Skip to main content Skip to footer

Anchored Brick Veneer: What Can Go Wrong and How to Prevent This

December 2, 2025

Anchored Brick Veneer: What Can Go Wrong and How to Prevent This

ANCHORED BRICK SYSTEMS

Anchored brick veneer is a cladding system that
is designed with a structural backup wall where
the brick is then structurally tied (or anchored)
to the backup wall. The brick veneer acts as a
rainscreen, with an air cavity and water-resistant
barrier that allows any rainwater that penetrates
the brick veneer to migrate along the rear face of
the brick toward a drainage system (flashing and
weeps) that directs the rainwater to the outside.
This system recognizes that brick and mortar are
porous and manages the flow of rainwater, so
it does not migrate into the backup wall or the
interior of the building.
Composite brick walls are a structural system
that utilizes the full thickness of the brick for the
strength of the wall, and they are usually made
up of two or more wythes (vertical columns of
brick) that are fully mortared together. These
wythes may be reinforced or plain (unreinforced).
Composite brick walls are mass walls and were
historically used in the construction of buildings
until the mid-20th century (and are still used
today). Composite walls absorb moisture yet
are thick enough that the moisture is typically
stored in the outer wythes of brick and then dries
out between weather events. Flashing is still
required at floor lines, parapets, and openings
to direct absorbed moisture to the exterior as it
migrates toward these areas.
ATTRIBUTES, SUSTAINABILITY,
AND BENEFITS OF BRICK
Brick has many positive attributes, including
aesthetics (warmth, beauty, and scale),
long-term performance, and sustainability.
Brick has been in use for thousands of years. Its
origins can be traced back to 7000 BCE, when
brick use was discovered in southern Türkiye.
Early bricks were made from clay and sun-dried
to harden. Later, the ancient Egyptians mixed
the clay with straw. (A similar process was used
to make adobe, used by the Native Americans
for centuries.) In 3,500 BCE, fired brick
was invented.1
Examples of brick can be found throughout
the world; however, one does not have to look far
to see its beauty and contribution to our historic
and contemporary architecture. For example,
Baltimore, MD, has used brick for more than
two centuries (Photo 1).
Interface articles may cite trade, brand,
or product names to specify or describe
adequately materials, experimental
procedures, and/or equipment. In no
case does such identification imply
recommendation or endorsement by
the International Institute of Building
Enclosure Consultants (IIBEC).
By Daniel Isackson, AIA, RRC, LEED AP
This paper was presented at the 2024 IIBEC/
OBEC BES.
Anchored Brick Veneer:
What Can Go Wrong and
How to Prevent This
Feature
Photo 1. The American Brewery, built in Baltimore, Maryland, in 1863 (rebuilt in 1887).
14 • IIBEC Interface November 2025
Brick is sustainable. According to the Brick
Industry Association (BIA), brick is recyclable
and can be reused in construction or crushed
and used for sub-base materials or permanent
landscaping mulch. Brick contributes to energy
efficiency by absorbing heat and releasing it later
(thermal mass), has a long lifespan (100 years),
and is easy to maintain.2
To fully utilize sustainability in brick, care
must be taken to design the brick veneer for
compliance with the codes and with a basic
understanding of its material properties to
avoid failures and costly repairs. For a material
that, when properly designed and constructed,
can last 100 years (or more), the benefits of
sustainability are greatly compromised if
failures appear within the first 10 to 20 years, or
less, due to improper design and/or installation.
MATERIAL PROPERTIES
There are several material properties related
to brick, including its compressive, shear, and
flexural tensile strengths; elastic modulus; and
the expansion of brick. These properties are
primarily structural in nature and should be
specified for its intended use by the designer.
More detailed information regarding these
properties can be found in BIA, “Brick Masonry
Material Properties,” Technical Notes 3A,3
and The Masonry Society, “Building Code
Requirements for Masonry Structures,” TMS 402,
Chapter 4.2.4
Temperature, moisture absorption, freezing,
and creep cause material properties in brick
to constantly move in different directions and
at different rates. Brick continues to expand
over time, and results in a net growth of
brick compared to other materials like wood
or concrete that experience shrinkage as
the wood dries out or as the concrete cures.
