Skip to main content Skip to footer

Fall Exclusive: A Deep Dive into Hail-Caused Dents: A Study of Corrosion Resistance within Dents in Galvalume-Coated Steel Roof Panels

August 12, 2025

FOR METAL ROOFS in hail-prone regions, such
as the area stretching generally from Wyoming,
through the Front Range, to Texas—commonly
referred to as “Hail Alley”—the occurrence of
hail-caused dents is more a question of “when”
than “if.” Consequently, in recent years the
insurance industry has been writing exclusions
or endorsements that limit coverage to the
effects of hail deemed “functional,” as opposed
to “cosmetic” or “aesthetic.” While various
definitions abound, and it is not the intent of
this paper to haggle over legalese, functional
damage is generally considered to be damage
(typically, dents or deformations) that results
in diminished water-shedding ability of the
roof assembly (in other words, that causes
leaks) and/or damage that will reduce the roof
assembly’s expected service life. Conversely,
cosmetic damage is generally understood to
be dents that only affect the appearance of the
panel, but not its performance or service life.
An oft-cited industry definition is that used by
United States Steel:1
In general, hailstone damage can be
categorized into two types: aesthetic
damage and functional damage.
Aesthetic damage is simply damage that
has an adverse effect on appearance
but does not affect the performance of
the roof. Functional damage results in
diminished water-shedding ability and a
reduction in the expected service life of
the roof.
The intent of the cosmetic damage
endorsements and exclusions is fairly clear:
to eliminate or reduce the insurance carrier’s
liability for hail-caused dents that do nothing but
affect the appearance of otherwise functional
roof panels.
Recently, however, various engineers,
metallurgists, forensic experts, and other
property-claim stakeholders have challenged
the idea that hail-caused dents can ever be
merely a cosmetic issue, even in cases that
do not result in moisture intrusion. In the
case of hail-caused dents that have not split,
fractured, or punctured the metal, or otherwise
compromised the panel’s ability to resist
moisture intrusion (such as by disengaging
a seam), the argument that the dents still
constitute functional damage generally comes
in the form of a concern for the long-term
performance, or service life, of the roof panels.
The arguments against cosmetic-only dents
typically take on one of two forms (or both). The
first challenge usually goes something like this:
“The hail-caused dents created microfractures
(or microfissures, coating craze cracks, and
the like), which will lead to premature failure
of the corrosion-resistant coating and, in turn,
premature corrosion of the underlying base
metal.” A related, but separate, challenge
usually states something along the lines of “The
hail-cased dents (or divots) will accumulate
water, which will evaporate slower than the
Online exclusive
A Deep Dive into Hail-Caused
Dents: A Study of Corrosion
Resistance within Dents in
Galvalume-Coated Steel
Roof Panels
By Jordan Beckner, PE, RRC; and
Stephen Patterson, PE, RRC
This paper was originally presented at the 2024
IIBEC International Convention and Trade Show.
Interface articles may cite trade, brand,
or product names to specify or describe
adequately materials, experimental
procedures, and/or equipment. In no
case does such identification imply
recommendation or endorsement by
the International Institute of Building
Enclosure Consultants (IIBEC).
©2025 International Institute of Building Enclosure Fall 2025 Consultants (IIBEC) IIBEC Interface • 1
panel would otherwise (increasing the time of
wetness) and accelerate coating deterioration,
thereby causing premature corrosion of the
underlying base metal.” The intent of this paper
is to evaluate these two assertions as they
pertain to Galvalume-coated steel panels.
While there are a number of different metal
panels currently available in the market, the most
common types of panel are Galvalume-coated
steel panels. As such, the focus of this paper
specifically relates to effects of hail-caused dents
in Galvalume-coated steel panels.
Previously, two recent research projects
on the effects of hail to Galvalume-coated
steel panels were commissioned by the Metal
Building Manufacturers Association (MBMA).2,3,4
A summary of these findings was also presented
at the 2023 IIBEC International Convention
and Trade Show in the proceeding “Oh Hail!
Metal Roofs, Hail Impact, and Long-Term
Performance.”5 In response to the arguments
based on coating damage, the researchers
concluded the following, as summarized
by Dutton:
The coating damage study is based
upon a metallographic assessment of
rollformed profile rib specimens from a
43-year-old roof in Denver. The profile
of the Denver roof is representative
of trapezoidal standing seam metal
roofing that is common industry wide.
