Skip to main content Skip to footer

Remediation Of A Lock-Strip Gasket Window Assembly

April 15, 2007

REMEDIATION OF A LOCKSTRIP
GASKET WINDOW ASSEMBLY
MATTHEW C. FARMER
WISS, JANNEY, ELSTNER ASSOCIATES, INC.
FAIRFAX, VIRGINIA
S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • NO V E M B E R 2 0 0 7 FA R M E R • 8 1
ABSTRACT
Many façades built since the 1950s employ a twopiece
rubber structural gasket system
to support glazing. This system is designed to replace a more rigid metal frame. These gaskets
are often integrated into a supporting steel or aluminum structure, used as mullions
between multiple glazing panels or to tie the glazing into a precast concrete panel wall system.
While the system offers many benefits, if poorly installed, severely aged, or damaged
during glazing replacement, the system offers no redundancy and minimal protection
against uncontrolled water leakage. Repair or remediation of the system is often difficult,
due to the inability to reliably adhere sealant to the rubber compounds. This problem, as
well as the problems associated with working on occupied buildings, can pose significant
repair challenges to buildings.
Wiss, Janney, Elstner Associates, Inc.’s recent involvement with one such project illustrates
a unique and innovative way to remediate a lockstrip
gasket system installed in precast
concrete wall panels that suffered from chronic uncontrolled water penetration. Our
solution did not require removal of glazing or modifications to the lockstrip
gaskets themselves,
though it did maintain the integrity of the barrier wall assembly. This paper presents
the history of this assembly and its common advantages and disadvantages. It also
describes this particular project and the process by which our repair strategy was developed
and implemented.
SPEAKER
MATTHEW C. FARMER — WISS, JANNEY, ELSTNER ASSOCIATES, INC. FAIRFAX,
VIRGINIA
MATTHEW C. FARMER joined Wiss Janney Elstner’s New Jersey office in 1985. Since
then, he has been involved with numerous evaluations of concrete, steel, and timber structures,
as well as failures of clay and concrete masonry, stone, and cast stone. Mr. Farmer
has concentrated on the area of design, investigation, and repair of new and existing building
envelope systems, including engagements as an expert witness for constructionrelated
litigation. He was appointed manager of the Washington, D.C. office in 1994. He is a graduate
of the University of Colorado and Cornell University and is a licensed professional engineer
in the District of Columbia, Virginia, and Maryland.
8 2 • FA R M E R S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • NO V E M B E R 2 0 0 7
REMEDIATION OF A LOCKSTRIP
GASKET WINDOW ASSEMBLY
INTRODUCTION
Many façades built since
the 1950s employ an innovative
twopiece
rubber structural
gasket system to support window
and curtain wall glazing.
Referred to as a lockingstrip
gasket system, the gaskets are
designed to replace a more rigid
metal frame. The gaskets are
often integrated with a supporting
steel or aluminum structure
and used as mullions between
glazing panels or to tie glazing
into precast concrete wall panels.
Figure 1 – Schematic of Hshaped
lockingstrip
While the system offers gasket.
many benefits, it is highly
reliant on installation practices. If improperly
installed, severely weathered, or damaged
during glazing replacement, the system
offers no redundancy and minimal protection
against uncontrolled water leakage.
Repair or remediation of the system is often
difficult, due to the inability to repair the
gaskets or reliably bond elastomeric
sealants to the rubber compounds comprising
the gasket system. These difficulties,
along with the problems normally associated
with working on occupied buildings, can
pose a significant repair challenge to lockingstrip
gasket systems that experience
uncontrolled water leakage.
THE LOCKINGSTRIP
GASKET
GLAZING SYSTEM
HISTORY1
Lockingstrip
glazing gasket systems
were first introduced for building façades in
the 1950s by the General Motors Corporation.
Manufactured by its Inland Manufacturing
division, the gaskets were an
adaptation of GMC’s automotive windshield
system. In 1961, Standard Products purchased
GMC’s glazing gasket technology
and manufactured the gaskets under the
brand name StanLock. Griffith Rubber Mills
purchased the StanLock Division of
Standard Products in 1989 and continues
to manufacture and market the twopiece
gaskets under the StanLock brand.
