Skip to main content Skip to footer

Aerogel-Based, Fluid-Applied Coatings: Solution for Thermal Bridging of Steel and Concrete

November 5, 2016

Thermal bridging issues facing
designers of modern-day buildings
have long been a major
challenge. With architects
searching for more than flat
curtainwall designs, as well as
trying to satisfy net-zero building requirements,
the need for a true “thermal break”
has never been greater. This article offers
a unique solution to the thermal bridging
issue by using fluid-applied aerogel-based
coatings—both to control condensation
within a wall cavity and to mitigate energy
loss for steel and concrete construction.
Discovered inadvertently while attempting
to develop a new form of intumescent coating
in 2010, the first aerogel-filled coating (AFC)
was developed by a U.S. coating supplier. In
this same time period, the world’s leading
manufacturer of particulate aerogel began
testing similar coatings for “safe-to-touch”
applications for burn protection.
Aerogel is an amorphous silica particle
(see Figure 1) used in many applications,
from cosmetics to deep-sea pipeline insulation.
Known for its ultra-low thermal conductivity,
silica aerogel is 50% more thermally
efficient than still air (12 mW/m-K
for aerogel vs. 26 mW/m-K for still air).
This material property of the aerogel particles
can reduce overall heat transfer on
steel and concrete by 45-50% for coating
thicknesses 100-150 mils. It is this level of
performance that has resulted in a rapidly
growing interest in aerogel-filled coatings as
a thermal break solution.
The design community needed a solution
by which the heat transfer on steel
cantilevered beams, concrete balconies, roof
penetrations, canopies, spandrel glass, and
ornamental architectural features could
be sufficiently reduced in order to mitigate
moisture formation. The presence of
water through condensation in wall cavities
and façades can potentially lead to the
growth of mold and mildew and a myriad
of other issues. Through selective use of
aerogel-based coatings, the likelihood of
condensation and energy loss can be dramatically
reduced.
Steel P enetrations U sing AFC
Existing market solutions, such as the
thermal break pad technology shown in
Figure 2, have become the “go-to” solution to
address thermal bridging issues. However,
while these pads represent an improvement
over steel beams, their comparatively high
thermal conductivity (259 mW/m-K) and
their high cost of installation limit their
effectiveness and acceptance. Design, fabrication,
and erection of these “thermal pad
connections” currently cost $450 to $2,500
per connection, depending on the depth
of the steel section. From the fabrication
perspective, buried in the overall cost of
steel fabrication and erected bid work, an
additional $300 to $500 for “special picks”
is typically included by the erector. These
costs and use of “pad thermal breaks” do
little from an energy perspective and virtually
nothing to mitigate moisture/condensation
from
entering the
building envelope.
Hence, an
alternative was
desired.
The advent
of AFCs with
thermal conductivities
of 35
mW/m-K (six
to seven times
more efficient
than thermal
2 2 • I n t e r f a c e N o v e m b e r 2 0 1 6
Thermal I nsulation M aterial
Thermal I nsulation Bushing
Thermal I nsulation
Washer
Figure 2 – Mechanical thermal break.
Figure 1– Aerogel-filled coating (AFC).
(Cabot Corporation)
pads) give building designers dramatically
more design flexibility, and their resultant
performance can effectively reduce condensation
formation by altering the dew point
in the areas of concern. Figures 3A and 3B
show how the use of such a coating system
can have a dramatic impact on the likelihood
of condensation formation as compared to
thermal break pads.
Thermal 3-D modeling, conducted by
Morrison Hershfield, a Vancouver engineering
firm, confirmed that while coating steel
beams with an AFC does reduce overall heat
transfer and alter surface temperature, the
risk of condensation is dramatic as well.
AFCs also satisfy the designers’ need for
durability in architecturally exposed structural
steel (AESS) applications, especially
in exterior environments. Formulation of
high-performance AFCs has now achieved
a new status, passing NORSOK 501 Rev 6.
This Norwegian exposure standard, used
as an offshore oil and gas testing protocol,
demonstrated that the aerogel-based coating
system is capable of maintaining thermal
performance in immersion conditions and
severe environments, including offshore oil
platforms or exterior exposures. Designers
now have options for use on steel and concrete
elements and can address heat loss
and—to a greater degree—moisture mitigation
in wall cavities.