The results show that a minor degree
of metallic coating crazing may occur
immediately upon manufacture and may
even occasionally penetrate through
the coating to expose the base steel,
but that no detrimental corrosion has
occurred on this roof for over 40 years.
This observation is consistent with the
unique and well-documented corrosion
resistance mechanism characteristics of
55% Al-Zn alloy-coated steel globally.
This study also demonstrated that the
occasional minor degree of rollformed
coating damage is much smaller in size
than the size of 55% Al-Zn alloy-coated
steel uncoated spots of up to 0.079 inches
in diameter which, upon exposure to
marine, industrial and rural atmospheres,
showed no adverse effects on corrosion
resistance after 9 years. In addition, the
degree of coating damage associated
with a recent hailstorm “functional”
damage insurance claim was about
50 times smaller than the coating
damage associated with roll-forming
on the 43-year-old Denver roof. Thus, it
is concluded that such minute coating
cracks or base steel exposures from
hail impacts do not rise to the level of
“functional” damage when compared
to the degree of coating crazing which
may occur on newly produced 55% Al-Zn
alloy-coated steel roof panels.
In response to the arguments based on
the accumulation of water (“ponding”), the
researchers concluded the following, as
summarized by Dutton:
The water ponding study is based upon a
controlled laboratory assessment of the
time required for water to evaporate from
simulated hail divots in a commercially
produced GALVALUME standing seam
panel. A standard laboratory impact
testing apparatus was used to produce
simulated hail divots by delivering
energy impacts of 1, 4, 8 and 13.3 ft-lbs,
energies which correlate with hail stone
diameters of about 1 to 1-3/4 inches
striking a surface at terminal velocity.
The resulting divots ranged in depth
from 0.035 to 0.159 inches. To put this
in perspective, hail stones measuring up
to about 1-3/4 inches in diameter have
been documented as representing about
75 to 95% of the hail stone diameters
associated with hailstorms in the US
and Canada.
The study shows that the time for water
to evaporate from 0.150- inch divots is
faster than the times for evaporation
to occur at intentionally manufactured
mechanical deformations associated with
panel flutes employed to strengthen
roof panels. For hail divots up to about
0.160-inch depth, water evaporates in a
small fraction of the time required for the
sheared-edge panel eave to dry.
Based on these results, any argument
that divots produced by hail stones up to
about 1-3/4-inch diameter will result in
accelerated corrosion of the 55% Al-Zn
alloy-coated steel panel due to ponding
water in the divots is not supported. Such
55% Al-Zn alloy-coated steel [standing
seam roof] systems featuring flutes and
sheared-edge conditions have performed
excellently in service for over 40 years.
Our research builds on the findings of
the previous research conducted by Dutton,
Wilson, Giansante, Haddock, and others, in
order to expand the knowledge base of this
often-controversial topic. Our research was
twofold:
• We commissioned a metallurgist for
laboratory salt spray testing of panels with
simulated hail dents.
• We evaluated the condition of in-service panels
that were subjected to large hail impact (from
hailstones up to approximately 2.5 inches in
diameter) more than 27 years prior.
SALT SPRAY TESTING
Roof Technical Services Inc. (ROOFTECH)
secured a 26-gauge Galvalume-coated steel
R-panel meeting ASTM A653 Grade 80 and UL
2218 Class 4 hail rating. Fig. 1 is a drawing by
ROOFTECH showing the profile of the R-panel
that was tested.
The R-panel was tested in general accordance
with UL 2218-2012, Impact Resistance of
Prepared Roof Covering Materials,6 which is a test
Figure 1. Diagram of a typical R-panel.
2 • IIBEC Interface Fall 2025
method that “provides impact resistance data for
the evaluation of roofing materials.” In addition,
a rib of the panel was stepped on to simulate a
typical foot-step deformation (buckle) in a rib,
which commonly occurs on these types of roofs
as a result of foot traffic or mishandling during
maintenance, construction, or other rooftop
activity. UL 2218 provides Class 1 through 4 hail
impact resistance classifications. The test was
based upon dropping 1.25-, 1.50-, 1.75-, and
2.00-inch steel balls from a distance calculated
to simulate the kinetic energy of hail impacts of
1.25-, 1.50-, 1.75-, and 2.00-inch hailstones. The
kinetic energy of hailstones has been established
by the National Bureau of Standards and others.
