Skip to main content Skip to footer

Moisture Control Requirements in Codes

May 15, 2005

INTRODUCTION
National model codes attempt to prescribe
moisture control in various ways and
fail miserably, sometimes unwittingly prescribing
failure! One solution does not fit
all! Potential national solutions that are less
prescriptive and more performance-based
are reviewed in this article.
Moisture control in a building depends
on three variables: 1) local weather and
subsoil conditions, 2) interior environment
of the building, and 3) the proposed building
enclosure assembly components.
Moisture has different phases – solid, liquid,
and gas. Snow and ice need to be managed,
and liquid moisture must be controlled
and deflected back out of building
assemblies without damage to the materials.
The mechanisms of capillary moisture
and water vapor transfer, however, are quite
complex. Moisture moves in building materials
by capillary pressure, by convection of
air caused by surface temperature differences,
by air transfer under pressure differentials,
and by diffusion through materials
under gas pressure. The primary method of
moisture control in enclosure materials is
by determining that the increase in moisture
content of those materials (inboard of
the drainage plane) will not rise to levels
where mold, decay, or corrosion will result.
Moisture in Buildings
The source of moisture in buildings can
be summarized as follows, from the importance
of the quantity of moisture to the
magnitude of problems it can cause to the
building and its enclosure:
1. Liquid water from precipitation and
from ground sources, causing
leaks, moist conditions, and “rising
damp.”
2. Water vapor carried by air pressure
differences across or through the
envelope, causing condensation.
3. Water vapor diffusion through
building materials.
The solid phase of water, snow, and ice:
So long as it stays solid, it does not damage
the envelope. Freezing water due to freezethaw
cycles of wet, porous enclosure materials,
however, can damage those materials.
1. LIQUID WATER
By far the greatest problem is liquid
water intrusion and its management.
Because of the loss of use of facility space
and the liability such leaks create to designers
and builders, most codes require the
use of flashings, drainage planes, waterproofing,
etc., and most designers understand
how to manage liquid water. Wall
assemblies must be designed with flashings
and drainage planes and should not depend
on a single sealant layer as the primary
means of water resistance; they should
have a secondary drainage plane inboard of
the rain screen and flashings to direct water
out of the assembly via weep holes. Because
they eventually leak, all windows should
have a pan flashing. The building enclosure
below grade must be designed to manage
liquid water intrusion using waterproofing,
dampproofing, and dewatering techniques.
A capillary break will reduce the likelihood
of rising damp. Roof assemblies are either a
membrane in low-slope applications or
shingled in pitched applications. Therefore,
roofs must be pitched to drains, and wall
panel systems should have two-stage
sealants in the joints.
Control of soil moisture without a hydrostatic
head
To control soil moisture, provide a capillary
break to rising moisture using a 6″-
28 • I N T E R FA C E MA R C H 2005
(150 mm) thick, highly permeable layer of
material beneath the slab and adjacent to
basement walls, such as crushed stone. Use
a perforated pipe network that connects the
sub-slab and footing drain pipes. Collect
and dispose of below-grade water by connecting
the pipe network to the storm
sewer, a retention pond, or other means of
water detention. Inhabited spaces below
outdoor, open-paved, or planted areas must
have a waterproof membrane (a protected
membrane roof) – usually pitched to drain –
and a water collection system. Walls below
grade must be dampproofed at the least.
Control of moisture in basements with a
hydrostatic head
Basement walls and floor slab, and possibly
the roof, need to resist the structural
load and pressure of the head of water. As
the structure is designed like a concrete
boat, with walls connected to the slabs by
moment connections, designs of the waterproofing
system should be appropriate to
hydrostatic head conditions.
That being said, the focus of this article
will be on the second and third sources of
water in buildings, probably the most misunderstood
subjects by national code writers.
These sources are moisture accumulation
due to convection and water vapor due
to diffusion.
2. CONDENSATION OF MOISTURE TRANSPORTED BY
AIR MOVEMENT
Weather in North America is extremely
varied and includes enormously different
combinations of rain-loading (rain and
wind) temperature, water vapor, solar radiation,
and cloud cover.
Below-grade conditions of soil temperature
and moisture also change dramatically
from location to location. An understanding
of exterior air and below-grade conditions is
vital to determining whether the requirements
in the codes of ventilating attics and
crawlspaces are actually effective. A clear
understanding of the exterior boundary
conditions in a particular site above and
below grade, and the specific configuration/
design of the building enclosure are
essential to implementing effective moisture
management solutions. The prescriptive
approach that codes take to these matters
can be extremely problematic if the specifics
are not studied.
