C E • 3 1
LOW VOLTAGE – WET METHOD
A wire loop, to act as a conductor, is
placed directly on the membrane or the
membrane’s protection course around the
perimeter of the area to be tested. One of
the two leads from a pulse generator is connected
to this wire loop. A second lead from
the pulse generator is grounded to the
structural deck at a drain, vent pipe, flashing,
or other grounded roof component. The
surface of the waterproofing must be wetted
(not flooded) to provide an electrically conductive
medium (Figure 1).
Every few seconds, a low-volt charge is
delivered from the pulse generator for one
second. As a result, an electrical potential
difference is set up between the roof surface,
which is wet, and the roof deck, which
is “earthed” or grounded – essentially producing
two electric plates. If there are any
“leaks” or breaches through the waterproofing
membrane (which acts as an electrical
insulator), the small electric current will
flow across the membrane surface and
down through the breach, completing the
circuit between the two “electric plates.”
A technician uses a receiver connected
to two probes to identify the direction of the
electric current. By moving the probes, he
or she is able to systematically follow the
flow to even the smallest breach or leak
through the membrane. Once located, the
leak can be marked for repair and plotted
on a roof plan.
HIGH VOLTAGE – DRY METHOD
With high-voltage ELD, the power
source is grounded to the conductive deck,
with the membrane acting as an insulator
(Figure 2). The other lead is attached to the
testing equipment. The testing equipment
looks much like a broom. The difference, for
ELD purposes, is that the bristles are small
conductors. When the broom is swept
across the membrane and over a breach,
the circuit is completed, allowing current to
flow, resulting in the unit emitting an audible
tone. When a breach has been initially
located within the electronic field of the
broom, the operator sweeps the area again
with the con tact
area re duced to
pinpoint the exact
breach location.
Unlike the lowvoltage
method,
the high-voltage
method does not
entail installing a
wire perimeter to
define the test
area, and water is
not used to
enhance the conductivity
over the
surface of the
m e m b r a n e /
insulator, due to the higher
voltage.
WHERE IS IT USED?
The structural roof deck
must be conductive. This
includes metal, concrete, composite,
and lightweight cementitious
decks. It is important to
know if the roof assembly has
a vapor retarder, as it will also
act as an insulator just as the membrane
does and break the current flow, masking
the breach.
Wood decks are not conductive, and
vapor barriers break current flow on conductive
decks. These assemblies can be
tested if a conductive layer (such as aluminum
screening) is included in the membrane
assembly. The conductive layer will
need to have a wire run to a location above
the membrane so that the company performing
the testing can use the lead to connect
to the ground (Figure 3).
Drains provide good grounding components,
as the drain lines are secured to the
structure. Drains with PVC piping are ineffective.
Metal vent pipes, metal flashings,
and exposed rebar secured to the structure
are additional grounds.
WHICH MEMBRANES?
ELD can be used on nonconductive
membranes such as built-up roofs, modified
bitumen, hot-fluid-applied rubberized
asphalt, self-adhering polymer-modified roll
goods, urethane, thermoplastic, and white
EPDM (thermoset) membranes. ELD is not
effective on black EPDM due to its conductive
composition (carbon black).
ELD testing can be completed on conventional
roof systems and on PMR membranes.
Low-voltage testing can be complet-
Figure 2 – The power source is grounded to the conductive deck, with the membrane acting as insulator.
Figure 3 – Testing at nonconductive decks or conductive decks with
vapor retarders.
32 • I N T E R FA C E F E B R U A RY 2010
ed with some overburden materials left in
place, such as but not limited to paver
blocks on sand setting beds, ballasted
membranes, vegetated roofs, and nonreinforced
topping slabs.
ADVANTAGES OF ELD OVER TRADITIONAL TESTING
TECHNOLOGIES
The advantages of ELD testing compared
with standard flood testing of membranes
applied directly to the structure are:
• ELD pinpoints the location of
breaches as compared to plotting
and hunting for breaches in flood
testing.
• This test method saves times compared
with filling and waiting 24 to
48 hours, then draining and drying
the test area to complete repairs.
• In many instances, the bond of
adhered membranes will isolate the
water intrusion to the breach itself,
resulting in no leak during the flood
test. However, over time, this minor
breach can allow enough water to
enter to undermine the membrane
integrity, resulting in a leak.
