Skip to main content Skip to footer

Electronic Leak Detection: Sound Science, Not a Magic Wand

July 8, 2017

Due to its many advantages
over flood testing, membrane
integrity testing with
electronic leak detection
(ELD) has rapidly become
the first choice for owners,
manufacturers, specifiers, consultants, and
contractors around the world. ELD on roofing
and waterproofing membranes is proving
to be faster, safer, more accurate, and
often less expensive than flood testing.
However, as with all new technologies, there
are growing pains.
When first introduced, ELD was largely
utilized for membrane integrity testing on
vegetative roofing assemblies and other
inverted roof membrane assemblies (IRMAs)
that would receive overburden. Now that
the benefits of ELD are more widely recognized,
it is being specified for a much
broader range of roofing and waterproofing
projects. However, the vast array of roofing
and waterproofing materials and constructions
means there can be confusion as
to what constitutes a testable assembly.
Increasingly, testing firms are being asked
to “wave the magic wands” and pinpoint
leak locations in systems that can be challenging
or impossible to test.
This article will address some of the
factors affecting the testability of commonly
employed roofing and waterproofing
assemblies, the benefits of installing alternative
grounding media, and the challenges
involved in leak detection on systems with
overburden.
ELD on Conventional Insulated
Roofing Systems
Electronic leak detection requires three
conditions for accurate testing: a grounding
medium beneath the membrane to receive
the electric current (typically a structural
concrete deck, metal deck, or alternative
grounding medium), a membrane that is
electrically nonconductive, and no electrically
insulating materials
between the membrane
and the ground.
ELD testing has always
been straightforward on
membranes applied directly
to a highly conductive
substrate such as a structural
concrete deck (Figure
1). Now ELD is often the
go-to integrity test on conventional
roofing systems,
with insulation installed
between the membrane
and the conductive deck.
However, the same properties
that make insulations
and coverboards thermally
insulating also create
electrical resistance to the
current utilized with ELD
(Figure 2). The presence
of these poorly conductive and nonconductive
materials typically requires that an
alternative ground be placed in the system.
Two commonly available ground materials
are lightweight wire grid and electrically
conductive primer. However, there are differences
of opinion regarding the reliability
of leak detection utilizing these alternative
grounds. In 2014, ASTM released Standard
D7877, providing guidelines for ELD testing
on conventional insulated systems:
2 0 • RC I I n t e r f a c e J u l y 2 0 1 7
Figure 1 – ELD test results are extremely reliable when the
membrane is applied directly to a highly conductive structural
concrete deck.
“In roof assemblies where the membrane
is installed over electric insulating
material such as insulating
foam or a protection board, or both,
the electric path to any conductive
deck is interrupted. The situation
can be remedied by placing a conductive
material directly under the
membrane. The conductive material
provides the return path for the test
currents.”
There are two commonly employed
responses to the requirements of D7877.
An electrically conductive primer can be
applied directly under the membrane (Figure
3), or conductive wire grids can be installed
directly under some membrane products
(Figure 4). However, while some manufacturers
have approved the use of conductive
primer in their assemblies, others are still
performing compatibility testing with their
materials. Also, some membrane manufacturers
have not approved the installation of
wire grid directly under their membranes.
This often leads to the placement of the
metal grid between the coverboard and the
insulation, rather
than directly
under the membrane
(Figure 4).
The effectiveness
of placing
wire grids under
c o v e r b o a r d s
remains in dispute.
While some
ELD vendors
express confidence
in testing
assemblies where
a wire grid is
installed under
the coverboard,
other service providers
have found
that commonly
employed coverboards such as fiber-reinforced
gypsum are insulators and interrupt
the flow of current to ground unless the
coverboards are wet. This calls into question
the accuracy of ELD testing on systems
with the wire grid between the coverboard
and the insulation, unless the assembly has
experienced significant rain events. It would
greatly benefit the entire industry if these
testability questions were resolved through
an independent evaluation of a wide variety
of membranes, insulations, coverboards,
structural decks, and grounding media.
J u l y 2 0 1 7 RC I I n t e r f a c e • 2 1
Figure 2 – When electrically insulating materials are present between
the membrane and the conductive deck, breaches can remain
undetected unless an alternative grounding medium is installed.
Flat roof leak detectors
www.buckleysinternational.com tel: +44 1303 278888 • email: sales@buckleys.co.uk
MANUFACTURERS OF SPECIALIST TEST EQUIPMENT
We manufacture two types of flat roof leak detector kit – one for use in dry conditions and one for wet conditions.