Take, for example, a building in Florida.
A code requirement to vent the attic (to dry
out moisture) would introduce hot, humid
air that can encounter air-conditioned surfaces
(such as ducts and vent pipes) that
are below the dewpoint of the outside air.
The result? Condensation, damage, rot, and
mold. Air conditioning has changed the picture.
Air that moves water vapor from the
outside to the interior (including interstitial
spaces) in hot, humid climates, and from
the inside to the outside in predominantly
colder climates, can cause major damage
due to condensation of large amounts of
moisture (over 200 times the amount that
can go through the assembly by diffusion in
the same amount of time.) (Quirouette,
1986.) There is confusion throughout the
United States about the importance of this
mechanism of water vapor transfer (i.e., by
air pressure differentials). The confusion is
with the function of vapor retarders (vapor
barriers) in controlling diffusion, versus airtransferred
moisture due to air migration.
In addition to condensation, uncontrolled
air infiltration can affect energy consumption,
disrupt HVAC design pressure
relationships, move pollutants, microbials,
and odors within and into buildings from
the exterior, and cause discomfort to the
occupants. How do codes and standards
deal with this issue? This subject is dealt
with usually in the energy code, not the
building code, presumably because the former
code recognizes the potential energy
impact. Typically, this is called “air sealing”
or air infiltration control. Usually, the code
provides a prescriptive list of which parts of
a building to tape and seal. The problem
arises when the desired result is not
described conceptually or philosophically, –
namely, to achieve a building envelope that
is airtight from roof to foundation.
Why don’t the codes state the goal outright?
An example would be: “The intent is
to achieve an airtight building envelope that
controls infiltration and exfiltration.” One of
the philosophical deficiencies of air infiltration
management in codes is that codes
have long focused on the maximum allowable
air leakage of glazed products such as
windows, skylights, and curtainwalls.
Doors, including garage and revolving
doors, have maximum air leakage rates that
are quantified in the codes. In the average
commercial building, windows and doors
account for perhaps 25-35% of exterior
walls. Strangely, few code writers thought to
quantify the maximum allowable air infiltration
of the opaque envelope, believing
that it was tight. Most building professionals
and code writers alike believe that infiltration
occurs through windows and doors.
MA R C H 2005 I N T E R FA C E • 2 9
Studies conducted at the National Institute
of Science and Technology (NIST) indicate
that we are designing and constructing
buildings with very large holes (Persily,
1998; Emmerich and Persily, 1998, 2003).
Those holes are primarily in the interconnection
of envelope materials and the lack
of continuity in the plane of air-tightness,
from one material to the next and from one
system to the next. (See Figure 1.)
The lack of quantification of acceptable
maximum air permeance rates for building
materials that form the plane of airtightness
in an assembly has caused major
blunders in the design of buildings. A prime
example is dramatized in the study conducted
by Florida Solar Energy Center,
where a suspended acoustical tile was the
only separation (besides the glass-fiber
insulation) between the conditioned space
and the ventilated attic. (Withers and
Cummings, 1998). The ceiling was performing
atrociously as an air barrier; in the
offices, conditioned air was being driven
through the ceiling into the attic, and in the
hallway, hot humid air was being sucked
into the conditioned space from the attic at
the air handler’s return grille.
Once a material in the envelope has
been targeted for air-tightening, it must be
understood that this layer will usually carry
the full design wind load, both positive and
negative. Stack effect pressure and HVAC
fan pressure may add to the wind pressure.
This is where the codes and many practicing
professionals fail in understanding that
vapor retarder films that are not rigidly
sandwiched between board materials and
only supported on one side by fiberglass
batts will fail under wind loading. The plastic
film will rupture. (See Figure 2.) (Lux and
Brown, 1986.) Structural support is essential.
Materials that are suitable to be part of
an air barrier system can be
either vapor permeable or vapor
retardant. In order to control air
pressures, air-tightening can be
done either on the high-vapor
pressure side of the enclosure or
on the low-vapor pressure side of
the wall. The preference is to
keep the air barrier on the stable
temperature side of the wall to
avoid too much movement and
possible failure of the joints.
Following is the code language
as it stands today, proposed
to ASHRAE SSPC 90.1 as
a continuous maintenance proposal
under negotiation for the
requirements of an air barrier
system in the building enclosure:
5.4.3.1 Building Envelope
Sealing. The building envelope
shall be designed and constructed
with a continuous air barrier to control
air leakage into, or out of, the
conditioned space. All air barrier
components of each envelope
assembly shall be clearly identified
on construction documents and the
joints, interconnections, and penetrations
of the air barrier components
shall be detailed.
