Skip to main content Skip to footer

Evaluating Condensation Resistance for the Design of Wall Assemblies

May 15, 2012

EVALUATING CONDENSATION RESISTANCE
FOR THE DESIGN OF WALL ASSEMBLIES
PATRICK ROPPEL, PENG; AND MARK LAWTON, PENG
MORRISON HERSHFIELD, LTD.
610-3585 Graveley Street, Vancouver, BC V5K 5J5
Phone: 604-454-0402 • Fax: 604-454-0403 • e-mail: proppel@morrisonhershfield.com
2 7 T H RC I I N T E R N A T I O N A L C O N V E N T I O N A N D T R A D E S H OW • MA R C H 1 5 2
0 , 2 0 1 2 RO P P E L • 1 1 1
ABSTRACT
The energy efficiency aspirations of regulators necessitate innovations in many aspects
of composite wall design. To meet energy standards in mild and cold climates, providing
insulation in both interior and exterior wall cavities is increasingly becoming the norm.
Designers’ failure to understand the multidimensional nature of construction and to consider
how buildings actually operate can unnecessarily restrain the condensation resistance
and efficiency of wall systems. This presentation will explore how available resources can be
leveraged by practitioners without specialized knowledge of heat-air-moisture computer
models to evaluate condensation resistance of wall assemblies.
SPEAKER
PATRICK ROPPEL, PENG — MORRISON HERSHFIELD, LTD. VANCOUVER,
BC
PATRICK ROPPEL, PENG, is a building science engineer in Morrison Hershfield, Ltd.’s
(MH) Buildings, Technology, and Energy Division. He specializes in the analysis of building
envelope performance through numerical methods. His mixture of field experience, investigations,
computer modeling, and research is leveraged at MH to set realistic expectations
for building envelope performance during design and evaluation of existing buildings.
Roppel’s research includes predicting indoor moisture levels for uncontrolled humidity,
thermal performance of the building envelope, generic solutions for wall assemblies with low
air- and vapor-permeance insulation, and attic ventilation.
1 1 2 • RO P P E L 2 7 T H RC I I N T E R N A T I O N A L C O N V E N T I O N A N D T R A D E S H OW • MA R C H 1 5 2
0 , 2 0 1 2
EVALUATING CONDENSATION RESISTANCE
FOR THE DESIGN OF WALL ASSEMBLIES
INTRODUCTION
In order to realize increased energy efficiency
required by many building codes and
energy standards, innovations in many
aspects of wall design for residential buildings
are necessary. Providing insulation in
both interior and exterior wall cavities is
becoming an increasingly common strategy
to meet energy standards in mild and cold
climates.1 Innovative structural cladding
attachments have been developed to accommodate
different cladding types and varying
levels of exterior insulation. Advanced evaluation
techniques are necessary to determine
the impact of thermal bridging on both
the heat flow and structural capacity of
complex wall designs. Additionally, in order
to evaluate the condensation resistance of
these designs, techniques are required that
are more advanced than hand calculations
based on conventional assumptions.
Failure to consider multidimensional heat
flow and how buildings actually operate
when evaluating condensation resistance
can unnecessarily restrain innovative and
efficient wall systems in design practice.
This paper explores how practitioners
can approximate the condensation resistance
of wall assemblies for residential
buildings during the design phase, allowing
identification of details where more comprehensive
analysis is warranted.
The focus of the paper is to outline a
methodology that may be used to evaluate
the condensation resistance of composite
wall assemblies for any mild or cold climate.
To achieve this, a method to determine
appropriate indoor moisture levels (indoor
humidity) must first be outlined, since
assumptions about the indoor humidity are
critical to the evaluation of condensation
resistance. In practice, this can be as simple
as specifying the same design criteria for
all residential assemblies. Additional background
information is presented to provide
an appreciation of the concepts upon which
these methods are based.
The remainder of the paper outlines a
methodology to evaluate condensation
resistance using the concept of a temperature
index. Included in the discussion are
examples that use these methodologies, as
well as strategies for leveraging past
research and case studies when designing
wall assemblies.
DETERMINING INTERIOR
MOISTURE LEVELS FOR DESIGN
Realistic assumptions of indoor humidity
are critical when evaluating the condensation
resistance of wall assemblies, since
the indoor humidity contributes to the
“load.” However, indoor humidity is typically
neither directly controlled nor constant in
most residential buildings. The indoor
humidity in residential buildings actually
fluctuates with the outdoor temperature or,
more accurately, by the moisture content of
the outdoor air. The relationship between
the outdoor air and the indoor humidity
must be considered when determining
appropriate assumptions for indoor humidity.
If the appropriateness of the assumption
of the indoor humidity for the climate is
not verified, the assembly will likely be
designed for unintentional loads. A discussion
outlining how to determine climatedependent
indoor humidity levels for the
heating season follows.
Uncontrolled indoor humidity is said to
occur in buildings that do not directly control
the indoor moisture levels by mechanical
dehumidification. In these buildings,
outdoor air is heated to the indoor operating
temperature; and the primary mechanism
for removing moisture generated indoors is
ventilation (i.e., the exchange of indoor and
outdoor air). This means that indoor moisture
levels are governed by outdoor moisture
levels; therefore, the indoor moisture
levels are higher than the outdoor moisture
levels for the entire heating season. How
much higher the indoor air moisture levels
are compared to the outdoor air is largely
dependent on the ventilation rate relative to
the rate that moisture is produced in the
indoor space. This relationship leads to the
following statement, which is the basis on
which we advise indoor humidity be defined
when evaluating the condensation resistance
of wall assemblies:
Residential buildings with similar
average ventilation and moisture
production rates will have a
similar excess of moisture in the
indoor air compared to the outdoor
air, regardless of the climate.
