Skip to main content Skip to footer

The Perils of Undue Structural Reliance on “Lag Screws”: A Case Study

September 19, 2022

The terms “lag screw” and “lag bolt” often are used interchangeably in construction and maritime fields. For example, guidance from the U.S. Department of Housing and Urban Development1 states, “Lag screws (often called lag bolts) function as bolts in joints where the main member is too thick to be economically penetrated by regular bolts.” However, such imprecise terminology can be irritating for those who assert that a bolt (that is, a fastener with a machine-threaded end that can accept a nut) should never be considered a screw, which instead has helical ridges (external screw threads that taper to a point) that engage with the comparable internal threading created when these threads are rotated into a wood framing member.
In short, a bolt is a structural fastener that is assembled and tightened by rotating a nut onto machine threads, whereas a screw is installed by rotating the head of the fastener. Because lag screws are neither secured with nuts nor attached by rotating each fastener, the common term “lag bolt” can be highly misleading.
Similarly, hanger screws, to the bane of some professionals, commonly can be called “hanger bolts,” even though they have helical ridges at both ends. At one end are coarse threads (for screwing into wood), and at the other end are finer machine threads, which—similar to traditional through bolts—accommodate nuts and supporting washers. Despite such differences, hanger screws still make up a distinct subset of the lag screw family.
A key advantage of using lag screws is convenience.2 Load-resisting connections to wood framing members can be achieved without requiring access to both ends of a fastener. However, compared with the long-term performance of through bolts, the structural integrity of this attachment can be more readily degraded over time by the effects of rainwater intrusion, wood decay, overloading, and wood shrinkage.
Furthermore, it is difficult for later building inspectors to verify that the contractor followed code-prescribed installation procedures. Lastly, as demonstrated by the following case study, lag screws are, in many instances, “used in connections where very little redundancy exists, and as such, an individual fastener failure can readily lead to global failure.”3
INVESTIGATION – BALCONY COLLAPSE DUE TO SUDDEN
LAG SCREW WITHDRAWAL
This case study examines the ornamental wrought iron balcony (Fig. 1) collapse at a circa-1948 two-unit, three-story apartment building in San Francisco, Calif. This balcony was installed in 1960 and was first made accessible to the building’s occupants and their guests via aluminum-framed horizontal sliding windows installed in 1972. The two operable sashes slide open toward a fixed center lite to provide openings that are 24 in. (610 mm) wide and 74 in. (1880 mm) high.
Figure 2 shows where the upper balcony was located, and Fig. 3 provides a view of that balcony’s remnants after it collapsed. Four partygoers were occupying the upper balcony when it suddenly failed at midnight. While two guests managed to safely leap back through the openings, two others were seriously injured during the fall. As would be expected, the ensuing personal injury litigation process encom32
• IIBEC Interface October 2021
Figure 1. Wrought iron balcony attached to a three-story apartment building in San Francisco, Calif.
October 2021 IIBEC Interface • 33
passed a wide range of
expert-led analyses and
disputes, including:
• Were the two
balconies originally
intended for
solely “decorative”
purposes (perhaps
for flower
boxes)? Or might
they have been
attached to this
apartment building
in a manner
that afforded the
minimum “live
load” capacity
for human occupancy,
as prescribed
by the
controlling 1956
San Francisco
Building Code?
• Had the circa-1972 retrofitted windows
(which had replaced original woodframed
windows) promoted subsequent
unsafe human usage of nonoccupiable
ornamental balconies? Most of
the residential buildings in this particular
San Francisco district date to the
post-World War II construction boom.
To appeal to military veterans who had
been stationed in Europe, developers
often installed narrow ornamental balconies
(wrought iron and wood) that
were not intended for human occupancy.
However, over the ensuing decades,
many of these decorative elements have
been occupied by unwary homeowners.
• Should the long-term property manager
have known that tenants were using
the narrow balconies for various lifestyle
purposes?
• Should the tenants (and their guests) be
expected to have sufficient knowledge
to recognize that these small (14.75-ft2
[1.37-m2]) balconies might not be safe
for human occupancy?
The purpose of this case study is not to
relitigate the merits of competing expert opinions
in this now-settled litigation. Instead, the
goal for this article is to delve into long-term
safety risks potentially associated with the use
Figure 3. After
its sudden
collapse, the
failed balcony
was stored in
the backyard
for expert
inspection.
Figure 2.
Window at
the upper
apartment after
the wrought
iron balcony
collapsed.
The collapsed
balcony was
identical to the
one shown in
Fig. 1.
of lag and hanger screws to “hang” such decorative or human-occupiable Juliet balconies—so named for their supposed similarities to the famous (but apocryphal4) balcony from William Shakespeare’s play, Romeo and Juliet.