Not only have AFC fluid-applied thermal
breaks been shown to perform, they have
become the low-cost solution. Referring back
to Figure 2, there are a number of hidden
costs that come into play with thermal break
pad systems. These include the cost of fabricator
detailing during shop drawings, added
steel fabrication time and erector labor to
install the pads in the field (see washers and
bolts required in Figure 2), and additional
design review costs by structural engineers
and architects for seismic load and viability
of all connections. These are all costs
associated with achieving a thermal break
No v e m b e r 2 0 1 6 I n t e r f a c e • 2 3
Figure 3A – Condensation risk for bare steel vs. mechanical thermal break and Fabreeka
beams. (Data from Cabot Corporation.)
Note: Red zone indicates condensation risk; green zone is where no condensation will occur.
Figure 3B – Condensation risk for mechanical thermal break vs. AFC fluid-applied thermal
break. (Data from Cabot Corporation.)
Note: Red zone indicates condensation risk; green zone is where no condensation will occur.
Figure 4 – AFC fluidapplied
thermal
break, shop-applied.
Figure 5 – AFC
used in conjunction
with bolted AD
moment connections
(blocked out) and
touched up in field.
that can more effectively be addressed by a
spray-applied solution, resulting in shop or
field application (Figure 4) of aerogel-based
coatings that is less than 50% the
cost of pad technology (Figure 5).
So why does an AFC work on
steel and concrete? Heat
transfer occurs along a
heated perimeter of an
element, whether that
element is steel or concrete.
The definition of a thermal
break is “a thermal barrier of lower
thermal conductivity in an assembly
to reduce or prevent the flow
of thermal energy between conductive
materials.” AFCs with thermal
conductivities of 35 mW/m-K are
significantly better insulators than
carbon steel with a thermal conductivity
of 19,000 mW/m-K. The
use of these coatings allows for an
approach that can alter surface temperature
enough to move the dew
point outboard of the air barrier.
With AFC tightly bonded to a substrate
(steel or concrete) with no air
gaps to conduct heat transfer across
the “heated perimeter,” surface temperature
can be altered to move
dew point outboard of the building
assembly (Figures 6 and 7).
Concrete S lab E dges
and Balconies
Continuous concrete pours for concrete
balconies have been and continue to be
a method used throughout the U.S. and
Canadian markets. The use of aerogel-filled
coatings on concrete can solve both condensation
and energy loss problems. Morrison
Hershfield thermal models demonstrate that
the use of these coatings in thicknesses
ranging from 100 to 200 mils can result
in energy savings in southern and northern
climates of 19 to 24.5% (see Figure 8).
Since these concrete balconies essentially
represent heat transfer fins on the outside
of buildings, the coating only needs to be
applied over the first two feet outboard of
the interior studs.
Coating beyond this point is unnecessary,
as at that juncture, the “fins” can be
considered infinite, and their temperature
will very closely approximate that of the
exterior environment. Protruding steel
beams and concrete structures on buildings
have long been identified as thermal issues
in new building construction in desperate
2 4 • I n t e r f a c e N o v e m b e r 2 0 1 6
Figure 7 – Precast balconies placed directly on AFC-coated outriggers.
Figure 6 – Shop-applied AFC fluid-applied thermal break coating
applied to outriggers on 20-story mixed-use project.
Figure 8 – Concrete balconies coated
with 100 mils of AFC beneath pavers
(ICON Architects, Righter Group.)
need of a viable solution. The inadvertent
development of an aerogel-based coating system
provides designers and architects with
a workable solution to a nagging problem.
Beyond the thermal benefits, these coatings
have demonstrated compatibility with air
and vapor barriers, along with cementitious,
intumescent fireproofing and roof cutoff
coatings—all in a low-to-no VOC formulation
that meets LEED v4 requirements.