It is important to recognize that the previous
statement is supported by physics
and has been observed in numerous measurements
in real buildings. Please note,
however, that it is not the intent of this
paper to provide a comprehensive assessment
and foundation of an indoor moisture
model. Research into indoor moisture models
and measuring the indoor moisture levels
compared to the outdoor moisture levels
has a long history. Work related to establishing
indoor moisture levels for design is
reported to date back to the 1970s. Recent
publications are included in the references
to this paper (Roppel et al., 2009; Sanders,
2009; Kalamees et al., 2009; Kumaran et
al., 2008). The objective of this paper is to
recognize that residential buildings with
uncontrolled humidity can be categorized
by the likely excess of moisture in the
indoor air and to illustrate how convenient
this information can be for defining indoor
humidity.
Next, units are needed to define indoor
humidity by the likely excess of moisture in
the indoor air. There are many units that
can be used to define the excess of moisture
in the indoor air compared to the outdoor
air, but there are advantages to the following
approach:
Define the excess of moisture in
the indoor air compared to the
outdoor air by vapor pressure difference
(ΔVP).
Vapor pressure is a measure of the
moisture in air, which can be calculated
when the temperature and relative humidity
(RH) are known. The difference in vapor
pressure directly defines the “load” and
indicates the overall vapor pressure gradient
that drives vapor through the assembly.
2 7 T H RC I I N T E R N A T I O N A L C O N V E N T I O N A N D T R A D E S H OW • MA R C H 1 5 2
0 , 2 0 1 2 RO P P E L • 1 1 3
Example 1 Determining Indoor
Moisture Levels by ΔVP
Design Vapor Pressure Difference ΔVP)
ASHRAE Handbook Fundamentals
the European Indoor Climate Class Model
established by European statistical data
(ISO standard 13788-01). The ΔVP limits
are defined by a single parameter that represents
the combined effects of moisture
generation, moisture removal by ventilation,
and secondary effects such as moisture
buffering and window condensation.2
This standard specifies 0.117 psia (810 Pa)
as high indoor humidity for dwellings with
high occupancy and/or moisture generation.
These limits should be used with some
caution, since the single parameter does not
provide guidance with regard to their
applicability to acceptable ranges of building
construction (airtightness), ventilation,
and climate type (heating degree days and
outdoor moisture region). However, by making
modest reality checks, one can overcome
prudence regarding European ΔVP
limits without unnecessarily restraining the
design of innovative assemblies with overly
cautious and unrealistic design assumptions.
Reality checks can include: comparisons
to traditional accepted RH levels for
specific climate, accepted RH levels for
health and occupant comfort, ΔVP limits
compared to typical condensation resistance
of windows, moisture balance equations,
and measured data. A broad discussion
of reality checks of ΔVP limits for mild
and cold climates is available (Roppel et al.,
2009).
The European humidity classifications
contained in ISO standard 13788-01 do not
directly state whether the ΔVP limits are for
average conditions (weekly, monthly, or
seasonal intervals) or peak design conditions
(hourly to daily intervals). The difference
between average conditions and peak
design conditions should be considered
based on the type of condensation resistance
evaluation being performed. This
paper is focusing on quick analyses of condensation
resistance of building envelope
assemblies to target problematic details at
steady-state design conditions.
In monitored buildings, ΔVP will fluctuate
due to varying rates of moisture generation
and removal over hourly and daily periods.
The average ΔVP over the winter
months is fairly constant. ΔVP values at
design conditions should represent high
moisture levels that are only occasionally
exceeded in code-compliant buildings. In
other words, an appropriate ΔVP value for
peak design conditions should be a value
that is not the highest ever recorded ΔVP,
but should instead represent high moisture
Moreover, indoor humidity is dependent on
ΔVP; therefore, it is highly desirable to
define interior moisture levels by ΔVP
directly. An example showing how the
indoor air moisture levels are defined by
ΔVP follows.

This example demonstrates how the
indoor humidity can be calculated for any
climate using a single ΔVP value to account
for the excess moisture in the indoor air.
This example includes a comparison
between two climates: Chicago, Illinois, as a
cold climate; and Portland, Oregon, as a
mild marine climate. The ΔVP value selected
for this example is 800 Pa (pascal units
of pressure, whose corresponding imperial
unitl is pounds per square inch or psi). The
significance of this value will be discussed
later.
The ASHRAE Handbook – Fundamentals
(2009) provides outdoor design conditions
for these climates in Chapter 14, “Climatic
Design Information.” These values are listed
as the 99% January humidification design
conditions and the mean coincident drybulb
temperature. The values relevant to
this example are summarized in Table 1.
These values provide a measure of the outdoor
moisture content and temperature at
January design conditions, and therefore
we can determine the design outdoor vapor
pressure (Pout). This can be calculated directly
from the outdoor dewpoint temperature
by the saturation vapor pressure at the
dewpoint temperature using Table 3 or
Table 1 – Outdoor design conditions for example climates determined by design
tables in the – .