FORENSIC ANALYSIS
Our inspection found that these wrought iron balconies had been attached to the stucco-clad wall with (a) five wood screws (Fig. 4) at the bottom with overall lengths of 2 in. (50 mm), and (b) two ½-in.-diameter, 4-in.-long (13-mm-diameter, 100-mm-long) (overall length) hanger screws at each upper corner (Fig. 5 and 6). Note that even though the nominal dimensions of a 4-in.-long lag screw and 4-in.-long hanger screw are the same, the hanger screw (see Fig. 5 and 7) provides significantly shorter net penetration into a structural member because of the positioning of the machine-threaded nuts.
The combined thickness of the stucco cladding assembly—including the ¼-in. (6-mm) decorative layer of plaster cement seen in Figure 8, and its underlying diagonal wood board sheathing—was approximately 1.75 in. (44 mm). As a result, only the two hanger screws were structurally engaged with the wood (Douglas fir) framing. Approximately 1.5 in. (38 mm) of the 4-in.-long hanger screws was exposed (see Fig. 5), which indicates that approximately 1 in. (25 mm) of the tapering ends of the hanger screws penetrated into the wood framing.
For the following reasons, we concluded that repeated human loading (since 1972) of these decorative balconies had gradually compromised the physical engagement of the upper leftmost fasteners for both Juliet balconies, thereby intermittently exposing these critical connections to windblown rainwater infiltration:
• Our inspection confirmed that a progressive collapse (defined as “the spread of an initial local failure from element to element resulting, eventually, in the collapse of an entire structure or a disproportionate large part of it”5) had commenced at the top left corner of the upper balcony (viewed from the exterior).
• Various deposition testimonies suggested that the most common route of tenant access onto these balconies had been over the invitingly low, 7-in. (178-mm) threshold (Fig. 9), at the right side (viewed from the interior) of these windows.
• The hanger screw at the left corner (as viewed from the exterior) of the still-attached lower balcony exhibited clear evidence of axial (overturning) overloading and withdrawal (Fig. 5).
We posited that the unexpected absence of severe wood decay within these two holes reflected
• the relatively limited amounts of windblown rainwater that could migrate into these outwardly downward-sloping (see Fig. 5) and somewhat weather-sheltered holes;
• the ameliorating effects of solar heating of this highly sun-exposed wall; and/or
• the “moderately” decay-resistant properties of Douglas fir timber.6
Water molecules are commonly described as being “sticky”: the two slightly positively charged hydrogen atoms are attracted to any available oxygen atoms (which are slightly negatively charged), including the open oxygen atoms at the surface of bare steel fasteners. This hydrogen-oxygen bond (surface tension) between water molecules and iron-based materials is the first step in the complex process of corrosive degradation known as rust oxidation. At this building, intermittent films of windblown moisture would have bonded via surface
34 • IIBEC Interface October 2021
Figure 4. The bottom edge of the failed balcony was secured to the stucco-clad wall with five wood screws. Note: 1 in. = 25.4 mm.
tension to the steel threads of the hanger screws for multiple decades, with the ensuing rust oxidation slowly degrading the screws’ axial load-bearing capabilities. This worsening degradation made these downward-sloping fasteners even more susceptible (particularly when wetted) to the pull-out forces of human loading of these Juliet balconies.
Finally, we noted that even though the helical threading at the partially failing hanger screw (see Fig. 5 and 7) at the lower balcony was more severely deteriorated than the failed screw (Fig. 8) from the upper balcony, it was this top balcony that, due to human loading related to this party, suddenly collapsed. This indicates that the lower Juliet balcony was also at high risk for sudden collapse if subjected to human loading.
HISTORICAL CODES REVIEW—UNIFORM LIVE LOAD AND
THE USE OF LAG SCREWS
As noted, the two balconies were installed in 1960. Our research confirmed that from 1956 through 1975, successive editions of the San Francisco Building Code (SFBC) (a) prohibited reliance on lag screws to resist axial (overturning) forces related to human occupancy, instead requiring the use of through
October 2021 IIBEC Interface • 35
Figure 5. The lower balcony was attached at the upper corners with 4-in.-long, ½-in.-diameter hanger screws. This fastener exhibits evidence of an axial prying action and withdrawal, as compared with the opposite hanger screw shown in Fig. 6. Note: 1 in. = 25.4 mm.
