Skip to main content Skip to footer

Expanding Possibilities: Engineered Design of Masonry Veneer

April 9, 2026

By Robert M. Chamra, PE
This paper was presented at the 2025 IIBEC
International Convention and Trade Show.

 

MASONRY VENEER IS a well-known and
commonly used cladding system found in
the built environment due to its aesthetic
possibilities and durability. Historically,
this “nonstructural” element has fallen
under the architect’s purview in the design
process, but with increasing complexity
in building performance and geometry,
building enclosure consultants are frequently
joining the design team for, or providing
third-party design review of, masonry veneer
construction.
When project demands require masonry
to exceed the prescriptive design limitations,
engineered design of masonry veneer is
required. The 2022 edition of The Masonry
Society’s TMS 402/6021 includes engineered
design methods, which allow for new design and
construction possibilities for masonry veneer
beyond prescriptive limitations.
A BRIEF USE AND CODE
HISTORY OF MASONRY VENEER
ASTM International defines masonry as “the type
of construction made of manufactured masonry
units laid with mortar, grout, or other methods
of joining,”2 although colloquially, natural
stone or “dimension stone” unit assemblies
are regularly referred to as masonry veneer
as well. Natural stone masonry structures,
such as ancient Egyptian pyramids, have
existed for millennia, so users of masonry as
a building material have expectations that it
will be durable. Subsequently, mass masonry
structures used multiple layers, or wythes, of
smaller masonry units to maintain the durability
and aesthetics of the ancient structures with
improved constructability. Nonetheless, mass
masonry walls remained a labor-intensive
construction method.
In modern construction, masonry veneer was
the next evolution to decrease installation costs.
The Masonry Society (TMS) defines masonry
veneer as “a masonry wythe that provides the
exterior finish of a wall system and transfers
out-of-plane load directly to a backing but is not

considered to add strength or stiffness to the
wall system.”1
Masonry veneer can be broken into two
attachment categories: anchored veneer and
adhered veneer. An anchored veneer assembly
transfers out-of-plane load to the backing
predominantly through veneer ties (Item 32 in
Fig. 1).3 An adhered masonry veneer assembly
transfers out-of-plane load to the backing
through either direct bond or mechanical
fasteners and lath into the backing (Item 40 in
Fig. 2).4 Unlike mass masonry walls, masonry
veneer typically contains a drainage cavity and
associated accessory products to expel incidental
water that penetrates the porous masonry units
and mortar. The detailing to prevent bulk water
infiltration and provide lateral attachment of
the masonry veneer is critical to maintain the
durability and safety of masonry cladding.
The code history for masonry veneer is
relatively short, as summarized in Table 1.
The masonry veneer standard referenced in
the 2024 International Building Code5 is TMS
402/602-22.1 As the numbering suggests,
the document is split into two sections: the
design code (TMS 402) and the construction
specification (TMS 602). TMS 602 includes the
minimum construction requirements that can
be incorporated into design specifications and
drawing notes by reference. TMS 402 includes
the remaining design requirements that must
be defined in either the design specifications
or drawings to convey the intended masonry
veneer design for a given project. To avoid
misinterpretation of the design intent, TMS 402
cannot be incorporated into design documents
by reference.

