Skip to main content Skip to footer

Continuous Insulation for Code-Compliant, High-Performance Exterior Walls

May 15, 2012

J A N U A RY 2012 I N T E R FA C E • 1 3
INTRODUCTION
National model energy codes are
advancing the way in which we approach
building commercial and residential exterior
walls by emphasizing the use of continuous
insulation (CI) systems, which provide a
continuous insulation layer over an entire
wall, not just in the wall cavities. Building
science experts and energy-efficiency programs
such as EnergyStarTM have known for
some time that CI is a very effective way to
insulate building envelopes for energy savings.
Now, modern building and energy conservation
codes are putting this knowledge
into mainstream practice in response to
national interest, resulting in policy to better
conserve energy.
WHAT IS CONTINUOUS INSULATION?
Continuous insulation is defined as
“insulation that is continuous across all
structural members without thermal
bridges other than fasteners and service
openings. It is installed on the interior [or] exterior, or is integral to any opaque surface
of the building envelope.”1 Figures 1A-1C
show several common applications of CI.
As shown in Figure 1A-1C, continuous
insulation can be used with a variety of wall
structural systems and cladding materials
such as cement board, PC stucco, wood lap,
brick veneer, stone, and vinyl siding.
Furthermore, CI can be placed on the interior
or exterior side of the wall with proper
consideration of climate-dependent moisture
vapor control code requirements. For
example, it is common to place CI on the
inside face of foundation walls and also
above-grade masonry walls, which is considered
a typical practice in Florida where
the exterior masonry wall face is parge-coated.
Finally, it is possible to use CI alone to
meet energy code without any cavity insulation
for the ultimate “warm-wall” design.
Figures 1A-1C – Light frame and
mass wall systems with
continuous insulation for codecompliant
residential and
commercial building construction.
CONTINUOUS INSULATION MATERIALS
There is a variety of code-compliant foam plastic insulating sheathing
materials that can be selected to meet a multiplicity of CI design applications,
as discussed above. The most common products are manufactured
in accordance with ASTM C578 or ASTM C1289 (www.astm.org). Material
types include expanded polystyrene (EPS), extruded polystyrene (XPS), and
polyisocyanurate (polyiso) foam. Each product type has different thermal
properties that affect required thickness, costs, and capabilities (see Table
1). Model building code requirements for foam plastics are found in
Chapter 26 of the International Building Code and Section R316 of the
International Residential Code (www.iccsafe.org). A technical bulletin about
the use of polyiso insulation as CI can be found at www.polyiso.org.
ENERGY CODE COMPLIANCE WITH CONTINUOUS INSULATION
There are at least two good reasons to include CI in exterior wall assemblies:
code compliance and high performance. CI provides one of the most
thermally efficient ways of complying with modern energy codes. It practically
eliminates avoidable heat loss due to thermal bridging in walls that
are not continuously insulated (see Figures 2A–2C). Modern energy code
requirements for walls including CI are shown in Figure 3, together with a
color-coordinated U.S. climate zone map (Figure 4). Clearly, CI plays a signi
ficant role in advancing energy codes and best practices for a more energyefficient
future.
14 • I N T E R FA C E J A N U A RY 2012
CONTINUOUS INSULATION R-VALUE PER INCH
MATERIAL TYPE OF THICKNESS
EPS (ASTM C578, Type II) 4.0
XPS (ASTM C578, Type X) 5.0
Polyiso (ASTM C1289, Type 1) 6.0
Table 1 – Examples of R-Value for common types of continuous insulation (foam sheathing).
Figure 2A – Cavity insulation only.
Figure 2B –
Cavity
insulation
only.
Figure 2C – Wall with continuous
insulation.
Figure 3 – Modern energy-code R-value requirements for commercial and residential
building walls (ci = continuous insulation).
1. IECC = International Energy Conservation Code published by the International Code
Council, Inc. Refer to ASHRAE 90.1 for alternate code-compliant wall R-values.
2. Wall R-values are shown as cavity insulation alone or as XX + X where the first
number is the cavity insulation R-value and the second is for continuous insulation.
Continuous insulation “ci” R-values are shown in red.
3. The commercial wall R-values are based on all commercial building-use groups, except
R (residential), which may require additional continuous insulation R-value depending
on climate zone.
4. Refer to climate zone map (Figure 4) for geographic extent of climate zones listed in
Figure 3. 610.579.9075
www.Durapax.com
RUGGED &
RECYCLED
Durapax Coal Tar
Delivers Roofing
Reliability
Coal tar is the most reliable and
long-lasting membrane roofing
technology for flat and low-slope
commercial roofs, due to its
superior resistance to weather
extremes, extended exposure to
ponded water, and low total cost
of ownership.