Table 2 – Calculated indoor design conditions for example climates.
Equations 5 and 6, all of which are in
Chapter 1 of The ASHRAE Handbook – Fundamentals
(2009), “Psychrometrics.” Outdoor
temperature, RH, and outdoor moisture
content are provided as reference values
and to allow comparison with values
determined by psychrometric charts.
The indoor vapor pressure (Pin) for a ΔVP
equal to 0.123 psia (800 Pa) is calculated by
adding the ΔVP to the outdoor vapor pressure
(Pout): Pin = Pout + ΔVP. Table 2 summarizes
the calculated indoor vapor pressure
and RH at 70ºF (21ºC) for these two example
climates.
The remaining step in establishing
indoor humidity by the likely excess of
moisture in the indoor air is to determine
an appropriate value for ΔVP for design. The
significance of a ΔVP equal to 0.116 psia
(800 Pa) is now presented.
(
Guidance on appropriate design ΔVP
values for North American buildings for
diverse occupancies, construction, operation,
and climates is sparse. Sources of
information on ΔVP limits appropriate for
design are available, although this information
is largely based on data from European
buildings (Roppel et al., 2009; Sanders,
2009; Kalamees et al., 2009; Kumaran et
al., 2008; ISO standard 13788-01). However,
it is possible to make reasonable
assumptions for evaluating condensation
resistance of wall assemblies for North
American buildings.
A good starting point for finding guidance
on appropriate design ΔVP values is
Climate Outdoor
Dewpoint
Temperature
ºF (ºC)
Outdoor
Temperature
Humidity
ºF (ºC)
Outdoor
Relative
Pressure
(%)
Outdoor
Vapor
psia (Pa)
Chicago -8 (-22) 4 (-16) 56 0.012 (85)
Portland 16 (-9) 35 (2) 40 0.042 (284)
Climate Outdoor Vapor
Pressure, Pout
psia (Pa)
ΔVP
psia (Pa)
Indoor Vapor
Pressure, Pin
psia (Pa)
Indoor Relative
Humidity
@ 70ºF (21ºC)
(%)
Chicago 0.012 (85 0.116 (800) 0.128 (885) 36
Portland 0.042 (284) 0.116 (800) 0.158 (1084) 44
1 1 4 • RO P P E L 2 7 T H RC I I N T E R N A T I O N A L C O N V E N T I O N A N D T R A D E S H OW • MA R C H 1 5 2
0 , 2 0 1 2
Figure 1 – Example of ΔVP distribution of a monitored building in Vancouver,
Canada, during the heating season.
levels for most buildings the majority of the
time. Figure 1 illustrates this point for a
monitored building in Vancouver, Canada,
during the heating season.
A ΔVP value of approximately 0.116 psia
(800 Pa) would appear to be appropriate for
mild and cold climates for steady-state calculations
for the following reasons:
1. An upper-bound ΔVP for cold weather
can be determined by recognizing
that humidification is typically necessary
to maintain an RH of 35% in
cold weather. Additionally, there is
very little difference in moisture levels
for temperatures less than -13ºF
(-25ºC). Therefore, a reasonable
upper bound is the vapor pressure
of indoor air at 35% RH and 70ºF
(21ºC) minus the small amount of
moisture in the outdoor air for the
cold-weather design temperatures. A
value of 0.116 psia (800 Pa) is the
ΔVP for saturated outdoor air (i.e.,
100% RH) at -13ºF (-25ºC) and
indoor air at 35% RH and 70ºF
(21ºC).
2. The upper-bound ΔVP of 0.116 psia
(800 Pa) can also be verified for mild
weather by recognizing that ventilation
rates in residential buildings
should be set such that the indoor
RH is maintained less than 60% RH
for all seasons,3 as per typical
assumptions in ASHRAE standards
and many building codes. This is
dependent on occupant behavior—
i.e., opening windows or turning on
a fan when uncomfortable, but is
the accepted upper limit for indoor
humidity. Indoor air at 60% RH and
70ºF (21ºC) roughly translates to a
ΔVP of 0.116 psia (800 Pa) for average
winter outdoor temperatures in
mild marine climates.
3. The typical thermal performance of
windows can also provide a realistic
upper bound of ΔVP because windows
are typically the coldest interior
surface exposed to interior air
and, therefore, the location where
condensation is most likely to occur.
Indoor humidity should be controlled
such that excessive condensation
will not occur on commonly
available good-quality windows.4
Furthermore, window condensation
can moderate the indoor vapor pressure
by dehumidifying the indoor air
by condensation. Evaluation of the
condensation resistance of typical
good-quality, double-glazed win-
Is the temperature
dows5 available in cold climates supports
an upper bound of ΔVP at
0.116 psia (800 Pa).
These reality checks provide an upper
bound for a ΔVP value of approximately
0.116 psia (800 Pa) that seems appropriate
for steady-state design conditions. Note
that a lower ΔVP value is appropriate for
both average conditions and analyses that
consider varying outdoor conditions. This
upper bound of ΔVP allows the indoor moisture
level to be defined for any climate by
utilizing the outdoor design conditions provided
by building codes and standards, as
shown in example calculations above for
Chicago and Portland.
