A Consultant’s Guide to the Use of Siliconized Gypsum-Based Roof Boards

February 27, 1998

A Consultant’s Guide to the Use of
Siliconized Gypsum-Based Roof Boards

 

By Jerry Teitsma, RRC
Roof Systems Consultants,
Roswell, GA
Abstract
This paper provides a guide for the use and specification of siliconized
gypsum-based roof boards. Addressed are advantages and limitations of
these products in single-ply, BUR, and modified bitumen roof systems.
Specifically addressed are issues affecting use specifications.
Gerard J. Teitsma
Owner of Roof Systems Consultants, Roswell, GA, Gerard J. Teitsma is a roofing and
waterproofing consultant and a Registered Roof Consultant through RCI. He holds a
bachelor’s degree in Wood Technology and a master’s in Construction Engineering from
Michigan State University. Teitsma’s career began at Dow Chemical, where he was responsible
for development of the IRMA Roof System. In the early 70s, Teitsma was an assistant
professor in the Construction Management Dept, of the University of Nebraska, later doing
research on the thermal performance of buildings in a jointly-sponsored program of Dow
and the National Bureau of Standards. In 1982, he and two partners started Styro Systems
Inc., selling insulation a nd allied construction products. In 1989, he became president and
co-owner of Insulation Systems of Georgia, Inc., transforming the company from a tapered
insulation distributor to a tapered insulation fabricator distributing a full line of commercial
roofing materials. Teitsma is former chairman of TC 4.4, Insulation and Vapor Retardants,
with ASHRAE; past-president of the Atlanta Chapter of CSI and a Construction Document
Technologist, a member of the Georgia Rofoing and Sheet Metal Contractors Association,
and a staff instructor with RIEL

 

A Consultant’s Guide To The Use Of
Siliconized Gypsum-Based Roof Boards
By Jerry Teitsma, RRC