As a pre-consumer recycled
product, coal tar contributes
to your LEED certification
(Credit #4); and may qualify
as a locally-produced material
(Credit #5). Durapax coal tar
roofing systems are ideal under
vegetated roofs, which are
subject to constant moisture. And
coal tar’s exceptionally long life
span represents the ultimate in
sustainability, with less landfill
volume generated.
Specify your next “green roof”
with a Durapax coal tar roofing
system.
J A N U A RY 2012 I N T E R FA C E • 1 5
BUILDING CODE COMPLIANCE WITH CONTINUOUS
INSULATION
Fortunately, there are many options
available to arrive at an optimal, buildingcode-
compliant exterior wall assembly
using CI. To begin, CI may be used as oversheathing
or as the sole sheathing layer on
the outside of an exterior wall. Over-sheathing
is simply the installation of CI directly
over a solid wall (like masonry or concrete)
or over solid structural sheathing such as
wood structural panels or gypsum sheathing.
Which approach to use is best determined
by proper consideration and coordination
of interrelated design decisions. For
example, if structural sheathing is used as
wall bracing, an exterior application of CI
must be done as over-sheathing (unless the
structural sheathing is installed over the CI,
and bracing capacity is adjusted accordingly).
Or, if an exterior fire-rated assembly is
required (e.g., very small building separation
distances), the CI may be placed over a
layer of Type X gypsum sheathing.
Conversely, if X-bracing is used to brace
exterior bearing walls (or for typical nonload-
bearing curtain walls), CI can be used
as the sole sheathing layer (including interior
sheathing/finish as required). Thus, the
decision to over-sheath with CI or use it as
the primary sheathing layer must be integrated
with other building design decisions.
Some other important wall design and
building code-compliance considerations
include those explored below.
Water-Resistive Barrier – Many CI
products can be used as a code-compliant,
water-resistive barrier layer behind
cladding. Sheathing joints and interfaces
with other wall components must be properly
flashed by an approved means, usually
by application of a durable flashing tape
and mechanical flashings as appropriate.
Refer to manufacturer installation instructions
and code-compliance data.
Wind Pressure Resistance – When
used as the sole sheathing layer on the
exterior side of an exterior wall, CI must be
capable of resisting design wind pressure.
Fortunately, many code-compliant CI solutions
are available. Refer to Technical Eval –
uation Report TER No. 1006-01, “Pre scrip –
tive Wind Pressure Performance of Foam
Plastic Insulation Used as Insulating
Sheath ing in Exterior Wall Covering Assem –
blies” (www.foamsheathing.org). For specific
products, refer to the manufacturer’s
installation instructions and design data.
Be sure to verify the wind pressure resistance
of other wall assembly components,
including framing and siding. Wind pressure
testing of CI has shown that the wall
assembly capacity may be governed by
framing, connections, or siding, not the CI
material.
Cladding (Siding) Attachment – Clad –
ding attachments must provide the required
wind pressure resistance (attachment to
framing behind foam sheathing) and must
also cantilever through the foam sheathing
to support the weight of the cladding and
also furring, if used. Various proprietary
and standard fasteners can be used for this
purpose, based on recent testing sponsored
by the Foam Sheathing Coalition (FSC), the
New York State Energy Research and
Development Authority (NYSERDA), and the
Steel Framing Alliance. For additional information
and design guidance, refer to the
FSC’s Tech Matters “Guide to Attaching
Exterior Wall Coverings Through Foam
Sheathing to Wood or Steel Wall Framing”
(www.foamsheathing.org). This document
provides code-compliant fastening recommendations
for cladding weights ranging
from <3 psf to 25 psf and foam thicknesses
ranging from ½ to 4 in. Requirements are
also provided for attachment of wood or
steel furring such that cladding attachments
do not need to penetrate the CI layer.
Similar fastener requirements have also
been adopted into the 2010 New York State
Energy Code.
Fire Performance – Foam plastics are
held to a very comprehensive set of fire performance
requirements which, in some
cases, exceed those applied to other materials.