Figure 6. This hanger screw at the opposite end of the lower balcony from the screw in Fig. 5 did not exhibit evidence of axial (overturning) overloading and withdrawal comparable to that shown in Fig. 5.
bolts; and (b) required occupiable balconies to provide 75 lb/ft2 (3.6 kPa) of uniform live-load support. In short, if these 14.75-ft2 (1.37-m2) balconies had been intended for human occupancy, each should have supported approximately 1100 lb (500 kg).
By the mid-1970s, certain California state agencies were nearing completion of their decades-long political battle to use the model Uniform Building Code (UBC) to take control of San Francisco’s long-independent “home rule” code-writing processes.7 The UBC had long prescribed a lesser minimum of 40 lb/ft2 (1.9 kPa) uniform live load for occupiable residential balconies, even if they were secured only with lag screws. Still, despite acceding on this uniform live-load issue, the 1975 and 1984 editions of the SFBC continued to discourage the use of lag screws for such axial loading purposes, stating: “Lag screws or lag bolts may be used in withdrawal only by prior written approval by the Superintendent with special inspection as a requirement.”
Since 1988, all editions of the statewide California Building Code (CBC) have approved the use of lag screws for resistance to axial loading. The 1988 and 1991 editions of the CBC continued to prescribe a 40 lb/ft2 (1.9 kPa)
36 • IIBEC Interface October 2021
Figure 8. Damage from the failed wood screw shown in Fig. 4 to the ¼-in.-thick layer of decorative plaster cement applied for aesthetic relief atop an underlying ¾-in.-thick stucco cladding assembly. Note: 1 in. = 25.4 mm.
Figure 7. San Francisco Police Department photograph of a failed hanger screw from the night of the balcony collapse.
minimum uniform live load for
residential balconies. However,
beginning with the 1994 CBC
(as part of the early process of the
eventual melding of the regional
UBC, Standard Building Code,
and National Building Code into
a single model International
Building Code [IBC]), successive
editions of the CBC and the new
nationwide model IBC have prescribed
a minimum 60 lb/ft2 (2.9
kPa) uniform live load for residential
balconies.
Additionally, most modern
code agencies across North
America broadly accept engineer-
prescribed uses of lag screws
for resistance to axial loading at
exterior balconies, although there
are local exceptions—for example,
the City of Phoenix, Ariz.,8
has specific requirements related
to concerns about excessive wood
shrinkage caused by Arizona’s hot
climate.
JULIET BALCONIES AND
LAG SCREWS—DISCUSSION
Safe human usage of narrow balconies
such as the ones installed in the San Francisco
apartment building warrants close attention
from designing architects and engineers. The
American Society of Civil Engineers emphasize
this point in ASCE/SEI 7-16, Minimum Design
Loads and Associated Criteria for Buildings
and Other Structures,5 stating in Section C4.3
that “balconies and decks are recognized as
often having distinctly different loading patterns
than most interior rooms…As always, the
designer should be aware of potential unusual
loading patterns in the structure that are not
covered by these minimum standards.”
As exemplified by this case study in which
four partygoers occupied a Juliet balcony measuring
only 14.75 ft2 (1.37 m2), a key design
factor for such theoretically occupiable projections
is whether the building code’s minimum
live load provisions are sufficient for potential
future usages by tenants. Specifically, even if
minimum axial withdrawal resistance requirements
can technically be achieved with the
use of only two lag screws, an extra degree of
engineered redundancy may be warranted to
October 2021 IIBEC Interface • 37
Publish in IIBEC Interface
INTRODUCTION
In evaluating building enclosure
problems, the author has encountered
many newly constructed, wood-framed,
low-slope roofs and exterior balconies
and decks that exhibit excessive/sustained
ponding of water (Figure 1). These
conditions can lead to interior water
damage through premature deterioration
of roof coverings and/or excessive
deflection of roof framing members. The
ponding (and associated creep of the
framing) can be so significant that it
may ultimately lead to failure of the roof
framing.
The purpose of this article is to provide
insight into the most likely causes
of these problematic ponding conditions
as they relate to commonly accepted
design and construction methods.
36 • IIBEC IntErfaCE OCtOBEr 2019
Figure 1 – Excessive ponding water
on a roof.
Figure 2 – Ponding typically occurs prior to reaching discharge points.
INTRODUCTION
The concept of building for resilience
has been increasingly adopted by various
organizations over the past five years.
Organizations use different definitions or
phrases to describe resilience and the hazards
that are included in resilient design.
These definitions from six sources are compared
and a single definition incorporating
these is developed.