• Sloped decks pose problems for
flood testing due to water depths
necessary to flood large areas. Even
with one-quarter in/ft slope, it only
takes 40 ft to require a minimum of
12 inches for a flood test resulting in
a load of over 62 lb/sq ft at the deepest
location.
• With roof renovations, ELD does not
risk causing interior damage from
two inches or more of water on the
roof.
• ELD will locate breaches where flood
tests will not reveal leaks. These are
the type of breaches that present
problems years later.
• ELD does not risk damage to
drainage systems when the drains
are unplugged.
• Much less water is needed for testing.
• With high-voltage tests, repairs can
be completed immediately.
ADVANTAGES OF ELD OVER INFRARED, NUCLEAR,
AND ELECTRONIC IMPEDANCE ON CONVENTIONAL
ASSEMBLIES
• ELD identifies the exact breach location.
• With low-voltage testing, by leaving
the wire in place, testing can be
completed in the future, within limitations.
• The amount of moisture needed
to enter the assembly is much
less to obtain a reading than to
identify a breach. Testing can be
completed sooner, with less sustained
damage.
Anomalies identified include but are
not limited to:
• Punctures as a result of fasteners
used by numerous other
trades.
• Punctures or splits as a result of
materials dropped on the membrane.
• Damage as a result of slits or tears
from construction traffic.
• Membrane burns as a result of welding.
• Damages as a result of slits or tears
caused by dragging equipment
across the roof.