Fitting within the broad category of roof utility boards such as wood fiberboard, perlite board, and
gypsum wallboard is a relatively new product known generically as glass mat gypsum board
(GMGB). This product started out in 1987 as a weatherable gypsum based sheathing board.
Contractors and specifiers started incorporating this sheathing product into roofing applications as a
replacement for gypsum wallboard. As a result, in 1988 the manufacturers made a version of the
sheathing product produced and packaged specifically as a roof underlayment/overlayment board.
This product has become widely used in a broad array of roofing applications. Initially
manufactured in only 1/2″ and 5/8″ thickness, acceptance was accelerated with the introduction of a
lighter weight, more economical 1/4″ thickness. In 1997, it is estimated that over 50MM square feet
of GMGB have been sold specifically for roofing and projections are that usage will increase by 50%
in 1998. It is sold through existing roofing products distribution houses. The manufacturers
broadly recommend the product for use with built-up, modified asphalt, single-ply, metal systems,
wood shingle and shake, tile and slate, as a recover board, as an overlayment/underlayment board for
plastic foams, as a thermal barrier, and for fire protection.
Because of the distribution nature of the sale of this product and because the manufacturers are not
manufacturers of roofing systems, they indicate they do not know where the majority of the product
is specifically used. Further, the manufacturers state that the GMGB “is designed to act as a
component of a properly designed roof system. The actual use of this product as a roofing
component is the responsibility of the systems designing authority.” Repeatedly, the specifier is
advised to consult with the roof systems manufacturer for specific installation or use
recommendations.
This paper has been provided to fill a need in providing broad technical guidance for the specifier. It
is not the result of original research but is rather the result of literature review, manufacturer
interviews, and a survey of the technical departments of most of the major roofing system
manufacturers. As a result, recommendations are provided for the specifier for a variety of
applications.
It is important to be aware of the author’s basis for making these recommendations. First, one of the
basic considerations for the specifier is the technical soundness of the application. The second basis
for the following recommendations is that the roof system manufacturer endorse the application.
Commonly, a specifier requires that all roof system components be supplied by a single roofing
system manufacturer. This is done to assure single source responsibility. This is not possible in this
case because the manufacturer of GMGB is not a roof system manufacturer and very few reseller
agreements have been entered. However, it is possible that the roof system manufacturer specifically
include this product in their system’s warranty since the manufacturer of the GMGB will back
warrant their product for a period of ten years to the roof system manufacturer.
TECHNICAL DESCRIPTION OF GLASS MAT GYPSUM BOARD
Glass mat gypsum board is similar to gypsum wallboard in that the core of the product is gypsum.
However, the core is modified with an increase in density for strength and fire resistance. The core is
also modified with silicone for increased moisture resistance. Instead of paper facings as on
wallboard, this product has surfaces of non-woven glass mats for strength, moisture resistance,
and adhesion characteristics. There is an ASTM Standard Specification for glass mat gypsum board,
ASTM Designation C-l 177-95. It is available in 1/4″, 1/2″, and 5/8″ thickness with a standard width
of 4 feet and a length of 8 feet.
Teitsma- 1
First of all, this is not an insulation product. Thermal resistance is low, ranging from 0.28 to 0.67,
depending upon thickness. At 500 psi, compressive strength is high, higher than normally required
for roofing applications. Due mainly to the glass facers, flexural strength is excellent allowing flute
span of 2-5/8″ with 1/4″ thickness, 5″ with 1/2″ thickness, and 8″ with 5/8″ thickness. As with most
gypsum-based materials, fire properties are excellent. Tested by ASTM E84, the surface burning and
flame spread/smoke generation is zero.
Moisture resistance of GMGB requires greater scrutinizing. This product is specifically formulated to
resist moisture penetration. Table 1 shows moisture content at saturation of GMGB versus other
roofing boards, expressed as a percent by weight as typically shown by the manufacturer. Table 2
shows the same data, only as expressed as a percent by volume. This product has good moisture
resistance as compared to porous insulations such as wood fiber or perlite or as compared to gypsum
wallboard. However, it compares poorly to a product such as glass mesh-faced cement board (used as
tile backer, not roofing). GMGB is not waterproof, it is water resistant. Although it will not wick
water like gypsum wallboard or wood fiberboard, it will become saturated if left exposed to
continuous water. While wet, GMGB will lose strength, becoming vulnerable to mechanical damage.
If allowed to dry prior to being damaged, GMGB will reportedly regain much of its strength and will
retain its fire barrier characteristics. One BUR manufacturer reported on a roof in the South that had
water trapped in the system and the GMGB was virtually gone when the roof was replaced.
The manufacturers of GMGB recommend that their product be protected from moisture during
storage and that only as much product be installed as can be covered on a daily basis. This is good