The remainder of the paper outlines a
methodology to evaluate condensation
resistance for indoor conditions defined by
ΔVP.
EVALUATING CONDENSATION
RESISTANCE
The basis of the methodology to evaluate
condensation resistance is to determine the
risk that interior surface temperatures and
surface temperatures within the enclosure
will be colder than the dew point of the air
in contact with that surface. Predicting surface
temperatures for wall assemblies can
be extremely complex when considering
heat-air-moisture transfer through threedimensional
wall assemblies. However,
there are specialists in this type of analysis
who can calculate these values. The
methodology presented here leverages the
work of others that has evaluated some of
these complexities for generic assemblies
and applies this information to the design of
similar assemblies for specific climates.
This can be accomplished through the use
of temperature indices by comparing a temperature
index for an assembly under consideration
(assembly temperature index) to
the minimum acceptable temperature index
(design temperature index). In simpler
terms, the following evaluation is done (see
Evaluation 1).
Temperature index is explained below,
The minimum or
index of the
assembly
(Tassembly)
Greater
Than
design temperature
index
(Tdesign)
Evaluation 1
2 7 T H RC I I N T E R N A T I O N A L C O N V E N T I O N A N D T R A D E S H OW • MA R C H 1 5 2
0 , 2 0 1 2 RO P P E L • 1 1 5
Temperature Index
Assembly Temperature Index
T reasonable estimates surface – Toutside of the surface temper- Ti = atures of common
T assemblies available inside – Toutside that consider threedimensional
heat
Where flow, either by lab
Ti is the temperature index (-) measurement or com-
Tsurface is the coldest temperature of the surface puter modeling
Ooutside is the outdoor temperature
Tinside is the indoor temperature
Equation 1
followed by a discussion of the steps
required to determine the values for each of
the boxes in Evaluation 1.
A temperature index is a way to represent
a surface temperature of interest (or
concern) relative to a temperature difference.
It allows a surface temperature to be
extrapolated to any set of indoor and outdoor
temperatures. Essentially, it is the
temperature drop between the inside air
and a surface, divided by the total temperature
difference. Temperature indices for a
surface are calculated as follows (see
Equation 1).
A temperature index of zero is the outdoor
air temperature, and a temperature
index of one is the indoor air temperature.
There are many variations of this concept
embodied in standards by various
organizations. Most commonly, these methods
are used by standards for fenestration
products to compare the condensation
resistance or to rate different products
(AAMA 1503-09, NFRC 500-2010,
CAN/CSA A440-00). However, these methods
are sometimes also contained in standards
for evaluating the condensation resistance
of any building envelope component
(ISO 13788:2001 [E]). The indices vary with
respect to the way in which temperatures
are averaged or the specific environmental
conditions upon which they are based. The
only indices relevant to wall assemblies are
the I-value (CAN/CSA A440) and temperature
factor, fRsi (ISO 13788:2001 (E)), each of
which are nearly identical to the temperature
index.
Predicting surface temperatures can be
extremely complex when considering heatair-
moisture transfer through three-dimensional
wall assemblies. However, there are
(Brown et al., 1993;
Kosny et al., 1994;
Roppel et al., 2011).
Before discussing
how to use these
data, readers are alerted to the limitations
of extrapolating temperature data (which
has been determined for one set of conditions
through either modeling or direct
measurement) to other conditions through
the use of temperature indices. Surface
temperatures of building envelope components
are affected by heat and moisture
storage effects, air transport, and localized
variations (for example, fastener locations,
surface resistances, moisture levels, etc.),
which may or may not be incorporated into
the method of determining temperatures.
Reported temperature indices are most
commonly determined for conditions that
are either controlled or set up to determine
surface temperatures as a result of steadystate
conduction and radiation.
Accordingly, temperature indices should be
used with attention to the limitations, and
users should not perceive temperature
indices as the absolute minimum temperatures
that can be expected in practice.
Nevertheless, temperature indices can be
used to target areas where the risk of condensation
does not appear to be effectively
minimized.
Figure 2 illustrates the three-dimensional
(3-D) temperature distribution of a steel
stud wall assembly in which the exterior
insulation is interrupted by horizontal
Z-girts that support the cladding and interior
insulation in the stud cavity. The temperature
distribution of this wall assembly
is dependent on the spacing, size, and orientation
of the various thermal bridges. For
comparison, if the insulation is continuous,
then the coldest temperature on the exterior
sheathing is between the steel studs.
However, if the Z-girts are vertical and in
Figure 2 – Temperature distribution of a steel-stud assembly with 3-D heat flow
paths.
1 1 6 • RO P P E L 2 7 T H RC I I N T E R N A T I O N A L C O N V E N T I O N A N D T R A D E S H OW • MA R C H 1 5 2
0 , 2 0 1 2
Design Temperature Index
Design Temperature Index for Surfaces
in Contact to the Interior Air
Example 2 Determining the Design
Temperature Index for Interior Air at
Winter Design Conditions
Figure 3 – Distribution of surface temperatures of exterior Figure 4 – Relationship of design temperature index to ΔVP.
sheathing for an example steel-stud assembly with exterior
Z-girts and insulation.
line with the steel studs, then the coldest
temperature will be at the intersection of
the girts and studs. For the horizontal girt
system shown in Figure 2, the coldest surface
temperature of the sheathing occurs
along the steel girts between the steel studs
as shown by the ovals.