Unlike concrete, brick is made from clay. Brick
or concrete will experience expansion and
contraction due to temperature changes;
however, brick will also gradually absorb
moisture over time, causing it to expand (not
shrink), reaching most of its maximum size
within the first several years after installation.
Brick will not return to its original size; the
expansion due to moisture retains a net growth
that is permanent. The expansion of brick due
to temperature change is nearly the same as
the expansion due to absorption of moisture.
Two other components affecting the growth of
brick are creep and freezing, though these have
a smaller overall impact on brick. The designer
should be familiar with the material properties
of brick veneer when used with a wood-framed
back-up wall, the brick veneer stresses at corners
and openings and the best practices for sizing
and placement of expansion joints to prevent
unsightly cracks or gaps at window openings.
Properties of Brick Veneer
Anchored with a Structural
Wood-Framed Backup Wall
Wood framing will shrink as it dries out, in
contrast to brick, which expands over time. Wood
shrinkage adjacent to expanding brick should
be accounted for at openings in the brick veneer
or else sealant can split and result in gaps at
windows, doors, and other sizable openings
(Photo 2 and 3). The anticipated shrinkage of
wood must be added to the calculated expansion
of the brick veneer. Given the current trends to
construct midrise buildings with wood framing
that are typically five or six stories in height, the
overall shrinkage of the wood is a function of its
overall length and the deadload of the structure.
Framing must be designed to minimize shrinkage
and horizontal expansion joints, supported by
steel shelf angles, are recommended at each floor
to accommodate the anticipated net movement
due to expansion of the brick and shrinkage of the
wood framing or damage can occur.
Properties of Brick at Corners,
Offsets, and Openings
How does brick veneer behave? The brick will
move in all directions and stress tends to build
up at building corners and openings (Fig. 1).5
Designing for Expansion Joints
The movement of brick requires that large areas
of brick veneer be divided up into smaller areas
by installing expansion joints to minimize the
stress on the brick veneer and prevent cracking.
Adequately sized brick areas for appropriate
stress relief are just part of the equation; how
the brick is supported is just as important
when it comes to minimizing stress due to
differential building movements, deflection
and/or movement of the supporting shelf angle.
Assuming a 100-degree Fahrenheit (38°C)
change in temperature as a rule of thumb, these
factors together result in a combined movement
Photo 2. Sealant separation at a window secured to wood framing due
to shrinkage of the wood framing and expansion of the brick veneer.
Photo from Rimkus Archives.
Photo 3. Sealant separation at a window secured to wood framing due
to shrinkage of the wood framing and expansion of the brick veneer.
Photo from Rimkus Archives.
November 2025 IIBEC Interface • 15
of 0.0009L (where L equals the length of the wall,
or the distance between expansion joints).6
So, what is the recommended expansion
joint strategy? The BIA has the following
recommendations for vertical expansion joints:5
• Brickwork without openings: 25 ft (7.6 m.) o.c.
• Multiple openings in brickwork:
20 ft (6.1 m.) o.c.
• Widen the joints for parapet walls when the
joints are more than 15 ft (4.6 m.) o.c.; or
separate with a horizontal joint and then place
another joint midway at the parapet wall.
• Place joints at or near corners (within 2 ft)
(0.6 m.), offsets, wall intersections, changes
in substrate (backing system), and changes in
brick support.
For horizontal joints:
• Locate immediately below shelf angles
with a minimum ¼ in. joint (0.6 cm.) and
compressible filler within the joint.
When detailing the expansion joint, a backer rod
and sealant must be provided to reduce moisture
intrusion through the brick veneer and to reduce
infestation by insects (you don’t want a beehive
behind your brick!). Some sealants can compress
as much as 50%, so the calculated joint width
should be doubled to accommodate the sealant.
It’s not just the vertical joints where the sealant
limitations must be factored into joint size. As
noted earlier, brick moves in each direction, and
an undersized joint can cause sealant to squeeze
out of horizontal joints (Photo 4). The horizontal
joint should be located below the steel shelf angle
with compressible filler.