5.4.3.1.1 Compliance Options. Compliance
of the continuous air barrier
for the opaque envelope can be
demonstrated by meeting the air
permeance requirements of individual
materials, or by meeting air
leakage rates for assemblies of components,
or by whole building testing
of the completed building.
(a) Individual materials are compliant if
they have an air permeance not to
exceed 0.004 cfm/ft2 under a pressure
differential of 0.3 in. water
(1.57psf or 0.02 l/s.m2 @ 75 Pa)
when tested in accordance with
ASTM E-2178.
(b) Assemblies of materials and components
are compliant if they have an
average air leakage not to exceed
0.04 cfm/ft2 under a pressure differential
of 0.3″ w.g. (1.57psf or 0.2
l/s.m2 @ 75 Pa) when tested in
accordance with ASTM E-1677.
(c) A completed building is compliant if
the air leakage rate of the building
envelope does not exceed 0.40
cfm/sf at a pressure differential of
0.3″ w.g. (1.57 psf or 2.0 l/s.m2 @ 75
Pa) in accordance with ASTM E-779
or an equivalent approved method.
The exterior envelope area is comprised
of the lowest floor area, the
roof or highest ceiling area, and the
area of all exterior envelope walls,
including below-grade walls.
Exception to 5.4.3.1.1: Buildings in
Zones 1, 2, and 3 constructed with mass
walls are exempt.
5.4.3.1.2 Characteristics. The continuous
air barrier shall have the following
characteristics:
(a) It shall be continuous throughout
the envelope (at the lowest
floor, exterior walls, and ceiling
or roof), with sealed connections
between all transitions in planes
Figure 2 and changes in materials, at all
30 • I N T E R FA C E MA R C H 2005
Figure 1: Lux and Brown, 1986.
joints and seams, and at all penetrations.
(b) It shall be joined and sealed in a
flexible manner to the air barrier
component of adjacent assemblies,
allowing for the relative
movement of these assemblies
and components.
(c) It shall be capable of withstanding
positive and negative combined
design wind, fan, and
stack pressures on the air barrier
without damage or displacement,
and shall transfer the load
to the structure. It shall not displace
adjacent materials under
full load.
(d) The air barrier materials shall be
maintainable in accordance with
the manufacturer’s instructions,
or, shall meet durability requirements
established by the design
professional.
(e) Where lighting fixtures with ventilation
holes are to be installed
in such a way as to penetrate the
continuous air barrier, provisions
shall be made to maintain
the integrity of the continuous
air barrier.
Control of Moisture Accumulation due to
Convection
One of the most common problems
throughout most of the United States is the
“musty basement syndrome.” Caused by
surfaces with temperatures lower than the
dewpoint of the air, it is generally caused by
the fact that surfaces below -rade are at
temperatures closer to the average annual
temperature for a locale. This temperature
is usually lower than the summer dewpoint
of the air. Another contributor is concrete,
which is a good conductor of heat and
therefore tends to have a surface temperature
close to the soil temperature. Add to
that interior fiberglass insulation, and one
has a recipe for mold – air adjacent to the
concrete cools down to a high relative
humidity, and the moisture is absorbed into
the concrete, increasing the moisture content
and providing an environment supporting
mold growth. The cooled air is heavier
and drops, entraining more air with moisture
at the top of the wall.
The solution is simple: decouple the
concrete from the earth temperature by a
layer of rigid insulation on the exterior of
walls and slabs. This brings the concrete
temperature closer to the temperature of
the air and less likely to present itself as a
MA R C H 2005 I N T E R FA C E • 3 1
CONTINUOUS AIR BARRIER:
The combination of interconnected materials,
flexible sealed joints, and components
of the building envelope that
provide the air-tightness of the building
envelope.
AIR LEAKAGE OF THE BUILDING
ENVELOPE:
Q/S, the average volume of air in cubic feet
per minute (liters per second) that passes
through a unit area of the building envelope
in square feet (square meters), expressed
in cfm/sf (l/s.m2), where Q is the
volume of air in cubic feet per minute
(liters per second) flowing through the
whole building envelope when subjected to
an indoor/outdoor pressure in accordance
with ASTM E-779, and S, measured in
square feet (square meters), is the total
area of the envelope air pressure boundary
including the lowest floor, any below-grade
walls, above-grade walls, and roof or ceiling
(including windows and skylights) separating
the interior conditioned space from
the unconditioned environment.