Figure 3 plots the temperature distribution
of the interior surface of the exterior
sheathing through horizontal sections at
the Z-girts and between the Z-girts to show
the range of surface temperatures on the
exterior sheathing of the assembly illustrated
in Figure 2.
In this example, the assembly temperature
index (Tassembly) for evaluating the risk of
condensation on the exterior sheathing is
approximately 0.32 (i.e., the lowest index).6
There are a couple of things worth noticing
from this example. First, Tassembly could have
been determined for any surface–for example
the interior surface–but one must
remember that the design temperature
index Tdesign must be evaluated at the same
surface (this will be discussed in the next
section). Secondly, for this example, 3-D
heat flow must be considered to evaluate
the surface temperatures. 3-D heat transfer
calculation methods are not necessary if the
heat flow through the section occurs only in
one or two dimensions. However, consideration
of the heat flow path, judging by the
orientation of highly conductive components,
is critical for evaluating surface temperature.
It is important to recognize this
when using temperature data for evaluating
condensation resistance.
The design temperature index can be
the interior air dew point temperature, the
dew point of the air in contact with that
surface, or minimum surface temperature
based on an acceptable RH at that surface.
Each of these values is determined by first
establishing the indoor vapor pressure
using the ΔVP methods presented in the
first part of this paper. Where and how one
can determine the design temperature
index for these three conditions follows.
Tdesign values for surfaces in contact with
the interior air are determined by first calculating
the temperature index (Ti) using
Equation 1 above, and the interior air dew
point. These steps are outlined in the following
example.

Using Chicago as an example again, the
indoor vapor pressure
of (Pin) of 0.128 psia Where (885 Pa) calculated in
rics.” For this example, the interior air dewpoint
is 42ºF (5ºC). Using Equation 1 above,
the design temperature index can be calculated.
See Equation 2.
A minor complication is that ΔVP has an
exponential relationship with varying outdoor
temperature, but temperature indices
have a linear relationship with varying outdoor
temperature. The significance of this
relationship is that a design temperature
index defined by the coldest outdoor conditions
for a climate might not be good
enough for milder weather for the same climate.
This is something we observe in practice
for mild marine climates. Window condensation
will occur in mild, moist weather
(i.e., 40º to 50ºF [5º to 10ºC]) during rain,
but will not occur on the same windows
during dry and cold weather (i.e., less than
32ºF [0ºC]). Figure 4 illustrates this by plotting
the minimum temperature index equal
to ΔVP = 0.116 psia (800) for varying outdoor
temperature.
As can be seen in Figure 4, between 32º
and 40ºF, for outdoor RH levels greater than
85%, the minimum temperature index
Tsurface is the interior air dew point equal to 42ºF (5ºC) Example 1 is used to Toutside is the outdoor temperature equal to 4ºF (-16ºC) calculate the interior- Tinside is the indoor temperature equal to 70ºF (21ºC) air dew point. This Therefore, can be done using a
psychrometric chart 42 4 or using Equation 39 –
or 40 in Chapter 1 of Tdesign = = .058
the ASHRAE Hand70
– 4 book – Fundamentals
(2009), “Psychromet- Equation 2
2 7 T H RC I I N T E R N A T I O N A L C O N V E N T I O N A N D T R A D E S H OW • MA R C H 1 5 2
0 , 2 0 1 2 RO P P E L • 1 1 7
increases with warmer temperatures. For
this reason—especially for a mild marine
climate—the design temperature index
should be defined considering milder temperatures
as well as the heating design outdoor
temperature. However, it is only necessary
to consider up to around 40ºF (5ºC) at
95% RH because ΔVP characteristically
decreases in mild-to-warm weather (Roppel
et al., 2009; Sanders, 2009; Kalamees et al.,
2009; Kumaran et al., 2008).
For designs with air-permeable insulations
inboard of or within the building
structure, the condensation resistance
requires that a design temperature index be
defined for surfaces within the enclosure.
A cautious assumption is to define the
minimum temperature index by the indoor
air dew point as per the previous section,
based on the view
that air leakage can
bring moisture into
the enclosure from
the indoor air. However,
this assumption
will restrain the design
of many wall
assemblies with split
insulation for noncombustible
construction.
A Glaser or dew
point calculation
method can be used
to determine the vapor
pressure or dew
point at a surface
within an assembly.
Add up all the vapor
resistances (the inverse
of vapor permeance)
for each material,
and determine the
vapor pressure at the pertinent surface by
the ratios of the resistances. An example
follows.
This example demonstrates how to
evaluate the condensation resistance by
calculating Tdesign at the interior surface of
the exterior sheathing for Portland and
Chicago climates using a Glaser or dew
point calculation method and comparing to
tabulated Tassembly values. This example
assumes minimal vapor control at the interior
surface.
The vapor pressure at the inside surface
of the exterior sheathing, Psurface, is
Psurface Pin Rin/Rtotal*ΔVP,
where Rin is the sum of the vapor resistances
inboard of the surface being evaluated.
For Chicago, using the information in
Tables 2 and 3 and Figure 5, the vapor pressure
at the inside surface of the exterior
sheathing is
Pin 0.128 – (0.006 + 0.2 + 0.03)/
4.3*0.116 = 0.128 – 0.05*0.116 = 0.12 psia
The dew point temperature can now be
calculated using Equation 39 or 40 in
Chapter 1 of the ASHRAE Handbook
Fundamentals (2009), “Psychrometrics.”