Although there have been a few other competing
systems introduced over the years,
StanLock continues to be an industry
leader and the most common system in use
today.
DESCRIPTION
The lockingstrip
gasket system is a
twopiece,
preformed, elastomeric mechanical
seal used to surround and attach a
building panel or glass unit to a supporting
structure made, typically, of metal or concrete.
The gasket system consists of the
gasket itself, which captures the edges of
the panel or insulating glass (IG) unit, and
a separate locking strip with
durometer (Shore A) rating that,
when forced into a groove provided
in the gasket, puts sufficient
compression on the panel
to secure it to the supporting
structure and create an intended
“watertight” seal. The lockingstrip
gasket system is also
often referred to as a “zipper
gasket,” due to its resemblance
to a zipper as the locking strip
is installed or removed.
Although a number of configurations
exist, the most common
locking strip gasket profile
is an “H” shape (see Figure 1).
This profile is designed to bridge
between a building panel and
a higher
the flange of a supporting structure, and it
is often used for individual window openings.
The gaskets are vulcanized into a single
square shape by a combination of extrusion
and injection molding. An example of
this gasket in service is shown in Figure 2.
A second common configuration of the
locking strip gasket system utilizes the “H”
shape to receive two building panels and
also incorporates a spline to mechanically
engage the supporting structure (see Figure
3). These can be completely vulcanized systems
or can consist of extruded lengths
Figure 2 – Example of Hshaped
lockingstrip
gasket securing an IG
window unit to a precast concrete
panel in service.
Figure 3 – Schematic of splinetype
lockingstrip
gasket.
S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • NO V E M B E R 2 0 0 7 FA R M E R • 8 3
replace building panels or glazing;
improper installation/removal of
the locking strip or the gasket can
lead to damage of the system and
water leakage.
MATERIAL
The most common material used for the
lockingstrip
gasket system is neoprene. It
is highly durable as well as flame,
oil,
and
chemicalresistant.
It functions well under
temperature extremes and remains elastic
with low compression set over its service
life. Neoprene is typically only available in
black. Though the material is stable under
exposure to ultraviolet light, the material
surface exposed to the environment undergoes
oxidation and forms a friable “dust” on
that surface as it degrades. This characteristic
makes adhesion of elastomeric
sealants unreliable,
since the bonding surface is
difficult to clean and continues
to break down over time.
The flexibility inherent with
the lockingstrip
gasket system
accommodates variations in
alignment between the opening
substrate and the building
panel, thereby reducing stresses
induced by racking and
glasstometal
contact. It also
can be effective in dampening
noise and vibration. The gasket
joined in the field to molded corners
and tees. Figures 4 and 5
illustrate an example of an installation
using a splinetype
gasket.
All of the gasket profile systems
rely on the installation of the
locking strip into the gasket to
secure the glazing or building panels.
Special tools and techniques
are required to properly install and
Figure 4 – Example of splinetype
lockingstrip
gasket in a
curtain wall configuration in
service.
Figure 5 – Preformed “Tee” gasket as part of a
splinelockingstrip
gasket system.
conductance between the interior and exterior
of the wall assembly. It also can easily
be designed to allow glass removal from
either the interior or exterior.
WATER PENETRATION RESISTANCE
The locking strip gasket systems are
considered barrier systems from a waterresistance
standpoint, since they do not
offer redundancy against water penetration
and do not typically incorporate drainage
provisions for water reaching the interior of
the assembly.
Water is resisted at the interface
of the gasket and the building
panel by compression of the gasket created
by the locking strip. If the gasket compression
is compromised by debris, damage, or
improper installation, water can collect in
the gasket and eventually leak to the interior.
Field sealing of splices between extruded
sections and molded intersections is also
extremely sensitive to installation techniques,
as these extend the full depth of the
extrusion and represent a direct path by
which water can reach the interior of the
structure.