Expansion Joints at Building
Corners and Offsets
Placing the vertical expansion joint within 2 ft
(0.6 m.) of the corner is preferred since it is
convenient for a typical mason, who can reach 2 ft
(0.6 m.) around the corner (Fig. 2).5
The location of the vertical expansion joint
from the corner (2 ft or 0.6 m.) is then added to
the distance to the next vertical expansion joint
on the adjacent wall so you do not exceed your
calculated distance between expansion joints.
Corner crack failures are usually located within
4 in. (10.1 cm.) of the outside corner (the nominal
thickness of a brick) and are usually caused by
insufficient or lack of vertical expansion joints to
accommodate movement (Photo 5 and 6).
Expansion Joints at
Punched Openings
For brickwork with regularly spaced punched
openings, the brick will move more above and
below the openings (long brick panels) than
between the openings (shorter brick panels).5
A natural location for the joint would be at the
opening corner; however, the supporting loose
laid lintel would require flashing to function as
a slip plane on the expansion joint side of the
lintel to move independently from the adjacent
brick (Fig. 3). This allows the lintel bearing end
Figure 1. Movement of brick veneer at
corners, offsets, and punched openings.
Image from BIA, TN 18A, pp. 4-5, May 2019.
Photo 4. Compressed sealant at a horizontal
movement joint. Photo from Rimkus Archives.
Photo 5. A corner crack in the anchored brick
veneer. Photo from Rimkus Archives.
Photo 6. A corner crack in the anchored brick
veneer. Photo from Rimkus Archives.
Figure 2. Expansion joints near corners and
offsets. Image from BIA, TN 18A, pp. 4-5,
May 2019.
Figure 3. Detail of an expansion joint at a
punched opening corner. Image from BIA, TN
18A, p. 6, May 2019.
16 • IIBEC Interface November 2025
that overlaps the vertical expansion joint to
move independently from the movement in the
adjacent brick.
Expansion Joints Differing
Adjacent Conditions
Expansion joints should also be provided at
different environmental exposures, such as a
fence or parapet wall, or when supported by
different conditions (Fig. 4).5
BRICK VENEER CODE
REQUIREMENTS
The building codes commonly used throughout
the United States are the International Building
Code (IBC) and the International Residential
Code (IRC), each published by the International
Code Council. Always verify with local
jurisdictions regarding amendments and the
currently effective edition of the code. For this
presentation, the 2024 editions of the IRC and
IBC were used. The IRC is limited to one- and
two-family dwelling units that do not exceed
three stories above grade plane.7 The IBC applies
to all buildings, and you have the option to use
the IRC if you have a residential building that
meets the applicable limitations noted above.
Both codes include brick veneer requirements
and reference TMS 402 for specific brick veneer
requirements. The 2022 edition of the TMS
was referenced in this presentation. This article
does not discuss the National Building Code
of Canada or local provincial/territorial codes.
The reader should consult with local codes for
applicable guidance.
2024 IRC
The 2024 IRC allows the design of anchored
brick veneer to comply with the prescriptive
requirements within the IRC (Section 703.8) or
applicable provisions of TMS 402 (2022),4 TMS
403 (2017),8 or TMS 404 (2022).9
The use of anchored brick veneer with a
backing of wood-framed or cold-formed steel is
limited to the “first story above grade plane and
shall not exceed 5 inches in thickness.” Exceptions
that allow the use of brick more than one story
above grade plane include the following:
• Buildings in Seismic Design Categories
A, B, and C that are supported above a
noncombustible foundation.
• Detached one- and two-family dwellings
in Seismic Design Categories D(0),
D(1), and D(2) as permitted above a
noncombustible foundation.
Generally, the exceptions allow the following:
• Up to 30 ft (9.1 m.) and three stories in
Seismic Design Categories A, B, and C if wood
framed (plus an additional 8 ft (2.44 m.) at the
gable end).
• Up to 30 ft (9.1 m.) and three stories (plus
an additional 8 ft (2.44 m.) at the gable
end) in Seismic Design Category D(0) if
wood-framed and each story does not
exceed 11 ft 7 in. (3.5 m.) or up to 13 ft
7 in. (4.1 m.) per story if meeting specific
exceptions). Cripple walls are not allowed.
(A cripple wall is a type of raised foundation
wall framed in wood that is susceptible to
earthquake damage.)