PRESCRIPTIVE DESIGN OF
MASONRY VENEER
Before diving into engineered design, it is
important to note that prescriptively designed
masonry veneer is allowed and used in many
situations. This overview of the prescriptive
design requirements is intended to differentiate
the circumstances where each design method
is appropriate. A good starting point for the
discussion is the masonry unit materials used
within the veneer. Figure 3 can be found
in the commentary to TMS 402/602-22.1
While compliance with code commentary is
not required for design or construction, this
particular table summarizes the specific unit
requirements in the subsequent prescriptive and
engineered veneer sections. Dimension stone is
defined as “natural stone that has been selected
and fabricated to specific sizes and shapes.”1
The properties of natural stone inherently
vary depending on the type of material and
location of the quarry. Because naturally
occurring materials cannot be standardized
like manufactured masonry units, anchored
dimension stone veneer design requires material
testing to determine the compressive strength,
durability, and mortar bond strength. The results
of the testing determine whether the design
assumptions were correct, or revisions are
needed to meet the design intent. Therefore, the
design of all anchored dimension stone masonry
veneer must be engineered.
Seismic design category and wind pressure
control the permitted design method (Fig. 4).
Strength-level design wind pressures for
masonry veneer (pveneer) are determined using
the ASCE/SEI 7 Chapter 30 components and
cladding provisions, including, but not limited
to, surrounding topographical conditions,
required design wind speeds, and total height.6
Sites located at the top of a hill or in a dense,
urban area will naturally experience higher wind
pressures. Proximity to coasts or mountains
will increase the required wind speeds and the
correlating wind pressures. Wind pressures also
increase with height above grade, so midrise and
high-rise buildings may require an adjustment of
the masonry veneer design along the height or
near building corners.
Seismic activity provides another source
of lateral loading on masonry veneer. Due to
the mass of the anchored masonry veneer,
high-seismic areas (Seismic Design Category
D and higher) require more restrictive design
provisions regardless of wind pressures. As a
result, the anchored veneer prescriptive design
method in TMS 402 was split into basic and
enhanced provisions for veneer tie spacing
(Table 2). Simply stated, as lateral loads from

wind or seismic increase, the maximum veneer
tie spacing decreases to maintain the same
assumed load per veneer tie.
Correspondingly, prescriptive adhered
masonry veneer provisions are limited to a
maximum wind pressure pveneer of 60 lb/ft²
(2.87 kPa). For Seismic Design Category D and
higher, the required mechanical fastener spacings
for securing lath over wood and coldformed metal
framing are reduced to 80% for adhered masonry

veneer.1 Lastly, the maximum height allowed for
prescriptively designed adhered masonry veneer
is limited to 60 ft (18.3 m) above grade.
The prescriptive design method is based upon
the masonry unit limitations shown in Table 3.
Any masonry units not meeting the criteria in
Table 3 must use the engineered design method.
For anchored masonry veneer, the mortar
joint width is also required to be at least twice
the thickness of embedded tie materials. For
example, a mortar joint containing a 3/16 in.
(4.76 mm) diameter wire tie must be at least
3/8 in. (9.53 mm) wide. Anchored veneer mortar
type must also be specified; Type N is commonly
used in anchored veneer for balance in strength
and stiffness. TMS 402/602-22 prescriptively
requires the setting bed mortar for adhered
veneer units to be a polymer-modified mortar for
superior bond.1 Mortar materials greatly impact
the overall performance of the masonry veneer,
so it is critical that the design intent is conveyed
within the design documents.
Figure 5 illustrates the different veneer tie
types referenced in TMS 402/602. The 2022
edition reorganized the previous prescriptive
anchored veneer requirements into tables
limited to the type of backing (Fig. 6) and the
selected veneer tie type (Fig. 7).
While it is not the intent of this paper to review
each of the prescriptive design requirements
for anchored veneer, Fig. 6 and 7 are included
because they are referred to within the
engineered design requirements of anchored
masonry veneer that are discussed later.
Dependent upon the backing type, different
veneer tie types are allowed in the prescriptive
design requirements. For each veneer tie type,
the prescriptive design requirements include but
are not limited to the following:
• Maximum specified cavity width
• Fastener type

