Skip to main content Skip to footer

Misconceptions of Wind Damage to Asphalt Composition Shingles

January 10, 2018

The topic of wind-lifted shingles
remains a controversial subject
in the roofing industry.
There are many misconceptions
and a number of issues
with asphalt shingles that are
commonly incorrectly attributed to wind
effects. Some of the current and most hotly
debated issues relate to the assertions by
some that:
1. “Wind-lifted” or “wind-damaged”
shingles are not always visually
apparent, but are damaging to the
roof.
2. Any shingle with inadequate adhesion
is a “wind-lifted” or “wind-damaged”
shingle.
3. Empirical tests can easily demonstrate
the strength reduction of a
shingle after a storm event.
This article discusses these positions
and the misconceptions associated with
these positions.
“WIND-LIFTED” OR “WIND-DAMAGED”
SHINGLES ARE NOT ALWAYS
VISUALLY APPARENT
When considering if wind-related damage
to asphalt composition shingles can be
hidden or not visually apparent, one must
consider how damage to a shingle occurs.
First, a wind-induced pressure differential
between the front and back of a shingle
(i.e., uplift force) has to occur, such that the
1 0 • RC I I n t e r f a c e J a n u a r y 2 0 1 8
Figure 2 – Creased shingle tab.
Figure 1 – Relative increase in projected area (hatched box) as shingle is lifted by the wind.
As a shingle tab rises in the wind, more surface area is exposed and, thus, a stronger force
occurs.
factory-applied adhesive fails.
As the shingle rises in the
wind, more surface area is
exposed to the wind and, thus,
a greater uplift force occurs.
Refer to Figure 1.
This progression will tend
to flip and crease or tear the
shingle. The wind forces cause
the shingle to flutter and bend
such that further creases may
develop (Figure 2). Eventually,
if the wind force is strong
enough, the tabs or shingle
sections break off and are
carried downwind (Figure 3).
This is particularly the case
in areas of the roof that are
exposed to higher wind forces
(e.g., eaves, hips, ridges, etc.).
Failure typically occurs at the
top of the exposed section,
just below the butt end of the
overlying shingle.
It has been our experience
(both by field observations and laboratory
testing) that any sealed-down shingle
affected by wind will leave lasting evidence
of the event having occurred. This evidence
is exhibited as creases, folds, tears, missing
shingles or portions of shingles, or any combination
thereof. Further, this evidence is
visible when the roof is examined carefully.
A shingle that is simply not adhered and is
not creased, folded, torn, or missing, is not
evidence of wind-caused damage. (This item
is discussed in further detail in the following
section.)
A recently completed test performed by
Haag Research/Testing (HRT) documented
the mechanisms by which shingles are
damaged by wind. HRT employed a wind
simulator (Figure 4) capable of producing
wind speeds up to 175 mph and compliant
with ASTM D3161, Standard Test Method
for Wind-Resistance of Steep Slope Roofing
Products (Fan-Induced Method). Post-test
inspection of all shingles that unbonded
during the testing revealed that, at a
minimum, creases were present. Shingles
utilized in this test were not weathered,
but were placed on the test assembly days
before the test. In the new, pliable shingles
tested, the creases required very close
inspection and tactile manipulation (i.e.,
placing hand pressure from underneath the
shingle) of the granular surface to observe
the crease; nonetheless, they were present
and observable.
ANY SHINGLE WITH INADEQUATE
ADHESION IS A “WIND-LIFTED” OR
“WIND-DAMAGED” SHINGLE
It is important to explicitly define the
characteristics that identify a wind-damaged
shingle. In the absence of such a definition,
many in the industry imply that any shingle
with inadequate adhesion is a “wind-lifted”
or “wind-damaged” shingle. This practice is
particularly careless because it ignores the
many reasons shingle adhesives can fail,
even in the absence of strong wind forces.
To be more specific, wind can lift and
remove poorly adhered shingle tabs; however,
not all poorly adhered shingle tabs are
caused by wind.
There are multiple factors that negatively
influence the adhesion of shingles. These
factors include manufacturing inconsistencies,
improper installation, aging and deterioration,
installations during cold weather,
contamination of the adhesive, as well as
cyclic thermal expansion and contraction.