• Up to 20 ft (6 m.) in Seismic Design Categories
D(1) and D(2), or 30 ft (9.1 m.) (plus an
additional 8 ft [2.44 m.] at the gable end), if
wood-framed and the lower 10 ft (3.1 m.) has a
backing of a concrete or masonry wall. Cripple
walls are not allowed.
The fasteners for the ties must be secured
to the structural stud or into a wood structural
panel (Table R703.8.4[1]). Table R703.8.4[1] establishes the type of tie, fastener, and air space
allowed for fastening to structural studs (Fig. 5).
An air space of 1 in. (2.54 cm.) nominal is
allowed for corrugated or wire ties, up to 45 8
in. (11.7 cm.) for smaller-diameter adjustable
wire ties, and between 45 8 and 65 8 in. (11.7 and
16.8 cm.) for larger-diameter adjustable
wire ties.
Each veneer tie shall support not more than
2.67 ft2 (0.25 m2) of wall area and not exceed
32 in. (81 cm.) o.c. in the horizontal direction or
24 in. (61 cm.) o.c. in the vertical direction. In
Seismic Design Category D or C (for townhouses)
or in wind areas with design pressures exceeding
30 psf (0.48 kpa), then each tie shall not exceed
2 ft2 (0.18 m2) of wall area.
What About Drainage?
Section R703.1.1.1 states, “The exterior wall
envelope shall be designed and constructed
in a manner that prevents the accumulation of
Figure 4. Expansion joints at different
environmental exposure and support conditions.
Image from BIA, TN 18A, p. 6, May 2019.
Figure 5. 2024 IRC Table R703.8.4(1). Image cropped by Rimkus.
November 2025 IIBEC Interface • 17
water…and a means of draining to the exterior
water that penetrates the exterior cladding.”
Weep holes should be spaced at 33 in.
(84 cm.) o.c. and located immediately above
the flashing.
2024 IBC
The 2024 IBC differs from the 2024 IRC in that
anchored masonry veneer requires compliance
with Sections 1404.7 through 1404.10 as
well as Sections 13.1 and 13.2 of TMS 402.10
For anchored brick veneer, IBC defaults only
to chapters 13.1 and 13.2 of TMS 402, since
Sections 1404.8 through 1404.10 are specific
to anchored stone veneer, slab-type veneer, and
terra cotta veneer.10 IBC Section 1402.2 requires
exterior walls to include a drainage system that
provides a means to drain water that enters the
assembly to the exterior.
TMS 402
TMS 402 (2022)4 is used as a basis here, but
other editions may currently be in effect, so the
chapter numbers and requirements may differ
from what referenced below. The requirements
for brick veneer ties are primarily located in TMS
402 Chapter 13 (IBC requires compliance with
Sections 13.1 and 13.2).
Section 13.1 includes general requirements
for the system to comply with the weather,
structural, fire, and thermal requirements of
the legally adopted building code. It requires
the veneer to accommodate deformations and
differential movement, states that the deflection
of structural elements supporting masonry
shall not exceed L/600 and includes loading
limitations on the face of the anchored veneer
within a 5-by-5 ft (1.5-by-1.5 m.) area. Section
13.1 also requires compliance with TMS 402
Part 1 and Chapter 4, which address contract
document requirements, definitions, and
quality assurance.
Section 13.2 provides the requirements for
anchored masonry veneer. The code allows
for two paths: Prescribed Design Method or
Engineered Design Method. This article will
generally address the Prescribed Design Method,
as it relates to masonry with a running bond. A
running bond is how brick is usually constructed,
where the vertical joints in the row of bricks
above and below a brick line up with the middle
of the brick unit. The Prescribed Design Method
includes Basic and Enhanced options. The
Enhanced path generally requires the ties to be
spaced closer together to meet increased surface
pressures and/or seismic design categories.
Regarding the veneer ties, the specified
requirements for most uses include
the following:
• The thickness of the mortar bed joint
should be at least twice the thickness of the
veneer tie.
• Deflection limits for the backup wall for wind
and seismic loads
• Requirements for lintels above openings
• Isolation of the sides and top of the anchored
veneer in Seismic Design Categories C, D,
E, and F; support at each floor; and added
movement joints.