• Pinholes in the membrane as a
result of moisture in the deck.
• Incomplete lap welds.
Implementing this state-of-the-art quality
assurance testing after membrane
installation and immediately before installation
of the overburden (be it insulation or
soil media) is the single most cost-effective
step in reducing immediate and latent
leaks.
LIMITATIONS
It should be noted that if water gets
behind flashings or under the membrane
from adjacent surfaces such as windows,
storefronts, porous masonry, or unsealed
base flashings, and there are no breaches in
the membrane or flashings, no reading will
be obtained. This is because there is no
breach in the membrane or flashing materials
to create a grounding connection.
Many owners, designers, and contrac-
Figure 4 – ELD section with overburden in place.
􀀧􀁒􀁑􀂶􀁗􀀃􀁏􀁈􀁗􀀃􀁄􀁑􀁜􀁒􀁑􀁈􀀃􀁗􀁈􀁏􀁏􀀃
􀁜􀁒􀁘􀀃􀁌􀁗􀀃􀁇􀁒􀁈􀁖􀁑􀂶􀁗􀀃􀁋􀁘􀁕􀁗􀀄
􀀨􀁙􀁈􀁕􀁜􀀃􀁋􀁒􀁏􀁈􀀃􀁜􀁒􀁘􀀃􀁓􀁘􀁗􀀃􀁌􀁑􀀃􀁜􀁒􀁘􀁕􀀃􀁖􀁗􀁄􀁑􀁇􀁌􀁑􀁊􀀃􀁖􀁈􀁄􀁐􀀃
􀁐􀁈􀁗􀁄􀁏􀀃􀁕􀁒􀁒􀁉􀀃􀀃􀁙􀁒􀁌􀁇􀁖􀀃􀁜􀁒􀁘􀁕􀀃􀁐􀁄􀁑􀁘􀁉􀁄􀁆􀁗􀁘􀁕􀁈􀁕􀂶􀁖􀀃􀁚􀁄􀁕􀁕􀁄􀁑􀁗􀁜􀀃
􀁄􀁑􀁇􀀃􀁕􀁌􀁖􀁎􀁖􀀃􀁏􀁈􀁄􀁎􀁖􀀑􀀃
􀀲􀁑􀁏􀁜􀀃􀀶􀀐􀀘􀀄􀂌􀀃􀁘􀁗􀁌􀁏􀁌􀁗􀁜􀀃􀁄􀁗􀁗􀁄􀁆􀁋􀁐􀁈􀁑􀁗􀀃􀁆􀁏􀁄􀁐􀁓􀁖􀀏􀀃􀁚􀁌􀁗􀁋􀀃􀁗􀁋􀁈􀁌􀁕􀀃
􀁓􀁄􀁗􀁈􀁑􀁗􀁈􀁇􀀃􀁕􀁒􀁘􀁑􀁇􀀐􀁓􀁒􀁌􀁑􀁗􀀃􀁖􀁈􀁗􀁖􀁆􀁕􀁈􀁚􀁖􀀃􀁓􀁕􀁒􀁙􀁌􀁇􀁈􀀃􀁐􀁄􀁛􀁌􀁐􀁘􀁐􀀃
􀁖􀁗􀁕􀁈􀁑􀁊􀁗􀁋􀀃􀁚􀁌􀁗􀁋􀁒􀁘􀁗􀀃􀁓􀁌􀁈􀁕􀁆􀁌􀁑􀁊􀀃􀁒􀁕􀀃􀁇􀁄􀁐􀁄􀁊􀁌􀁑􀁊􀀃􀁗􀁋􀁈􀀃
􀁓􀁄􀁑􀁈􀁏􀁌􀁑􀁊􀀑􀀃􀀷􀁋􀁈􀁜􀀃􀁌􀁑􀁖􀁗􀁄􀁏􀁏􀀃􀁔􀁘􀁌􀁆􀁎􀁏􀁜􀀃􀁄􀁑􀁇􀀃􀁈􀁄􀁖􀁌􀁏􀁜􀀄
􀀤􀁗􀁗􀁄􀁆􀁋􀀃􀁄􀁏􀁐􀁒􀁖􀁗􀀃􀁄􀁑􀁜􀁗􀁋􀁌􀁑􀁊􀀃􀁗􀁒􀀃􀁖􀁗􀁄􀁑􀁇􀁌􀁑􀁊􀀃
􀁖􀁈􀁄􀁐􀀃􀁕􀁒􀁒􀃀􀀃􀁑􀁊􀀃􀁚􀁌􀁗􀁋􀁒􀁘􀁗􀀃􀁓􀁌􀁈􀁕􀁆􀁌􀁑􀁊􀀃􀁗􀁋􀁈􀀃􀁓􀁄􀁑􀁈􀁏􀀑
􀀷􀁒􀀃􀁏􀁈􀁄􀁕􀁑􀀃􀁐􀁒􀁕􀁈􀀃􀁄􀁅􀁒􀁘􀁗􀀃􀁗􀁋􀁈􀀃􀁈􀁑􀁗􀁌􀁕􀁈􀀃􀀶􀀐􀀘􀀄􀂌􀀃􀁏􀁌􀁑􀁈􀀃􀁒􀁉􀀃􀀃
􀁄􀁗􀁗􀁄􀁆􀁋􀁐􀁈􀁑􀁗􀀃􀁖􀁒􀁏􀁘􀁗􀁌􀁒􀁑􀁖􀀃􀁄􀁑􀁇􀀃􀁖􀁑􀁒􀁚􀀃􀁕􀁈􀁗􀁈􀁑􀁗􀁌􀁒􀁑􀀃
􀁖􀁜􀁖􀁗􀁈􀁐􀁖􀀃􀁙􀁌􀁖􀁌􀁗􀀃􀁘􀁖􀀃􀁄􀁗􀀃
􀀶􀁈􀁈􀀃􀁘􀁖􀀃􀁄􀁗􀀃􀀬􀁑􀁗􀂶􀁏􀀃􀀵􀁒􀁒􀂿􀀃􀁑􀁊
􀀨􀁛􀁓􀁒􀀃􀀥􀁒􀁒􀁗􀁋􀀃􀀆􀀔􀀗􀀕􀀔
􀁚􀁚􀁚􀀑􀀶􀀐􀀘􀀐􀁆􀁏􀁄􀁐􀁓􀀑􀁆􀁒􀁐
􀁒􀁕􀀃􀁆􀁄􀁏􀁏􀀃􀁘􀁖􀀃􀁄􀁗􀀃􀀛􀀛􀀛􀀐􀀛􀀕􀀘􀀐􀀖􀀗􀀖􀀕􀀃
F E B R U A RY 2010 I N T E R FA C E • 3 3
tors desire to keep the wiring in place so
that the system may be used permanently.