Both models can pinpoint leaks in a wide range of roof finishes which are too small to see with the naked eye.
• lightweight & portable
• easy to use
• clear backlit lcd display
• alarm volume control
• audible & visual fault indicators
• ce approved
• kit contains all items required
PD40R
dry roof leak detector
Scan code to see our short video guide on roof
leak detection, or find us on YouTube.
WRP01
wet roof leak detector
• easy to set up and use
• lightweight
• selectable audible alarm
• clear backlit lcd displays
• ergonomic case & neck strap
• fully ce compliant
• kit contains all items required
ELD on Systems with Overburden
Ideally, ELD integrity testing of a new
assembly is performed on an exposed membrane.
Once overburden materials such as
vegetation, pavers, ballast, etc. are installed,
leak investigations are subject to a number
of practical limitations.
Assemblies that will receive overburden
are typically fitted with on-demand leak
detection systems when the initial integrity
test is performed. These systems consist
of conductive wire loops installed on the
surface of the membrane and connection
boxes installed above the overburden to
provide access to the wire loops at a later
date. Specifications typically require that
the loops be installed in area increments not
exceeding 7000 sq. ft. However, there are
many factors that can impair the accuracy
of testing through overburden.
Low-voltage ELD is required on systems
with overburden installed. (High-voltage
ELD relies on direct contact between the
electrically charged brushes and the membrane
and is not an option on assemblies
with overburden.) Low-voltage testing
involves generating and interpreting electrical
patterns on the membrane surface
at low levels of voltage and amperage. To
achieve accurate test results, these relatively
subtle patterns must be sensed and
interpreted through the overburden material.
The membrane surface must be wet,
which may require large volumes of water;
dry areas of membrane will not be tested.
In some cases, the type and/or thickness
of the overburden can negatively impact the
testing. The difficulty of interpreting these
patterns increases with the depth of the
overburden, and thick layers of insulation
and/or vegetation can weaken and even
disrupt the signal.
Electrical interference within the overburden
can also adversely affect the test
results. Some assemblies contain electrically
insulating protection membranes
between the overburden and waterproofing
membrane. Lightning protection systems,
roof drains, metal conduit, and other unintended
metal grounds in the overburden
can create false positives or disrupt the
patterns so that accurate testing cannot be
performed. Metal counterflashings that contact
the overburden can also cause unintentional
grounding.
Pavers in setting beds involve unique
challenges, while pavers on pedestals are
not reliably testable assemblies. The prospects
for a successful test of a membrane in
the middle of a split slab are also poor due
to their monolithic nature. Also, topping
slabs often contain reinforcing steel, which
disrupts the electrical patterns.
Unfortunately, many of these potential
pitfalls may not be recognized due to
the presence of the overburden, and often
the testability of an assembly can only be
established on-site as the ELD technician
conducts the low-voltage procedure.
If the plan is to employ ELD on the system
after the overburden installation, the
design team must be certain that it is using
material and design approaches that will
not interfere with any subsequent testing.
Designers can benefit from utilizing experienced
ELD service providers to provide
guidance in the selection of materials and
techniques.
On-demand leak detection systems are
relatively inexpensive and are often included
in the base cost when quality assurance
ELD testing is performed on a newly
installed membrane. They can prepare the
2 2 • RC I I n t e r f a c e J u l y 2 0 1 7
RCI DoCument CompetItIon
– RaIse the BaR –
Do you have reports and construction documents you are proud of?
Raise the bar in the building envelope industry by showcasing
your talent, and gain the respect of your peers by entering the
2018 RCI Document Competition.
There is no fee to enter.
Entries will be accepted in four categories that
include reports and construction documents directly
Download Your Entry Form Today!
RCI, Inc.
800-828-1902 rci-online.org
entRy DeaDlIne septemBeR 30, 2017
Winners receive awards and
recognition at the 33rd RCI
International Convention and
Trade Show in Houston, TX,
March 22-27, 2018.
Winning documents will be
featured in RCI Interface.
rci-online.org/document-competition
Charles Sietmann (left) receives a
document competition award from
Christopher Giffin.
system for future
testing without
the expense of
moving overburden
to install
the wire at a
later date. While
the presence of
the system does
not guarantee
successful leak
detection with
the overburden
in place, they are
recommended in
most assemblies,
as they can often
locate leaks and
can help avoid the costs involved in removing
and replacing overburden to perform
visual leak inspections.