advice even though it is moisture resistant and will shed incidental water. Do not install where water is
trapped in the system such as on a wet membrane in a recover situation.
In addition to purely technical considerations, economics are of obvious importance. Table 3
compares the approximate contractor costs for various utility boards purchased in the Georgia area.
It is obvious that the introduction of 1/4″ product and subsequent code approvals put GMGB in a
more competitive position.
RECOMMENDED APPLICATIONS
A. THERMAL BARRIERS
The original GMGB used in sheathing was developed to replace gypsum sheathing by improving
its strength and weatherability characteristics. It should be no surprise then that the initial use for
GMGB in roofing was as a direct replacement for gypsum wallboard in roof systems requiring a
thermal barrier or a heat sink. Bound water of hydration is driven out of gypsum products when
exposed to fire in a process called calcination, delaying the transfer of heat from one surface to
the opposing surface. Because GMGB is manufactured to a higher density than gypsum
wallboard, calcination takes slightly longer allowing the use of thinner product. Both 1/4″ thick
GMGB and 1/2″ gypsum wallboard have passed UL Test 1256 (Thermal Barrier). This is one
application for GMGB that was universally endorsed by the roof system manufacturers surveyed.
Within hourly rated systems, under the “P” prefix in the UL Fire Resistance Directory, GMGB
products have many listings as a substitution for gypsum wallboard. As a general statement, 5/8″
GMGB is a type X product and can replace any generic type X gypsum board in any of the “P”
constructions. In several cases, a thinner GMGB product is approved.
B. HOT APPLIED BUILT-UP ROOF AND MODIFIED BITUMEN SYSTEMS
There is a lot of confusion and hesitancy among roof system manufacturers when it comes to
using GMGB in conjunction with hot applied BUR and modified bitumen systems. One area
where there appears to be agreement, however, is the use of GMGB directly on the deck as a base
for vapor retarders in high humidity applications. The good high humidity performance of
GMGB combined with its low thermal resistance makes this a logical application. This is also true
Teitsma-2
for Protected Roof Membrane (PMR) Systems constructed with GMGB on steel benefit from
physical characteristics during construction and the low thermal resistance allows the roof
membrane to function as a vapor retarder as well as the moisture barrier.
The confusion expressed is in the area of direct mopping of hot roofing systems to the surface of
GMGB. Some of the major manufacturers are currently not allowing this application at all at this
time, citing concerns about blistering of the membrane. There have been reported problems in
this area although they are difficult to document. There are also examples cited with no
problems. The concern about blistering apparently stems from frothing of hot-applied pitch or
asphalt when it is mopped to the surface of GMGB. This frothing is the result of water vapor
being driven out of the GMGB by the hot bitumen. When similar frothing occurs while mopping
on concrete or other substrates such as perlite board, the presence of this moisture often leads to
subsequent blisters. In the case of GMGB, the moisture evidenced by frothing may or may not
lead to blistering since the porosity of GMGB may allow the water vapor to be driven down rather
than causing blisters. Regardless, roof system manufacturers are typically hesitant to endorse
direct application of hot bitumen to GMGB leaving the specifier vulnerable. At a minimum, the
specifier should obtain approval from the hot-applied system manufacturer and specific inclusion
in the warranty prior to specifying direct hot application on GMGB. I also anticipate further
studies in this area to clarify the question of blistering.
In those instances when direct application is used, the roof system manufacturers generally
recommend priming the GMGB surface prior to application. Although the manufacturers of
GMGB have run tests indicating that taping of GMGB joints over polystyrene foam insulation is
not necessary, roof system manufacturers who approve this application require taping of the
joints. Perhaps most disconcerting was the response of one bituminous roof system manufacturer
that they would consider direct application of hot systems depending on the specifier, the
applicator, and the competitive situation. Not a comforting response.
C. TORCH OR MODIFIED BITUMEN SYSTEMS
There is less concern about torching to the surface of GMGB than direct mopping. No examples
of blistering of torch-applied modified systems were cited. Where accepted, the manufacturers
expressed the logic that even though surface temperatures are high during the torching process,
there is not the same mass of hot materials as experienced in mop-in systems. The acceptance of
this application by the roof system manufacturers is not universal, however, with some
manufacturers taking a wait-and-see attitude. Two manufacturers stated they approve direct
application of torch-on systems but only if two or more plies were installed. They would not
torch-on single-ply systems.
Some manufacturers approve the use of GMGB as a recover board for torch-on systems.
However, where going over a stone-surfaced BUR system, they require a minimum thickness of
1/2″, citing concern for breakage of 1/4″ thick product. The GMGB manufacturers go one step
further stating that the existing membrane shall be free of debris and swept “smooth.”
D. SINGLE-PLY SYSTEMS
The acceptance and even desire to use GMGB is much greater in the single-ply arena. The
biggest driving force for the use of GMGB with single-ply systems is the ability to obtain Class A
fire ratings over combustible decks, either used as an overlayment or underlayment. The use of