From this value, the Tdesign can be calculated
as per Example 2. Table 4 summarizes values
that need to be determined to calculate
Tdesign at a surface within the assembly using
dew point calculation methods for Chicago
and Portland.
The minimum temperature index for the
interior surface of the exterior sheathing for
the assembly shown in Table 3 is Tassembly
0.32. The lowest temperature is located
between the steel studs along the exterior
girts as illustrated in Figures 2 and 3.
Design Temperature Index for Surfaces
Within the Assembly
Example 3 Evaluation of the
Condensation Resistance at an Interior
Surface Using a Dew Point Calculation
=


= – =
Component Vapor
Permeance
(Perm)
Vapor
Resistance
(Perm-1)
Interior air film 160 0.006
½-in. (13-mm) drywall with primer and paint 5 0.2
R12 fiberglass batt 32 0.03
½-in. (13-mm) ext. sheathing 50 0.02
Sheathing membrane 7 0.14
3-in. (75-mm) XPS insulation 0.27 3.70
½-in. (13-mm) air space 240 0.01
Painted fiber cement siding 5 0.2
Exterior air film 1000 0
Total (Rtotal) 4.3
Table 3 and Figure 5 – Vapor resistances of example steel-stud wall assembly with split insulation.
Climate Pout
psia
(Pa)
Pin
psia
(Pa)
Psurface
psia
(Pa)
Dew Point Temperature
at Surface
ºF
(ºC)
Outdoor
Temperature
ºF
(ºC)
Indoor
Temperature
ºF
(ºC)
Tdesign
Chicago 0.012 0.128 0.12 40 4 70 0.54
(85) (885) (874) (4.4) (-16) (21)
Portland 0.042 0.158 0.15 46 35 70 0.30
(284) (1084) (1073) (7.6) (2) (21)
Table 4 – Tdesign at interior surface of exterior sheathing.
1 1 8 • RO P P E L 2 7 T H RC I I N T E R N A T I O N A L C O N V E N T I O N A N D T R A D E S H OW • MA R C H 1 5 2
0 , 2 0 1 2
Evaluation of
Condensation
Resistance for
Assemblies With 3-D
Heat Flow and Air
Leakage
Example 4 Establishing Minimum
Insulation Ratios for Assemblies With
3-D Heat Flow
Figure 6 – Temperature index at curtain wall spandrel
panel is lower than for clear field area of example steelstud
assembly.
condensation must
also be considered. Air
leakage can both wet
and dry-out assemblies,
which depends
on varying outdoor
and indoor conditions
specific to a climate.
Luckily, there are solutions
available that
consider the complex
he a t – a i r -mo i s tur e
transfer through stud
cavities to help determine
minimum insulation
ratios for many
climates. An example
of leveraging these solutions
is presented
next.
Considering multidimensional
heat flow
and air leakage is
important when evalu-
Clearly, the condensation resistance of
the wall design is not adequate for Chicago
(Tassembly << Tdesign) but marginally adequate for
Portland (Tassembly ~ Tdesign). However, closer
attention to the details is warranted for this
assembly in Portland (i.e., at transition
details to other assemblies) because of the
marginal adequateness of this assembly for
the design conditions. For example, without
modifications, the condensation resistance
would not be sufficient at a transition to the
curtain wall spandrel panel detail illustrated
in Figure 6. The assembly temperature
index is 0.26 along the exterior girts near
the spandrel panel.
The condensation resistance of the wall
assembly can be improved by providing a 1-
ating the condensation
resistance of many
wall designs. There are solutions available
that provide the minimum amount of outboard
insulation for many climates and
conditions. However, these solutions do not
typically consider 3-D heat flow directly.
This limitation can be overcome by utilizing
the assembly temperature indices determined
by 3-D heat-transfer modeling. The
following examples show how this is done.

Solutions to the minimum amount of
outboard insulation required for stud walls
with insulation in the stud cavity, considering
the effects of air leakage, are available
(Kumaran et al., 2002, 2005, NBC; Brown
et al., 2007; Craven et al., 2010). However,
these solutions typically assume continuous
outboard insulation, and the assumed
indoor moisture levels are not always
defined by a constant ΔVP during the winter.
This example shows how to use generic
solutions for minimum insulation ratios
and apply them to assemblies with thermal
bridging through the exterior insulation.
Generic solutions suggest a minimum of
27% of the thermal resistance (sheathing,
insulation, cladding) should be placed outboard
of the studs to minimize7 air leakage
condensation for a ΔVP equal to 800 for
heating degree days up to 12600 HDD 65ºF
(7000 HDD 18ºC).8 A more conservative
solution, with stricter acceptance criteria,
suggests that 50% of the insulation should
be placed outboard of the studs to maintain
the sheathing temperature above the
interior-air dew point for a ΔVP equal to 800.
Tdesign can be established by the insulation
ratio from recognizing that thermal
resistance is directly proportional to the
temperature distribution through an
assembly for 1-D heat flow. Therefore, Tdesign
is equal to the minimum thermal resistance
required outboard of the studs.
For this example, the wall assembly is a
steel-stud assembly that must comply with
ANSI/ASHRAE/IESNA 90.1-2007 for nonresidential
buildings as outlined in Table 5.