REMEDIATION OF A LOCKINGSTRIP
GASKET ASSEMBLY
As previously mentioned, lockingstrip
gasket systems rely heavily on knowledgeable
technicians for proper installation and
maintenance. Over time, these systems can
be irreparably damaged during routine
glass replacement by glaziers not familiar
with the lockingstrip
technology or not
equipped with the tools necessary to correctly
replace failed glazing. Improper maintenance
can result in uncontrolled water
penetration, damage to interior finishes,
and discomfort to building occupants.
The author’s recent involvement with
one such project illustrates the potential
damage from a lack of proper maintenance
and incorrect glazingreplacement
procedures.
It also offers a unique and innovative
way to remediate the damaged lockingstrip
assembly in a costeffective
manner and
with minimal disruption to building operations.
PROJECT DESCRIPTION
The subject project is a 13story,
midrise
office building located in the midFigure
7 – Lockingstrip
gaskets were used
to secure glazing into precast concrete
wall panels.
is also a natural thermal Figure 6 – Office building utilizing a lockingbreak,
minimizing thermal strip gasket system to secure glazing.
8 4 • FA R M E R S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • NO V E M B E R 2 0 0 7
Atlantic region and originally constructed in
the 1970s. The structure consists of conventionally
reinforced concrete flatplate
floor slabs supported by conventionally
reinforced columns. The exterior façade
consists of precast concrete panels that
incorporate rectangular openings recessed
between horizontal spandrels and vertical
“fins” to accept individual, insulatingglass
(IG) units to form the windows (see Figures
6 and 7). The upper floors vary slightly from
the typical precast/window configuration in
that glazing units, and spandrel panels are
stacked to form an uninterrupted “column”
of glazing between the precast concrete fins
(see Figure 8). An Hshaped
lockingstrip
glazing gasket system is used to engage the
IG units and secure them to flanges on the
precast concrete panels at the opening
perimeters.
Over the past several years, the building
suffered from ongoing uncontrolled water
infiltration and IGunit
failure, along with
other deficiencies resulting from deferred
maintenance of the exterior wall system.
The project objective was to determine the
cause of the water infiltration and develop
appropriate repairs to address the deficient
conditions observed. The following specific
conditions were observed with respect to
Figure 9 – Example
of lockingstrip
gasket deformation.
Figure 8 – Precast
concrete wall panels also
incorporate vertical groupings of glazing and
spandrel panels.
the locking strip
gasket system:
• Many of the
gaskets were distorted
and misaligned
due to a
lack of compliance
with construction
tolerances. This
condition resulted
in distorted gasket
position and poor
glass/gasket seals that led
to water infiltration (see
Figures 9 and 10).
• Some gaskets did not completely
engage the glazing.
Sealant was typically applied
to fill the gap between
the glazing and the gasket
(see Figure 11).
• Many of the locking strips
were missing, leaving the
gasket without adequate
compression against the
glass and allowing water to
enter the gasketglazing
pocket (see Figure 12). The
gaskets were also often cut
at the corners to allow for
glazing replacement without
removal of the locking
strips. This condition also
led to reduced glass compression
and allowed water
in the glazing pocket to
leak to the interior.
• Water collected in the glazing
pockets. Because the
IG units were not
Figure 10 – Example of lockingstrip
gasket
deformation.
Figure 11 – Sealant was used to fill the gaps
between the glazing and the gasket where fit
was poor.
S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • NO V E M B E R 2 0 0 7 FA R M E R • 8 5
Figure 12 – Location
where the locking
strip of the gasket
system is missing.
Note cut at corner.
shimmed, their edge seals
remained wet for prolonged
periods, leading to
eventual failure in the
form of condensation
between the glass bites
and loss of insulating
properties (see Figure 13).
• Elastomeric sealant was
present between the lockingstrip
gasket and the Figure 13 – Evidence of water accumulation in
precast concrete panels, the glazing pocket including IG spacer
as well as between the corrosion.
gasket and the glass. This
sealant was deteriorated and lacked ditional barrier system repair
adhesion to the gasket system (see approaches impractical without
Figure 14). substantial associated maintenance.