Cyclic thermal expansion and contraction,
for example, will yield a pattern
of unbonded shingle overlaps extending
up-slope diagonally, reflecting the pattern in
which these shingles were installed (Figure
5). A similar pattern is often observed with
shingles installed in a straight-up pattern,
referred to as “racked.” An unbonded pattern
of shingle tabs in a racked installation
is commonly referred to as zippering (chalk
lines in Figure 6 show the nonbonded shingle
portions). These unbonded overlaps will
not vary in direction or increase/decrease
in areas of the roof where wind uplift would
J a n u a r y 2 0 1 8 RC I I n t e r f a c e • 1 1
Figure 3 – Torn shingle tab.
ENVIROSPEC INCORPORATED
The PAVE-EL®
Pedestal System
 Transforms flat roofs into attractive,
maintenance-free,
paver stone terraces.
 Elevates paver stones for
perfect drainage.
 Levels paver stones and ensures
their uniform spacing for
an ideal roof terrace surface.
 A perfect solution for laying
mechanical walkways for use
by maintenance personnel.
 Ideal for laying paver
walkways in roof gardens.
Turn roof tops into
beautiful deck areas
Easy to
Install
1-905-271-3441 • www.envirospecinc.com
be greater/less. In such cases, it is
clear that wind would not come from
all directions with just enough force to
compromise the adhesion on the sides
of the shingle overlaps.
Experiments by others have also
concluded that unsealed shingles can
occur in the absence of a high-wind
event. In particular, recent research
funded by the Southeast Region
Research Initiative (SERRI), managed
by Oak Ridge National Laboratory and
conducted by The University of Florida
(Dixon, 2013) for the U.S. Department of
Homeland Security, found that “partially
unsealed shingles were a result of a
systematic failure of the shingle’s sealant
strip rather than a random unsealing
event.” Further, the study by Dixon
et al. (2014) found that “shingles appear
to remain sealed for the first 4-5 years of
service life, but beyond that timeframe, the
frequency of unsealing trends upwards.” In
effect, these and other studies have found
that shingles undergo a systematic natural
pattern of unsealing, which progresses
with age and is not induced by wind.
These findings confirm decades of our field
observations (Marshall et al., 2010) and our
aforementioned laboratory testing.
Experiments by The University of Florida
(Dixon, 2013) have also found that unsealed
shingles can be attributed to “installation
errors that prevented the shingle from
sealing to the course below. These errors
included: under-driven nails in the sealant
strip, debris in the sealant strip, and
release tape that was inadvertently stuck to
the shingle’s sealant strip due to packaging
errors.” Further, their experiment found
that “a distinct pattern of partial unsealing
was observed on 70% (19 out of 27) of the
roofs surveyed, including both laminate and
three-tab systems. The eight roofs that did
not exhibit a pattern had less than or equal to
1% unsealed shingles. There were no cases
where widespread unsealing was observed
with no pattern,” demonstrating that 70%
of the surveyed roofs had a substantial
quantity of unsealed shingles that exhibited
a distinct pattern. These patterns, however,
are not consistent with wind-related
damage.
EMPIRICAL TESTS CAN EASILY
DEMONSTRATE THE STRENGTH
REDUCTION OF A SHINGLE AFTER
A STORM EVENT
Some in the industry refer to ASTM
D7158, Standard Test Method for Wind
Resistance of Asphalt Shingles (Uplift Force/
Uplift Resistance Method) as a proper and
simple method to empirically demonstrate
the strength of a shingle after a storm
event. In particular, they aim at comparing
field-measured strengths to the rating
originally determined by the manufacturer.
The major difficulty that arises is that the
manufacturers list compliance with ASTM
D7158 (at design wind speeds) on material
packaging and/or reference documents.
They do not list uplift coefficients or the calculated
uplift forces determined from ASTM
D7158. Typically, this information is not
readily available from manufacturers. Thus,
the uplift forces must be calculated by the
interested party using test results from an
independent laboratory. We note, however,
that laboratories with the capacity to perform
ASTM D7158 are not common, and
when available, testing may be cost-prohibitive
(it requires a modified version of
the testing apparatus for ASTM D3161 as
shown in Figure 2).