Table 1 shows UL 2218’s four hail classifications
and associated kinetic (impact) energy.
Samples from the test panel subjected to the
simulated hail impacts and footstep damage
were delivered to Hurst Metallurgical Research
Laboratory Inc. (HMRL) for metallurgical testing,
which included a visual examination, salt spray
(fog) testing, and evaluation at low and high
magnifications using a variety of metallurgical
methods both before and after salt spray (fog)
testing was performed.
UL 2218 Impact Testing of Prepared
Roof Covering Materials
The panels were stored inside at approximately
73°F, and each panel was subjected to two steel
ball impacts: one in the rib and one in the flat
portion of the panel. The locations of the impacts
were circled and noted on the panel. Fig. 2
shows the tower used to drop the steel balls and
a view of a typical panel after the UL 2218 impact
testing (in this case, the impacts shown were
from 1.25- and 1.50-inch steel balls dropped
from a height calibrated to approximate the
energy of 1.25- and 1.50-inch hailstones).
The width and depth of the resulting dents
were measured. Fig. 3 shows the measurement
of the depth of the dents resulting from the
2.00-inch steel ball impacts to the rib and flat
portion of the panel.
Research performed by others and
ROOFTECH’s experience had found the impact
dents in metal panels typically exhibit an inside
diameter and an outside or overall diameter.
Mathey7 first reported the phenomenon wherein
impacts to metal panels form a shallower outside
dent and a steeper inside diameter. Mathey7
included a diagram showing these diameters,
which are depicted in a diagram of the typical
cross section shown in Fig. 4.
The depth and width of the indentations were
measured. Table 2 summarizes the recorded
measurements of the width and depth of the
indentations resulting from the various hail
sizes. UL 2218 states, “visual observations are
to be facilitated by examining the samples
under 5x magnification and the observations
recorded for each impact location.” The samples
were examined under 5x magnification, and
there were no visible cracks in the coating
or other evident failure of the metal panel.
There was some scuffing of the Galvalume
surfacing resulting from the steel ball impacts,
which would not be expected from actual
hailstones. The impact locations were also
examined under 80x magnification. Figs. 5
and 6 are photographs taken at the maximum
magnification of an 80x microscope with no
evidence of a fracture in the Galvalume coating
or failure of the panel.
Most metal roof panels, including 26-gauge
Galvalume metal R-panel roofs, meet UL 2218
Class 4, which is the highest rating available
with the UL 2218 test. Our testing corroborates
the Class 4 resistance and provides an example
of the approximate sizes of dents that can be
expected from the various hail sizes.
Hurst Metallurgical Research Laboratory
A total of 11 samples were extracted from the
test panel and delivered to HMRL in Euless,
Texas, for metallurgical testing. The salt spray
testing was performed in accordance with ASTM
G85-11, Annex 5 Dilute Electrolytic Cyclic Fog/Dry
test method. The HMRL examination included a
visual examination; salt spray (fog) testing; and
evaluation under various levels of magnification,
using a variety of metallurgical methods both
before and after salt spray (fog). The 11 test
TABLE 1. Drop height and kinetic energy
Class
Steel ball diameter Distance Energy
in. mm ft m ft-lbf J
1 1¼ 31.8 12 3.7 3.53 4.78
2 1½ 38.1 15 4.6 7.35 9.95
3 1¾ 44.5 17 5.2 13.56 18.37
4 2 50.8 20 6.1 23.71 32.12
Note: Data from Underwriters Laboratories (2012).
Figure 2. Test apparatus. Figure 3. A field dent depth measurement.
Fall 2025 IIBEC Interface • 3
samples included the eight samples that had
been impacted by the 1.25-, 1.50-, 1.75-, and
2.00-inch steel balls and two samples that HMRL
scribed (scratched) to simulate a large crack in
the Galvalume coating. Finally, the sample with
the rib buckle caused by foot pressure was also
tested. The HMRL findings are contained in
Madhani.8 Table 3 shows Madhani’s summary
of the findings of the salt spray testing; note that
the rust observed within the 1.-inch dent on the
rib surface and 2-inch dent on the rib surface was
found to be corrosion of the superficial residue
from the steel ball and was not corrosion of the
steel panel itself.