• Although there were relatively few
CHALLENGES opening sizes, there were multiple
This project presented many challenges configurations of the glazing units
with respect to the remediation design. (see prior Figure 8) and variability in
These are discussed below: the relationship between the gaskets
• The client required that the building and the edges of the precast conremain
fully occupied throughout crete openings. It was preferable
the course of the work, with minimal from a design and maintenance perdisruption
to the tenants. This spective to utilize a similar and connecessitated
that the majority of the sistent approach at as many window
repair work be conducted
from the exterior and
eliminated the potential
for repairs requiring
removal of glass on a
large scale.
• It was critical to provide
an adequate overlap between
the IG units and
the gasket, or glass bite,
to avoid any reduction
in resistance to wind
loading.
• The inability to reliably
bond elastomeric compounds
to the neoprene
gaskets made more traFigure
15 – Overlay extrusion application
at typical windowsill.
Figure 14 – Sealant between the gasket
and the precast concrete panel, as well
as between the gasket and the glass,
had failed.
configurations as possible, regardless
of the deviations.
• The client appreciated and wanted
to maximize the clear glass area at
each opening to preserve natural
light and desirable views.
PROPOSED SOLUTION
After reviewing the existing field conditions,
it was decided to design an overlay
barrier system for the existing lockingstrip
gasket system. The final solution consisted
of a customfabricated,
siliconecompatible
rubber extrusion applied directly over the
existing glazing gaskets that bridged from
the glass to the adjacent precast concrete
panels without relying on adhesion to the
gasket itself.
The final design was an “L”shaped
extrusion formed to fit the external profile of
the lockingstrip
gasket at the glass line.
The edge in contact with the glass was
Figure 16 – Overlay extrusion application at
typical window head.
8 6 • FA R M E R S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • NO V E M B E R 2 0 0 7
Figure 17 – Overlay extrusion
application where glazing meets at
inside corners.
thickened to allow it to be “bedded” in
sealant against the glass surface, but without
a visible external seal. The opposite leg
length was trimmed to accommodate variable
dimensions between the lockingstrip
gasket and the surrounding precast concrete.
Once in place, a fillet bead of sealant
was applied between the new overlay extrusion
and the precast concrete panels, creating
a watertight seal. Figures 15 through 18
illustrate the final profile concept and its
relationship to the existing wall system at
typical locations. This repair approach
offered several key advantages with respect
to the overall project:
• The bedding of the extrusion in
sealant eliminated exposure of the
sealant to the environment, prolonging
its service life. It also offered a
clean, narrow sight line in comparison
to an exposed wet seal using
elastomeric sealant.
• The installation of the overlay gasket
did not require removal of the existing
sealant between the existing
locking strip gasket and the precast
concrete, saving cost and eliminating
a laborintensive
step in the
repair process.
• The gaskets are made of siliconecompatible
rubber (SCR), a highly
durable, environmentally stable
material. It has many of the qualities
and the appearance of the original
neoprene gaskets, but reliably
accommodates the application of
elastomeric sealants.
• The entire installation could be performed
from the exterior without
glass removal.
• Repairs to the original locking strip
Figure 18 – Overlay extrusion application where
glazing and spandrel panels meet vertically.
figurations on the project.
Contract documents were
developed for the design to provide
sufficient detailing and
information for the repair contractors
to competitively bid the
fabrication and installation of
the overlay extrusions and associated
work. Once the bids were
received, each bid was carefully
examined to assure that it recognized
the intricacies of the repair
process necessary to arrive at a
final overlay extrusion product.
Each contractor was asked to
submit his preferred extrusion
manufacturer as part of his bid.
After awarding the contract
gaskets were not required. for the repairs to the successful bidder, the
• All of the various glazing configuraspecified
overlay extrusion manufacturer
tions could be addressed using comwas
contacted to perform field measurebinations
of the custom overlay ments and develop a prototype extrusion for
extrusion and widely available stantrial
installation (see Figure 19).
dard preformed
SCR shapes. A trial installation proved critical to
• New sealant installed in joints refine the final extrusion design and develbetween
the precast
concrete
panels could be
seamlessly integrated
into the
sealant joints
around the window
openings.