DEFINITIONS:
condensing surface. Another compromise
strategy is to insulate on the inside using a
layer of rigid insulation with sealed edges to
avoid convective currents entrained behind
it. An additional layer of batts is optional
but unnecessary. Code language can be
drafted to eliminate this common problem.
3. CONTROL OF WATER VAPOR CONDENSATION
DUE TO DIFFUSION
Third on the list and the least serious of
all sources of moisture is the diffusion of
water vapor through building materials. It
does, however, deserve a clearer understanding
of the mechanisms of control.
Water vapor moves due to a difference in
water vapor pressure from the high-vapor
pressure to the low-vapor pressure side of
an assembly. It is the writer’s belief that it
is impossible to safely prescribe a specific
vapor retarder that will work for all buildings
and assemblies because the high-vapor
pressure side changes from inside to outside
in the same building during the same
day, and changes also from building type to
building type. It is the writer’s belief that
diffusion control must be left to the designer
to determine in a responsible manner.
The code takes too much responsibility
away from the design profession when it
prescribes vapor retarders and ineffective
assemblies that do not work for some buildings
and assemblies under certain climatic
conditions. Code enforcement officials who
blindly enforce the requirements in situations
where the designer knows better create
enormous problems and are counterproductive,
to say the least.
Following is the proposed performance
language:
The design of building enclosures
(envelopes) shall not create conditions of
wetting due to condensation caused by diffusion
of water vapor:
1. To the exterior in winter conditions,
2. Due to contact of humid air with a
surface temperature below the dewpoint,
or
3. Due to vapor drive to the interior
due to solar heating of rain-saturated
cladding materials.
Envelope materials shall be selected for
maximum drying potential outward as well
as inward, and, therefore, design shall avoid
the use of vapor retarders (vapor barriers)
whenever possible, using Methods 2 or 3
below. Vapor retarders to control diffusion
shall be selected with the highest permeance
value that will satisfy the design
requirements.
1. Underslab and below-grade vapor
retarders shall be selected to withstand
punctures and damage during
construction, and chemical and biological
attack during their service
life. All joints, penetrations, and
perimeter terminations shall be sealed.
2. Design for control of moisture due to
diffusion in walls, roofs, and floors
shall be in accordance with either:
• Method 1: Follow procedures
outlined in ASTM C-755,
“Standard Practice for Selection
of Vapor Retarders for Thermal
Insulation.” Assume steadystate
heat transfer. Assume
indoor air design conditions
determined by a licensed professional
and exterior air temperature
indicated as “Average
Temperature for the Coldest
Month” in Table 1.
• Method 2: Design assemblies
without vapor retarders by
maintaining the temperature of
potential condensing surfaces
(typically the temperature of the
exterior sheathing/cavity insulation
interface) above the dewpoint
of the indoor air. Under
this design approach, assume
an indoor air temperature of
70°F and 35% relative humidity
(unless determined otherwise by
a licensed professional). Assume
indoor air design conditions de-
32 • I N T E R FA C E MA R C H 2005
Annual Mean Daily
Temperature
termined by a licensed professional
and exterior air temperature
indicated as “Average Temperature
for the Coldest Month”
in Table 1. Assume steady-state
heat transfer and follow the
“Dewpoint Method” described in
Chapter 23 of the 2001 edition of
the ASHRAE Fundamentals
Handbook, “Steady State Design
Tools.”
• Method 3: Design envelope systems
that maintain the moisture
content of all building materials
in the assembly below the equilibrium
moisture content that
the materials would achieve
when exposed to a relative
humidity of 80%. For calculation
purposes, use Chapter 23 in the
2001 edition of the ASHRAE
Fundamentals Handbook,
“Mathematical Models.” Assume
indoor air design conditions determined
by a licensed professional.
If Method 1 above is used, materials
selected for the envelope outboard (toward
the exterior) of a vapor retarder shall be at
least five times more permeable than the
vapor retarder.