This can be done, but there are limitations
(Figure 4). These include:
• Accuracy in leak location is diminished.
On a vegetated roof, a threedimensional
electronic field is now
being created due to the depth of the
soil. The electrical flow is shaped
like an inverted cone. The deeper the
soil, the larger the cone.
• The soil media must be wet throughout,
because an area of dry soil will
produce no conductivity, which
could result in a missed breach.
• As more layers of materials are
added on a vegetated roof, one must
be aware of the implications.
— Extruded polystyrene is an insulator.
In testing, thorough wetting
is imperative so that the
electrical flow registers moisture
on the top horizontal surface of
the insulation and down the
joints at the perimeter of the 2-
by-8-ft pieces of insulation.
— Since 20- to 40-mil polyethylene
is a widely used root barrier and
a nonconductive material, testing
must rely on water migrating
across the surface to a lap in
order to have the electrical flow
follow the water to the membrane.
Sheets may be 6-, 10-, or
20-ft wide, and in many applications,
the laps are thermally
fused or taped, resulting in
potentially greater flow distances.
— Dimple-type drain boards are
high-density polypropylene or
polyethylene (HDPE), and as
such are nonconductive, once
again re quiring water migration
and elec trical flow to laps.
• With paver-on-pedestal applications,
the pedestals are set for 3/16-in joints
between the pavers, which does not
allow sufficient room to position
ELD probes between the pavers to
take readings with a receiver.
In conclusion, ELD provides the ability
to implement exacting quality assurance
testing methods to provide owners with
longer-lasting, leak-free roofing and waterproofing
applications. ELD can also be used
in locating existing leaks on conventional
and protected membrane roof assemblies.
Within limits, ELD can be used in leak
detection with various overburden assemblies.
Another generation of leak detection
equipment will be required to fully meet
owners’ expectations for permanent leakdetection
systems.
34 • I N T E R FA C E F E B R U A RY 2010
Dave Honza has over 35 years of experience in the roofing
and waterproofing industry, 21 of which were spent with
major manufacturers, promoting products to the architectural
community and technical support and application training
to contractors. For 14 years, Honza was a roofing and waterproofing
consultant involved in identifying problems and
implementing solutions. For the last decade, Honza has
actively promoted green roofs, acting as a course trainer. He
is accredited as a Green Roof Professional (GRP) through
Green Roofs for Healthy Cities. His company, the Honza
Group, has provided ELD services since 2006.
Dave Honza
One of the most architecturally stunning
features of the 2012 London Olympic
buildings – the wave-shaped roof of the
£251 million Aquatics Centre – was lowered
into place November 11, 2009. Designed by
Iraqi-born architect Zaha Hadid, the center
will mark the gateway to the Olympic Park
in Stratford, east London.
The 160-meter-long, 3,000-ton roof is made of steel, aluminum covering, and timber
cladding and rests on two concrete supports at one end and a supporting wall at
the other. It was one of the most complex engineering and construction challenges of
the Olympic Park build, organizers stated.
British builder Balfour Beatty was the only
company left in the bidding for construction
after France’s Eiffel and Germany’s Hochtief
withdrew.
The 17,500-seat center will host swimming,
diving, and water polo during the
Olympic Games, but will be reduced to 2,500
seats afterwards. It will cover two 50-meter
pools, a dive pool, and a dry diving area.
The area, on a former industrial site, was
severely polluted with oil, tar, solvents, and heavy metals such as arsenic and lead in
the soil, which had to be cleared and decontaminated.
— financialmirror.com and other sources
Abstracts are being considered
for presentation and publication
at RCI’s 2010 Symposium on
Building Envelope Technology to
be held November 8-9, 2010, in
San Antonio, TX. Abstracts should
be 200 words and received at
1500 Sunday Drive, Suite 204,
Raleigh, NC 27607 no later than
April 16, 2010. Notification of
acceptance will be received by
May 3, and papers of accepted
speakers will be due July 9. For
more information, contact Karen
McElroy, director of conventions
and meetings, at 800-828-1902 or
kmcelroy@rci-online.org.
AP Photo by Kirsty Wigglesworth.
London Aquatic
Centre Roof
Lowered
RCI Seeks
Abstracts for
BE Symposium