No visual evidence of corrosion (specifically,
iron oxide or rust) was observed on the scribed
roof surface after 336 hours. Isolated rust
was observed within the footstep buckle
after 72 hours. Slight rust-colored spots were
observed on the dented ribs from the 1.75- and
2.00-inch simulated hail impacts after 252 hours
on the 1.75-inch test sample and after 336 hours
on the 2-inch test sample.
However, the examination of these
rust-colored spots “revealed that the rust-colored
spots were extremely superficial” and, upon
further investigation, were found to be caused
by residuals from the steel ball—an effect that
would not occur with real hailstone impact.
Madhani8 noted that there was “no evidence of
cracking or pitting of the coating” at the impact
locations. The spots were cleaned and examined
and “no cracking or corrosion of the coating or
the substrate” was observed.
The scribed sample, which was tested to
simulate a crack in the coating, revealed no
evidence of rust after 336 hours of salt spray
(fog). The cracks extended through the coating
and into the carbon steel and were visible
without magnification. Madhani8 concluded,
Figure 4. Diagram showing inside and outside or overall diameter of impact dents in
metal panels.
TABLE 2. Depth and width measurements of the panel dents by various-sized steel balls
Hail size,
in.
Field dent,
mm
Rib dent,
mm
Field dent,
in.
Rib dent,
in.
1.25
Depth 0.14 1.01 0.01 0.04
Width 5.08 24.13 0.20 0.95
1.5
Depth 0.32 2.14 0.01 0.08
Width 10.16 27.94 0.40 1.10
1.75
Depth 0.96 3.13 0.04 0.12
Width 12.7 30.48 0.50 1.20
2.0
Depth 1.17 3.56 0.05 0.14
Width 13.97 27.94 0.55 10.10
Figure 5. A view of a 1.75-inch steel ball impact point center under 80x
magnification. The red point indicates a coating scuff.
Figure 6. A view of a 2-inch steel ball impact point center under 80x
magnification. The red point indicates a coating scuff.
4 • IIBEC Interface Fall 2025
“the absence of corrosion of the carbon steel
demonstrates the galvanic protection provided
by the coating on exposed areas of the
substrate.” Fig. 7 is an excerpt from Madhani8
showing the scribed area after 336 hours of
salt spray (fog) testing with no evidence of
corrosion. However, at the crimped area of the
foot-pressure-created rib buckle, corrosion was
evident after 162 hours in the salt spray at the
crimped area of the footstep buckle. Fig. 8
shows the corrosion at the footstep buckle after
162 hours.
Madhani8 concluded, “The various
metallurgical tests and evaluations of the
simulated cracks and hail impact dents in the
GALVALUME® carbon steel panels … performed
satisfactorily and disclosed no evidence of any
corrosion to the substrate carbon steel material”
even after exposure to 336 hours of salt spray
(fog). The metallurgical testing did reveal
corrosion occurring in the sample damaged by
the footstep and within a mechanically scuffed
portion. This indicates that the salt spray testing
was sufficient to cause corrosion to portions
of the panel at which the Galvalume coating
sustained significant damage.
REAL-WORLD CASE STUDY
Background
One of the most damaging hailstorms in history
occurred in Fort Worth, Texas, on May 5, 1995.
The storm caught 10,000 people outside
without shelter at a spring Mayfest event.
More than 400 of those attending Mayfest
were injured, including 60 who required
hospitalization. There was widespread
TABLE 3. Summary of salt spray testing
Specimen
Results
Comments
After 72 hours After 162 hours After 252 hours After 336 hours
Within
dent.
Outside of
dent.
Within
dent.
Outside of
dent.
Within
dent.
Outside of
dent.
Within
dent.
Outside of
dent.