• For water penetration resistance, flashing and
weep holes to resist water migration below
the drainage plane (water-resistant barrier)
with a minimum of 1 in. (2.54 cm.) air cavity
and weep holes spaced no more than 33 in.
(84 cm.) o.c.
• General anchored veneer requirements
(TMS Table 13.2.2.3)4: Brick veneer can be
anchored to a supporting backup wall using
several types of acceptable brick veneer ties,
depending on the substrate, height, and
cavity width. The type of tie required depends
on the use of the building (single-family
home or not), and the type of structural
backup wall (wood-framed, steel-stud framed,
or concrete masonry unit). The appropriate
veneer ties, including spacing requirements,
and attachment are essential to the long-term
performance of brick veneer. There are
numerous types of acceptable veneer ties.
Following are some basic examples:
❑ Corrugated sheet metal ties (for use on
wood-framed residential buildings, 1 in.
(2.54 cm.) cavity width and no more than
30 ft (9.1 m.) high or 38 ft (11.6 m.) at a
gable end. The fasteners must be within
½ in. (1.2 cm.) of the right-angle bend
(Fig. 6).
❑ Sheet metal ties (for use on wood-framed
substrate, limited to 4 in. (10.1 cm.) cavity
width and a height limit of 30-ft (9.1 m.)
or 38 ft (11.6 m.) at the gable end. The
ties come in corrugated or noncorrugated
configurations (Fig. 7).
❑ Adjustable ties (for use on wood-framed/
cold-formed/concrete, or concrete
masonry unit substrates, limited to 4 in.
(10.1 cm.) cavity width and up to 6 in.
(15.2 cm.) cavity width with additional
requirements. May exceed 30 ft (9.1 m.)
or 38 ft (11.6 m.) at the gable end for
wood-framed and cold-formed metal
stud backing if designed for differential
movement, and must meet pullout
resistance requirements for concrete
backing (Fig. 8).
Figure 6. Corrugated sheet metal tie—
Hohmann and Bernard product sheet.
Image cropped by Rimkus.
Figure 7. Sheet metal tie—Heckmann Building Products sheet. Image cropped by Rimkus.
18 • IIBEC Interface November 2025
❑ Adjustable, unit wire, and joint
reinforcement ties (for use with clay [brick] or concrete unit masonry substrates),
limited to 6 in. (15.2 cm.) air cavity. Must
meet pullout resistance requirements
(Fig. 9 and 10).
• Out-of-plane corbelling (per Section 5.6).
Corbelling is the out-of-plane projection or
recession of a row of bricks).
❑ Solid units or units with holes grouted
solid must be used.
❑ The maximum projection from the face of
the wall must not exceed one-half of the
nominal brick wythe.
❑ Each corbelled brick projection must not
exceed one-half of the nominal unit height
and one-third of nominal brick wythe.
❑ Total corbelling is limited to no more than
a 1 in. (2.54 cm.) offset from rear face
of brick units. This will generally be the
limiting factor when modular size brick
units are used.
❑ Note: brick supported by steel shelf angles
would “corbel” beyond the lip of the angle.
This means a minimum of 2 3 of the brick
must be supported by the angle.
• Fastener pullout resistance shall have a
minimum design strength of 335 pounds
(152 kg.) or an allowable load of 200 pounds
(90.7 kg.).
• Cavity width (not drainage space) is from face
of framing (not the face of the sheathing).
• Veneer tie specifications (Table 13.2.2.4)
• Veneer tie spacing requirements for Basic and
Enhanced prescriptive design methods:
❑ Basic: 2.67 ft² (0.25 m2) per tie, no
more than 24 in. (61 cm.) spacing in
either direction.
❑ Enhanced: 1.78 ft² (0.16 m2) per tie, no
more than 16 in. (40.6 cm.) spacing in
either direction (this meets recommended
spacing from manufacturers).