As mentioned, these requirements are
found in IBC Chapter 26 and IRC Section
R316. The requirements include various
types of fire tests and criteria to address
flame spread, smoke development, ignition
protection, etc. By far the most significant
code requirement that applies to walls with
continuous insulation (foam plastics) is the
NFPA 285 flame spread test, which uses
full-scale, multistory wall assemblies. With
appropriate installation details, material
properties, and wall assembly components,
a substantial number of wall assembly variations
have passed the requirements of
NFPA 285, and that number is growing
steadily. For more information, refer to
FSC’s Tech Matters’s “NFPA 285 Tested
Assemblies Using Foam Sheathing”
(www.foamsheathing.org) and the manufacturer’s
technical data to be sure the latest
available information is used.
It is interesting to note that some common
code-compliant wall assemblies using
materials other than CI are unable to pass
the NFPA 285 test. But this is just a further
indication that code-compliant continuous
insulated walls are fire-safe. Finally, wall
assembly compliance with NFPA 285 is not
required for buildings meeting limitations
for Type V construction or otherwise
designed with height and area sizes with
use of fire separation walls to allow consideration
as Type V construction. NFPA 285
Figure 4 – U.S. Climate Zone Map. Source: 2006 International Energy Conservation Code
(IECC).
16 • I N T E R FA C E J A N U A RY 2012
J A N U A RY 2012 I N T E R FA C E • 1 7
compliance also is not required for one- and
two-family dwelling construction.
CONCLUSION
Continuous insulation or “CI” can be
