Skip to main content Skip to footer

Testing of Metal Flashing For Water-Shedding Effectiveness

May 15, 2006

INTRODUCTION
Metal flashings are commonly used in
buildings as parapet caps, at the windowsills
and heads, and at horizontal junctions
of building components. Water flow
over vertical cladding is greatly affected by
small changes in the geometry of horizontal
projections. Figure 1 shows the water flow
pattern at two different horizontal projections
on the cladding of a building in downtown
Toronto. Water staining can be seen
below the parapet coping.
At windowsill locations, a metal flashing
with different drip geometry prevents this
phenomenon by more effectively shedding
water. Although the presence of water can
be noted at two ends of the windowsill,
there is no water below the drip, indicating
that it is effectively shedding water. In two
case studies reported by Doshi (2005), the
rainwater flowing over cladding was greater
than could be predicted by the effect of
wind-driven rain deposition only. This was
attributed to water flow over buildings due
to ineffective shedding at horizontal projections.
Maurenbrecher (1998) reports on
water-shedding details that improve
masonry and emphasizes the key role
played by metal flashing.
This paper details a test method that
was developed to quantify the water-shedding
effectiveness of metal flashing used in
buildings. The test apparatus and the testing
procedure developed for this purpose,
as well as the parameters which impact the
effectiveness of flashing, are described.
BACKGROUND
Literature Review
Despite the importance of metal flashing
in building construction, a literature search
revealed that there are no consistent guidelines
for the design of a metal flashing.
Practice guides and building codes include
some prescriptive information on metal
flashing. This provides details about the
material and thickness of flashing, but very
little or no information on aspects that
affect its water-shedding ability.
The included information varies in content
and detail. The Sheet Metal and Air
Conditioning Contractors National Association
(SMACNA, 1993), the National Roofing
Contractors Association (NRCA, 2001), and
the Canadian Roofing Contractors’
Association (CRCA, 1997) are examples of
trade association whose manuals are frequently
referenced by designers for components
and installation specification details.
These manuals include general information
about the shape and size of metal flashing
used for parapets, but they do not provide
any particular information on the design of
the water-shedding aspect of the flashing.
The Aluminum Association (2000) manual
also provides general information on
metal flashing. Again, it does not provide
Figure 1 – the effect of small changes in geometry of horizontal projections on
water flow over cladding.
24 • I N T E R FA C E S E P T E M B E R 2006
any detailed information about the requirement
pertaining to the geometry of the drip
edge.
Building codes (IRC, 1995) used in
Canada contain information on sheet metal
flashing. This information pertains predominantly
to the type of materials used for
flashings and their applicable thicknesses.
Very little information is available that
relates to the drip geometry.
Recently, the Canadian Mortgage
Housing Corporation (CMHC, 1997a, b)
produced practice manuals that provide
some prescriptive information pertaining to
the design of drip. This information is not
consistent among different cases.
The literature survey was limited to
North American sources. It has been
brought to the attention of the authors that
there might be some emerging ideas from
Europe. The authors were unable to source
the documents from Europe through many
of the publicly available databases in
Canada. It is expected that a review of these
European practices will be conducted in
future versions of this work.
Review of existing practices
In addition to the published information,
the authors reviewed the practices of
design offices and of contractors as it
relates to the geometrical considerations of
the drip edge of metal flashing. Both new
construction and retrofit construction projects
were examined (Construction Control
Inc., 2004a and b; Quadrangle Architects
Limited, 2004; and Young and Wright
Architects Inc., 2004). For each of these
cases, the drawings, the specifications, and
the field practices were examined.
It was noted that the drawing and specifications
referenced some of the abovementioned
trade publications for the flashing
requirements. Discussion with the contractors
revealed that the girth of the flashings,
the angle of the drip, and the length of
the drip were considered in forming the
metal flashings. The actual value of these
parameters was determined by the shops
forming the metal, rather than the designers.
Summary of Findings from Literature Review and
Review of Existing Practices
Test method to determine watershedding
effectiveness of flashing
The literature survey revealed that there
is a lack of information on testing the
water-shedding effectiveness of different
configurations of metal flashing. The
authors did not find any test method applicable
to the measure of the performance of
the drip edge of flashing.
Variables affecting water-shedding performance
of metal flashing
Three parameters that impact the
water-shedding effecttiveness of metal
flashing that can be controlled by designers
and fabricators were identified in reviewing
the existing information. They are shown in
Figure 2:
1. The angle of the drip-edge.
2. The length of the drip-edge or its
horizontal projection from the wall.