As a result, rather than performing
ASTM D7158 (which includes physical testing
of panels subjected to wind to derive
uplift forces), some opt to calculate the
design or intended uplift forces using other
methods. This is incorrect; uplift loads
calculated using ASTM D7158 and those
calculated using other tools can vary substantially.
For this reason, there are no
provisions in ASTM D7158 for an alternative
calculation of design loads.
We also note that while ASTM
International and the International Code
1 2 • RC I I n t e r f a c e J a n u a r y 2 0 1 8
Figure 5 – Unbonded diagonal pattern of shingle overlaps.
Figure 4 – Haag wind simulator.
Council (ICC) have adopted wind ratings
for asphalt composition shingles
that range up to 150 MPH, windrelated
performance issues remain,
as discussed in the preceding section.
This translates into many shingles
in the field not meeting their design
criteria.
Assessments of asphalt shingle
roofs by Haag after hurricanes and
other wind events have revealed deficiencies
in each of the mentioned
areas. Similar findings have been
made by McDonald and Smith (1990)
after Hurricane Hugo, Smith (1995)
after Hurricane Andrew, Rash (2006)
after Hurricane Ivan, and the Roofing
Industry Committee on Weather
Issues (RICOWI) in 2006, 2007, and
2009, after Hurricanes Charley and
Ivan, Katrina, and Ike, respectively.
Further, ASTM D6381, Standard Test
Method for Measurement of Asphalt
Shingle Mechanical Uplift Resistance (which
is referenced in ASTM D7158), states “many
factors influence the sealing characteristics
of shingles in the field; for example, roof
slope, and interference by misplaced fasteners.”
It is not the objective of the ASTM test
methods to address these issues. Therefore,
in rating shingles, new, unweathered products
are tested with much care being taken
in the installation and the preparation of
each specimen. To assume that all installed
shingles will meet the uplift loads determined
using the ASTM test methods is
unrealistic.
CONCLUSION
In conclusion, while wind can lift and
remove poorly adhered shingle tabs, we
have found that sealed shingles that have
been affected by wind show lasting evidence
of the event having occurred. Further,
there are multiple factors that influence
the adhesion of shingles that must also be
considered. For this reason, great care must
be taken in discriminating among shingles
that have been affected by wind loads and
shingles with compromised sealant strips
related to other factors. Additionally, while
ASTM test methods can be used to determine
the uplift capacity of field shingles,
calculated loads used to compare with field
results must be calculated appropriately by
laboratories with the capability to perform
the testing. Even then, the totality of factors
that influence proper adhesion should be
considered. Further, test shingles should be
properly selected and reductions in capacity
must be properly investigated before sweeping
and unfounded conclusions are drawn.
Proper wind damage assessments should
consider locations of damaged shingles,
any patterns of unsealed shingles across
a roof slope and across the entire roof, the
J a n u a r y 2 0 1 8 RC I I n t e r f a c e • 1 3
ISSUE SUBJECT SUBMISSION DEADLINE
April 2018 Sustainability January 15, 2018
May/June 2018 Convention issue February 15, 2018
July 2018 Decks April 13, 2018
August 2018 Adhesives and accessories May 15, 2018
September 2018 Building envelope (misc.) June 15, 2018
October 2018 Walls July 13, 2018
Publish in RCI Interface
RCI Interface journal is seeking submissions for the following issues. Optimum article size is
2000 to 3000 words, containing five to ten graphics. Articles may serve commercial interests but
should not promote specific products. Articles on subjects that do not fit any given theme may be
submitted at any time.
Submit articles or questions to Executive Editor Kristen Ammerman at 800-828-1902
or kammerman@rci-online.org.
Figure 6 – Unbonded racked pattern of shingle overlaps.
directions of slopes with unsealed shingles,
and the prevailing direction of the wind
during the storm event in question.
REFERENCES
ASTM International. ASTM D3161,
Standard Test Method for Wind-
Resistance of Steep Slope Roofing
Products (Fan-Induced Method).
ASTM International. ASTM D7158,
Standard Test Method for Wind
Resistance of Asphalt Shingles (Uplift
Force/Uplift Resistance Method).
ASTM International. ASTM D6381,
Standard Test Method for
Measurement of Asphalt Shingle
Mechanical Uplift Resistance.