integrated into exterior wall assemblies in
many ways to provide code-compliant, highperformance
wall constructions. CI can
serve several important functions, including
continuous thermal insulation, moisture
vapor control, water-resistive barrier, and
air barrier. Some proprietary insulated
sheathing laminates can even be used as
structural bracing. When used as a multifunctional
sheathing, CI simplifies the steps
to construct a code-compliant, highperformance
wall assembly. For more information
on the advantages of continuous
insulation over other noncontinuous insulation
wall sheathing choices, refer to
“Overview of Wall Sheathing Options: The
Value of Foam Sheathing as a Wall
Covering” (www.foamsheathing.org).
FOOTNOTE
1. ASHRAE 90.1-2007, Energy Standard
for Buildings Except Low-Rise
Residential Buildings, American
Society of Heating, Refrigerating,
and Air-Conditioning Engineers,
Inc., Atlanta, GA.,
Jay Crandell, PE, (d/b/a ARES Consulting) has over 22
years of experience in building codes and standards development,
innovative building technology research, construction,
and design. ARES Consulting serves the technical
needs of government agencies, associations, manufacturers,
builders, and owners. For more information, refer to
www.aresconsulting.biz.
Jay Crandell, PE
The Canadian economy continues
to outperform its U.S. counterpart,
according to McGraw-Hill
Construction Research & Analytics.
Its real GDP was expected to
increase 2.1% in 2011, as opposed
to 1.6% in the U.S.; and 2.4% versus
2.2% in 2012. From a provincial
standpoint, Alberta, British Colum –
bia and Saskatchewan will lead the
country in growth, fueled by a