3. The gap between the face of flashing
and the vertical surface of the wall.
Figure 2 – Flashing design parameters.
PARAMETER SPECIFIED RANGE
(OUT OF 3 SOURCES)
Angle of drip edge 0 –
Horizontal projection 3 10mm – 25mm
Gap 2 25mm
Table 3. Reported window sill flashing requirements.
S E P T E M B E R 2006 I N T E R FA C E • 2 5
PARAMETER SPECIFIED RANGE
(OUT OF 3 SOURCES)
Angle of drip edge 0 –
Horizontal projection 3 5mm – 10mm
Gap 0 –
Table 2. Reported through-wall flashing requirements.
PARAMETER SPECIFIED RANGE
(OUT OF 17 SOURCES)
Angle of drip edge 4 45°
Horizontal projection 9 13.5mm – 35.8mm
Gap 0 –
Table 1. Reported parapet flashing requirements.
Other factors will impact
the performance of the flashing
that cannot be controlled
by designers and fabricators.
These include parameters
related to the nature of winddriven
rain such as the quantity
of rain and the spatial and
temporal nature of wind. The
focus of this work is on studying
the impact of controllable
factors.
Values for variables affecting
water-shedding performance
Based on a review of published
information and a
review of practices, values for
the parameters affecting
water-shedding performance
were found to be as shown in
Tables 1 to 3. The column
titled “Parameter” lists the
variables of interest as
explained above. The next column, titled
“Specified,” lists the number of sources
reporting a value for the respective variable.
The total number of sources reporting the
particular flashing configuration is shown
in the column heading. The last column
provides a summary of the range of values.
As can be seen from Tables 1 through 3,
there is a wide variation among the existing
requirements and practices of the three
variables that impact the water-shedding
effectiveness of metal flashing. In the following
section, a test method is presented
which attempts to study this effectiveness.
PROPOSED TEST METHOD
A test method was developed to study
the impact of the three mentioned variables
on the water-shedding effectiveness of a
metal flashing. In order to do this, the following
issues were considered.
Test Considerations
Efficiency measure
Water flowing over a flashing should
ideally be directed away from the building
face. Some of it will flow back toward the
building and run down the wall cladding
below the flashing. The efficiency of a flashing
profile is directly proportional to the
amount of water that drips away from the
drip-edge without coming in contact with
the vertical wall surface below it. The
greater this amount, the better the performance
of the flashing. Equation 1 expresses
the water-shedding efficiency of a flashing
profile as a percentage:
where E = the efficiency of a profile; O = the
original amount of water flowing on the
flashing; and Dw = the amount of water
dripped back on the wall surface.
The method by which the original
amount of water (O) is introduced over the
flashing, and manner in which the water
that flows back on the wall surface (Dw) is
collected and measured, is explained in
subsequent sections.
Figure 4 – Water being sprayed at the test specimen (flashing flatness in the test
assembly was ensured during installation by fastening).
Equation 1
Figure 3 – Tested flashing profiles.
26 • I N T E R FA C E S E P T E M B E R 2006
Flow rate
The rate of water flow will affect the
water-shedding performance of flashing. A
higher rate of flow will direct more water
away from the flashing than a lower rate of
flow. This should be a control variable in
the test. Test results reported in this paper
were done using only one rate of flow of
water. However, the test method can be easily
adapted to include a flow rate control
mechanism.
Wind pressure
Wind will have a considerable impact on
the water deposition on the wall and the
subsequent flow over the cladding. This
paper focuses on the study of water flow
over different flashing profiles and evaluating
the profiles based on their watershedding
effectiveness. It does not take into
account the impact of wind on the water
flow. In relative comparisons between different
flashing profiles, wind will likely have
the same effect on tested specimens and
will change the test results equally. It is for
this reason that ignoring the effect of wind
is not expected to change the relative effectiveness
of different flashing profiles.
Surface flow considerations
Test specimens are 500-mm-wide galvanized
sheet steel profiles. This width is considered
to be reasonable in order to achieve
the desirable test results. Profiles are
designed with a 300-mm-tall vertical flange
at the top end. Water is sprayed at this surface
first to create a uniform water flow at
the top of the flashing. Two sides of the
flashing specimens are treated with a strip
of foam tape to prevent water run-off at the
ends (Figures 3 and 4).
