Skip to main content Skip to footer

The Politics of Roof Cut Tests

May 15, 2003

July 2003 Interface • 35
Introduction
Over the last few decades, the diversity of views has grown on
whether or not roof test cuts are beneficial. On one side are roofing
contractors and their national and regional associations; on
the other side are consultants, building owners, and specification
writers. The purpose of this paper is to review what has been said
and to propose some suggestions that might lead to finding a
common ground.
Standards
There are two ASTM
standards that relate to
test cuts: D 2829 for
existing roofs and D
3617 for new construction.
Both standards
provide for the removal
of a 305 x 305 mm sample
to determine the ply
count, interply mopping
weight, and insulation
when part of the roof
membrane system. D
3617 analysis may
include top coating
before aggregate application;
D 2829 includes
flood coat and aggregate. The substantial difference between the
two standards is that D 3617 is intended for field evaluation with
any sample removed being returned to the membrane (if practicable)
and repaired. D 2829 involves destructive analysis in a laboratory
and the repair method is, therefore, not done with the
sample being replaced. The data generated by D 2829 is based on
measurement of all components of the membrane; data from D
3617 may not be based on such measurement.
The Arguments
The basic argument against is that the “… test cut is not considered
to be a reliable measure of quality control or
assurance…”1 A further argument is that a small sample taken as
outlined in D 2829 does not take into account variances in BUR
systems.2 NRCA states, “A thorough, continuous visual inspection
by a knowledgeable person… is far preferable to test cuts as a
means to monitor roof application.”3 A further argument is that
the precision and accuracy of the test method are questionable.4
The basic argument for test cuts is that they “ …can provide
quality-control information for owners, roofing manufacturers,
and roofing contractors.”5
These arguments form the basis of the controversy.
Why Test?
The asphalt, felt, and gravel used in constructing a four-ply
roof have to meet certain standards. For asphalt, these are ASTM
D 312 and CSA 123.4 in Canada; ASTM D 226 or CSA 123.3 for
organic felts; ASTM D 2178 for glass; and ASTM D 1863 for aggregate.
All these standards have ranges and/or tolerances that the
materials must meet. In some instances, the tolerance value is
0.7%. Single-ply membranes are manufactured to close tolerances
before being installed, as are modified bitumen sheets. In spite of
all these standards for materials, we are to accept that there is to
be no quality control during the on-site construction of a built-up
roof.
Engineers and consultants are increasingly being required to
certify that a completed roof meets all plans and specifications.
Issuing a certification for a roof based solely on a visual inspection
and without any hard data can incur a risk for the issuer.
Figure 1: Felt lap sample as received.
36 • Interface July 2003
This certification requirement is one important reason for plans
and specifications to call for minimum values for interply and
flood coat asphalt. Consequently, tests are required to confirm
application rates.
What do tests provide? They give data that indicate an adequate
flood coat has been applied to ensure proper aggregate
adhesion, reducing the risk of scouring and felt exposure. They
show that an adequate interply mopping is provided. This is particularly
important with glass felts to reduce the possibility of
moisture wicking.
Who is Correct?
The National Roofing
Contractors Association
(NRCA) and the
Canadian Roofing
Contractors’ Association
(CRCA) publish application
targets of 1.0 kilogram
per square meter
interply bitumen (1.2
kilograms for glass) and
3.0 kilograms per square
meter flood coat bitumen.
The tolerance is ±
25%. Having published
application values of a
specific quantity, they
then assert that the only
legitimate means of verifying
correct application is by visual inspection. Further, by implication,
they assert that regardless of a tolerance of ± 25%, it is
unreasonable to use test cuts as a means of rooftop quality control.
It is interesting to note that the Roofing Contractors
Association of British Columbia (RCABC) in its Roofing Practices
Manual Millennium Edition 7 publishes asphalt tolerances of ±
25% on any cut test and ± 10% on job total requirement with total
coverage of felts.
Ranged against this position is that of owners, architects,
engineers, and consultants who are expressing a desire to verify
that the specified product is delivered. At this point, the only
method for obtaining empirical data is to collect and analyze test
cuts.
How do we reconcile these opposing viewpoints? To do this we
need education, understanding, and cooperation. It is necessary
to educate those requiring test cuts as to what can reasonably be
expected from them and how to interpret and use the data. I
agree with the roofing associations that the use of a single or even
two or three data points to condemn a roof is imprudent. I would
not, and I know of no reputable laboratory that would suggest
that this be done.
A sufficient sample population must be analyzed to acquire
adequate data. In addition, the variables of roof construction need
to be taken into account. One to three samplings on a large roof
area, indicating borderline or below specification values, are not
enough to condemn an entire roof. Given timely analysis and
reporting, remedial action in suspect areas or agreement to monitor
them will suffice. The average of all samplings is the best indication
of overall roof application. Test cut analyses should not be