• Fastener diameter
• Fastener length
• Veneer tie dimensions
TMS 402/602-22 includes general
requirements for both anchored and adhered
veneer regarding water-penetration resistance
and accommodation for differential movement.
Due to an ever-changing array of building
enclosure materials, specific flashing and
drainage components are not explicitly
mentioned by TMS 402/602-22. Differential
movement encompasses thermal, moisture,
and structural movements, which must be
accommodated to avoid the masonry veneer
providing unintended restraint, and associated
potential future distress conditions, of the
completed building system.
ENGINEERED DESIGN
OF MASONRY VENEER
The following conditions, though not intended
to be exhaustive of all design scenarios, exceed
the prescriptive design methods discussed
previously and must be engineered:
• Anchored dimension stone veneer (Fig. 3)
• Anchored veneer with components and
cladding wind pressures exceeding 75 lb/ft2
(366 kg/m2) (Fig. 4)
• Anchored veneer with veneer tie spacing
tributary area or spacing exceeding the
basic prescriptive and enhanced prescriptive
maximum requirements (Table 2)
• Anchored veneer masonry units less than
2.625 in. (66.7 mm) or greater than 5 in.
(127 mm) in depth, or greater than 16 in.
(406 mm) in height (Table 3)
• Anchored veneer masonry units with weights
exceeding 50 lb/ft2 (244 kg/m2) (Table 3)
• Anchored veneer or veneer ties not
compliant with prescriptive limitations
(Fig. 6 and 7)
• Adhered veneer with components and
cladding wind pressures exceeding 60 lb/ft2
(2.87 kPa)
• Adhered veneer exceeding a height of 60 ft
(18.3 m) above grade
• Adhered veneer masonry units greater than
2.625 in. (66.7 mm) in depth (Table 3)
• Adhered veneer masonry units with weights
exceeding 30 lb/ft2 (146 kg/m2) (Table 3)
Prior to TMS 402/602-22, any masonry
veneer not complying with the prescriptive
limitations was required to be designed using
the alternative design method, which resembles
the current engineered design of adhered veneer
conditions1 and the modeling analysis method
for anchored veneer. This design method for
masonry veneer includes the following:
• Units shall comply with the prescriptive
requirements or be tested to determine
material properties.
• Loads shall be distributed through the
veneer to the backing using the principles of
mechanics.
• Masonry veneer assembly shall comply with
TMS 602 or be tested to determine design
properties.
This means engineering analysis can be
used to determine the nonprescriptive load
path for the given masonry veneer assembly.
When the installation of adhered masonry units
differs from the prescriptive requirements, the
assembly and installation method must be
tested to determine the properties to be used
with the engineering analysis.
For anchored masonry veneer, two engineered
design methods are outlined: the tributary area
method and the modeling analysis method.1
Regardless of the selected engineered method,
the veneer tie properties included in Fig. 8 or
the veneer tie manufacturer’s product literature
may be used. A veneer tie testing standard

is being developed by ASTM International at
the time of this writing. With the publication
of this new standard, the masonry industry is
facilitating more regular publication of veneer
tie capacities and tie assembly stiffnesses for
use in engineered design. The tributary area
method determines the strength-level force
in each veneer tie through the strength-level
out-of-plane load on the masonry veneer (pu),
the tributary area of the veneer tie (At), and
the stiffness of the veneer tie (ktie) using the
following equations:1
• 2puAt when ktie ≤ 2,500 lb/in. (438 N/mm)
(Equation 1)
• 2.5puAt when 2,500 lb/in. (438 N/mm) < ktie ≤
5,000 lb/in. (876 N/mm) (Equation 2)
• 3puAt when 5,000 lb/in. (876 N/mm) < ktie ≤
8,000 lb/in. (1,400 N/mm) (Equation 3)
• 4puAt when ktie > 8,000 lb/in. (1,400 N/mm)
(Equation 4)
Design strengths in Fig. 8 implicitly include
strength reduction factors and can be directly
compared with the strength-level forces.1