GMGB on plywood decks in the West is very popular. EPDM manufacturers claim that they can
obtain a Class A rating over fully-adhered standard sheet using GMGB overlayment.
Sheet membrane manufacturers like the smooth rigid surface for a base for their membrane.
Direct adhesion for applicable adhered systems is approved; although, at least one manufacturer
claimed that additional adhesive is required due to porosity of GMGB. Welded and adhered
seams are reportedly easier over a rigid substrate such as GMGB. It is recognized that the
Teitsma-3
fastener plates are not recessed into the GMGB, but difficulties have not been experienced
because of the use of galvanized plates with provisions for recessed screw heads.
As a recover board for those applications where additional insulation is not desired, single-ply
manufacturers caution against entrapped moisture and also cite concerns about breakage of thin
product over rough surfaces. Because of previous roof system irregularities and the rigid nature
of GMGB, some manufacturers stated a preference for more conforming type substrates such as
isocyanurate insulation for recover applications.
With all fully adhered single-ply and bituminous systems, it is important to properly fasten
GMGB to the deck using approved fasteners or adhesives. GMGB is a rigid, strong board but
fastener density requirements depend upon GMGB thickness and required wind resistance. See
Table 4 for typical fastener density and layout.
E. MISCELLANEOUS ROOFING APPLICATIONS
In addition to the above main stream applications, there are some “niche” applications for
GMGB which appear to be ideal. For example, 1/4″ GMGB is gaining rapid acceptance on the
West Coast as an underlayment for wood shingles and shakes, allowing treated shingles to obtain a
Class A rating. The same is true with metal shingles and with more conventional metal roof
systems.
GMGB is also used advantageously with spray-in-place polyurethane roof systems. In new and
reroof applications, GMGB is installed on steel deck, creating an ideal flat surface for foam
application. For similar reasons, GMGB is also used for a recover board over an existing BUR
system.
Another niche application is the use of GMGB as a replacement for gypsum wallboard forms for
the pouring of gypsum concrete decks.
RECOMMENDATIONS AND CONCLUSIONS
A. There are many ideal applications for GMGB in roofing systems. Where GMGB is installed
under insulation, on a deck, GMGB is generally considered part of the deck and as such is not
included in the roof system warranty. However, for all fully attached membrane systems and in
application directly under the membrane, it is advised to specify that the GMGB product be
specifically included in the roof system manufacturer’s warranty. The purpose in getting the
manufacturer to take a warranty position is not to obviate the design or installation oversight
responsibility of the consultant but to make the approval of the roof membrane manufacturer
obvious and to eliminate discussion in the event of membrane product malfunction.
B. Because of expressed concern with blistering of hot-mopped systems, be cautious with this
application. At a minimum, insist on roof system manufacturer’s endorsement and warranty.
Also, specify that materials are properly protected from moisture in storage and are roofed in
place on a daily basis.
C. When using GMGB as a base for torch-on modified systems, prequalify your list of approved
manufacturers in your specifications to ensure that the manufacturer endorses this application.
As mentioned previously, insist on roof system manufacturer’s inclusion of GMGB in system
warranty.
D. Although highly moisture resistant, recognize long-term moisture susceptibility and prevent
entrapped moisture and water exposure during construction.
E. Specify GMGB as a replacement for gypsum wallboard in roofing systems where applicable. The
increased cost is justified for the benefits of increased durability and physical properties.
Teitsma-4
TABLE 1
GLASS MAT GYPSUM BOARD (GMGB)
WATER ABSORPTION (% BY WEIGHT, MAXIMUM)
GMGB 38%
1/2″ Perlite Retro 244%
3/4″ Perlite 136%
HD Wood Fiberboard 181%
TABLE 2
GLASS MAT GYPSUM BOARD (GMGB)
WATER ABSORPTION (% BY VOLUME, MAXIMUM)
GMGB 32%
1/2″ Perlite Retro 47%
3/4″ Perlite 26%
HD Wood Fiberboard 38%
TABLE 3
COMPARATIVE UTILITY BOARD PRICES
ROOFER LEVEL ■ ATLANTA, GA
1/2″ Oriented Strand Board (OSB) $25.25/sq
1/2″ High Density Wood Fiberboard 13.OO/sq
3/4″ Perlite Board 18.25/sq
1/2″ Gypsum Wallboard 20.25/sq
5/8″ Gypsum Wallboard 22.75/sq
1/4″ GMGB 34.5O/sq
5/8″ GMGB 37.OO/sq
Teitsma-5
TABLE 4
FULLY-ADHERED MEMBRANE SYSTEMS
FASTENER DENSITY REQUIREMENTS – GMGB
(FASTENERS PER 4′ X 8′ BOARD)!
1/4″ GMGB Used As Overlayment
1/4″ GMGB Used As Underlayment2
60 psf = 16/Bd 90 psf = 18/Bd
60 psf = 11/Bd 90 psf = 16/Bd
60 psf = 16/Bd 90 psf = 18/Bd
60 psf = 11/Bd 90 psf = 16/Bd
EPDM & Thermoplastic
BUR & Multi-ply Mod. Bit.
EPDM & Thermoplastic
BUR & Multi-ply Mod. Bit.
1/2″ & 5/8″ GMGB Used As Overlayment
EPDM & Thermoplastic 60 psf = 16/Bd 90psf=Not tested
BUR & Multi-ply Mod. Bit. 60 psf = 16/Bd 90 psf = 16/Bd
1/4″, 1/2″ & 5/8″ Used As Overlayment/Underlayment Under Mechanically-Attached
Sheet Membrane3
Sheet Membranes 60 psf = 4/Bd 90 psf = 4/Bd
1. Fastening requirements based on tests conducted by FMRC. For 60 psf ratings, multiply fasteners
per 4′ x 8′ board by 1.5 on roof comers and for 90 psf, multiply by 1.5 at roof perimeters.
2. 1/4″ underlayment not tested because 1/2″ or 5/8″ GMGB is required for FM Class I. When 1/4″
GMGB is used as underlayment in non-Class I assemblies, overlayment fastening pattern is advised.
3. Assumes membrane is mechanically fastened through insulation and GMGB to deck.
Teitsma-6