Different insulation strategies and methods
to attach the cladding are being considered
for Chicago.
U-values and Tassembly values are tabulated
in Table 6 and Figures 7, 8 and 9 for
three example assemblies.
The two assemblies with only exterior
insulation exceed both the minimum
requirement of 27% outboard thermal resistance
and a more conservative design criterion
of 50% outboard thermal resistance.
The split insulated assembly, on the
other hand, can meet the minimum requirement
of 27% outboard thermal resistance
but cannot practically meet the 50% outperm
vapor retarder (i.e., low-perm paint).
This is still not good enough for Chicago,
but it will provide an extra margin of safety
for Portland. The Tdesign values decrease to
0.48 and 0.20 for Chicago and Portland,
respectively, with the addition of a 1-perm
vapor retarder. The Chicago Tdesign decreases
to below 0.32 with the addition of a 0.2-
perm vapor retarder. However, air leakage Table 5 – Insulation requirements for example climates per ASHRAE 90.1-2007.
Example Climates Zone Insulation U-Value
Btu/ft2 hr ºF
(W/m2 K)
Portland, Chicago,
Toronto, Edmonton
4 to 7 R-13 cavity insulation
+ R-7.5 continuous
outboard insulation
0.064
(0.36)
2 7 T H RC I I N T E R N A T I O N A L C O N V E N T I O N A N D T R A D E S H OW • MA R C H 1 5 2
0 , 2 0 1 2 RO P P E L • 1 1 9
board thermal resistance design criterion. It
is interesting to note that the energy
requirements can be met with the intermittent
girts assembly by providing around
R-17 of insulation and has a very good condensation
resistance. Conversely, the splitinsulated
assembly can meet the energy
requirements with around R-10 exterior
insulation and R-12 batt insulation, but
has marginal condensation resistance.
CONCLUDING REMARKS
As energy-efficiency requirements tighten,
providing insulation in both interior and
exterior wall cavities is becoming the norm
to meet energy standards in mild and cold
climates. Not all assemblies are going to
have the ideal of continuous insulation. The
effects of 3-D heat flows on condensation
resistance need to be evaluated during the
design of some wall assemblies. However,
considering the combined effects of heatair-
moisture transfer is often not practical
in the middle of designing a building, and
simple dew point methods will typically restrain
innovative design because the duration
of wetting and drying cannot be effectively
evaluated.
This paper explored analysis methods
that are available to practitioners to quickly
evaluate the condensation resistance of wall
assemblies for residential buildings during
design by leveraging generic solutions. The
key to leveraging generic solutions for evaluating
condensation resistance is the ability
to reasonably approximate indoor conditions
and surface temperatures for a range
of climates without detailed analysis. ΔVP
limits and temperature indices provide the
mechanism for quick analysis that is supported
by more detailed analysis and measurement.
REFERENCES
2006 IECC, International Energy Conversation
Code, International Code
Council, Falls Church, Virginia.
2009 ASHRAE Handbook Fundamentals,
American Society of Heating,
Refrigeration and Air-Conditioning
Engineers, Inc., Atlanta, GA.
AAMA 1503-09, Voluntary Test Method
for Thermal Transmittance and
Condensation Resistance of Windows,
Doors, and Glazed Wall Sections,
American Architectural Manufacturers
Association (AAMA),
U-value R-5 0.146 (0.83) 0.075 (0.42) 0.132 (0.75)
Btu/ft2hrºF R-10 0.106 (0.60) 0.061 (0.35) 0.089 (0.50)
(W/m2 K) R-15 0.088 (0.50) 0.054 (0.31) 0.068 (0.39)
R-20 0.076 (0.43) 0.49 (0.28) 0.057 (0.32)
R-25 0.069 (0.39) 0.045 (0.26) 0.049 (0.28)
Tassembly R-5 0.63 0.21 0.63
R-10 0.69 0.28 0.7
R-15 0.72 0.32 0.73
R-20 0.75 0.36 0.76
R-25 0.76 0.38 0.78
Table 6 – U-values and temperature indices for example assemblies.
Figure 7 Figure 8 Figure 9
Exterior Exterior Insulated Split Insulated Exterior Insulated
Insulation Horizontal Girts Horizontal Girts Intermittent Girts
@ 24 in. o.c. @ 24 in. o.c. @ 36 in. o.c.

1 2 0 • RO P P E L 2 7 T H RC I I N T E R N A T I O N A L C O N V E N T I O N A N D T R A D E S H OW • MA R C H 1 5 2
0 , 2 0 1 2
Schaumburg, IL.
ANSI/ASHRAE 169-06, Weather Data
for Building Design Standards,
American Society of Heating, Refrigeration
and Air-Conditioning
Engineers, Inc., Atlanta, GA.
ANSI/ASHRAE/IESNA 90.1-07, Energy
Standard for Buildings Except LowRise
Residential Buildings, American
Society of Heating, Refrigeration and
Air-Conditioning Engineers, Inc.,
Atlanta, Georgia.
C.M. Brown, P. Roppel, and M. Lawton,
“Developing a Design Protocol for Low
Air and Vapor Permeance Insulating
Sheathing in Cold Climates,” Proceedings
of the X International
Conference on the Performance of
Whole Buildings, Clearwater, FL.
www.morrisonhershfield.com/
newsroom/TechnicalPapers/Pages/
default.aspx, 2007.