used to indict a roofer, but rather they should assist him in applying
a better roof.
It is necessary for all involved in the process to understand
the purpose and function of test cuts. The owner, consultant,
engineer, or architect must understand what the data will indicate
and how to use them. The roofer must understand that the owner
has a reasonable right to verify what is on his roof and that the
data will be used to assist rather than hinder him. This is part of
the educational process.
All parties must enter the process with a spirit of cooperation
TM
Figure 2: Felt lap sample gravel and flood coat removed.
July 2003 Interface • 37
instead of a confrontational
attitude. Part of
this co-operation
requires all parties to
know what is required,
how it will be done, and
how the end result will
be accomplished.
Testing and
Evaluation
In the late 1980s,
two separate evaluations
of test cuts
were done. One
was by ASTM,6 the
other by NRCA,
called Project
Perfect Square.7
The data generated
is interesting and
worthy of mention.
The ASTM data was
the result of a clinical
study. Samples
were constructed in
a laboratory and
then sent to six different
laboratories
for analysis. Each
laboratory received
four samples. The
data obtained showed remarkable consistency in the results
obtained:
The NRCA study used applied quantities to a 65 square foot
area. Six samples were sent to a single laboratory. The data
obtained are shown in the opposite table.
ASTM Test Data
The target range is based on published tolerances for a specific
job average, in this case 25 and 60 lbs./sq. for interply and
flood coat respectively. The low interply value was from the sample
that had the second highest flood coat value (62.3 lbs./sq.).
The low flood coat value was from a sample that had 22.2 lbs./sq.
interply mopping.
Overall, the roof was fine. The sample with low flood coat had
62.2% adhered surfacing, so surfacing loss should not be a problem.
The sample with a low interply mopping had more than
enough flood coat. The roof should be monitored but not rejected.
The ASTM study shows that accurate, reproducible results
can be obtained.
Figure 3: Felt lap sample
scrapped.
Figure 4: Example of negative (missing) headlap.
COMPONENT TARGET RANGE
Sample Weight 650 647.92 – 652.08
Total Aggregate 400 390.84 – 409.16
Adhered Aggregate 200 184.30 – 215.70
Flood Coat 60 53.99 – 66.01
Interply 25 23.98 – 26.02
Felt Plies 4.17 4.15 – 4.19
Felt Headlap 2 1.78 – 2.22
Note: All values in lbs./sq. except plies and headlaps
COMPONENT TARGET RANGE
Sample Weight 587 – 741.5
Total Aggregate 417.2 – 542.7
Adhered Aggregate 267.6 – 401.2
Flood Coat 45 – 75 42.6 – 75.9
Interply 18.75 – 31.25 17.5 – 23.6
Felt Plies N/R
Felt Headlap N/R
Note: All values are in lbs./sq.
ASTM Test Data
38 • Interface July 2003
The NRCA study confirms application variables and, if anything,
underscores the need for empirical quality control during
application.
Other Areas
Roofers in general do not have the facilities to conduct material
testing. The roofer, therefore, has to blindly accept what has
been shipped to the job site. Testing laboratories can be of assistance
in confirming that the materials being used meet the relevant
standards.
This can take the form of pre-qualifying materials on site prior
to use and/or ongoing analysis to monitor material quality.
Ongoing analysis is also beneficial in that it provides data relating
to the felts that can be utilized in the test cut analysis. Asphalt
analysis, particularly of bulk product, will verify that the roofer
received Type II not Type I or Type III or even flux. By conducting
ongoing analysis, the roofer has confidence that the materials
used are as
required by the
plans and specifications.
Conclusion
Test cuts can
be useful in several
ways. To the
owner, architect,
specification
writer, and consultant,
the results
offer useful data
on the membrane
construction. Used
properly, data can
pinpoint deficiencies
and facilitate corrective
action on new
construction. Optimally,
the data offer proof that
the membrane was
installed to specification.
The roofer benefits as
well. Analysis results
coupled with material
evaluation give proof that
the materials used meet
specification. This proof
of compliance at the time
of installation can reduce
or eliminate future disputes.
Timely reporting
of deficiencies should allow remedial action to be carried out within
a reasonable time, reducing any additional costs. Test cut data
should be regarded as a tool, not a weapon.
Instead of the posturing currently in vogue, roofing associations,
consultants, specification writers, and testing facilities
should come together to develop accepted protocols and interpretations.
If we have consensus, then we should have uniformity,
and the roofing industry will benefit.
References
1. Graham, Mark S., “Test Cuts are Not Quality Assurance,”
Professional Roofing, August 1998.
2. Ibid.
3. NRCA, Quality Control in the Application of Built-Up Roofing,
page 10.
4. LaCosse, Bob, “Studies Show Questionable Nature of Test
Cuts,” Professional Roofing, October 1989.
5. Koontz, Jim D., Letter to the Editor, Professional Roofing,
December 1998.
6. Koontz, Jim D., “Cutting Up On The Job,” Roofer
Magazine, October 1987.
7. Cullen, William, “The Perfect Square: Can it be Built?”
Roofing Spec, Feb. 1987.
Figure 6: Measuring felt exposure.
Figure 5: Felt
exposure of 9.5
inches.
Raymond A. McNulty is president of R.A.M.-Bitutech
Analytical Services Inc. Bitutech is a testing facility for asphalt
roofing materials. McNulty’s background is in product development
and quality assurance of steep and low slope asphalt
roofing materials. He is a member of ASTM and CSI and sits on
a number of technical committees with those organizations.
Raymond is also a member of RCI.
ABOUT THE AUTHOR