Height of fall of water from drip edge
Profiles to be tested are placed in the
test assembly at a height of 1 meter from
the water collection assembly. This is a
common distance from a windowsill flashing
to the ground or a parapet flashing to a
window head. Field observations showed
that water dripping from a flashing hits the
wall surface at a distance of approximately
0.5 meters from the flashing; therefore, a
Figure 5 – Test frame of assembly (approximate size of assembly = 300mm deep x
500mm wide x 1600mm high).
with
Next
generation
…the
Lighter,
Stronger
“P”Curb
www.chemlinkinc.com
CHEMCURBTM
No Mixing
10 Minute Installation
Durable
10 Year Warranty
Profitable
Maintenance Free
Environmentally
Friendly
Non-Shrinking, No V.O.C.’s
CONTRACTOR HOT LINE
800-826-1681
Call for FREE CD!
S E P T E M B E R 2006 I N T E R FA C E • 2 7
height of 1 meter will provide enough distance
for water to either drip away or hit the
wall surface.
Other consideration
The metal flashing test specimen is held
in place by using two magnets. These magnets
are powerful enough to keep the flashing
in place while being tested and enable
the researcher to change the position of the
profile in order to create different gap sizes
between the flashing
and wall face.
Design of Test
Apparatus
Test frame
The test assembly
is made of
a 300mm x 500mm
x 1600mm steel
frame that contains
the flashing
profile to be tested,
as well as water
spray and water
collection assemblies.
A piece of plywood
connected to
the front side of
the frame performs
as the surface
of the building. This is referred to as
the “back-wall” in the test assembly. The
plywood is protected with a waterproof layer
that provides a non-absorbent surface over
which water can flow without loss due to
surface absorption (Figures 5 and 6).
Water spray assembly
The flashing profile is sprayed with water
dispersed from the water spray apparatus. A
400 x 200mm bucket filled with 14 liters of
water is placed on top of the test assembly at
a height of 700mm from the test specimens.
Water is sprayed to the vertical flange of the
flashing through the nozzles placed on a
copper pipe. The copper pipe is connected to
the bucket of water. A valve is placed at the
end of the loop to control the water flow.
Once this valve is open, water flows until all
the water in the bucket has drained. The
results in this paper are for a flow that was
timed to last for ten minutes.
Figure 6 Figure 7 – Water spray assembly.
Figure 8 – Water collection assembly.
28 • I N T E R FA C E S E P T E M B E R 2006
Sprayed water flows over the
flashing and either drips away from
the drip-edge, or drips back and runs
down the back wall (Figure 7).
Water collection assembly
To collect the water runoff, a plastic
tube is placed at the bottom end of
the back wall. This is placed in such a
way so as to minimize any extraneous
water except for the amount to be collected.
The tube is inclined in order to
direct the runoff water to a container
placed at the end of the tube. The
amount of collected water is measured
(Figure 8). The efficiency of a flashing
profile is calculated by substituting
this amount in Equation 1.
Description of test specimen
Flashing profiles are constructed
of galvanized sheet steel. Tested flashing
profiles are constructed based on
the design parameters explained previously.
Combinations of three sizes of
angle (30˚, 45˚, and 60˚), three sizes of
horizontal projection (10mm, 15mm, and
25mm), and two sizes of gap between the
face of the flashing and the vertical surface
of the wall (0 and 25mm), were used. This
made 18 different flashing profiles that were
tested. These sizes were chosen because
they were seen more frequently in the
reviewed design guidelines.
Figure 9 – Effect of horizontal projection on efficiency for angles shown.
S E P T E M B E R 2006 I N T E R FA C E • 2 9
TEST RESULTS
A series of tests was conducted on the
fabricated flashing profiles. The results
reveal that a change in the design parameters
of a flashing has a definite effect on its
performance in water shedding.
Using the test assembly described in
this paper, 18 different flashing profiles
were tested. Each test was repeated three
times and the average was calculated for
the results reported in this paper. The
results from each repetition did not show
any significant variation. The efficiency of
each profile was calculated as described
above. The following observations could be
made from the results:
As the horizontal projection of a dripedge
increases, the size of the angle (and
consequently the size of the drip-edge itself)
should be larger for that profile to have a
better performance. This relationship is
shown in Figure 9. When testing profiles
with 10mm horizontal projection, a profile
with a 30˚ angle has the best efficiency. By
increasing the size of the horizontal projection
to 15mm, the profile with a 45˚ angle
has the best efficiency. Finally, with a
25mm horizontal projection, the 60˚ angle
profile performs the best.