CAVITY WALL DRAINAGE
In addition to the requirements of movement
joints, proper brick support, and the
requirements for veneer ties and veneer
tie spacing, the IRC, IBC, and TMS all have
requirements for cavity wall drainage. Cavity
wall drainage is essential to prevent the
buildup of rainwater that may bypass any
overlap joints in the water-resistant barrier or
other flashing systems, resulting in corrosion of
steel elements and fasteners and deterioration
of the sheathing and framing. The BIA provides
information on “proper design, detailing and
construction to minimize water penetration into
or through a wall system” (Fig. 11 and 12).11
This includes the following:
• Through-wall flashing locations
and installation and termination
recommendations
• Water-resistant barrier recommendations
• Air-barrier recommendations
• 1 in. (2.54 cm.) minimum drainage cavity
• Weep requirements (referenced earlier)
Through-wall flashing is an impervious
material of, and is essential for, the drainage
system. Through-wall flashing materials
may include sheet metal, flexible copper
fabric, polyvinyl chloride, and bituminous
(self-adhered) membranes. Through-wall
Figure 8. Adjustable brick tie—Hohmann and Bernard. Image cropped by Rimkus.
Figure 9. Nonadjustable unit wire tie—Heckmann Building Products cut sheet. Images cropped
by Rimkus.
Figure 10. Ladder-type joint reinforcement
tie—Hohmann and Bernard. Image cropped
by Rimkus.
Figure 11. Brick veneer with wood framing.
Image from BIA TN 7 page 3. Image cropped
by Rimkus.
November 2025 IIBEC Interface • 19
flashing is required at the base of walls,
windowsills, window lintels, shelf angles,
projections, chimneys, tops of walls, and roofs.
Flashing must extend vertically at least 8 in.
(20.3 cm.) above the horizontal leg. The BIA
recommends that a metal drip edge insert be
provided at the exterior (Fig. 13).
The BIA recommends end-dams in flashing
to prevent moisture from migrating behind
the flashing. Weep tubes or wicks should be
spaced no more than 16 in. (40.6 cm.) o.c., and
open-head joint weeps no more than 24 in.
(61 cm.) o.c. (closer than the 33 in. [84 cm.] maximum spacing allowed in the IRC and
TMS) (Fig. 14).
There are several critical flashing locations
that must be addressed. These include the
base of the wall (no more than 10 in. [25.4 cm.] above grade) and consider ground treatment,
such as mulch and the slope of the grade. If
the brick veneer extends below grade, then
fully grout the collar joint below the flashing
(Fig. 15).
Other critical areas include lintels, windowsills,
and shelf angles. As noted earlier, provide for
end dams at window flashing at windowsills and
lintels (Fig. 16 and 17).
COMMON ANCHORED
BRICK VENEER FAILURES
In addition to the corner cracks noted above,
other examples of cracking include:
Stairstep Pattern Cracks
Stairstep-pattern cracks are usually wider
on one end and can taper to a hairline
width on the other end. They are typically
caused by differential movement within
the field of brick, either by unequal
foundation settlement or by movement
on one end or the other of the steel angle
Figure 12. Brick veneer with cold-formed
steel framing. Image from BIA TN 7, p. 3.
Image cropped by Rimkus.
Figure 14. End dams and weep spacing. Image from BIA TN 7, p. 7. Image cropped by Rimkus.
Figure 13. Drip edge and through-wall flashing. Image from BIA TN 7, p. 6. Image cropped
by Rimkus. The through-wall flashing selected must be compatible with other materials
and components. The BIA recommends that the system of flashing, water-resistant
barrier, sealants, and any adhesives and primer be sourced from a single manufacturer to
confirm compatibility.
Figure 15. Base of wall flashing. Image from BIA TN 7, p. 9. Image cropped by Rimkus.
20 • IIBEC Interface November 2025
lintel due to insufficient torque of the
anchor bolts. By pointing downward in a
perpendicular direction from the crack, one
can approximate the location where the
differential movement occurred. IRC, IBC
and TMS 13.1 require that the building meet
structural requirements to limit differential
movement (Photo 7).
Vertical Cracks
Vertical cracks are failures typically caused by an
undersized steel angle (lintel). When the angle
deflects, a vertical crack occurs that is wider
at the bottom than at the top (The TMS limits
deflection to L/600) (Photo 8).
Horizontal Cracks
Horizontal cracks are typically caused by
insufficient or lack of horizontal movement
joints or movement of the shelf angle due to
insufficient torque of the anchor bolts. The
TMS contains commentary that references
BIA, Technical Notes 18A, for expansion joint
requirements (Photo 9 and 10).