booming resource sector. The larger
provinces of Ontario and
Quebec will be restrained by their
weak housing markets.
– ENR
Canadian
Construction
Recovering
More Quickly
Fiberboard Structural Sheathing
is recognized in the 2012 ICC In-
􀆚􀄞􀆌􀅶􀄂􀆟􀅽􀅶􀄂􀅯􀀃 􀁚􀄞􀆐􀅝􀄚􀄞􀅶􀆟􀄂􀅯􀀃 􀀒􀅽􀄚􀄞􀀃 􀄨􀅽􀆌􀀃
use as
Wall Bracing and
􀀒􀅽􀅶􀆟􀅶􀆵􀅽􀆵􀆐􀀃􀁞􀅚􀄞􀄂􀆚􀅚􀅝􀅶􀅐􀍘􀀃􀀃
􀀾􀅽􀅽􀅬􀀃􀄨􀅽􀆌􀀃􀆌􀄞􀄨􀄞􀆌􀄞􀅶􀄐􀄞􀆐􀀃􀆚􀅽􀀃􀁞􀀦􀀑􀀃􀄂􀅶􀄚􀀃
􀀒􀁞􀍲􀁞􀀦􀀑􀀃􀅝􀅶􀀃􀆚􀄂􀄏􀅯􀄞􀆐􀀃􀄂􀅶􀄚􀀃􀄮􀅐􀆵􀆌􀄞􀆐􀀃􀅝􀅶􀀃
􀆐􀄞􀄐􀆟􀅽􀅶􀆐􀀃􀁚􀏲􀏬􀏮􀍘􀏭􀏬􀀃􀄂􀅶􀄚􀀃􀁚􀏲􀏬􀏮􀍘􀏭􀏮􀍘􀀃
To learn more about the
􀄮􀄏􀄞􀆌􀄏􀅽􀄂􀆌􀄚􀀃􀅝􀅶􀄚􀆵􀆐􀆚􀆌􀇇􀀃􀇀􀅝􀆐􀅝􀆚􀀃
􀇁􀇁􀇁􀍘􀄮􀄏􀄞􀆌􀄏􀅽􀄂􀆌􀄚􀍘􀅽􀆌􀅐􀍘
􀁤􀅚􀄞􀀃 􀀄􀀦􀀄􀀃 􀅝􀆐􀀃 􀄐􀄞􀅯􀄞􀄏􀆌􀄂􀆟􀅶􀅐􀀃 􀏮􀏬􀀃 􀇇􀄞􀄂􀆌􀆐􀀃
􀅽􀄨􀀃􀆐􀄞􀆌􀇀􀅝􀄐􀄞􀀃􀆚􀅚􀅝􀆐􀀃􀇇􀄞􀄂􀆌􀍘􀀃􀀄􀆐􀀃􀆉􀄂􀆌􀆚􀀃􀅽􀄨􀀃􀆚􀅚􀄞􀀃
􀄐􀄞􀅯􀄞􀄏􀆌􀄂􀆟􀅽􀅶􀀃 􀇁􀄞􀀃 􀄂􀆌􀄞􀀃 􀄐􀅚􀄂􀅶􀅐􀅝􀅶􀅐􀀃 􀅽􀆵􀆌􀀃
􀅶􀄂􀅵􀄞􀀃 􀆚􀅽􀀃 􀆌􀄞􀄐􀅽􀅐􀅶􀅝􀇌􀄞􀀃 􀆚􀅚􀄂􀆚􀀃 􀇁􀄞􀀃 􀆌􀄞􀆉-
􀆌􀄞􀆐􀄞􀅶􀆚􀀃 􀄂􀅯􀅯􀀃 􀅽􀄨􀀃 􀆚􀅚􀄞􀀃 􀁅􀅽􀆌􀆚􀅚􀀃 􀀄􀅵􀄞􀆌􀅝􀄐􀄂􀅶􀀃
􀅵􀄂􀅶􀆵􀄨􀄂􀄐􀆚􀆵􀆌􀄞􀆌􀆐􀍘􀀃 􀀄􀄐􀆟􀇀􀅝􀆟􀄞􀆐􀍕􀀃 􀄂􀄚-
􀄚􀆌􀄞􀆐􀆐􀍕􀀃 􀆉􀅚􀅽􀅶􀄞􀍕􀀃 􀄞􀅵􀄂􀅝􀅯􀀃 􀄂􀅶􀄚􀀃 􀇁􀄞􀄏􀆐􀅝􀆚􀄞􀀃
􀆌􀄞􀅵􀄂􀅝􀅶􀀃􀆚􀅚􀄞􀀃􀆐􀄂􀅵􀄞􀍘
􀁤􀅽􀀃􀅯􀄞􀄂􀆌􀅶􀀃􀅵􀅽􀆌􀄞􀀃􀇀􀅝􀆐􀅝􀆚􀀃
􀇁􀇁􀇁􀍘􀄮􀄏􀄞􀆌􀄏􀅽􀄂􀆌􀄚􀍘􀅽􀆌􀅐􀍘
american
association
FIBERBOARD
􀂋
􀀔􀀜􀀜􀀔􀀐􀀕􀀓􀀔􀀔
in a century old industry
c e l e b r a t i n g 2 0 y e a r s
􀀦􀆌􀅽􀅵􀀃􀆚􀅚􀄞􀆌􀄞􀀃􀆚􀅽􀀃􀅚􀄞􀆌􀄞􀍗
american
association
FIBERBOARD
􀂋
􀀔􀀜􀀜􀀔􀀐􀀕􀀓􀀔􀀔
in a century old industry
c e l e b r a t i n g 2 0 y e a r s
american
association
FIBERBOARD
􀂋
􀀔􀀜􀀜􀀔􀀐􀀕􀀓􀀔􀀔
in a century old industry
c e l e b r a t i n g 2 0 y e a r s
􀁴􀅚􀇇􀀃􀆉􀄂􀇇􀀃􀄂􀀃􀆐􀅝􀅐􀅶􀅝􀄮􀄐􀄂􀅶􀆚􀀃􀆉􀆌􀄞􀅵􀅝􀆵􀅵􀀃􀄨􀅽􀆌􀀃
􀅐􀇇􀆉􀆐􀆵􀅵􀀃 􀄏􀄂􀆐􀄞􀄚􀀃 􀆌􀄞􀄐􀅽􀇀􀄞􀆌􀇇􀀃 􀆉􀆌􀅽􀄚􀆵􀄐􀆚􀆐􀀃
􀄨􀅽􀆌􀀃􀆵􀆐􀄞􀀃􀅝􀅶􀀃􀀒􀅯􀄂􀆐􀆐􀀃􀀄􀀃􀄂􀅶􀄚􀀃􀀒􀅯􀄂􀆐􀆐􀀃􀏭􀀃􀆌􀄂􀆚􀄞􀄚􀀃
􀆌􀅽􀅽􀄨􀀃􀄂􀆐􀆐􀄞􀅵􀄏􀅯􀅝􀄞􀆐􀍍􀀃
􀀒􀅽􀅶􀆐􀅝􀄚􀄞􀆌􀀃􀀦􀅝􀄏􀄞􀆌􀄏􀅽􀄂􀆌􀄚􀍊
􀁺􀀜􀁞􀍕􀀃 􀀦􀀯􀀑􀀜􀁚􀀑􀁋􀀄􀁚􀀘􀍘􀀃 􀀄􀆉􀆉􀆌􀅽􀇀􀄞􀄚􀀃 􀅝􀅶􀀃
􀆚􀅚􀅽􀆵􀆐􀄂􀅶􀄚􀆐􀀃 􀅽􀄨􀀃 􀀒􀅯􀄂􀆐􀆐􀀃 􀏭􀀃 􀄂􀅶􀄚􀀃 􀀒􀅯􀄂􀆐􀆐􀀃 􀀄􀀃
􀆌􀄂􀆚􀄞􀄚􀀃 􀆌􀅽􀅽􀄮􀅶􀅐􀀃 􀆐􀇇􀆐􀆚􀄞􀅵􀀃 􀄂􀆐􀆐􀄞􀅵􀄏􀅯􀅝􀄞􀆐􀍖􀀃
􀄮􀄏􀄞􀆌􀄏􀅽􀄂􀆌􀄚􀀃 􀅝􀆐􀀃 􀆚􀅚􀄞􀀃 􀄚􀆵􀆌􀄂􀄏􀅯􀄞􀍕􀀃 􀅐􀆌􀄞􀄞􀅶􀍕􀀃
􀆋􀆵􀄂􀅯􀅝􀆚􀇇􀀃􀆌􀅽􀅽􀄮􀅶􀅐􀀃􀆉􀆌􀅽􀄚􀆵􀄐􀆚􀀃􀆐􀄞􀆌􀇀􀅝􀅶􀅐􀀃􀆚􀅚􀄞􀀃
􀅚􀅝􀅐􀅚􀀃􀆋􀆵􀄂􀅯􀅝􀆚􀇇􀀃􀄚􀄞􀅵􀄂􀅶􀄚􀆐􀀃􀅽􀄨􀀃􀇇􀅽􀆵􀆌􀀃􀄏􀆵􀅝􀅯􀄚-
􀅝􀅶􀅐􀆐􀀃􀇁􀅚􀅝􀅯􀄞􀀃􀄂􀆚􀀃􀆚􀅚􀄞􀀃􀆐􀄂􀅵􀄞􀀃􀆟􀅵􀄞􀀃􀄂􀆉􀆉􀄞􀄂􀅯-
􀅝􀅶􀅐􀀃􀆚􀅽􀀃􀇇􀅽􀆵􀆌􀀃􀄐􀅯􀅝􀄞􀅶􀆚􀍛􀆐􀀃􀄏􀆵􀄚􀅐􀄞􀆚􀄂􀆌􀇇􀀃􀄐􀅽􀅶-
􀆐􀆚􀆌􀄂􀅝􀅶􀆚􀆐􀍘􀀃
􀁞􀄂􀇀􀅝􀅶􀅐􀀃􀎨􀎨􀎨􀎨􀀃􀅵􀄂􀅬􀄞􀆐􀀃􀎨􀀜􀁅􀁞􀀜􀍘
􀁤􀅽􀀃􀅯􀄞􀄂􀆌􀅶􀀃􀅵􀅽􀆌􀄞􀀃􀇀􀅝􀆐􀅝􀆚􀀃􀇁􀇁􀇁􀍘􀄮􀄏􀄞􀆌􀄏􀅽􀄂􀆌􀄚􀍘􀅽􀆌􀅐􀍘