W.C. Brown and D.G. Stephenson,
“Guarded Hot Box Measurements of
the Dynamic Heat Transmission
Characteristics of Seven Wall Specimens,
Part II,” ASHRAE Transactions,
Vol. 99, Part 2, Paper 3684,
(ASHRAE 515-RP), 1993.
CAN/CSA A440-00, “Windows,” CSA
International, Toronto, Ontario,
Canada.
CAN/CSA A440.1-00, “User Selection
Guide to CSA Standard A440-00,
Windows,” CSA International, Toronto,
Ontario, Canada.
C. Craven and R. Garber-Slaght, “Safe
and Effective Exterior Insulation
Retrofits: Phase I”, Cold Climate
Housing Research Center (CCHRC).
Fairbanks, Alaska.www.cchrc.org
/ d o c s / s n a p s h o t s /RS _ 2 0 1 0 –
03_Exterior_Insulation.pdf, 2010.
ISO 13788:2001 (E), “Hygrothermal
Performance of Building Components
And Building Elements –
Internal Surface Temperature to
Avoid Critical Surface Humidity and
Interstitial Condensation – Calculation
Methods,” Geneva, Switzerland.
T. Kalamees, J. Vinha, “Indoor Humidity
Loads and Moisture Production in
Lightweight Timber-frame Detached
Houses,” Journal of Building
Physics, Volume 29, No. 3.
http://jen.sagepub.com/cgi/content
/refs/29/3/219, 2006.
J.P. Kosny, J.E. Christian, E. Barbour,
J. Goodrow, “Thermal Performance air via condensation. Hygroscopic
of Steel-Framed Walls,” CRADA materials, such as wood, also have a
Final Report, CRADA Number ORNL moderating effect on indoor air
92-0235, 1994. moisture levels.
M.K. Kumaran and J.C. Haysom, “Low- 3. At winter operating temperatures
Permeance Materials in Building between 68ºF (20ºC) and 74ºF
Envelopes,” Construction Technol- (23ºC) and summer operating temogy
Update No. 41, National Re- peratures between 73ºF (23ºC) and
search Council Canada, 2002. 79ºF (26ºC), which represent human
M.K. Kumaran, C.H. Sanders, F. Tariku, occupancy comfort for 80% of
S. Cornick, H. Hens, B. Blocken, J. sedentary or slightly active persons
Carmeliet, M. de Paepe, and A. in a thermally controlled environ-
Janssens, “Boundary Conditions ment (ASHRAE Standard 55).
and Whole Building HAM Analysis,” 4. If excessive condensation were to
Annex 41, Whole Building Heat, Air, occur on typical windows, it would
Moisture Response, Volume 2, ISBN be necessary to increase ventilation
978-90-334-7059-2, KU Leuven, effectiveness or dehumidify the
Belgium, 2008. indoor air.
NBC 2005, National Building Code of 5. A temperature index of 0.65 was
Canada, Section 9.25, National Re- used for this analysis. More about
search Council Canada. temperature index is presented later
NFRC 500-2010, Determining Fenesin
the paper. Refer to the reference
tration Product Condensation Resistpaper
for more details on this point.
ance Values, National Fenestration 6. This temperature index value was
Rating Council Incorporated, determined for ASHRAE research
Greenbelt, Maryland. project 1365-RP. A catalogue of ther-
P. Roppel, M. Lawton, and W.C. Brown, mal performance data, including
“Setting Realistic Design Indoor temperature indices, for 40 common
Conditions for Residential Buildings building envelope for mid- and highby
Vapor Pressure Difference,” rise construction is contained in the
Journal of ASTM International, Vol. final report (Roppel et al., 2011).
6, No. 9, West Conshohocken, 7. Condensation may occur under
Pennsylvania. Paper available on extreme conditions but occurs infrewww.
astm.org, 2009. quently, and moisture does not
P. Roppel and M. Lawton, “Thermal Per- accumulate.
formance of Building Envelope 8. Assuming an air barrier is provided
Details for Mid- and High-Rise that controls air movement through
Buildings (1365-RP),” ASHRAE Rethe
assembly (assumed 0.1 L/(s·m²)
search Project 1365RP
Final Report, at 75 Pa maximum). Value deter-
Atlanta, Georgia. Paper available on mined by heat-air-moisture modelwww.
ASHRAE.org, 2011. ing (Brown et al., 2007).
C. Sanders, “Heat, Air, and Moisture
Transfer in Insulated Envelope
Parts, Task 2: Environmental Conditions”
Report Annex 24, Volume 2,
KU Leuven, Belgium, www.ecbcs.org
/annexes/annex24.htm, 1996.
FOOTNOTES
1. Climate Zones 4 to 8 as identified in
2006 IECC, ANSI/ASHRAE 169-06,
and ANSI/ASHRAE/IESNA 90.1-07.
2. Typically, windows are the thermally
weakest components of the building
envelope and present the coldest
interior surface temperature. Windows
can therefore moderate the
interior air moisture levels by
removing moisture from the indoor
2 7 T H RC I I N T E R N A T I O N A L C O N V E N T I O N A N D T R A D E S H OW • MA R C H 1 5 2
0 , 2 0 1 2 RO P P E L • 1 2 1