Increasing the size of the horizontal projection
(drip-edge) of a profile will improve
its performance for a given angle of drip
edge. Also seen in Figure 9 (as the lines representing
performance of each angle move
higher in the graph, showing a better efficiency),
the size of the horizontal projection
increases toward the right side of the graph.
Increasing the size of the gap between
the flashing and the vertical face of the wall
will increase the efficiency of the flashing.
This relationship can be noted for the
majority of tested profiles, except for those
with a 60˚ drip-edge angle, in Figure 10. In
this figure, each two joined bars represents
a specific profile and the numbers below it
explain the specification of that profile. For
example, profile 60-10 is a flashing with 60˚
angle and 10mm horizontal projection. The
bar with lighter color represents the efficiency
of the profile with no gap between
the flashing and the face of the wall. The
bar with darker color represents its efficien-
30 • I N T E R FA C E S E P T E M B E R 2006
Figure 10 – Effect of increasing gap size on efficiency.
cy with a 25mm gap. The results indicate
that at larger drip-edge angles, the impact
of gap is reduced.
POSSIBLE FUTURE IMPROVEMENTS
Further improvements can be applied to
the proposed test assembly to more fully
discern the impacts of the variables tested
and to test the effect of additional variables.
Keeping the same duration of water flow
over the specimen was a challenge in these
tests. This problem was due to an inconsistent
water spray pattern. Small holes in the
copper pipe get plugged with particles in the
water, which results in increasing the duration
of water flow over the specimen. Using
a more accurate water spray apparatus
could eliminate this problem.
Due to unavailability of an accurate flow
meter at this stage, tests were conducted
using no particular flow, although the
amount of water and duration of spray were
kept consistent for each test. We attempted
to use a flow meter at the early stages of the
design; however, a very high flow was
required for the apparatus to show the flow
rate. Use of a sensitive flow meter to accurately
show the rate of flow will be a significant
improvement to this test method. Also,
the effect of various rates of flow on watershedding
effectiveness of metal flashing
could be studied in the future.
Metal flashing specimens used for testing
were fabricated from unpainted galvanized
sheet steel. This material was chosen
because it was readily available at the time
and could be easily bent to the required
profiles. The unpainted nature of the surfaces
seemed to impact the flow. Water did
not seem to flow uniformly over the
unpainted metal surface and it tended to
form random streams of water that
splashed away from the edge. Further testing
can be conducted on painted metal
flashing specimens. This might give a more
representative result.
CONCLUSION
This paper has described the need to
study the water-shedding performance of
metal flashing and one test method to serve
this purpose.
Conducting a literature survey on current
design guidelines revealed that there
are no consistent design requirements for
the drip-edge portion of a metal flashing.
Also, studying some construction practices
revealed that the drip portion of the metal
flashing varies among projects.
A test method was developed to study
the water-shedding performance of metal
flashing. The test assembly consisted of a
frame, which allows the testing of various
flashing profiles one at a time, as well as
water spray and water collection assemblies.
Different flashing profiles were constructed
based on the variables that were
identified to impact drip-edge performance.
These flashing profiles were placed in the
test assembly and were sprayed with water.
The efficiency of each tested profile was calculated
based on the collected water run-off
and the results were compared. Test results
revealed that small variations in the geometry
of the drip can have a significant impact
on the water-shedding characteristics of the
flashing.
Improving this test method by using a
more accurate water spray apparatus and a
sensitive flow meter has the potential for
use as a standard for comparing the performance
of flashings used in modern cladding
systems.
ACKNOWLEDGEMENTS
The authors wish to acknowledge assistance
from Ability Fabricators Inc. for help
in fabricating the test specimens; Halcrow
Yolles and Construction Control Inc. for
providing resources and information; and
staff from the workshop of the Department
of Architectural Science at Ryerson University
for assistance in constructing the test
assembly.
References
Canadian Mortgage Housing Corporation
(CMHC). Best Practice Guide:
Brick Veneer Concrete Masonry Unit
Backing. Ottawa: CMHC. 1997a.
Canadian Mortgage Housing Corporation
(CMHC). Best Practice Guide:
Flashing. Ottawa: CMHC. 1997b.
Canadian Roofing Contractors’ Association
(CRCA). Roofing Specifications.
Ottawa: CRCA. 1997.
Construction Control Inc. Specifications
for the Replacement of the Roof
Membrane and Associated Work at
1615 Clark Boulevard, Brampton.
Woodbridge: Construction Control
Inc. 2004a.