RESILIENCE AS DEFINED BY SELECT
ORGANIZATIONS
Industry Statement
Twenty-one organizations, including the
U.S. Green Building Council (USGBC), the
American Society of Heating, Refrigerating,
and Air-Conditioning Engineers (ASHRAE),
the American Institute of Architects (AIA),
the American Society of Civil Engineers
(ASCE), the Building Owners and Managers
Association (BOMA), and the National
Institute of Building Sciences (NIBS) issued
an industry statement on resilience[1] that
stated (the bold or red text is theirs):
Representing more than 750,000
professionals, America’s design and
construction industry is one of the
largest sectors of this nation’s economy,
generating over $1 trillion in
GDP. We are responsible for the
design, construction, and operation
of the buildings, homes, transportation
systems, landscapes, and public
spaces that enrich our lives and
sustain America’s global leadership.
We recognize that natural and
manmade hazards pose an increasing
threat to the safety of the public
and the vitality of our nation. Aging
infrastructure and disasters result
in unacceptable losses of life and
property, straining our nation’s ability
to respond in a timely and efficient
manner. We further recognize
that contemporary planning, building
materials, and design, construction,
and operational techniques can
make our communities more resilient
to these threats.
Drawing upon the work of the
National Research Council, we define
resilience as the ability to prepare
8 • IIBEC IntErfaCE SEptEmBEr 2019
This article is reprinted with permission
from Advances in Civil Engineering
Materials, Vol. 7, No. 1, 2018, copyright
ASTM International, 100 Harbor Drive,
West Conshohocken, PA 19429
www.astm.org.
IIBEC Interface journal is seeking submissions for the following issues. Optimum article size is
2000 to 3000 words, containing five to ten high-resolution graphics. Articles may serve commercial
interests but should not promote specific products. Articles on subjects that do not fit any given
theme may be submitted at any time.
Submit articles or questions to Technical Editor Emily Lorenz at 800-828-1902
or elorenz@iibec.org.
ISSUE SUBJECT SUBMISSION DEADLINE
February 2022 Testing October 15, 2021
March 2022 The Building Enclosure November 15, 2021
April 2022 Sustainability December 15, 2021
May/June 2022 Convention Issue January 15, 2022
July 2022 Roofing March 15, 2022
Figure 9. The invitingly low (7 in.) interior threshold height for the operable sashes at these circa-1972
horizontal sliding aluminum windows encouraged tenant access to the two balconies. Note: 1 in. = 25.4 mm.
minimize the risk of progressive collapse if these structural bonds weaken over time. Section 1.4 of ASCE 7-05, Minimum Design Loads for Buildings and Other Structures,9 states:
Buildings and other structures shall be designed to sustain local damage with the structural system as a whole remaining stable and not being damaged to an extent disproportionate to the original local damage. This shall be achieved through an arrangement of the structural elements that provides stability to the entire structural system by transferring loads from any locally damaged region to adjacent regions capable of resisting those loads without collapse.
Further, even when the convenience of using lag screws outweighs the increased degree of long-term safety afforded by through bolts, special inspection of their installation may be warranted (for example, as required by the City of Phoenix, Ariz.8).
Decisions about such issues should be guided by the goal of promoting and maintaining life safety over the service life of the building. Although code-prescribed minimums are important, ASCE 75 emphasizes that they should never “replace the sound judgment of a competent professional, having knowledge and experience in the appropriate field(s) of practice, nor to substitute for the standard of care required of such professionals.”
Lastly, construction professionals and property managers who inspect older buildings should be aware that severely injurious or fatal falls (due to guardrail deficiencies or structural collapse) have occurred nationwide at non-live-load-resistive decorative Juliet balconies that were only accessible through window openings. For example, in 2017, a man refinishing floors in a Harrisburg, Pa., apartment building died from a fall after he leaned on a Juliet balcony rail and it collapsed. The building had been inspected in 2015, but the inspector regarded the balcony as a decorative feature and did not evaluate whether it could withstand a human load.10 The Harrisburg tragedy and the case discussed in this paper demonstrate why it is critical to pay particular attention during inspections to human-occupiable small decks and balconies that might originally have been constructed for ornamental purposes only.
REFERENCES
1. U.S. Department of Housing and Urban Development. “Residential Structural Design Guide: A State-of-the-Art Engineering Resource for Light-Frame Homes, Apartments, and Townhouses.” 2nd ed. October 2017. https://www.huduser.gov/publications/pdf/residential.pdf.
2. U.S. Department of Agriculture Forest Service Forest Products Laboratory. “Wood Handbook: Wood as an Engineering Material. Centennial Edition.” FPL-GTR-190. 2010. https://www.fpl.fs.fed.us/documnts/fplgtr/fpl_gtr190.pdf.