1¼ in. dent on
rib surface 10 10 10 10 10 10 10 10
1¼ in. dent on
flat surface
between ribs
10 10 10 10 10 10 10 10
1½ in. dent on
rib surface 10 10 10 10 10 10 10 10
1½ in. dent on
flat surface
between ribs
10 10 10 10 10 10 10 10
1¾ in. dent on
rib surface 10 10 9-S 10 9-S 10 9-S 10
Isolated
rust-colored
spots observed
after 162 hours
1¾ in. dent on
flat surface
between ribs
10 10 10 10 10 10 10 10
2 in. dent on rib
surface 10 10 10 10 10 10 9-S 10
Very slight
rust-colored
spots observed
after 336 hours
2 in. dent on
flat surface
between ribs
10 10 10 10 10 10 10 10
Scribed on rib
surface 10 10 10 10 10 10 10 10
Scribed on
flat surface
between ribs
10 10 10 10 10 10 10 10
Footstep on rib 9-S 10 9-S 10 9-S 10 8-S 10
Isolated rust
at scuffed area
first observed
after 72 hours
Note: Data from Madhani (2017). For dents, 10 = <0.01% surface rust; 9 = >0.01% and <0.03% rust; S = spot per ASTM D610-08 (2012). For
scribes, 10 = 0 in. creepage per ASTM D1654-08 (2016).
Fall 2025 IIBEC Interface • 5
softball-sized hail across Fort Worth that caused
an estimated $2 billion in damages, and the
hailstorm became known as the “Mayfest
Storm.”9 According to the National Centers for
Environmental Information’s Storm Events
Database, there were several reports of hail
within Fort Worth (the location of the subject
case-study building), including reports of 2.75-,
3.5-, and 4-inch hailstones.10
The building that is the subject of this case
study is a one-story strip shopping center built
in 1986 and located on the east side of Fort
Worth. The general construction consists of a
slab-on-grade foundation with pre-engineered
metal building framing and a 26-gauge
Galvalume steel R-panel roof. The roof panels
were attached to Z-purlins approximately 5 feet
apart using screws with rubber washers. There
were stitch screws at the side laps approximately
24 inches on center.
Inspection and Analysis
The roof on the building was subjected to
impact from hailstones up to at least 2.
inches in diameter, with some hailstones
possibly reaching 4 inches. The roof was not
replaced after the Mayfest Storm. The roof
on the building had numerous dents but no
hail-related leaks. The building has a history
of minor leaks occurring at the end laps of the
metal panels and at screws. In 2013, one of
the authors reinspected the roof to evaluate its
performance. Fig. 9 is a photograph of the roof
taken in 2013, approximately 18 years after the
hail event, when the roof was 27 years old. The
roof leaks were minor and in generally the same
locations, related to end laps and screws, as they
were in 1995. There were a few repairs to the
screws and penetrations.
Numerous hail-caused dents were visually
examined, including examination at 10x to
determine if there had been any deterioration as
a result of the hail-caused dents. Fig. 10 shows
typical hail-caused indentations with stains in
the dents that were randomly spaced across
the roof.
The larger hail-caused dents were stained
with sediment in the dents. Fig. 11 shows a
close-up of one of the larger hail-caused dents
with stains. Fig. 12 shows the hail-caused dent
cleaned. There was no evidence of corrosion or
other evidence of deterioration. Fig. 13 shows a
10x view of the impact area. There is no visible
corrosion or deterioration of the Galvalume
coating at 10x.
Stains at the screws and end laps of the
panels had stains similar to the stains at the
hail-caused dents. This type of staining is normal
and commonly occurs on these types of metal
Figure 7. Photograph of the scribed samples of Galvalume roof panel sample showing the lack of
visible evidence of corrosion following 336 hours of test cycle. Reproduced with permission from
Madhani (2017).
Figure 8. Photograph of footstep buckle showing corrosion after 162 hours of salt spray testing.
Reproduced with permission from Madhani (2017).
Figure 9. Photograph of the case study roof taken in 2013, approximately 18 years after the hail
event, when the roof was 27 years old.
6 • IIBEC Interface Fall 2025
roof. There was no evidence of corrosion in the
Galvalume panel. There was, however, corrosion
on the screw. At the end lap panels, the overlap
results in a shallower slope (with slower drainage
and evaporation) and, consequently, staining
similar to the staining in the hail-caused dents.
There also appeared to be some evidence of
slight pitting of the Galvalume coating at the
end lap.
In 2022, one of the authors again reinspected
the roof to evaluate its performance. Fig. 14
shows an overview of the roof on the building
taken in 2022 approximately 27 years after the
Mayfest Storm. The roof was approximately
40 years old at the time of this inspection.