Construction Control Inc. Specifications
for the Replacement of the Roof
Membrane and Associated Work at
2780-2800 Skymark Ave., Mississauga.
Woodbridge: Construction
Control Inc. 2004b.
Doshi, H. “Rainwater on Building
Test your knowledge of roofing with the
following questions, developed by Donald E.
Bush Sr., RRC, FRCI, PE, chairman of the RRC
Examination Development Subcommittee.
1. Which are the five basic
types of construction
identified under the
International Building
Code that define the
degree of fire resistance
for buildings?
2. Where would a designer
look to determine the
IBC-required fire rating
for the roof assembly?
3. FM Global’s classification
of resistance to interior
fire divides roof
assemblies into two basic
categories: sprinklered
and unsprinklered.
Which roof assemblies
do not require
sprinklers?
4. Which four tests for external
fire resistance
does UL perform to determine
roof covering
fire classification?
5. Flame spread depends
chiefly on which three
parameters?
Answers on page 32
S E P T E M B E R 2006 I N T E R FA C E • 3 1
Cladding: Two Case Studies.” 10th
Canadian Conference on Building
Science and Technology, May 12-13,
2005. Ottawa: IRC/NRC. 2005.
Institute for Research in Construction
(IRC). National Building Code of
Canada. Toronto: IRC. 1995.
Maurenbrecher, A. H. P. “Water-shedding
Details Improve Masonry Performance.”
Construction Technology
Update No. 23, National Research
Council of Canada. Ottawa: NRC.
1998.
National Roofing Contractors Association
(NRCA). Roofing & Waterproofing
Manual, 5th Ed. Rosemont:
NRCA. 2001.
Quadrangle Architects Limited. City-
Gate2 Architectural Drawings and
Specifications. Toronto: Quadrangle
Architects Limited. 2004.
Sheet Metal and Air Conditioning
Contractors National Association
(SMACNA). Architectural Sheet Metal
Manual, 5th ed. Chantily: SMACNA.
1993.
The Aluminum Association. Specifications
for Aluminum Sheet Metal Work
in Building Construction, 4th Ed.
Washington, D.C: The Aluminum
Association. 2000.
Young and Wright Architects Inc. The
Uptown Architectural Drawings and
Specifications. Toronto: Young and
Wright Architects Inc. 2004.
Answers to questions on page 31:
1. Type I — Non-combustible,
protected.
Type II — Non-combustible,
protected and unprotected.
Type III — Non-combustible
exterior walls, interior building
elements of any permitted
material.
Type IV — Non-combustible
exterior walls, interior building
elements of heavy timber.
Type V — Combustible; i.e., any
materials permitted by code.
2. Each of the five types of construction
identified by the IBC
has subclasses and each subclass
carries its own required fire
rating for the roof assembly.
3. a. Class 1 steel deck assemblies.
b. Non-combustible decks –
concrete, gypsum, asbestos
cement, and preformed
structural mineralized wood
fiber.
c. Wood decks treated with fireretardant
in organic salts
limiting flame spread to 25
feet or less.
4. a. Flame spread.
b. Flame exposure.
c. Burning brand.
d. Flying brand.
5. a. Roof slope.
b. Nature and quantity of
surfacing.
c. Membrane composition.
Reference: Manual of Low-Slope Roof
Systems – Fourth Edition
32 • I N T E R FA C E S E P T E M B E R 2006
Saba Saneinejad has a bachelor’s degree in architectural science
from Ryerson University. She is currently employed as a
building science specialist at Halcrow Yolles in Toronto. This
is her undergraduate thesis paper, conducted under the
supervision of Professor Hitesh Doshi.
Saba Saneinejad
Hitesh Doshi is a professional engineer and a faculty member
in the Department of Architectural Science at Ryerson
University in Toronto. He is involved in practice, research,
and teaching related to a variety of building science issues.
The information presented in this paper is a result of ongoing
work conducted by students at Ryerson under Doshi’s supervision.
Hitesh Doshi
The Building Enclosure Technology and Environment Council (BETEC) of
The National Institute of Building Sciences (NIBS) announces its new relationship
with Matrix Group Publishing in the production of the Journal of Building Enclosure
Design. As the need for better-performing building wall, below-grade, roof and fenestration
systems and related indoor environments grows, the journal will provide a
forum for new ideas and initiatives. Focus will be on the latest developments in
building energy conservation, security, and improved building envelope design and
performance.
The journal will be produced biannually, with the first edition expected in
August 2006. For more information, visit www.nibs.org.
Journal of Building Enclosure Design