To convert to allowable stress level forces,
pu is replaced with pallow, the allowable wind
pressure on the masonry veneer. The tributary
area method is limited to anchored veneer
with masonry units equal to or less than 5 in.
(127 mm) in depth. Veneer ties with lower
stiffness allow for a more uniform distribution
of lateral forces between the ties. As the
stiffness increases, more force is attracted by
the veneer tie.
For this sample calculation, consider the
following scenario:
• Cold-formed metal framing backing
• Masonry unit depth between 2.625 and 5 in.
(66.7 to 127 mm)
• Adjustable two-leg pintle veneer tie type (see
“plate or prong” type depicted in Fig. 5)
• Typical tie spacing of 18 in. (457 mm) by 16 in.
(406 mm) or At = 2.00 ft2 (0.186 m2)
• pu of 60 lb/ft2 (2.87 kPa)
Engineered design is required due to the
maximum tributary area exceeding 1.78 ft2
(0.165 m2), which is the enhanced prescriptive
limit. Due to the stiffness of the veneer tie type, use
Equation 1 and the veneer tie properties in Fig. 7.
2puAt = 2 × 60 lb/ft2 (2.87 kPa) × 2.00 ft2
(0.186 m2) = 240 lb (1,068 N) > 210 lb (934 N),
therefore, the solution is not acceptable.
Let’s retry using the adjustable slotted veneer tie
type. Due to the stiffness of the veneer tie type,
use Equation 2.
2.5puAt = 2.5 × 60 lb/ft2 (2.87 kPa) × 2.00 ft2
(0.186 m2) = 300 lb (1,334 N) < 330 lb
(1,468 N), therefore, the solution is acceptable.
When adjusting the veneer tie type does
not reach acceptable results, the tributary
area can be reduced by reducing the tie
spacing. Alternatively, if large out-of-plane load
resistance requires the masonry veneer to be
engineered, a wind-tunnel analysis could be
performed to potentially reduce the calculated
wind-pressure requirements for the components
and cladding.
POSSIBILITIES OF ENGINEERED
MASONRY VENEER
Anchored dimension stone veneer is a common
exterior cladding system where limestone,
sandstone, and other natural stone types
are readily available. Dimension stone offers
an aesthetic that can define the regional
architecture where the stone exists. While some
natural stone types exceed the properties of
manufactured units, many types have poor