Craig R. Dixon. “SERRI Project:
Investigation of the Wind Resistance
of Asphalt Shingle Roof Coverings.”
Oak Ridge National Laboratory, U.S.
Department of Energy. June 2013.
p. 232.
Craig R. Dixon. “The Influence of Unsealing
on the Wind Resistance of Asphalt
Shingles.” Journal of Wind Engineering
and Industrial Aerodynamics. Vol.
130. Elsevier. 2014. pp. 30-40.
T.P. Marshall, S. Morrison, R. Herzog,
and J. Green. “Wind Effects on
Asphalt Shingles.” 29th Conference
on Hurricanes and Tropical
Meteorology. American Meteorological
Society. 2010. Hyannis, MA.
p. 11.
J.R. McDonald and T.L. Smith.
“Performance of Roofing Systems
in Hurricane Hugo.” Institute for
Disaster Research. 1990. p. 42.
D. Rash. “Three-tab Shingle Performance
During Hurricane Ivan.” RCI
Interface, RCI, Inc. 2006. pp. 5-11.
RICOWI Inc. “Hurricane Katrina Wind
Investigation Report.” Oak Ridge
National Laboratory, U.S. Department
of Energy. August 2007. p. 202.
RICOWI Inc. “Hurricanes Charley and
Ivan Wind Investigation Report.”
Oak Ridge National Laboratory, U.S.
Department of Energy. March 2006.
p. 260.
RICOWI Inc. “Hurricane Ike Wind
Investigation Report.” Oak Ridge
National Laboratory, U.S. Department
of Energy. December 2009. p. 364.
Thomas L. Smith. “Improving Wind
Performance of Asphalt Shingles:
Lessons from Hurricane Andrew.”
11th Conf. on Roofing Technology.
1995. Gaithersburg, MD. pp. 39-48.
Scott Morrison graduated
from Iowa
State University
with a BA in architecture
and a BS in
civil engineering. He
also received a MS
in civil engineering
from the University
of Oklahoma. He
is a member of the
American Society of
Civil Engineering,
American Institute
of Steel Construction, American Concrete
Institute, American Association of Wind
Engineers, American Society for Testing and
Materials, and Chi Epsilon. Morrison has
been with Haag Engineering since 1989 and
leads the research and testing program there.
Scott Morrison
Dr. Carlos Lopez
graduated from the
University of Florida
with a BS, MS, and
PhD in civil engineering.
Currently, he
is a member of the
American Society
of Civil Engineers,
the American
Concrete Institute,
and the American
Association for
Wind Engineering.
Dr. Lopez has been with Haag Engineering
since 2012 and has inspected and assessed
hail- and wind-caused damage to roofs.
Dr. Carlos Lopez
Dr. Jonathan Goode
holds BS, MS, and
PhD degrees in agricultural
and civil
engineering from the
University of Georgia,
the University of
Colorado at Boulder,
and Colorado State
University, respectively.
He is a
licensed professional
engineer in 17 states
and was an assistant
professor at Oklahoma State University
prior to coming to Haag Engineering in 2010.
Dr. Goode is a member of the American Society
of Civil Engineers and serves on the Technical
Council of Forensic Engineering, Forensic
Practices Committee.
Dr. Jonathan Goode
1 4 • RC I I n t e r f a c e J a n u a r y 2 0 1 8
Four roofing companies have formed the Asphalt Underlayment Council (AUC) to
cultivate the long-term success of underlayment products for building envelope applications.
They are Carlisle, Gardner-Gibson, Maryland Paper, and Mid-States Asphalt.
Other current members are Owens Corning, Polyglass USA, Mulehide Manufacturing,
GMC Roofing & Building Paper, GAP Roofing, Warrior Roofing Manufacturing, and GAF.
Because standards and requirements for roof repair, reroofing, roof recovering,
and roof replacement “often lack clarification within the definition of underlayment,”
AUC’s inaugural technical committee will focus on code classifications and industry
regulations. “The pathways to code compliance vary depending on the product type,”
said John Woestman, AUC’s technical director. AUC plans to actively assist in the development
of building codes.
Visit aucunderlaymentcouncil.org for further information.
Asphalt Underlayment Council Formed