Condensation reduction (formation of
water on concrete floors), as well as “heat
loss” through a concrete balcony can be
solved with a simple and effective coating
process. By applying AFC 24 inches (Figure
9) onto all sides of the concrete, returning
the material to indoor ambient conditions
(to inside face of studs
or further) can result in
reduced condensation on
interior floor slabs, and
also reduce energy loss
(Figure 10). The increase
of AFC thickness above
100-250 mils can reduce
additional energy loss
up to 24.5%, according
to documentation
by Morrison Hershfield
(Figure 11).
The incremental
capital cost was
assumed to be $35/
ft2 of installed surface
area. The coating is applied to
a 2-ft.-wide strip along the base of
the balcony on both the top and
bottom surfaces. While the quantity
of the floor slab that has [a] balcony
strongly affects the effective
wall R-Value, the change in energy
cost savings with and without [aerogel-
filled] coating is proportional to
the additional installation cost of
the coating over a greater surface
area. As a result, the simple payback
period changes very little based on
balcony quantity, typically with less
than 0.2 years’ decrease in payback
period for 25% [of] balconies compared
to 100% [of] balconies.1
PRECON is a composite sheet
membrane comprised of a nonwoven
fabric and elastomeric
membrane bonded to an exclusive
plasmatic matrix. This product
provides a permanent seal
between the membrane and
poured concrete wall or floor.
It helps prevent moisture
migration into the structure
and improves resistance to
termites, methane and radon
gas. Make PRECON part of your
next foundation waterproofing
system.
© W. R. MEADOWS, INC. 2015
For a solution based on your needs, visit
wrmeadows.com or call 1-800-342-5976.
WR_Meadows_ Precon_RCI_Interface_hr
No v e m b e r 2 0 1 6 I n t e r f a c e • 2 5
Figure 9 – AFC spray-applied to concrete 24 in. outboard of
studs (ICON Architects, Righter Group.)
Figure 10 – AFC applied to concrete balconies of a residential tower in Boston, MA.
Overall Building I mpac t
Data analyzed by Morrison Hershfield
is shown in the remaining figures. Figure
12 shows a concrete balcony with raised
window wall on curbs with different coating
scenarios, while Figure 13 shows an
infrared thermal profile and temperature
locations for the balcony and window wall.
Figure 14 shows application of AFCs from 2
to 7 ft. showed no difference in energy loss,
based upon fin theory analysis. Additional
analysis (not shown) determined as much
as 2.9% overall energy impact for the building
with multiple balconies can be realized.
This 2.9% savings is a significant impact
for thermal modelers looking for additional
energy savings on passive house, green
building, and LEED designs. Aerogel-filled
coatings used as a “fluid-applied thermal
break” in lieu of other mechanical thermal
breaks is an alternative during value engineering
exercises, as cost savings of up to
60% per square foot have been documented
by Morrison Hershfield.
The final figure (15), also developed
through the analysis done by Morrison
Hershfield, depicts a payback chart using
AFCs with different building components in
various areas of North America.
As building designers look for incremental
efficiencies in energy loss, AFCs can help
solve multiple design issues. As a result,
AFCs will significantly alter field construction
costs for construction managers and
building owners.
FOOTNOTE
1. Morrison Hershfield, thermal modeling
data. Total Building Model
Energy Study.
SOUR CES
Aerogel data dew point charts
James Pidhurney and Peter Pescatore,
Cabot Corporation, Billerica,
MA.
Thermal modeling data
Morrison Hershfield, Vancouver, BC
Tnemec Company, Kansas City, MO
One Canal Place project
Architect: ICON Architects, Boston, MA
Steel fabrication: Canatal, Parcel, BC
Coating installation: Drytec, Terre
bonne, PQ and EMC, Boston, MA
Trip Advisor project
Architect: Elkus Manfredi Architects,
U-Value of S lab Slab PSI V alue
Aerogel-Filled Coating BTU /hr•˚F•ft2 BTU /hr•˚F•ft % R eduction in S lab
Scenario (W/m2K) (W/mK) U-Value
No coating 0.554 (3.14) 0.645 (1.116) –
Coating 100 mil 2 ft. 0.452 (2.57) 0.527 (0.912) 18.3%
Coating 100 mil full 0.452 (2.57) 0.527 (0.912) 18.3%
Coating 150 mil 2 ft. 0.438 (2.49) 0.510 (0.883) 20.9%
Coating 200 mil 2 ft. 0.427 (2.43) 0.498 (0.861) 22.9%
Coating 250 mil 2 ft. 0.418 (2.37) 0.487 (0.843) 24.5%
2 6 • I n t e r f a c e N o v e m b e r 2 0 1 6
2017
RCI DoCument CompetItIon
Earn rCI Dollars anD othEr InCEntIvEs
The winners of the 2017 RCI Document Competition will receive a
plaque and recognition during the annual awards luncheon at the 32nd
RCI International Convention and Trade Show, publicity of their winning
projects in Interface, and RCI Dollars. Prizes will be awarded to
nine winners in three categories.