Despite the many
advantages of this remediation
design, one
major drawback to this
solution is the need to
access the exterior and
remove/reinstall the
overlay extrusions to
replace failed IG units in
the future. The owner
was provided with attic
stock for future repairs
/replacement.
IMPLEMENTATION
The first steps
toward the repair implementation
began with
design of the concept.
This involved field measuring
and documenting
the various glazing conditions
and components
to assure that the design
concept could address
the multiple glazing conFigure
19 – An early schematic of the overlay extrusion
profile proposed by the manufacturer.
Figure 20 – Final overlay extrusion profile. Note the
modifications to vertical leg (area circled).
S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • NO V E M B E R 2 0 0 7 FA R M E R • 8 7
Figure 22 – Example of final overlay extrusion
corner detail developed during the trial
installation.
sult, it was discovered that
the extrusion leg bearing on
the glass was not being fully
bedded, leading to water
entrapment behind the overlay
extrusion and uncontrolled
water leakage (see
Figure 23). In response, the
installation methods were
adjusted to assure a waterFigure
21 – Trial installation of overlay tight bedseal
that could be
extrusion was used to optimize corner and visually verified from the
overlap detailing. building interior.
RESULTS
Once an effective installation
procedure was estabop
an efficient and reliable installation procedure.
Minor modifications included a
longer leg to accommodate greater deviations
in distance between the original gasket
and the precast
concrete panels, as
well as a shorter leg
bearing on the glass
to assure it did not
displace outward
when compressed
(see Figure 20). The
trial installation also
allowed for the
opportunity to experiment
with different
corner treatments
to maximize
gures 21 and 22).
Once the overlay extrusion
profile and the installation procedure
were finalized, a mockup
installation was
performed to
establish the
standards for
the project and
for the client’s
aesthetic approval
prior to
implementing
repairs buildingwide.
Wat
e r p
e n e t r a tionresistance
testing was conducted to
verify that the overlay
extrusion concept would
be successful. As a relished,
the overlay extrusions
were applied with surprising quickness.
They maximize clear window area while
substantially reducing water penetration.
This method avoided expensive deglazing
Figure 23 – The success of the overlay system is
heavily dependent upon full bedding of the
extrusion to the glass.
Figure 25 – Example of completed overlay extrusion
installation at upper floors where glazing and
Figure 24 – Example of completed overlay
extrusion at a typical punched window opening.
wa t e r t
i g h t n e s s
while simplifying the
installation (see Fispandrel
panels are joined vertically.
8 8 • FA R M E R S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • NO V E M B E R 2 0 0 7
and gasketreplacement
options, while having
a minimal impact on the overall wall
assembly. Overlaying
the damaged lockingstrip
glazing gasket
system resulted in a
crisp, clean line
around the glass that
is very similar in
appearance to the
original lockingstrip
gasket system installation
(see Figures 24
through 27). The overlay
extrusions integrated
into the existing
wall system
should continue to
serve well into the
future as an effective barrier against uncontrolled
water penetration with minimal
maintenance requirement.
ACKNOWLEDGEMENTS
The author wishes to recognize the contributions
to this project and paper from
Griffith Rubber Mills, of Eugene, Oregon;
Tremco Sealant/Weatherproofing Division,
of Ashland, OH; Suzanne Thorpe, project
associate (WJE); and Rita Sparacino, project
associate (WJE).
1 StanLock Lockstrip Gasket Systems
product literature, available at
www.stanlock.com.
EDITOR’S NOTE: A
shortened version of
this paper, titled,
“Repairing a Gasket
with a Gasket; Remediation
of a LockingStrip
Window Gasket
Assembly Provides Similar Appearance,
Effective Water Barrier,” appeared in the
Spring 2007 issue of Applicator magazine,
published by the Sealant Waterproofing &
Restoration Institute.
S Y M P O S I U M O N B U I L D I N G E N V E L O P E T E C H N O L O G Y • NO V E M B E R 2 0 0 7 FA R M E R • 8 9
Figure 27 – Completed building exterior renovation that
incorporates overlay extrusions to remediate a damaged
lockingstrip
gasket system.
Figure 26 – Typical appearance of the
completed overlay extrusion installation at
a punched window opening.