Overall, the appearance of the roof was in a
substantially similar condition to its condition at
the previous inspection.
Figure 10. Photograph of the dents in the case study roof caused by the
Mayfest Storm.
Figure 12. Photograph of a cleaned hail-caused dent—note the absence
of evident corrosion.
Figure 14. Photograph of case study roof taken in 2022 approximately 17 years after the
Mayfest Storm.
Figure 11. Photograph of typical hail-caused indentations with stains in
the dents.
Figure 13. Photograph of a cleaned hail-caused dent under 10x
magnification—note the absence of evident corrosion.
Fall 2025 IIBEC Interface • 7
Again, numerous hail-caused indentations
were visually examined and examined under
10x magnification. Fig. 15 shows a large
dent in the rib of the panel with sediment
accumulation. Fig. 16 shows a 10x view of
a rib dent after cleaning with no evidence of
corrosion. However, small spots of corrosion
were beginning to show at the eaves after
40 years of service, shown in Fig. 17.
Case Study Conclusions
There was no evidence of corrosion at the various
hail-caused impacts after 27 years of weathering,
though there were staining and sediment
accumulations at the hail-caused dents. The Galvalume
panels were performing well, and there was no
evidence of corrosion in the metal panels caused by the
hailstone impacts. We found that there was no visible
evidence of corrosion at the hail-caused indentations.
We also found that the sediment in at the
depressions in the metal panels at the screws and
the sediment at the end laps and eaves were similar
in appearance to the stains in the hail-caused dents,
which is consistent with the findings reported in
Dutton and Wilson.3 In this case study, it appeared
that there were some minor pits from corrosion in
the Galvalume coating at end-lap seams that were
not present in the hail-caused dents.
Figure 15. Photograph of large dent in the rib of the panel. Figure 16. Photograph of cleaned dent in the rib under 10x magnification.
Figure 17. Photograph of small spots of corrosion at the eave panels of the 40-year-old roof.
8 • IIBEC Interface Fall 2025
CONCLUSION
The salt spray metallurgical testing verified
that dents caused by impacts from steel balls
up to 2 inches (with the approximate energy
of a similarly sized hailstone) would not be
expected to corrode at a rate that would
exceed the rate of other areas of the panel
due to normal weathering, such as at end-lap
seams or overtightened fasteners, or at areas
with mechanical-type damage, such as at rib
buckles. The metallurgical study included
subjecting the dented samples from the test
panel to salt spray testing for 336 hours, which
is a significantly more corrosive environment
than normal atmospheric conditions, and
evaluating the sample before and after the
test. This metallurgical evaluation confirmed
that there was no corrosion as a result of the
simulated hail-caused dents in the metal
panels even when subjected to the salt spray
testing. The metallurgical study also showed
that there was no corrosion in the scribed
areas. Moreover, the lack of corrosion in the
scribed areas confirmed that the coating
performed as designed to prevent corrosion,
even if the coating had minor scratches or
cracks. The testing was, however, sufficient to
cause corrosion in areas of the panel that were
buckled by footfall and mechanically scuffed.
The observations of the subject case study
found that Galvalume-coated steel panels
were not corroded at the hail-caused dent
locations, even after 27 years of weathering. The
Galvalume-coated panels were performing well,
and there was no evidence of any significant
deterioration in the metal panels caused by
the hailstone impacts. We also found that the
sediment in at the depressions in the metal
panels at the screws and the sediment at the
end laps and eaves were similar in appearance
to the stains in the hail-caused dents, which
is consistent with the findings reported in
Dutton and Wilson.3 While this study was
limited to panels subjected to hailstones up
to approximately 2½ inches, larger hail is an
extremely rare occurrence and thus, these
results are comparable to the large majority of
cases of hail-dented Galvalume-coated panels,
most of which would have been impacted by
smaller hail. This case study was consistent with
the authors’ experience inspecting thousands
of hail-dented Galvalume-coated metal roof
panels, none of which have ever exhibited
corrosion correlated to the dent locations.
Moreover, the authors have never seen
photographs of Galvalume-coated panels with
corrosion specifically correlated to hail-caused
dents (though if such photographs exist, we
welcome their production).