largE ProjECt | small ProjECt | rEPort
First-place winners ……… 1,000 RCI Dollars
Second-place winners ….. 500 RCI Dollars
Third-place winners …….. 200 RCI Dollars
RCI Dollars will be redeemable for any product or service provided by
RCI or the RCI Foundation. RCI Dollars are redeemable by the award
winner or by anyone specifically designated by the award winner.
Use winnings for yourself or to help a friend or colleague buy a reference
book or attend a seminar.
rci-online.org/document-competition
DownloaD Your EntrY Form toDaY!
RCI, Inc. 800-828-1902
EntrY DEaDlInE: oCtobEr 31, 2016
Figure 11 – Energy savings on concrete balconies at different coating thicknesses. Energy
savings could be maximized up to 24.5% (Morrison Hershfield and Tnemec Company).
Boston, MA
Steel fabrication: Ocean Steel &
Construction Ltd., Saint John, NB
Elkus Manfredi project
Architect: Elkus Manfredi Architects,
Boston, MA
Mass DOT Material Lab project
Architect: Elkus Manfredi Architects,
Boston, MA
Iron works: Novel Iron Works, Inc.,
Greenland, NH
Since 1980, Greg
Pope has been a
key member of
Righter Group,
Inc., for which he
now serves as vice
president in his
Wilmington, MA,
office. In 2013,
Pope assisted in
the development
of the first fluidapplied
thermal
break coating utilizing aerogel-filled coating
technology. Pope has been a longtime member
of the Society for Protective Coatings
(SSPC) and NACE (the worldwide corrosion
authority), and is a NACE Level II coatings
inspector and consultant. He is the past technical
director of the Boston chapter of CSI.
Greg Pope
No v e m b e r 2 0 1 6 I n t e r f a c e • 2 7
Figure 12 (left) – Concrete balcony with raised window wall on curb
showing coating scenarios (Morrison Hershfield and Tnemec Company).
Figure 13 – Thermal profile and temperature locations for concrete
balcony with window wall (Morrison Hershfield and Tnemec Company).
Figure 14 (left) –
Concrete balcony with
window wall. Note:
Data on concrete
balconies with respect
to energy loss.
Application of AFC
from 2 – 7 ft. showed
no difference in energy
loss based upon
fin theory analysis
(Morrison Hershfield
and Tnemec Company).
Figure 15 – Payback chart for different building components in different regions of North
America based on kilowatt uses and types of energy sources (Morrison Hershfield and
Tnemec Company).
Slab PSI V alue
U-Value of S lab with Adjacent % R eduction
Scenario BTU /hr•˚F•ft2 Window W all in S lab
(W/m2k) BTU /hr•˚F•ft2 U-Value
(W/mK)
No coating 0.554 (3.14) 0.65 (1.12) –
Aerogel 2-ft. band 0.452 (2.57) 0.53 (0.91) 18.3%
Aerogel full 7 ft. 0.452 (2.57) 0.53 (0.91) 18.3%
Slab PSI V alue
U-Value of S lab with Adjacent % R eduction
Scenario BTU /hr•˚F•ft2 Window W all in S lab
(W/m2k) BTU /hr•˚F•ft2 U-Value
(W/mK)
No coating 0.859 (4.88) 0.57 (0.99) –
Aerogel 2-ft. band 0.691 (3.92) 0.46 (0.80) 19.5%
Aerogel full 7 ft. 0.819 (4.65) 0.46 (0.80) 19.6%