Spalling
Spalling failure can be caused by several
factors, such as age-related deterioration of
the brick, or by allowing it to retain moisture,
become soft, or flake off fragments due
to the freeze/thaw cycle (aka spalling).
Nonpermeable paint can also trap moisture
within the brick. Spalling can also result from
inadequate allowance for movement joints or
from embedded items within the brick. For
historic brick buildings, the use of incompatible
portland cement mortar over the existing
lime-rich mortar can result in spalling. For more
information on spalling, see BIA, Technical
Notes (Photo 11 and 12).
Bowed Brick
Bowed brick veneer is typically caused by
failed brick veneer ties, which allow the brick to
move outward, resulting in separation gaps at
the windows and vertical and diagonal cracks
at the stress points. IRC, IBC and TMS specify
requirements for brick veneer ties (Photo 13
through 15).
Figure 17. Stand-off steel lintel detail.
Image from BIA TN 7, p. 11. Image cropped
by Rimkus.
Figure 16. Windowsill and lintel flashing. Image from BIA TN 7, p. 10. Image cropped by Rimkus.
Photo 8. A vertical crack. P Photo 7. A stair-step-pattern crack. Photo from Rimkus Archives. hoto from Rimkus Archives.
WIDER
NARROW
DIRECTION OF
MOVEMENT
November 2025 IIBEC Interface • 21
Photo 10. A view of the steel shelf angle below a horizontal crack.
Photo from Rimkus Archives.
Photo 12. Spalled and fractured brick due to compression. Photo from
Rimkus Archives.
Photo 9. A horizontal crack. Photo from Rimkus Archives.
Photo 11. Spalled brick. Photo from Rimkus Archives.
22 • IIBEC Interface November 2025
Efflorescence
Efflorescence develops when excess moisture in
the masonry causes the salts in the mortar and
brick to dissolve and to crystalize on the surface
as the moisture dries out. It appears as a white,
powdery surface deposit (Photo 16).
Photo 14. Joint separation at the window in a bowed brick veneer wall.
Photo Photo 13. Bowed brick veneer. Photo from Rimkus Archives. from Rimkus Archives.
Photo 15. A vertical crack in a bowed brick veneer wall. Photo from Rimkus Archives.
Photo 16. Efflorescence on the
brick-and-mortar joint surfaces. Photo from
Rimkus Archives.
November 2025 IIBEC Interface • 23
CORRELATION ISSUES WITH
CODES/STANDARDS
“Cavity width” as defined by TMS varies
when compared to “air space” as used in
IRC—inconsistent when using corrugated
sheet metal ties. Although TMS and IRC
require a minimum 1 in. (2.54 cm.) drainage
plane (air space in IRC), TMS limits the “cavity
width” when installed on a wood-framed
backup wall to 1 in. (2.54 cm.). The TMS
cavity width is from the stud face to the back
face of the brick, effectively making the joint
approximately ½ in. (1.3 cm.) when you
subtract the sheathing. The TMS commentary
says that both requirements can be satisfied
within the tolerances of each, yet tolerances
are not clearly specified other than that some
mortar droppings are allowed within the air
cavity. The TMS code allows an alternative
to measure the cavity width from the face of
the sheathing if the sheathing has a bearing
stress of 100 psi (689 kpa) or the ties used
to penetrate the sheathing to the light frame
backing have a compressive strength of
200 psi (1379 kpa). Best practice is to provide
at least a 1 in. (2.54 cm.) drainage plane to
meet the TMS strength requirements for
the sheathing. Another option is to use an
adjustable tie where up to a 6 in. (15.2 cm.)
cavity width per TMS is allowed (the IRC
allows up to 65 8 in. (16.8 cm.).
There are variables for veneer tie spacing, as
noted in IRC and TMS. IRC allows the veneer
ties to be spaced no more than 32 in. o.c.
(81 cm.) horizontal and no more than 24 in.
o.c. (61 cm.) vertical, whereas TMS limits the
spacing to no more than 24 in. o.c. (61 cm.) in
either direction. The maximum brick area per
tie in both codes is limited to 2.67 ft2 (0.25 m2).