Since there are several factors that can
negatively impact the success and accuracy
of leak detection through overburden, it is
important that consultants, contractors,
and leak detection service providers carefully
manage the customer’s expectations.
Even with everyone’s best efforts
to design and install an ELDcompatible
assembly, all parties
should be made aware that the
presence of the wire loops does
not necessarily guarantee that
an accurate leak test can be performed
through the overburden.
Technically advanced auto-
J u l y 2 0 1 7 RC I I n t e r f a c e • 2 3
Figure 3 – Electrically conductive primer is
installed directly under the membrane and meets
ASTM Standard D7877.
Figure 4 – In some assemblies,
lightweight wire grids can be installed
directly under the membrane, but due
to manufacturer’s concerns, they are
often placed between the insulation
and a coverboard.
American Hydrotech, Inc.
303 East Ohio | Chicago, IL 60611 | 800.877.6125 | www.hydrotechusa.com
© 2017 Garden Roof is a registered trademark of American Hydrotech, Inc.
American Hydrotech introduces the Garden Roof® Planning
Guide mobile app, a first-of-its-kind digital brochure that
helps design professionals take a vegetated roof from initial
concept to completion.
Packed with photography, technical information and videos,
design professionals can explore assembly options and
components, growing media and vegetation, and learn
about topics such as design considerations, economic
and sustainable benefits, installation and maintenance,
and much more.
20 years of vegetated roof experience…
brought to life in one app.
Download your copy today at
hydrotechusa.com/GRPG
7.50W X 5H.indd 1 1/23/17 2:23 PM
mated leak detection systems are also
available. Typically these systems use leak
detection sensors that are installed in the
roof assembly during construction, and
allow continuous monitoring of roof assembly
performance. Any developing maintenance
issues are quickly identified and
reported for action. While more expensive
than simple “on-demand” systems, they are
often specified for critical roof applications
such as hospitals, data centers, museums,
and government facilities.
Nontestable Membranes
ELD requires a nonconductive membrane
to separate the positive and neutral
sides of the circuit. If there are no breaches,
the circuit will never be completed. When
breaches are present, the ELD instruments
can determine the location where the current
has grounded through a breach in the
membrane.
Ethylene propylene diene monomer
(EPDM) membranes are manufactured with
an electrically conductive carbon black filler,
and will not function as an insulating
material between the two sides of the
circuit. Other examples of materials that
can’t be tested are metal flashings and
membranes with metallic coatings. Butyl
membranes are also conductive and cannot
be tested with ELD.
Electronic leak detection has quickly
become standard practice on roofing and
waterproofing membranes and has been
specified on some of the nation’s most prestigious
buildings. All stakeholders—owners,
manufacturers, designers and contractors—
benefit greatly from sound, watertight
installations. Properly applied, ELD testing
will help us all deliver higher-quality, more
trouble-free assemblies.
References
1. ASTM D7877-14, Standard Guide
for Electronic Methods for Detecting
and Locating Leaks in Waterproof
Membranes. ASTM International.
2. Sika Sarnafil Technical Bulletin
#15-8, “Electronic Leak Detection
Testing Limitations,” 8/11/2015,
https://s3.us-east-2.amazonaws.
c o m / r o o f i n g – t e c h n i c a l – d o w n –
l o a d / T e c h n i c a l + B u l l e t i n s /
W a t e r p r o o f i n g / 1 5 – 8 + E L D +
Testing+Limitations.pdf.
2 4 • RC I I n t e r f a c e J u l y 2 0 1 7
Peter Brooks is
president of IR
Analyzers/Vector
Mapping. He has
over 35 years of
experience in nondestructive
testing
and has worked
closely with hundreds
of architects,
engineers, consultants,
and contractors
and performed
infrared, nuclear,
and ELD testing and analysis in a wide variety
of built environments. Brooks has written
a number of articles on the technical and
practical aspects of applied infrared thermography
and ELD. He is a former director
of Region I of RCI.
Peter Brooks
At your own pace,
on your own time, at your fingertips …
Roof Drainage Design and
Calculations
Roof System Thermal and
Moisture Design
Roofing Basics
Roofing Technology
and Science I
Roofing Technology
and Science II
Rooftop Quality Assurance
Wind Design for
Low-Slope Roofs – Part I:
Understanding ASCE 7-05
Wind Load Calculations
Wind Design for
Low-Slope Roofs – Part I:
Understanding ASCE 7-10
Wind Load Calculations
Wind Design for
Low-Slope Roofs – Part II: FM
Global Guidelines and Best
Practice Considerations
Online Educational Programs
www.rci-e-learning.org