Together, the metallurgical testing and case
study indicated that metal roof panels will
generally corrode at various areas due to normal
weathering before they would be expected
to corrode at dents caused by impact from
hailstones up to 2½ inches. In other words, by
the time hail-caused dents corrode, the metal
panels will have already corroded elsewhere
and, therefore, these hail-caused dents will not
result in a reduction of their expected service life.
In sum, based on the salt spray testing and the
case study, it can be concluded that hail-caused
dents from hail 2½ inches or less will not corrode
at an accelerated rate such that their expected
service life is shortened. With regard to the
distinction between cosmetic and functional
damage, the authors conclude that unless they
cause a vector for moisture intrusion (such as
a split panel or seam disengagement), dents
caused by hail up to 2½ inches will generally not
meet the definition of functional damage and are
deemed cosmetic.
REFERENCES
1. United States Steel. 2015. Hail Damage on Coated
Sheet Steel Roofing. Technical Bulletin, Pittsburgh,
PA: United States Steel.
2. Dutton, Ron. 2021. Coating Damage due to Roll
Forming of GALVALUME® SSR Panels. Cleveland, OH:
Metal Building Manufacturers Association.
3. Dutton, Ron, and Jim Wilson. 2020. Water
Evaporation Rates of Simulated Hail Divots on a Low-
Slope GALVALUME® SSR Panel. Cleveland, OH: Metal
Building Manufacturers Association.
4. Dutton, Ron. 2021. The Effects of Hail Impacts on the
Durability of GALVALUME® SSR Panels. Cleveland,
OH: Metal Building Manufacturers Association.
5. Dutton, Ron, and Robert Haddock. 2023. “Oh
Hail! Metal Roofs, Hail Impact, and Long-Term
Performance.” In 2023 IIBEC International Convention
& Trade Show Conference Proceedings (Raleigh, NC:
IIBEC), 90–102.
6. Underwriters Laboratories. 2012. Impact Resistance
of Prepared Roof Covering Materials. UL 2218.
Bensenville, IL: Underwriters Laboratories.
7. Mathey, Robert C. 1970. Hail Resistance Tests
of Aluminum Skin Honeycomb Panels for the
Relocatable Lewis Building, Phase II. Port Hueneme,
California: US Department of Commerce, National
Bureau of Standards.
8. Madhani, Mahesh J. 2017. The Effects of a Corrosive
Environment on the Corrosion Resistance of Simulated
Hail Damaged and Cracked GALVALUME Roofing
Panels. Euless, TX: Hurst Metallurgical Research
Laboratory Inc.
9. National Weather Service. 1995. The Mayfest Storm:
May 5, 1995. Fort Worth, TX: United States Department
of Commerce, National Oceanic and Atmospheric
Administration, National Weather Service.
10. National Centers for Environmental Information.
“Storm Events Database.” https://www.ncdc.noaa.
gov/stormevents/.
ABOUT THE AUTHORS
Jordan Beckner, PE,
RRC, is the director of
engineering services at
Roof Technical Services
Inc. and a Registered
Roof Consultant. He
earned a bachelor of
science in mechanical
engineering from
Baylor University
and is a licensed
professional engineer
in eleven states. He
has been working in
the engineering field for more than 20 years,
with more than 10 of those years specifically
focused on roofs. He has investigated more
than a thousand engineering projects related to
storm damage, moisture intrusion, construction
defects, structural failures, and building
enclosure issues.
Stephen Patterson,
PE, RRC, has been in
the roofing industry for
50 years. He founded
Roof Technical Services
Inc. (ROOFTECH) in
1983 and has been
an active consulting
engineer and roof
consultant ever
since. ROOFTECH
has provided
laboratory testing,
including testing for
hail damage and hail resistance of prepared
roof coverings, since the late 1980s. Prior
to becoming a consultant in 1983, he was a
technical director/director of engineering for
two roofing manufacturers and managed a roof
contracting company.
JORDAN BECKNER,
PE, RRC
Roof Technical Services
Inc., Fort Worth, Texas
STEPHEN PATTERSON,
PE, RRC
Roof Technical Services
Inc., Fort Worth, Texas
Please address reader comments to
chamaker@iibec.org, including
“Letter to Editor” in the subject line, or
IIBEC, IIBEC Interface,
434 Fayetteville St., Suite 2400,
Raleigh, NC 27601.
Fall 2025 IIBEC Interface • 9