For seismic zones, TMS limits the area per tie
to 1.78 ft2 (0.16 m2), and IRC limits it to 2 ft2
(0.18 m2). Most exterior wall studs are at 16 in.
(40.6 cm.) o.c. Given the modular size of brick
(3 units per 8 inches or 2.67 in. (6.8 cm.) each,
you can greatly simplify and satisfy all TMS and
IRC requirements by spacing at 16 in. (40.6 cm.)
o.c. each way. Also, a common recommendation
from veneer tie manufacturers is to space the
ties at 16 in. (40.6 cm.) o.c. each way (one tie for
every 1.77 ft2 [0.16 m2] of brick veneer).
IRC and TMS also specify that weep holes
can be spaced no more than 33 in. (84 cm.)
o.c. BIA recommends that when wick weeps
are used, spacing shall not exceed 16 in.
(40.6 cm.) o.c.; when open-head-joint
weeps are used, then spacing shall not
exceed 24 in. (61 cm.) o.c. Use of weep
tubes is not recommended by the BIA.11 It is
recommended that the designer comply with
BIA recommendations, which are stricter than
the IRC or TMS.
CONCLUSION
Designing for anchored brick veneer can
be very complex due to the numerous code
requirements. The proper selection of the brick
veneer system, placement of flashing, and
expansion joints are critical to the long-term
performance of anchored brick veneer. The
codes and industry standards noted in this
paper vary in requirements, and the best
practice would be to follow the strictest of
requirements, identifying potential stress
points in the brick veneer during design and
design and placement of expansion joints
to minimize the stress and accommodate
expansion. Provide clear details at all flashing
locations and brick veneer expansion joints,
locate all expansion joints on the exterior
elevation drawings, and provide clear and
concise specifications. Equally important is the
need for active quality assurance observations
during construction at regular intervals.
REFERENCES
1. Brick Architecture (2017), “The History of Bricks
and Brickmaking,” https://brickarchitecture.com/
about-brick/why-brick/the-historyof-bricks-brickmaking.
2. Brick Industry Association, “Sustainability,”
https://www.gobrick.com/learn-about-brick/
sustainability.
3. Brick Industry Association, “Brick Masonry Material
Properties,” Technical Notes 3A, June 2024.
4. The Masonry Society, Building Code Requirements
for Masonry Structures, TMS 402 (Longmont, CO:
TMS, 2022).
5. Brick Industry Association, “Accommodating
Expansion of Brickwork,” Technical Notes on Brick
Construction 18A (May 2019), https://www.gobrick.
com/resources/technical-notes.
6. Brick Industry Association, “Volume Changes—
Analysis and Effects of Movement,” Technical Notes
on Brick Construction 18A (May 2019), https://www.
gobrick.com/resources/technical-notes.
7. International Code Council, International Residential
Code (Country Club Hills, IL: ICC, 2024).
8. The Masonry Society, Direct Design Handbook for Masonry
Structures, TMS 403 (Longmont, CO: TMS, 2017).
9. The Masonry Society, Standard for Design of Architectural
Cast Stone, TMS 404 (Longmont, CO: TMS, 2022).
10. International Code Council, International Building
Code (Country Club Hills, IL: ICC, 2024).
11. Brick Industry Association, “Water Penetration
Resistance—Design and Detailing,” Technical
Notes on Brick Construction 7 (November 2017),
https://www.gobrick.com/resources/technical-notes.
ABOUT THE AUTHOR
Daniel Isackson is
a technical director
of architectural
engineering at Rimkus
with more than
35 years of experience
in architectural design
and construction
administration on
commercial and
military buildings in
the eastern United
States. At Rimkus, he has experience with
building enclosure investigation, property
condition assessments, litigation, remediation
design, and construction administration on
commercial, military, and residential buildings.
His investigative and design work includes wall
cladding and roofing assemblies.
Please address reader comments to
chamaker@iibec.org, including
“Letter to Editor” in the subject line, or
IIBEC, IIBEC Interface Journal,
434 Fayetteville St., Suite 2400,
Raleigh, NC 27601
DANIEL ISACKSON,
AIA, RRC, LEED AP
24 • IIBEC Interface November 2025