3. City of Phoenix Planning and Development Department. “Lag Screws and Lag Bolts: Use and Installation.” January 2019. https://www.phoenix.gov/pddsite/Documents/TRT/dsd_trt_pdf_00251.pdf.
4. Leveen, L. “Romeo and Juliet Has No Balcony.” Atlantic. October 28, 2014. https://www.theatlantic.com/entertainment/archive/2014/10/romeo-and-juliets-balcony-scene-doesnt-exist/381969.
5. American Society of Civil Engineers (ASCE). Minimum Design Loads and Associated Criteria for Buildings and Other Structures. ASCE/SEI 7-16. Reston, VA: ASCE, 2016.
6. U.S. Department of Agriculture Forest
38 • IIBEC Interface October 2021
Figure 10. The hanger screw removed from upper left corner (see Fig. 5) of the lower balcony had severely corroded threads. Photo: Thomas H. Lutge, SE (http://www.quakestructural.com).
On July 21, Energy Secretary Jennifer Granholm announced a series of new building energy codes at the beginning of the two-day virtual National Energy Code Conference. She also stated that the U.S. Department of Energy (DOE) would be creating partnerships to support adoption of the new codes at the local level.
According to DOE, the latest energy code determinations, which estimate energy savings based on adoption of ANSI/ASHRAE/IES Standard 90.1-2019, Energy Standard for Buildings, Except Low-Rise Residential Buildings, are projected to save up to 4.7% on-site energy, 4.3% source energy, 4.2% greenhouse gas emissions, and 4.3% in energy costs. In an energy savings analysis accompanying the determinations, the department outlined the specific proposed changes, which include more high-efficiency lighting, increased wall and ceiling insulation, and improved efficacy for mechanical ventilation fans.
Other topics discussed during the first day of the conference included:
• Emerging State & Local Goals: From Zero Energy to Electrification to Decarbonization
• All for Nothing: Energy Codes, Above-Code Programs and Zero Energy
• Workforce Development: Opportunities for Building Codes and Compliance Programs
Day two of the conference focused on:
• The Role of Building Codes in Shaping Equity and Environmental Justice
• Building Performance Standards—The Pathway to Zero-Carbon Buildings: Setting Goals and Metrics, Compliance and Implementation
IIBEC monitors DOE programs and outreach efforts to advance their new energy codes and take action to advance the interests of consultants. IIBEC’s Codes and Standards Committee meets bi-monthly to discuss potential changes or implications of U.S. energy codes. In addition, IIBEC’s Senior Director of Technical Services, Emily Lorenz, represents IIBEC members as a member of the code committee developing the commercial provisions of the 2024 edition of the International Energy Conservation Code and is a consulting member of the envelope subcommittee of ASHRAE 90.1.
Service Forest Products Laboratory. “Chapter 14: Biodeterioration of Wood” in “Wood Handbook: Wood as an Engineering Material.” FPL–GTR–282. March 2021. https://www.fpl.fs.fed.us/documnts/fplgtr/fplgtr282/fpl_gtr282.pdf.
7. Haughton, L. “An Abridged History of the Statewide ‘California Building Code.’” 2020. https://avelar.net/an-abridged-history-of-the-statewide-california-building-code.
8. City of Phoenix Planning and Development Department. “Lag Screws and Lag Bolts—Use and Installation.” January 2019. https://www.phoenix.gov/pddsite/Documents/TRT/dsd_trt_pdf_00251.pdf.
9. ASCE. Minimum Design Loads for Buildings and Other Structures. ASCE 7-05. Reston, VA: ASCE, 2005.
10. Vendel, C. “Harrisburg Codes Officer Inspected Building, but not Balcony, Where Man Died in Fall.” Pennsylvania Real Time News. Published February 15, 2017. Updated: January 5, 2019. https://www.pennlive.com/news/2017/02/mike_clark_bowers_harrisburg_b.html.
Please address reader comments to elorenz@iibec.org, including “Letter to Editor” in the subject line, or IIBEC, IIBEC Interface Journal, 434 Fayetteville St., Suite 2400, Raleigh, NC 27601.
Lonnie Haughton, MCP, LEED AP, is a senior partner with AVELAR (https://avelar.net), a forensic architectural, engineering, construction, and codes consulting firm in Walnut Creek, Calif. (Founded in Oakland in 1976 as Richard Avelar & Associates, the firm rebranded and relocated in 2020.) Haughton is a licensed general contractor and is certified by the International Code Council as a Master Code Professional.
Lonnie Haughton, MCP, LEED AP
October 2021 IIBEC Interface • 39
DOE Announces New Energy Codes to Start Virtual National Energy Code Conference
Photo by Chris Montgomery on Unsplash