durability characteristics, such as freeze-thaw
resistance, or poor bond to modern masonry
mortars. Engineering anchored dimension stone
veneer, typically through material testing, will
confirm whether the available stone products
can be attached with veneer ties laid in mortar or
whether mechanical anchors, such as kerfstyle
anchors, are required to transfer the loads into
the backing.
While high-wind environments are
prescriptively excluded above 75 lb/ft2
(3.59 kPa) for anchored veneer and above
60 lb/ft2 (2.87 kPa) for adhered veneer,
hurricane- or tornado-prone regions can benefit
greatly from the use of engineered masonry
veneer. Manufactured masonry veneer units
can offer wind-blown debris or “missile” impact
resistance in highwind events. If exterior
cladding is installed correctly, the durability
of a masonry veneer finish also can protect
against one of the leading causes of damage
in a hurricane: water infiltration. A building
enclosure system protected by masonry veneer
will minimize wind-driven rain-related and
enclosure impact damage in the veneer area.
Engineered masonry veneer removes the
dimensional constraints of the prescriptive
design method, which provides the designer
with more aesthetic possibilities. Large cavity
widths can occur with continuous insulation
requirements. Any adjustments in unit depth
or corbelling pattern further exacerbate veneer
cavity depth issues. The prescriptive limitations
on cavity width remove compressive buckling as
a failure mechanism for the veneer ties. When
exceeded, the veneer tie capacity will decrease
with increased cavity depth to account for
buckling. Working with veneer tie manufacturers
to determine ways to counter buckling for
the desired cavity depth allows the use of
nonprescriptive wall sections.
For adhered veneer, units exceeding
30 lb/ft2 (146 kg/m2) or 720 in.2 (0.464 m2) may
affect constructability. Adhered veneer unit
installation methods are critical to the long-term
performance of the adhered masonry veneer
assembly. Large units are difficult to install with
the uniform pressure to fill the space behind the
adhered masonry unit and develop the intended
bond strength. As a result, poor installation
method is a leading cause of adhered masonry
veneer failures. Constructability must be a
consideration when developing engineered
adhered masonry veneer solutions.
Engineered masonry veneer requirements do
not necessarily have to exceed prescriptive design
method requirements. A powerful application
of engineered masonry veneer is optimization
of veneers that could be prescriptively designed.
Let’s revisit the tributary area method calculation
with new conditions to explore optimization. For
this sample calculation, consider the following
scenario:
• Concrete masonry backing
• Masonry unit depth between 2.625 and 5 in.
(66.7 to 127 mm)
• Adjustable two-leg pintle veneer tie type (see
wire component of “joint reinforcement” type
in Fig. 5)
• Typical tie spacing of 16 in. (406 mm) by
16 in. (406 mm) or At = 1.78 ft2 (0.165 m2)
• pu of 35 lb/ft2 (1.68 kPa)
• Located in Seismic Design Category C
Prescriptive design is allowed due to the
maximum tributary area not exceeding 2.67 ft2
(0.248 m2), pu < 50 lb/ft2 (2.39 kPa), and
location in a low-seismic region. Engineered
design is used to optimize the required veneer
tie spacing. Due to the stiffness of the veneer
tie type, use Equation 1 and the veneer tie
properties in Fig. 7.
2puAt = 2 × 35 lb/ft2 (1.68 kPa) × 1.78 ft2
(0.165 m2) = 125 lb (556 N) < 210 lb (934 N),
therefore, the solution is acceptable, but there’s
room for optimization.
Let’s retry using a typical tie spacing of 24 in.
(610 mm) by 16 in. (406 mm) (At = 2.67 ft2).
Due to the stiffness of the veneer tie type, use
Equation 1.
2puAt = 2 × 35 lb/ft2 (1.68 kPa × 2.67 ft2
[0.248 m2] = 187 lb [832 N] < 210 lb [934 N]),
therefore, the solution is acceptable.
The optimized veneer tie spacing removed
33% of the two leg pintles and layers of joint
reinforcement required for the masonry veneer.
The cost of the reduced material and labor could
be applied elsewhere on the project or used to
lower project cost.
CONCLUSION
Prescriptive design requirements and
limitations for masonry veneer are acceptable
in many situations. The new engineered design
requirements for masonry veneer in TMS
402/602-22 can be used in situations exceeding
the prescriptive limitations or to optimize masonry
veneer that could be prescriptively designed.
Through use of the engineered design provisions,
masonry veneer can be used in new applications
in a safe and durable manner. The possibilities of
engineering masonry veneer are endless.
REFERENCES
1. TMS (The Masonry Society), Building Code Requirements
and Specification for Masonry Structures, TMS 402/602-22
(Longmont, CO: TMS, 2022).
2. ASTM Subcommittee C15.08, Standard Terminology for
Masonry, ASTM C1232-24 (West Conshohocken, PA:
ASTM International, 2024).
3. IMI (International Masonry Institute), Base of Wall |
Anchored Brick Veneer, CMU Backing, CMU Foundation,
May 2, 2019, https://imiweb.org/wp-content/
uploads/01.030.0332-2.pdf.
4. IMI (International Masonry Institute), Base of Wall |
Adhered Brick Veneer, CMU Backing, Lath & Scratch
Coat, March 26, 2020, https://imiweb.org/wp-content/
uploads/01.070.0301.pdf.
5. ICC (International Code Council), International Building
Code (Country Club Hills, IL: ICC, 2024).
6. ASCE (American Society of Civil Engineers), Minimum
Design Loads and Associated Criteria for Buildings and
Other Structures, ASCE/SEI 7 (Reston, VA: ASCE, 2017).
ABOUT THE AUTHOR
Robert “Bobby” Chamra
is a professional
engineer with 12 years
of experience focused
on structural restoration
and building enclosure
consulting in existing
buildings. Chamra is
currently serving as a
voting member for The
Masonry Society’s TMS
402/602 Building Code
Requirements and Specification for Masonry
Structures for the 2028 Code Cycle and is the
secretary for the Veneer Subcommittee. He has
also served as a member of ASTM International
Committee C15 Manufactured Masonry Units,
Mortars, and Grouts. When not working on the
existing built environment, he enjoys spending
time with his family, playing golf, gardening,
cooking, and eating.