Exceptions:
1. Low-slope roof membranes.
2. Sealed double skin metal panels.
3. Materials outboard of a ventilated
rainscreen assembly.1
CONCLUSION
The New Buildings Institute has adopted
much of the language and concepts
described above in its new E-Benchmark,
the Advanced Building Guidelines. Codes in
the United States today fall far short of having
appropriate requirements for controlling
infiltration and moisture due to condensation
in the building enclosure. Codes
require ventilation of cavities in climates
that are hot humid, and it becomes counerproductive
to ventilate those cavities. Codes
are charged with protecting the health,
safety, and welfare of the public; yet in this
critical area of control that can cause mold,
aggravate asthma, cause deterioration by
corrosion and decay, and pollution migration
within the building, they fail to represent
a sufficient level of understanding of
the mechanisms or the solutions. Change is
needed, and a concerted effort is required to
educate code writers, design professionals,
the construction community, and enforcement
officials nationwide.
1 Mean Dry Bulb Temperature for January.
Available from the National Climatic
Data Center.
Roof Consultants Institute
1500 Sunday Drive, Suite 204, Raleigh, NC 27607-5151
Phone: 800-828-1902 • Fax: 919-859-1328 • www.rci-online.org
A monthly* publication
from the industry’s commercial
roofing experts, featuring the
latest technical information on
today’s roofing issues:
• avoiding trapped moisture
• energy efficient roof designs
• sustainable building products
• roof warranties
• protected membrane systems
• steep roofs vs. low-slope roofs
• bituminous roof systems
• cold-applied roof systems
• insulating cellular concrete
• wind resistance
• and more…
with
Interface
the technical journal of the
Roof Consultants Institute
K E E P O N T O P O F
Name ______________________________________________
Company __________________________________________
Address ____________________________________________
City ____________________State ________Zip __________
Phone __________________E-mail ______________________
Amount Enclosed $ __________________________________
❑ Check (payable to RCI) ❑ Visa ❑ Mastercard ❑ American Express
Card No.________________________Exp. Date __________
Name on Card ______________________________________
Signature __________________________________________
Subscribe
today!
ROOFING
TECHNOLOGY
MAIL OR FAX TO: *RCI publishes 11 issues of Interface a year
$90
ONLY
PER YEAR (US)
11 ISSUES*
MA R C H 2005 I N T E R FA C E • 3 3
Climate Zone Mean Dry Bulb Temperature
12a 29˚F
13a 28˚F
14a 21˚F
Table 1. Average Temperature for the Coldest Month
(Develop for all climate zones using Mean DBT for January.)
Editor’s Note: This article was originally presented at the 2003 RCI Building Envelope
Technology Symposium in Dallas, Texas. It has been updated by the author.
DOE Ashrae 90.1 -1999
Wagdy Anis, AIA, LEED, has an architectural career spanning
almost four decades. He has designed and led hundreds of
projects, both nationally and internationally. His professional
focus is the integrity and performance of the building envelope
from a research, design, and troubleshooting perspective,
as well as sustainable design and indoor air quality. As
a principal of Shepley, Bulfinch, Richardson, and Abbott
(SBRA) in Boston, he is head of technical resources. Mr. Anis
serves as a director of the Boston Society of Architects and
chairman of BETEC. He serves as chairman of the Energy Advisory Committee for the
Massachusetts State Board of Building Regulations and Standards. He is a board member
of the Boston Society of Architects’ Building Enclosure Council and co-chair of the
Indoor Air Quality Committee. He is a board member of the Air Barrier Association of
America and a member of its technical committee. He is a member of ASHRAE SSPC
90.1 and TC 4.4 committees. Anis is the author of Indoor Air Quality: A Design Guide,
published by the Boston Society of Architects. Most recently, he was primarily responsible
for the historic agreement between the AIA and NIBS to establish Building
Enclosure Councils in cities of the U.S.
Wagdy Anis,AIA, LEED
Figure 4: Mean dewpoint temperature isolines for August (1946 to 1965).
Source: Climatic Atlas of the United States.
34 • I N T E R FA C E MA R C H 2005
REFERENCES
Emmerich, S.J., and A.K. Persily, “Energy Impacts of Infiltration and Ventilation in
US Office Buildings Using Multi-zone Airflow Simulation,” paper delivered at
the ASHRAE IAQ and Energy Conference, 1998.
Emmerich, S.J, NIST, 2005
Lux, M.E., and W.C. Brown, “Air Leakage Control,” NRC, 1986.
Persily, A., “Blowing Holes in the Myth of Air Tightness of Institutional and
Commercial Buildings,” Whole Buildings VII.
Quirouette, R., “The Difference Between an Air Barrier and a Vapor Barrier,” NRC,
1986.
Withers, C.R. Jr., and J.B. Cummings, “Ventilation, Humidity and Energy Impacts
of Uncontrolled Airflow in a Light Commercial Building,” ASHRAE
Transactions, 1998.